OPERATING INSTRUCTIONS 8.

ISOLATION BREAKDOWN RATINGS:


AC line with respect to all inputs and outputs: 3. Circuit breaker or mains switch must be installed between 2. For bigger loads, use interposing relay / contactor
PIC101-N 2000 Volts power source and supply terminals to facilitate power 'ON'
or 'OFF' function. However this switch or breaker must be TC
9. ENVIRONMENTAL CONDITIONS: installed in a convenient position normally accessible to the TC Contactor
Operating Range: 0 to 50oC operator.
Storage Range: -20 to 75oC C NO
! CAUTION: R C
Humidity: 85% max.
1. The equipment shall not be installed in environmental MOV Snubber
10. CONNECTION: Wire clamping screw terminal conditions other than those mentioned in this manual.
C
LOAD
48 x 96 2. Fuse Protection: The equipment does not have a built-in-
11. WEIGHT: 250 grams
type fuse. Installation of external fuse ofrating75VAC/1Amp
FEATURES for electrical circuitry is highly recommended. 1) Snubber Part No.: APRC - 01.
SAFETY SUMMARY 2) MOV Part No.: AP-MOV - 03.
! Accepts Sensor Inputs : Thermocouple /
RTD All safety related codifications, symbols and instructions 3. Thermal dissipation of equipment is met through ventilation Note: For inductive loads, use of snubber and
Analog inputs: mV, Current, Voltage.
that appear in this operating manual or on the equipment holes provided on chassis of equipment. Such ventilation MOV, as shown above, is recommended.
must be strictly followed to ensure the safety of the operating
! High Indication Accuracy: ± 0.25%. holes shall not be obstructed else it can lead to a safety ELECTRICAL PRECAUTIONS DURING USE
personnel as well as the instrument.
! Sensor Break Detection. If the equipment is not handled in a manner specified by hazard. Electrical noise generated by switching of inductive
the manufacturer it might impair the protection provided by the loads can create momentary disruption, erratic display,
! 24 VDC Sensor Supply. latch up, data loss or permanent damage to the instru-
equipment. 4. The output terminals shall be strictly loaded to the
! 85 to 270 VAC Supply Voltage. manufacturer specified values/range. ment. To reduce noise:
! CAUTION: Read complete instructions prior to a) Use of MOV across supply of temperature
Installation and operation of the unit. MECHANICAL INSTALLATION: controller & snubber circuits across loads are
SPECIFICATIONS Recommended
1. DISPLAY CAUTION: Risk of electric shock. b) Use s eparate shielded wires for inputs.
For installing the controller
4-digit (7 segment LED) 0.5" height 1. Prepare the panel cutout with proper dimensions as
Display Messages: WIRING GUIDELINES shown (in mm)
TERMINAL CONNECTIONS
“Or” - Appears when mV/TC/RTD
CAUTION:
1) Measurement exceeds display scaling 1. To prevent the risk of electric shock power supply to the + - V mA CONFIG
range (9999) 50 45 46 Panel Cutout
equipment must be kept OFF while doing the wiring A B B’ + - + -
2) Open sensor is detected. arrangement.
“rE” - Appears when 97.5 88 92 1 2 3 4 5 6 7 8 9 10
10
1) Measurement is below display scaling 2. Wiring shall be done strictly according to the terminal 2. Push the controller into the panel cutout. Secure the 22 24
range (-1999) layout with shortest connections. Confirm that all controller in its place by pushing the clamp on the
2) Sensor reverse condition occurs. connections are correct. rear side. The screws, of the pane of the clamp, must 21 23
be in the farthest forward slot.
2. POWER SUPPLY 3. Use lugged terminals to meet M3 screws.
85 to 270 VAC/DC (AC: 50 or 60 Hz), 5 VA 11 12 13 14 15 16 17 18 N L
3. For proper sealing, tighten the screws evenly with
4. To eliminate electromagnetic interference use of short required torque. +24V GND
3. SETTINGS Via three keys on front panel. wire with adequate ratings and twists of the same in sensor supply - +
equal size shall be made. ! CAUTION:
4. MEMORY The equipment in its installed state must not come in CONFIGURATION SCHEME
5. Cable used for connection to power source, must have a
Nonvolatile EEPROM retains all close proximity to any heating sources, caustic vapors, oils, METHOD 1:
cross section of 1mm2 or greater. These wires shall have
programmable parameters and values. steam, or other unwanted process by-products. 1. Short terminals 9 and 10.
insulation capacity made of at least 1.5KV.
2. Turn Power ON. 3. Remove the shorting.
5. MAIN SENSOR INPUT MAINTENANCE EMC Guidelines: Unit will directly enter into programming mode.
Thermocouple inputs 1. Use proper input power cables with shortest METHOD 2:
J : -200 to 750oC 1. The equipment should be cleaned regularly to avoid
blockage of ventilating parts. connections and twisted type. Press + for 3 sec to enter into Programming
K : -200 to 1350oC
T : -200 to 400oC 2. Clean the equipment with a clean soft cloth . Do not 2. Layout of connecting cables shall be away from any Key press Display Description
R : 0 to 1750oC use isopropyl alcohol or any other cleaning agent. internal EMI source.
S : 0 to 1750oC 1. Lock code for program entry
Factory setting:
RTD input (2 wire or 3 wire) INSTALLATION GUIDELINES LOAD CONNECTIONS NOTE: This parameter will not be prompted if programming is
PT100: -100 to 850oC 1. For load current less than 0.5A entered using METHOD 1.
! CAUTION:
mV : 0 - 56 mV 1. This equipment, being built-in-type, normally becomes a
Voltage: 0 to 10 VDC part of main control panel and in such case the terminals N
L (Display for 1 second)
Current: 0 to 20 mA do not remain accessible to the end user after installation
and internal wiring. TC
6. SENSOR SUPPLY TC
24 VDC (30mA) to power the sensors 2. Conductors must not come in contact with the internal LOAD Press + key and program the lock code
C NO
circuitry of the equipment or else it may lead to a safety as
R C
7. INDICATION ACCURACY hazard that may in turn endanger life or cause electrical
MOV
Temperature: 0.25% of Span ±1oC (After shock to the operator. Snubber
20min. Warmup)
Document name: Operating / 0807/ PIC101-N / OP162-V03
Page 1 of 2
Key press Display Description Key press Display Description Program Exit: CALIBRATION CERTIFICATE
2. Press to program Sensor type Press + key for 3 sec Date:
7. Press key to program Display
Factory setting: Unit will auto exit the programming
scaling point high Factory setting: Model No:
NOTE: Valid for analog inputs (mV, current, voltage) mode if no key is pressed for 60 sec
(Display for 1 second) Sr. No.:
o (Display for 1 second) USER GUIDE
J : -200 to 750 C Claimed Accuracy: ± 0.25 % of full scale ± 1
SCALING FOR ANALOG INPUT:
Press + / digit (After 20min warmup time)
Press + K : -200 to 1350oC Range:DSCL to 9999 To scale the controller, two scaling points are necessary.
to change value. ( display as per decimal
Each scaling point has a coordinate pair of Display Values
Press + T : -200 to 400oC point selected.)
and Input Values. It is recommended that the two scaling Sources calibrated against:
points be at the low and high ends of the input signal being
o Hinditron Multimeter, Model 86, Sr.No.:1094
Press + R : 0 to 1750 C 8. Press key to program Input measured. Process value scaling will be linear between and
scaling point high continue past the entered points to the limits of the input
o Factory setting: Multimeter calibration report no:
Press + S : 0 to 1750 C range. (Factory settings example will display 0.0 at 0 mA
NOTE: Valid for analog inputs (mV, current, voltage) input and display 9999 at 20.00 mA input.) Reverse acting ERTL (W), Mumbai, INDIA
PT100 indication can be accomplished by setting
Press +
(-100 to 850OC) (Display for 1 second) The calibration of this unit has been verified at the
DISPLAY reverse scaling parameter
Press + mV : 0 to 56 mV following values:
as YES. In this case
Press + / referring the above eg.
Range : ISCL to 9999 CALIBRATION DISPLAY
Press + Current to change value. for 0.00 mA input the
20.00mA/10.00V/56mV SENSOR TEMP.(OC) VALUE
(default value changes as per display will show 9999 and ( 0.1Resolution) (oc)
Press + Voltage analog input selected) 20.00 mA input the display
0.0
will show 0.0. 35.0 35.0
3. Press to program Resolution. 9. Press key to select Reverse scaling 0.00mA 20.00mA
INPUT
NOTE : This change will K 700.0 700.0
Factory setting: Factory setting: not be visible in the 1350 1350
NOTE: Valid for analog inputs (mV, current, voltage) ISC.L = 0.00 ISC.H = 20.00 programming menu. 0.0 0.0
DSC.L = 0.0 DSC.H = 9999
(Display for 1 second) RSCL = no PT100 500.0 500.0
O
TC/RTD: 1 / 0.1 C (Display for 1 second) 800.0 800.0
Analog input: 1/ Connection with 2-wire Transmitter
CALIBRATION
Press + 0.1/0.01/0.001 Eg. : for 4-20 mA input SENSOR VALUE DISPLAY
(Decimal point Press + ( 0.1Resolution) VALUE
Press + Connection with Internal 24VDC Sensor supply :
position)
10. Press key to program Filter time - Voltage 0.0 0.0
Two-wire
Press + constant Transmitter (VDC)
Factory setting: + 10.0 10.0
4. Press key to select Temperature unit.
Factory setting:
mA CONFIG
Current 0.0 0.0
NOTE: Valid for TC / RTD inputs (Display for 1 second) + -
(mA)
1 2 3 4 5 6 7 8 9 10 20.0 20.0
Press + / Range : OFF, 1 to
(Display for 1 second) 22 24
to change value. 99 sec. The thermocouple / RTD curves are linearised in
21 23 this microprocessor based product; and hence the
11. Press key to program PV Bias
11 12 13 14 15 16 17 18 N L values interpolated between the readings shown
Press + Factory setting: above are also equally accurate; at every point in
+24V GND
- + the curve.
5. Press key to program Display
(Display for 1 second) Unit is accepted as accuracy is within the
scaling point low Factory setting:
Connection with external 24VDC supply : specified limit of claimed accuracy and certificate
NOTE: Valid for analog inputs (mV, current, voltage) Press + /
Range : -99.9 to +
is valid up to one year from the date of issue
(Display for 1 second) to change value. External
+ 99.9 OC 24 VDC
+
(Fixed 0.1 resl for TC/RTD
- Supply CHECKED BY:
Press + / Range: -1999 to DSCH & 1 unit for analog input)
Two-wire
Transmitter
( display as per decimal
to change value. point selected.) 12. Press key to select reset all -
6. Press key to program Input Factory setting: mV/TC/RTD
+ - V mA CONFIG (Specifications subject to change as development
scaling point low Factory setting:
+ - + -
A B B’ is a continuous process).
NOTE: Valid for analog inputs (mV, current, voltage) (Display for 1 second)
1 2 3 4 5 6 7 8 9 10
Selec Controls Pvt. Ltd., India.
(Display for 1 second) 22 24 (Formerly Selectron Process Controls Pvt. Ltd.)
Tel:91-22-28476443/1882, Fax:91-22-28471733,
Press + / 21 23 Toll free: 1800 227 353, Website: www.selecindia.com
Range: 0.0mA/V/mV Press +
to change value. 11 12 13 14 15 16 17 18 N L E- mail: sales@selecindia.com.
to ISCH
(default value changes Press key to reset all the parameters +24V GND Document name: Operating / 0807/ PIC101-N / OP162-V03