Documente Academic
Documente Profesional
Documente Cultură
Number of Area of open door Geometrical Area=Half Flow Total flow through
open doors m2 of actual area(AS PER velocity open doors (Q2)
ASHRAE) m/s L/s
3 2.42 1.21 1.5 5445
AIR LEAKAGE THROUGH STAIR 1
0.000014 0.00090691
0.0405 50 0.240 19 4.566
0.006 0.0396
4566
FAHU SCHEDULE
HEAT
SUPPLY AIR
TOTAL STATIC
SUPPLY AIR FLOW RETURN AIR FLOW SUPPLY AIR FLOW MOTOR ON WHEEL
AHU REFERENCE ESP (Pa) PRESSURE RATING
RATE (LPS) RATE (LPS) RATE (LPS) (kW) TEMP - DB /
(Pa) WB (°C)
1. Units shall be factory assembled and Eurovent certified for the following :
a) D1 class for mechanical strength
b) L1 class for negative (-400Pa) and positive (-700Pa) casing leakage
c) T2 class for thermal transmittance
d) TB2 class for thermal bridging using polyamide profiles
e) F9 class for filter bypass leakage.
2.Units shall be built with pentapost extruded aluminium profiles for rigid construction
3. Panels shall be of 50mm thickness with inner / outer skin of 0.7 mm GI /0.7 mm PPGI.
4. Roof exposed units to be provided with weather proof canopy.
5. Contractor shall provide static pressure calculations for all units and obtain approval before ordering the units.
6 Units shall be installed to manufacturer's installation instructions.
HEAT RECOVERY WHEEL HORSE SHOE HEAT PIPE DETAILS CO
TOTAL SENSIBLE
SUPPLY AIR AIR ON EXTRACT AIR
OFF WHEEL EXTRACT AIR ON PRE- AIR OFF PRE- AIR ON RE-HEAT AIR OFF RE-HEAT COOLING COOLING
OFF WHEEL
TEMP - DB / WHEEL TEMP - TEMP - DB / WB COOL TEMP - COOL TEMP - TEMP - DB / TEMP - DB / WB COIL COIL
DB / WB(°C) DB / WB (°C) DB / WB(°C) WB(°C) (°C) CAPACITY CAPACITY
WB(°C) (°C) (kW) (kW)
32.9 / 23.5 26.0 / 18.7 40.8 / 27.3 32.9 / 23.5 25.2 / 21.4 14.0 / 13.6 21.7 / 16.4 172.53 81.49
32.7 / 23.4 26.0 / 18.7 40.9 / 27.4 32.7 / 23.4 25.0 / 21.3 14.0 / 13.6 21.7 / 16.4 144.85 68.39
COOLING COIL DETAILS DIMENSIONAL DETA
EXTRACT
AIR ON COIL AIR OFF COIL FLUID FAN AIR ESP (Pa) TOTAL STATIC
TEMP - DB / TEMP - DB / CHW IN / OUT CHW FLOW MOTOR LENGTH
PRESSURE FLOW PRESSURE
TEMP(°C) RATE LPS RATE RATING (kW) (mm)
WB (°C) WB (°C) DROP (KPa) (Pa)
(LPS)
25.2 / 21.4 14.2 / 13.9 5.5 / 14.5 4.6 18.58 5350 500 840 11.0 5750
25.0 / 21.3 14.3 / 14.0 5.5 / 14.5 3.8 15.26 4548 500 835 7.5 5750
DIMENSIONAL DETAILS
2300 3290 1
2200 3060 1