Sunteți pe pagina 1din 4

IEC103 Protocol for ADR241S Thursday, November 08, 2012

Revision No.: 01

IEC103 Protocol for ADR241S

Function Code: 160 (A0h) for Over- current Protection Relay

Semantics of INFORMATION NUMBER: System Functions in monitor direction


(Ref. IEC60870-5-103 tabel-8)
INF Description GI TYP COT FUN (typical)
<0> End of general interrogation - 8 10 <255>
<0> Time synchronization - 6 8 <255>
<2> Reset FCB - 5 3 160
<3> Reset CU - 5 4 160
<4> Start/Restart - 5 5 160
<5> Power on - 5 6 160

Semantics of INFORMATION NUMBER: Status indications in monitor direction


(Ref. IEC60870-5-103 table-9)
INF Description GI TYP COT FUN (typical)
<18> Protection active X 1 1,7,9,11,12,20,21 160
<19> LED Reset - 1 1,7,11 160
<21> Test X 1 9,11 127
<22> Local Parameter setting X 1 9,11 160
<23> Char. 1 (Setting group1 active) X 1 1,7,9,11,12,20,21 160
<24> Char. 2 (Setting group2 active) X 1 1,7,9,11,12,20,21 160
<25> Char. 3 (Setting group3 active) X 1 1,7,9,11,12,20,21 160
<26> Char. 4 (Setting group4 active) X 1 1,7,9,11,12,20,21 160
<27> Status 1 X 1 1,7,9,11 160
<28> Status 2 X 1 1,7,9,11 160
<29> Status 3 X 1 1,7,9,11 160
<30> Status 4 X 1 1,7,9,11 160
<124> Trip X 1 1,7,9,11,12,20,21 127

ASHIDA Electronics PVT. Ltd., Thane Page 1 of 4


IEC103 Protocol for ADR241S Thursday, November 08, 2012
Revision No.: 01

Semantics of INFORMATION NUMBER: Fault indications in monitor direction


(Ref. IEC60870-5-103 table-12)
INF Description GI TYP COT FUN (typical)
<64> start/ pick-up L1 X 2 1,7,9 160
<65> start/ pick-up L2 X 2 1,7,9 160
<66> start/ pick-up L3 X 2 1,7,9 160
<68> General Trip - 2 1,7,9 160
<69> trip L1 - 2 1,7 160
<70> trip L2 - 2 1,7 160
<71> trip L3 - 2 1,7 160
<84> general start/ pick-up X 2 1,7,9 160
<90> trip I> - 2 1,7 160
<91> trip I>> - 2 1,7 160
<123> Trip Ie> - 2 1,7 126
<124> Trip Ie>> - 2 1,7 126
<155> OL1 pickup X 2 1,7,9 126
<156> OL2 pickup X 2 1,7,9 126
<157> OL3 pickup X 2 1,7,9 126
<158> Trip OL1 - 2 1,7 126
<159> Trip OL2 - 2 1,7 126
<160> Trip OL3 - 2 1,7 126
<225> CLP - 2 1,7 126

ASHIDA Electronics PVT. Ltd., Thane Page 2 of 4


IEC103 Protocol for ADR241S Thursday, November 08, 2012
Revision No.: 01

Semantics of INFORMATION NUMBER: Measurands in monitor direction


(Ref. IEC60870-5-103 table-14)
INF Description GI TYP COT FUN (typical)
<147> Measurand IN, VEN - 3.4 2, 7 160
<148> Measurand IL 1,2,3, VL 1,2,3. , P, Q, f - 9 2, 7 160
(Note : VL 1,2,3. , P, Q, f are invalid)

ASHIDA Electronics PVT. Ltd., Thane Page 3 of 4


IEC103 Protocol for ADR241S Thursday, November 08, 2012
Revision No.: 01

Semantics of INFORMATION NUMBER: System Functions in control direction


(Ref. IEC60870-5-103 table-16)
INF Description TYP COT FUN (typical)
<0> Initialization of general interrogation 7 9 <255>
<0> Time synchronization 6 8 <255>

Semantics of INFORMATION NUMBER: General commands in control direction


(Ref. IEC60870-5-103 tabel-17)
INF Description COM* TYP COT FUN (typical)
<19> LED Reset ON 20 20 160
<124> Trip ON 20 20 127

* Permissible selections of DCO values are specified in COM column (Ref. IEC60870-5-103
Section7.2.6.4)

ASHIDA Electronics PVT. Ltd., Thane Page 4 of 4