IEC103 Protocol for ADR241S Thursday, November 08, 2012
Revision No.: 01
IEC103 Protocol for ADR241S
Function Code: 160 (A0h) for Over- current Protection Relay
Semantics of INFORMATION NUMBER: System Functions in monitor direction
(Ref. IEC60870-5-103 tabel-8) INF Description GI TYP COT FUN (typical) <0> End of general interrogation - 8 10 <255> <0> Time synchronization - 6 8 <255> <2> Reset FCB - 5 3 160 <3> Reset CU - 5 4 160 <4> Start/Restart - 5 5 160 <5> Power on - 5 6 160
Semantics of INFORMATION NUMBER: Status indications in monitor direction
(Ref. IEC60870-5-103 table-9) INF Description GI TYP COT FUN (typical) <18> Protection active X 1 1,7,9,11,12,20,21 160 <19> LED Reset - 1 1,7,11 160 <21> Test X 1 9,11 127 <22> Local Parameter setting X 1 9,11 160 <23> Char. 1 (Setting group1 active) X 1 1,7,9,11,12,20,21 160 <24> Char. 2 (Setting group2 active) X 1 1,7,9,11,12,20,21 160 <25> Char. 3 (Setting group3 active) X 1 1,7,9,11,12,20,21 160 <26> Char. 4 (Setting group4 active) X 1 1,7,9,11,12,20,21 160 <27> Status 1 X 1 1,7,9,11 160 <28> Status 2 X 1 1,7,9,11 160 <29> Status 3 X 1 1,7,9,11 160 <30> Status 4 X 1 1,7,9,11 160 <124> Trip X 1 1,7,9,11,12,20,21 127
ASHIDA Electronics PVT. Ltd., Thane Page 1 of 4
IEC103 Protocol for ADR241S Thursday, November 08, 2012 Revision No.: 01
Semantics of INFORMATION NUMBER: Fault indications in monitor direction
IEC103 Protocol for ADR241S Thursday, November 08, 2012 Revision No.: 01
Semantics of INFORMATION NUMBER: Measurands in monitor direction
(Ref. IEC60870-5-103 table-14) INF Description GI TYP COT FUN (typical) <147> Measurand IN, VEN - 3.4 2, 7 160 <148> Measurand IL 1,2,3, VL 1,2,3. , P, Q, f - 9 2, 7 160 (Note : VL 1,2,3. , P, Q, f are invalid)
ASHIDA Electronics PVT. Ltd., Thane Page 3 of 4
IEC103 Protocol for ADR241S Thursday, November 08, 2012 Revision No.: 01
Semantics of INFORMATION NUMBER: System Functions in control direction
(Ref. IEC60870-5-103 table-16) INF Description TYP COT FUN (typical) <0> Initialization of general interrogation 7 9 <255> <0> Time synchronization 6 8 <255>
Semantics of INFORMATION NUMBER: General commands in control direction
(Ref. IEC60870-5-103 tabel-17) INF Description COM* TYP COT FUN (typical) <19> LED Reset ON 20 20 160 <124> Trip ON 20 20 127
* Permissible selections of DCO values are specified in COM column (Ref. IEC60870-5-103 Section7.2.6.4)