Sunteți pe pagina 1din 7

International Journal of Emerging Technology and Advanced Engineering

Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 10, October 2013)

Voltage Sag Mitigation in the Distributed Generation System


with STATCOM
Sumeet Trivedi1, D. Chattopadhyay2
1
M.E.Student, Power System Engg., S.S.C.E.T., Bhilai, C.G., India
2
Sr.Asso.Professor, E.E.E. Deptt., S.S.C.E.T., Bhilai, C.G., India
Abstract— This paper investigates the effect of Static
Synchronous Compensator (STATCOM) on the voltage sag in
a distributed generation system. For this purpose, the DG
system of an integrated steel plant, which is connected to 132
KV grid, is taken under study. The entire system is modelled
with STATCOM based Voltage Source Converter (VSC)
PWM technique. The voltage sag improvement of the DG
system is compared with and without STATCOM. Power
System Computer Aided Design/Electromagnetic Transients
including DC (PSCAD/EMTDC) is used to carry out
simulation of the system under study and detailed results are
shown to access the performance of STATCOM based Voltage
Source Converter.

Keywords— Distributed Generation, Voltage Sag,


STATCOM, PSCAD, PWM
Fig.1 A balanced three phase voltage sag
I. INTRODUCTION Traditional methods of Voltage Control include
A Voltage Sag as defined by IEEE Standard 1159-1995, Transformer Tap Changers both mechanical and SCR
IEEE Recommended Practice for Monitoring Electric switched units [4], Servo-Variac technology and Ferro-
Power Quality, is a decrease in RMS voltage at the power Resonant Transformers (constant voltage transformers) . In
frequency for durations from 0.5 cycles to 1 minute, some cases and for some applications these traditional
reported as the remaining voltage. The measurement of a technologies may still be applicable and work well but in
Voltage Sag is stated as a percentage of the nominal many cases they were designed to correct problems other
voltage, it is a measurement of the remaining voltage and is than voltage sags. Industrial UPS units are widely used to
stated as a sag TO a percentage value. Thus a Voltage Sag protect electronic process control equipment and to allow
to 60% is equivalent to 60% of nominal voltage, or 288 for an orderly shutdown of the process but it is rarely
Volts for a nominal 480 Volt system. Voltage sags can economic to install large UPS systems with their attendant
occur on Utility systems both at distribution voltages and large battery banks for high power electrical equipment
transmission voltages. Voltage sags which occur at higher such as high horsepower drives, extruders etc. Different
voltages will normally spread through a utility system and power electronics solutions are used for improving the
will be transmitted to lower voltage systems via performance of the power system by mitigating the voltage
transformers. Voltage sags can be created within an sag [7]. Mitigation devices are installed at the system-load
industrial complex without any influence from the Utility interface for power quality enhancement and prevent the
system. These sags are typically caused by starting large voltage dip [5],[8],[9].
motors or by electrical faults inside the facility.

153
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 10, October 2013)
At present, a wide range of very flexible controllers, By controlling the magnitude and the phase angle of the
which capitalize on newly available power electronics output voltage of the VSC, both active and reactive power
components, are emerging for custom power applications. can be exchanged between the distribution system and the
Among these, the static compensator (STATCOM) and the STATCOM. Being a shunt connected device, the
dynamic voltage restorer (DVR), both of them based on the STATCOM mainly injects reactive power to the system.
VSC principle, are the controllers which have received the
most attention. The DVR is a dynamic solution for
protection of critical loads from voltage sags / swells [6].
The DVR restores constant load voltage and voltage wave
form by injecting an appropriate voltage. Modern industrial
processes are based on a large amount of electronic devices
such as programmable logic controllers and adjustable
speed drives. Unfortunately, electronic devices are
sensitive to disturbances, and thus, industrial loads become
less tolerant to power quality problems such as voltage
sags, voltage swells, and harmonics. The dynamic voltage
restorer (DVR) has become popular as a cost effective
solution for the protection of sensitive loads from voltage
sags and swells [10].
A Static Synchronous Compensator (STATCOM) is a
static synchronous generator operated as a shunt connected
static var compensator whose capacitive or inductive output
current can be controlled in- dependent of the AC system
voltage. A STATCOM is a controlled reactive-power
Fig.2 STATCOM connected to a power system
source. It provides voltage support by generating or
absorbing reactive power at the point of common coupling The contribution of the STATCOM to the load bus
without the need of large external reactors or capacitor voltage equals the injected current times the impedance
banks. Voltage fluctuations caused by rapid industrial load seen from the device, which is the source impedance in
changes have been a major concern for both power parallel with the load impedance. The ability of the
companies and customers in the area of power quality [1]. STATCOM to compensate the voltage dip is limited by this
The fast response of the static compensator (STATCOM) available parallel impedance. In addition, the device should
makes it an efficient solution for improving power quality be installed as close to the sensitive load as possible to
in distribution systems. The STATCOM have a function of maximize the compensating capability. The STATCOM
compensating reactive power, absorbing the harmonic and also can be used in the function: power factor correction,
compensating the voltage dip [2]. mitigation of load fluctuation (including voltage flicker) [3]
and active filtering.
II. STATCOM A STATCOM functions as a shunt-connected
The Static Synchronous Compensator (STATCOM) is a synchronous voltage source which accounts for its superior
VSC that is shunt connected to the distribution system by functional characteristics, better performance, and greater
means of a tie reactance. In general, a coupling transformer application flexibility. Concerning the non-linear operating
is installed between the distribution system and the range, the STATCOM is able to control its output current
STATCOM for isolating the low voltage (STATCOM) over the rated maximum capacitive or inductive range
from the high voltage (distribution system), as shown in independently of AC system voltage. Thus, the STATCOM
Fig. The STATCOM can be seen as a current source since is more effective in providing voltage support under large
it is connected in shunt with the distribution system and the system disturbances during which the voltage excursions
load. would be well outside of the linear operating range of the
compensator.

154
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 10, October 2013)
The ability of the STATCOM to maintain full capacitive It may reduce the need for large infrastructure
output current at low system voltage also makes it more construction or upgrades because the DG can be
effective in improving the transient stability. constructed at the load location. If the DG provides power
for local use, it may reduce pressure on distribution and
transmission lines [11]. With some technologies, DG
produces zero or near-zero pollutant emissions over its
useful life (not taking into consideration pollutant
emissions over the entire product lifecycle i.e. pollution
produced during the manufacturing, or after
decommissioning of the DG system). With some
technologies such as solar or wind, it is a form of
renewable energy. It can increase power reliability as back-
up or stand-by power to customers and offers customers a
choice in meeting their energy needs [12].
In this paper, we have taken under study, the distributed
power system of NECO steel plant situated at Raipur. This
system consists of six turbo generators of small size which
generate electricity utilizing the heat of waste blast furnace
gas and coke oven gas in the boilers & produce steam to
Fig.3 STATCOM V-I characteristics run the turbines. Out of these, TG1 to TG5 generates power
The attainable response time and the bandwidth of the at 6.6 kV whereas TG6 generates at 11 kV. As it is clear in
closed voltage regulation loop of the STATCOM are the single line diagram that all the generators are ultimately
significantly better. In situations where it is necessary to connected to 132 kV CSEB grid, so the flow of power is
provide active power compensation the STATCOM is able possible in both the directions, as per condition.
to interface a suitable energy storage (large capacitor,
battery, ...) from where it can draw active power at its DC
terminal and deliver it as AC power to the system.

III. DISTRIBUTED GENERATION SYSTEM OF NECO STEEL


PLANT
Distributed generation (or DG) generally refers to small-
scale (typically 1 kW – 50 MW) electric power generators
that produce electricity at a site close to customers or that
are tied to an electric distribution system. There are many
reasons a customer may choose to install a distributed
generator. DG can be used to generate a customer’s entire
electricity supply; for peak shaving (generating a portion of
a customer’s electricity onsite to reduce the amount of
electricity purchased during peak price periods); for
standby or emergency generation (as a backup to Wires
Owner's power supply); as a green power source (using
renewable technology); or for increased reliability. In some Fig.4 Single Line Diagram of power system of NECO steel plant
remote locations, DG can be less costly as it eliminates the connected to 132 kV grid
need for expensive construction of distribution and/or
transmission lines. IV. SIMULATION IN PSCAD AND DESCRIPTION
Distributed Generation has a lower capital cost because PSCAD/EMTDC is an industry standard simulation tool
of the small size of the DG (although the investment cost for studying the transient behaviour of electrical networks.
per kVA of a DG can be much higher than that of a large
power plant).

155
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 10, October 2013)
Its graphical user interface enables all aspects of the This breaker is initially in closed condition. A portion of
simulation to be conducted within a single integrated the network is shown below with 132 kV bus and
environment including circuit assembly, run-time control, STATCOM & Fault block connected to it.
analysis of results, and reporting [15]. PSCAD/EMTDC
use in determining the exact switching times that allows the V. RESULTS AND DISCUSSION
simulation to run at high speed and does not introduce A. During Normal Condition
inaccurate results. Another valuable feature of
PSCAD/EMTDC is the accurate model provided for the 1) When the grid connected DG system is working under
wind turbine rotors, transformers, underground cables and the normal conditions and the simulation is run for no fault
other electrical and electronic devices. At present a wide (or voltage sag) introduced in the system, then the three
range of very flexible controllers, which capitalize on phase grid voltage is obtained as shown below:
newly available power electronics components, are RE : Graphs

emerging for custom power applications. Among these, the 100


V132

static compensator (STATCOM) and the dynamic voltage 75


restorer (DVR), both of them based on the VSC principle 50
and the SSTS are the controllers which have received the 25
most attention. PSCAD/EMTDC will be used to perform Voltage (kV)
0
the modelling and analysis of such controllers for a wide
-25
range of operating conditions [16]. PSCAD/EMTDC’s
-50
highly developed graphical interface has proved
-75
instrumental in implementing the graphics-based PWM
control the STATCOM [13],[14]. The single line diagram -100
Time S ...
shown above is modelled in PSCAD. 0.500 0.520 0.540 0.560 0.580 0.600 0.620 0.640
...
...

Fig.6 Three phase voltage during normal condition

2) The per unit voltage is also constant at 1.1 pu during the


whole simulation time which is in the voltage stable zone:
Voltage in pu
Vpu
2.00

1.50

1.00

0.50
Voltage pu

0.00

-0.50

-1.00

-1.50
Fig.5 Three Phase Fault block and STATCOM connected to 132 kV
bus of the network -2.00
Time S 0.0 1.0 2.0 3.0 4.0 5.0 ...
Now we connect a Three Phase Fault block in the ...
...
diagram in the 132 kV bus of the network with additional
resistance and inductance. This will create the effect of a Fig.7 Per unit voltage during normal condition
voltage sag instead of the fault, whose duration will be 3) In this condition, the fault current is zero for all the three
determined by the Timed Fault Logic. To mitigate this phases:
voltage sag, STATCOM is connected to the same bus via. a
filter, an HV breaker and a 2-wdg. transformer.

156
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 10, October 2013)
Fault Current
3) During the same interval, a fault current is flowing in all
Fault Current Ifa Fault Current Ifb Fault Current Ifc
2.00 the three phases i.e. Ifa, Ifb, Ifc is not zero for 0.75 sec.
1.50
Fault Current
1.00 Fault Current Ifa Fault Current Ifb Fault Current Ifc
Fault Current (KA)

2.00
0.50
1.50
0.00
1.00
-0.50

Fault Current (KA)


-1.00 0.50

-1.50 0.00

-2.00 -0.50
Time S 0.0 1.0 2.0 3.0 4.0 5.0 ...
-1.00
...
... -1.50

Fig.8 Fault current in three phases during normal condition -2.00


Time S 1.0 2.0 3.0 4.0 5.0 ...
B. During Voltage Sag Condition ...
...
1) By using the Three Phase Fault block, a voltage sag is
Fig.11 Fault current in three phases during voltage sag condition
introduced in the 132 kV bus voltage from 1.0 sec. to 1.75
sec. C. Effect of STATCOM on Voltage Sag
RE : Graphs 1) Now we connect a STATCOM in the 132 kV bus whose
100
V132
breaker is in initially closed position, and run the
80 simulation with the voltage sag created for 0.75 sec., we
60
observe that as soon as voltage sag is produced at 1.0 sec, it
40
is mitigated by the effect of STATCOM as it injects the
Voltage (kV)

20
0 voltage during the whole voltage dip of 0.75 sec.
-20
RE : Graphs
-40
V132
-60 150
-80
-100 100
Time S 1.0 2.0 3.0 4.0 5.0 ...
... 50
Voltage (kV)

...
0
Fig.9 Three phase voltage during voltage sag condition
-50
2) The dip in the per unit voltage is also obtained as it
-100
dropped from 1.1 pu to 0.85 pu for 0.75 sec.
Voltage in pu -150
Vpu Time S 0.80 1.00 1.20 1.40 1.60 1.80 2.00 ...
2.00 ...
1.50 ...

1.00 Fig.12 Voltage mitigation during fault by STATCOM


0.50
Voltage pu

0.00
2) Also the per unit voltage of the bus is also maintained at
-0.50 1.0 pu throughout the simulation run because STATCOM
-1.00 is connected to the bus from the starting of the run.
-1.50

-2.00
Time S 1.0 2.0 3.0 4.0 5.0 ...
...
...

Fig.10 Per unit voltage during voltage sag condition

157
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 10, October 2013)
Voltage in pu [6] Kantaria, R.A. Dept. of Electr. Eng., M. S. Univ., Baroda, India
Vpu Joshi, S.K. ; Siddhapura, K.R.‖ A novel technique for mitigation of
3.0
voltage sag/swell by Dynamic Voltage Restorer (DVR)‖
2.0
Electro/Information Technology (EIT), 2010 IEEE International
Conference on 20-22 May 2010 Page(s): 1 – 4
1.0 [7] Sannino, A. Dipt. di Ingegneria Elettrica, Palermo Univ., Italy
Miller, M.G. ; Bollen, M.H.J. ―Overview of voltage sag mitigation‖
Voltage pu

0.0 Power Engineering Society Winter Meeting, 2000.


IEEE (Volume:4) 2000 Page(s): 2872 - 2878 vol.4
-1.0
[8] Bin Wang Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
-2.0 Xinzhou Dong ; Zhencun Pan‖ Voltage sags mitigation with feeder
fast-tripping overcurrent protection‖ Electric Utility Deregulation
-3.0 and Restructuring and Power Technologies (DRPT), 2011 4th
Time S 1.0 2.0 3.0 4.0 5.0 ... International Conference on 6-9 July 2011 Page(s): 67 – 72
... [9] Ipinnimo, O. Electr. Eng. Dept., Univ. of Cape Town, Cape Town,
...
South Africa Chowdhury, S. ; Chowdhury, S.P. ―Voltage dip
Fig.13 Per unit voltage mitigation during fault by STATCOM mitigation with DG integration: A comprehensive review‖ Power
Electronics, Drives and Energy Systems (PEDES) & 2010 Power
India, 2010 Joint International Conference on 20-23 Dec. 2010
VI. CONCLUSION Page(s): 1 - 10
In this paper, the effect of voltage sag on the distributed [10] Rajasekaran, D. Department of EEE, R.M.D Engineering College,
power system of an steel plant has been studied and the role Chennai, Tamilnadu, India Dash, Subhransu Sekhar ; Vignesh, P.‖
Mitigation of voltage sags and voltage swells by Dynamic Voltage
of STATCOM on the mitigation of the voltage dip have Restorer‖ Advances in Recent Technologies in Communication and
been found out. The simulations are carried out in PSCAD Computing (ARTCom 2011), 3rd International Conference on 14-15
and its results are analysed with & without STATCOM Nov. 2011 Page(s): 36 – 40
connected in the 132 kV bus. It is clear that the presence of [11] Wang Bo Sch. of Electr. Eng., Wuhan Univ., Wuhan, China
STATCOM in the network helps in mitigating the voltage Lan Ka ―Analysis of the Distributed Generation System and the
Influence on Power oss‖ Power and Energy Engineering
sag and the bus voltage remains in the stable region. Conference (APPEEC), 2011 Asia-Pacific 25-28 March 2011
Page(s): 1 – 4
REFERENCES
[12] Barker, P.P. Power Technol. Inc., Schenectady, NY, USA
[1] Teleke, S. Quanta Technol., Raleigh, NC, USA Yazdani, de Mello, R.W.‖ Determining the impact of distributed generation on
A. ; Gudimetla, B. ; Enslin, J. ; Castaneda, J.‖ Application of power systems. I. Radial distribution systems‖
STATCOM for power quality improvement‖ Power Systems Power Engineering Society Summer Meeting, 2000.
Conference and Exposition (PSCE), 2011 IEEE/PES, 20-23 March IEEE (Volume:3 ) 2000 Page(s): 1645 - 1656 vol. 3
2011 Page(s): 1 – 6
[13] Champa Nandi, Sumita Deb, Minakshi Deb Barma, and A.K.
[2] Madhusudan, R. Dept. of Electr. & Electron. Eng., Sir C.R. Reddy Chakraborty, Member, IACSIT, ―Study and Simulation of the SVC
Coll. of Eng., Eluru, India Ramamohan Rao, G.‖ Modeling and and STATCOM Effect onVoltage Collapse and Critical Fault
simulation of a distribution STATCOM (D-STATCOM) for power Clearing Time‖, International Journal of Modeling and
quality problems-voltage sag and swell based on Sinusoidal Pulse Optimization, Vol. 2, No. 4, August 2012, Pg. no. 462-465
Width Modulation (SPWM)‖Advances in Engineering, Science and
Management (ICAESM), 2012 International Conference on 30-31 [14] Champa Nandi and A. K. Chakraborty , Wind Power Plants with
March 2012 Page(s): 436 – 441 VSC Based STATCOM in PSCAD/EMTDC Environment, 2012
2nd International Conference on Power and Energy Systems (ICPES
[3] Ag ero J. . Fac. de Ingenieria, Universidad Nacional de La 2012) DOI: 10.7763/IPCSIT.2012.V56.2 IPCSIT vol. 56 (2012) ©
Plata Issouribehere, F. ; Battaiotto, P.E.‖STATCOM modeling for (2012) IACSIT Press, Singapore, Pg. no. 7-11
mitigation of voltage fluctuations caused by electric arc furnaces
―Power Engineering Society General Meeting, 2006. IEEE [15] Olimpo Anaya-Lara and E. Acha, Modeling and Analysis of
Custom Power Systems by PSCAD/EMTDC, IEEE
[4] Salman, N. Dept. of Electr., Electron. & Syst. Eng., Univ. TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 1,
Kebangsaan Malaysia, Bangi, Malaysia ,Mohamed, A. ; Shareef, H.‖ JANUARY 2002, Pg. no. 266-272
Voltage sag mitigation in distribution systems by using genetically
optimized switching actions‖ Power Engineering and Optimization [16] S. Bozhko, R. Li, R. Blasco-Gimenez, G. M. Asher, J. C. Clare,
Conference (PEOCO), 2011 5th International Date of Conference: 6- L.Yao, and C. Sasse, STATCOM-controlled HVDC Power
7 June 2011 Page(s): 329 – 334 Transmission for Large Offshore Wind Farms: Engineering Issues,
Pg. no. 4219-4224
[5] Wang, P. Centre for Electr. Energy, Univ. of Manchester Inst. of
Sci. & Technol., UK Jenkins, N. ; Bollen, M.H.J. ―Experimental
investigation of voltage sag mitigation by an advanced static VAr
compensator‖ Power Delivery, IEEE Transactions on (Volume:13,
Issue: 4 ) Oct 1998Page(s):1461 – 1467

158
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 10, October 2013)
AUTHOR’S PROFI E D. Chattopadhyay is currently working as Sr. Asso.
Professor in S.S.C.E.T., Bhilai. She has done her M.E. in
Sumeet Trivedi is pursuing his M.E. in Power Systems.
Power Systems Engg. from S.S.C.E.T.,
Bhilai.

159

S-ar putea să vă placă și