Earthing concept
• IS 3043
• IEC 62305
system.
• Depth of Placement
• Salt Content
• Moisture / rainfalls
• Temperature
• Fulgurites
• Corrosion effect
1. Conventional Earthing
Resistance value is not stable for round the year i.e value changes due
to change in climate and temperature.
3. Electrolytic Grounding
Perforated Test Well Cover
a) Vertical Electrode
Test Well
Ventilation
• It is used in the soft & sandy Ports
soil conditions where digging
is easy Copper Conductor
• Normally the length of the
electrode varies from 8ft – Back Fill
10ft
Environmentally
Safe Salts
Copper Tube
Leaching Ports and
Electrolytic Roots
Electrolytic Grounding
b) Horizontal Electrode Perforated Test Well Cover
5.4.1 General
When dealing with the dissipation of the lightning current (high frequency
behavior) into the ground, whilst minimizing any potentially dangerous
overvoltage, the shape and dimensions of the earth-termination system are
the important criteria. In general, a low earthing resistance (if possible lower
than 10 Ω when measured at low frequency) is recommended.
0.5m
1m
0.5m
approx. 1m
Air-termination
“The minimum lengths stated in Figure 2
conductor
may be disregarded provided that an
earthing resistance of the earth-termination
system less than 10 Ω is achieved.“
min. 0.5 m
Horizontal earth electrode
5m
At the test joints, additional earth electrodes should be connected to the down-
conductors and foundation earth electrodes.
system.