Sunteți pe pagina 1din 2

D R I V E S &

S W I T C H G E A R

O n some electric motors, the internal and/or external fans can be fitted in
either direction. Frequently repair companies do not properly identify and
mark the fans and this results in fans being incorrectly re-fitted.

Centrifugal fans -
direction of rotation explained
There seems to be some confusion in the by Henk de Swardt, Marthinusen & Coutts
electric motor repair industry regarding
the rotation direction of a motor’s
cooling fans. We have seen cases where
the fans removed from the motor were
incorrectly installed. This paper explains
the basic principles behind correct fitting
of fans.
For general applications the rules listed
here should hold true.
Centrifugal fans can in general turn in
both directions. The performance of the
fan may however not be identical for
both directions. Centrifugal fans can
only blow air radially outwards. Fig. 1: Example of a bi-directional fan. Fig. 2: Example of a uni-directional fan
with curved blades.
Bi-directional fans
A “bi-directional fan” has straight
blades, perpendicular to the shaft,
which may or may not extend to the boss
(inside section of the fan that holds the
fan on the shaft).
This type of fan can rotate in both
directions, without any change in fan
power consumption and air volume.
Fig. 4: The “backwardly curved blades”
These fans are frequently used on principle is used in determining
a “slow” speed motor, i.e. a motor the direction of rotation for angled
with a rotational speed of less than Fig. 3: Example of a uni-directional fan, or curved blades.
1300 rpm. with straight blades.

Uni-directional fans directional fan with straight blades. The principle used for determining the
A “uni-directional fan” may have In these examples, the correct direction direction of rotation is “backwardly
straight or curved blades. The blades of rotation is clockwise as viewing curved blades”. Fig. 4 shows how this
are however at an angle to the shaft, the fans from the inlet side (as shown principle is used.
which may or may not extend to the boss currently in the Figs). Consequences of incorrect
(inside section of the fan that holds the Using these fans in the opposite direction of rotation
fan on the shaft). direction from that shown here will
Fig. 2 shows an example of a uni- Although the increase in air volume is
result in an increase in the fan’s power
directional fan with curved blades. good, unfortunately in most cases the
consumption, fan noise and also the air
Fig. 3 shows an example of a uni- increase in fan power usage outweighs
volume it moves.

July 2008 - Vector - Page 45


Item @ % Load Value Unit investigation it was found that the
Power Output 100% 1200 kW direction of the fans was incorrect. We
75% 900
0% 0
corrected this mistake and the motor
could deliver the correct full load power
Item @ % Load Direction of rotation Unit while still complying with the specified
Correct Incorrect temperature rise.
Air flow rate coefficient 3,03 3,33
"Fan losses increase: Power of" 3 5 Energy costs
Fan losses 35,0 46,6 56,4 kW
Current 100% 122,4 123,4 124,3 A To put the cost of incorrect fan fitment
75% 94,7 95,7 96,5 into perspective, the direct energy costs
0% 35,6 35,7 35,8 will be calculated using equation 1.
Speed 100% 2985,3 2985,2 2985,1 The rate for the energy will be used
75% 2989,1 2989,0 2988,9
Total losses 100% 64,5 76,6 86,8 kW
as 23c/kWh. The calculations will be
75% 54,8 66,7 76,8
annualised, assuming running times of
0% 42,2 54,4 64,2 firstly for a light duty, 12 hour per day,
Efficiency 100% 94.90% 94,00% 93,25% 5 days per week, and secondly for a
75% 94,26% 93,10% 92,13% normal duty, 24 hours per day, 7 days
Input Power 100% 1264 1277 1287 kW
per week. (See table 2).
75% 955 967 977
Temperature rise 75,4 77,6 80,8 °C

Table 1: Changes when rotation is reversed.


Eqn. 1: Calculating the direct energy cost.
I
Item Value Unit
Power Output 1200 kW
where:
Item Direction of rotation Unit h = hours running per day
Correct Incorrect
Fan losses increase: Power of 3 5 d = days running per year
Fan losses
Current
35,0
122,4
46,6
123,4
+ 24,9%
+ 0,9%
56,4
124,3
+ 37,9%
+ 1,6%
kW
A
If we apply this calculation to the case
Total losses 64,5 76,6 + 15,7% 86,8 + 25,7% kW study, we can see the additional costs as
Efficiency 94,90% 94,00% - 0,9% 93,25% - 1,7% a result of the lower efficiency.
Power Factor 0,905 0,906 + 0,1% 0,933 + 2,9%
"Light duty Energy cost R 910 k R 919 k + 0,9% R 926 k + 1,7% Although the percentage change
(one year)"
"Standard duty Energy cost R 910 k R 919 k + 0,9% R 926 k + 1.,%
looks relatively small, the result on a
(one year)"
population of a few hundred or a few
Table 2: Case study calculation. thousand motors of various sizes can
have huge implications on the energy
bill of the company. And these additional
the benefit of an increase in air flow. for both the best case of 33% increase in costs could have been easily avoided.
In practical terms, it is difficult to estimate fan losses as well as for the worst case
of 61% increase in fan losses. Conclusion
exactly what the increase in flow and
power will be for a specific fan without Even though the air flow increased In order for the electric motor to operate
extensive finite element modelling. significantly through the motor, which at its peak designed performance,
results in better cooling of the motor, the the fan needs to be correctly installed
Let’s assume some values for a specific and designed to suit the specific
application and study the effects on the much higher increase in the fan losses
far outweighs this improved cooling and application.
motor’s performance.
results in a motor that consumes more It must be noted that the influence of the
C o n s i d e r a 1 2 0 0 k W, 2 p o l e , direction of rotation on the air flow and
power and runs at a higher temperature.
6600 V motor that has been designed fan losses become less important in slow
The motor’s efficiency is greatly reduced
to turn in an anti-clockwise direction. speed motors.
This motor is coupled to a load that and the full load current is increased.
In many cases the direction of rotation
requires a clockwise direction of An interesting development is that
in relation to the construction of the
rotation and is electrically connected customers may experience overheating external fan can easily by checked by
accordingly. Let’s also assume the problems as a result of higher operating means of visual inspection on site.
three (two internal and one external) loads, as demands on production Whenever a motor is overhauled or
fans will produce as much as 10% increases. We have seen cases where repaired it is recommended that the
more air flow (even with the increased motors have run for years at less than full correctness of the orientation of the
pressure drop through the heat load power and at a lower temperature. internal and external fans should be
exchanger) because of the incorrect The customer did not know that the fan checked.
direction of rotation. In general the losses actually increased the running In instances where there is doubt, it is
increase in power would be between temperature of the motor, since the better to contact experts in the motor
the cube and the power of five of overall temperature was well below repair and manufacture industry to
the increase in flow, thus the power the limits. However, when production ensure the motor and plant’s long term
consumption of the fans would demands increased, and the load at reliability and dependability.
increase by between 33 and 61%. which the motor ran increased, it was Contact Henk de Swardt,
Let us compare the performance found that the motor actually could Marthinusen & Coutts,
characteristics for the correct and not drive the driven load at the full Tel 011 616 2320,
incorrect direction of rotation of the fans load power without overheating. On henkd@mandc.co.za D

July 2008 - Vector - Page 46

S-ar putea să vă placă și