Sunteți pe pagina 1din 3

1 2 3 4 5 6 7 8

=H06 =H07 =H08


+H06 +H07 +H08
=HZ06 =HZ07 =HZ08
A A

-Q0
B B

-Q1 -Q1

630 A 630 A
M M
-Q1

630 A

C C
-A51 -A51 -A51

-H71 -H71
D I >> I >> D
Sicam FCM Sicam FCM

-T21 L1,L2,L3
50A/1A
3 5 VA Cl. 5P10

E E

Arrivée Départ Départ


Boucle TRBRW4 Boucle

F System/rated frequency Operating voltage Rated voltage Rated short-time withst. curr. Rated normal current F
3~50 Hz 30.0 kV 36.0 kV 16.0 kA (1 s) 630 A
Printout 11/10/2016 8DJH36 aema-18fglpg =H00
Created by Dox ICC SAL Siemens AG 8DJH36 +H00 B01
Checked by Bloc 100_30kV TA30 BRW 8DJH36-08124 Sh.No 01-
Issue Revision Date Name Standard Orig. / Repl. f. / Repl. by Single Line Diagram 1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FRONT VIEW
=H06 =H07 =H08
+H06 +H07 +H08
A =HZ06 =HZ07 =HZ08 A

B B

C C

430mm 590mm
35mm
1485mm
D D

T*1

LOAD DATA AND MINIMUM DISTANCES

1.) MAX. PERMANENT LOADS


Fv VERTICAL SINGLE LOAD
PANEL WIDTH 430 mm 1.80 kN
PANEL WIDTH 500 mm 3.00 kN
PANEL WIDTH 590 mm
without vt’s 4.70 kN
E with vt’s 7.70 kN E
PANEL WIDTH 1100 mm 7.40 kN

2.) NON PERMANENT LOADS


pa MAX LIVE LOAD 12 kN/m²

3.) MINIMUM DISTANCES


WALL CLEARANCE REAR ≥ 30 mm
WALL CLEARANCE LEFT / RIGHT ≥ 100 mm
WITH EXTENSION ≥ 200 mm

4.) HEIGHT OF CEILING


SWITCHGEAR HEIGHT 1600 mm * ≥ 2000 mm
SWITCHGEAR HEIGHT 2000 mm ≥ 2200 mm
SWITCHGEAR HEIGHT 2200 mm ≥ 2400 mm

5.) MINIMUM DOOR OPENING


SWITCHGEAR HEIGHT ≤ 1700 mm * 1000 mm x 2000 mm
SWITCHGEAR HEIGHT 2000 mm 1000 mm x 2200 mm THE LOCATION AND DETAIL DIAGRAMS
F SWITCHGEAR HEIGHT 2200 mm 1000 mm x 2400 mm DO HAVE SYMBOLIC CHARACTER AND System/rated frequency Operating voltage Rated voltage Rated short-time withst. curr. Rated normal current F
* WITHOUT CABLE DUCT OR LV-CABINET DO NOT SHOW THE ACTUAL SCOPE OF
SUPPLY.
3~50 Hz 30.0 kV 36.0 kV 16.0 kA (1 s) 630 A
Printout 11/10/2016 8DJH36 aema-18fglpg =H00
Created by Dox ICC SAL Siemens AG 8DJH36 +H00 B01
Checked by Bloc 100_30kV TA30 BRW 8DJH36-08124 Sh.No 01-
Issue Revision Date Name Standard Orig. / Repl. f. / Repl. by Location diagram 1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PLAN VIEW
=H06 =H07 =H08
+H06 +H07 +H08
A =HZ06 =HZ07 =HZ08 A

B B

C WxD WxD WxD C


350x756 550x756 390x756

430mm 590mm

1450mm

T*1

D D

LOAD DATA AND MINIMUM DISTANCES

1.) MAX. PERMANENT LOADS


Fv VERTICAL SINGLE LOAD
PANEL WIDTH 430 mm 1.80 kN
PANEL WIDTH 500 mm 3.00 kN
PANEL WIDTH 590 mm
without vt’s 4.70 kN
E with vt’s 7.70 kN E
PANEL WIDTH 1100 mm 7.40 kN

2.) NON PERMANENT LOADS


pa MAX LIVE LOAD 12 kN/m²

3.) MINIMUM DISTANCES


WALL CLEARANCE REAR ≥ 30 mm
WALL CLEARANCE LEFT / RIGHT ≥ 100 mm
WITH EXTENSION ≥ 200 mm

4.) HEIGHT OF CEILING


SWITCHGEAR HEIGHT 1600 mm * ≥ 2000 mm THESE CONSTRUCTIONAL DATA OF
SWITCHGEAR HEIGHT 2000 mm ≥ 2200 mm SIEMENS AG ARE NOT BINDING FOR
SWITCHGEAR HEIGHT 2200 mm ≥ 2400 mm CONSTRUCTION. THEY ARE ONLY VALID
AS A BASE FOR PRODUCTION OF
5.) MINIMUM DOOR OPENING BINDING CONSTRUCTIONAL DRAWINGS.
SWITCHGEAR HEIGHT ≤ 1700 mm * 1000 mm x 2000 mm FURTHER INFORMATION ACCORDING
SWITCHGEAR HEIGHT 2000 mm 1000 mm x 2200 mm CONSTRUCTIONAL DATA CAN BE
F SWITCHGEAR HEIGHT 2200 mm 1000 mm x 2400 mm FOUND IN THE RELATED OPERATING System/rated frequency Operating voltage Rated voltage Rated short-time withst. curr. Rated normal current F
* WITHOUT CABLE DUCT OR LV-CABINET AND INSTRUCTION MANUAL. 3~50 Hz 30.0 kV 36.0 kV 16.0 kA (1 s) 630 A
Printout 11/10/2016 8DJH36 aema-18fglpg =H00
Created by Dox ICC SAL Siemens AG 8DJH36 +H00 B01
Checked by Bloc 100_30kV TA30 BRW 8DJH36-08124 Sh.No 01-
Issue Revision Date Name Standard Orig. / Repl. f. / Repl. by Constructional Data 1
1 2 3 4 5 6 7 8

S-ar putea să vă placă și