General Model RAMC-Series

Metal Short-stroke Rotameter®


Specifications

Rotameters operate on the principle of generating a


condition of dynamic balance within the flow meter in which
a float is positioned in accordance with the flow through the
flow meter. The position of the float is magnetically trans-
mitted to the indicator.
The short-stroke Rotameter allows the measurement of
high flow rates using a relative short metering tube. It is a
stainless steel armoured construction for the safe measure-
ment of a variety of liquids, gas and steam.
It’s special application is for hazardous, dangerous or
aggressive fluids, for high temperatures and high pressure
rates. The instrument is mounted in a vertical pipeline with
flow direction upwards.

FEATURES
● Different process connections like flanges
according to DIN and ASME
● All wetted parts in stainless steel
● Different linings for aggressive fluids
● Maximum flow 0.025 - 130 m3/h water resp.
0.75-1400 m3/h air (20°C, 1.013 bar abs.)
● Accuracy class 1.6 resp. 2.5 with lining
according to VDI/VDE 3513
● Conically forged and linearized tube
● Optional floatdamping to avoid vibrations of compres-
sions with gas applications
● Optional heating jacket for steam or liquid heat carrier
● Indicator housing in stainless steel, aluminium
or plastic of protection class IP65
● Local indication without additional power supply
● Microprocessor controlled transmitter with 24 V,
115 V or 230 V power supply
● Intrinsically safe version (Ex) possible
● Optional inductive alarms
Electronic transmitter as standard with
local-controlling display with the following featu-
res:
● Flow indication (totalizer, percent, actual)
● Indication of different volume and massflow units
● Second (manual) calibration storing
● Patented float blocking indication function
● Signal output damping
● Error message indication

GS 1R1B2-E-H
YOKOGAWA 9th edition
2

STANDARD SPECIFICATIONS A flow proportional output pressure is ermitted by an amplifier


The responsibility with respect to the suitability and unit coupled with a spring bellow.
according application of our flowmeter is only Linearity : ± 2.2 % f.s.
situated by the customer Reproducebility : ± 0.2% f.s.
Hystheresis : ± 0.9% f.s.
Metering tubes Supply pressure : (1.4 ±0.1) bar g
Construction : conically forged and linearized tube Output pressure : 0.2 ... 1.0 bar g
Min. air consumption: 250 l/h at 1.4 bar g and 20 °C
Material of wetted Max. air consumption
components : - stainless steel : > 700 l/h at 1 bar abs. and 20 °C
AISI 316Ti (1.4571) Supply pressure influence
- PTFE : 0.8% f.s. / 0.1 bar
- other materials on request Load influence (0.6 bar)
: 0.5 % f.s. at 120 l/h
Fluids to be : 1.2 % f.s. at 240 l/h
measured : suitable for a variety of liquids, : 3.2 % f.s. at 500 l/h
gas and steam Ambient temperature
Measuring range : refer to table 2 and 3 on page 12-15 : see fig. 6b on page 8
Rangeability : 10:1 Temperature influence: 0.04% f.s. /K

Process connections
- Flanges : - acc. to DIN 2501 formC
DN15 - DN100 PN40
DN100 PN16
- acc. to ASME B 16.5
1/2“ - 4“ 150 lbs RF
1/2“ - 4“ 300 lbs RF
- Threaded
connection : - acc. DIN 11851 male
- NPT-female, Rp-female
- Clamp : specification refer to table 4 on page 18

Indication
Principle : indication by means of magnetic
coupling between an encapsulated
magnet in the float and a magnet located
in the rear of the indicator which follows
the float movement

Indicator housing
- materials : - glass filled PA painted
- cast aluminium painted
- stainless steel (1.4301)
each with security glass window
- Protection : IP65

Scales
- standard : detachable aluminium plate with
single scale (dual optional)
- inscription : direct reading units or
percentage of maximum flow

Standard conduit glands


Aluminium housing
: PG11
Stainless steel and polyamid housing
: M16x1.5
- Cable diameter : 6 - 9mm
- Max. wire cross section
: Ø 1.5 mm2

Installation
Position : vertical
Flow direction : upwards
Face to face length: refer to table 5+6 on page 19
Straight pipeline : DN 80/100 at least 5D,
for smaller sizes not required

Weight
Refer to table 7 on page 19

GS 1R1B2-E-H
3

ELECTRONIC TRANSMITTER (WT-MAG) ELECTRIC TRANSMITTER FOR HAZARDOUS AREAS


Digital display : 8-digits 7-segments LCD-display According ATEX intrinsic safe EN 50020 (option XE)
character height 6 mm Output signal : 4 - 20 mA / 0 - 20 mA
Power supply Explosion proof : EG-Type Examination Certificate
- 4-wire units with galvanic isolation acc. EEx ia II T6
: 230 V AC +10 %/-15 %, 50/60 Hz, Entity parameters : acc. EC-Type Examination Certifi-
miniature fuse 0.063 A, time lag, cate PTB 96 ATEX 2160X
(5x20) mm (see fig. 4 on page 6)
: 115 V AC +10%/-15 %, 50/60 Hz,
miniature fuse 0.125 A, time lag, According ATEX non incendive EN 50021 (option XN)
(5x20) mm Output signal : 4 - 20 mA / 0 - 20 mA
- 2/3-wire units without galvanic isolation Explosion proof : acc. EEx nL IIC T6 X
: 13.5 V... 30 V DC (protection type „n“)
Output signal Entity parameters : see fig. 4 on page 6
- 4-wire units : 0 - 20 mA, 4 - 20 mA
pulse output (option /CP) Attention:
refer fig. 3 on page 6 The maximum allowed ambient temperature of the enclosured
- 3-wire units transmitter must not be exceeded due to heat transfer from the
: 0 - 20 mA, 4 - 20 mA measured fluid!
- 2-wire units : 4 - 20 mA The dependency between ambient temperature and maximum
HART-communication operation temperature is illustrated on page 8 and 9.
- 2-wire units : 4 - 20 mA
: FSK signal modulated on current output POWER SUPPLY FOR INTRINSICALL SAFE
acc. HCF protocoll. ELECTRONIC TRANSMITTER
Load resistance Type : intrinsically safe power supply with
- 4-wire units : ≤ 500 Ω galvanically separated input and
- 2/3-wire units : (VP-13.5 V)/20 mA output (SINEAX B811)
- HART units : 250 ... 500 Ω Supply voltage : 24 V to 60 V AC/DC
Medium temperature : 85 V to 230 V AC
: Dependant from the ambient Maximum load impedance: 750 Ω
temperature, Output signal : 0/4 mA - 20 mA
see graphs on page 8 and 9
Control circuit : intrinsically safe [EEx ia] IIC
Ambient temperature
Entity parameters : acc. to certificate of conformity
: see graphs on page 8 and 9
PTB 97 ATEX 2083,
Storage temperature
see fig. 4 on page 6.
: -40 °C up to +70 °C
PNEUMATIC TRANSMITTER
Linearity : ≤ ± 0.2% full scale
: For transmitting the measured value by a
Hysteresis : ≤ ± 0.1% full scale
pneumatic output signal, the pointer
Repeatability : ≤ ± 0.1% full scale
position is transmitted via an actuator pin
Influence of power supply
to a nozzle flapper system.
: ≤ ± 0.1% full scale
Temperature coefficient of output signal
: ≤ ± 0.5 %/10 K full scale
AC portion of output signal
: ≤ ± 0.15 % full scale
Long-time stability : ≤ ± 0.2 % /year
Max. output signal : 21.5 mA
Output signal in failure
: ≤ 3.6 mA (NAMUR NE 43)
Response time (99%): ca. 1.5 s

Electromagnetic compatibility
- Emission acc. EN 55011: 1998 + A1: 1999 Class A, Group 1
- Immunity acc. EN 61326: 1997 + A1: 1998
- EN 61000-3-2: 1995 + A1: 1998 + A2: 1998
- EN 61000-3-3: 1995

Unit Safety according to DIN EN61010: 1994


- Units with 115/230 V power
: safety class 1 (with non-fused,
earthed conductor)
- Units with 24 power : safety class III (SEL V-E, earthed safe
low voltage)
- Overvoltage category
: II (acc. to VDE 0110 or IEC 664)

GS 1R1B2-E-H
4

LIMIT SWITCHES IN STANDARD VERSION SC 3,5-N0 SJ 3,5-SN


Type : inductive approximity switch
Function indicator switch signal switch signal fail safe
SC 3.5-N0
acc. DIN EN 60947-5-6 (NAMUR) MAX above limit on 1 mA on 1 mA 1 mA
Ambient temperature : see temperature graphs page 8; 9 below limit off 3 mA off 3 mA
Nominal voltage : 8 V DC MIN above limit off 3 mA off 3 mA 1 mA
Output signal : ≤ 1 mA = 0, ≥ 3 mA = 2 below limit on 1 mA on 1 mA
Explosion protection : EEx ia IIC T1 - T6
Entity parameters : acc. certificate of conformity Tab. 1.1. Function of limit switches as Min, Max and Min-Max con-
PTB Nr.Ex-95.D.2195X tact in standard and fail safe version
(See fig. 4 on page 6)

LIMIT SWITCHES IN FAIL SAFE VERSION


Type : inductive approximity switch
SJ 3.5-S1N; SJ 3.5-SN SJ 3,5-SN SJ 3,5-S1N
acc. DIN EN 60947-5-6 (NAMUR) Function indicator switch signal switch signal fail safe
in fail safe version upper MIN above limit off 3 mA off 3 mA 1 mA
Technical data on demand below limit off 3 mA on 1 mA
LIMIT SWITCHES FOR HAZARDOUS AREAS lower MIN above limit off 3 mA on 1 mA 1 mA
According CENELEC ATEX (option XE) below limit on 1 mA on 1 mA
Explosion proof : EEx ia IIC T1-T6
Tab. 1.2. Function of limit switches as Min-Min contact
Entity parameters : acc. certificate of confirmity
in fail safe version
PTB 00 ATEX 2049X for type SJ
and
PTB 99 ATEX 2219X for type SC
resp. acc. EC-Type Examination
Certificate PTB 99 ATEX 2219X
SJ 3,5-SN SJ 3,5-S1N
HYSTERESIS OF LIMIT SWITCHES Function indicator switch signal switch signal fail safe
Min-contact upper MAX above limit on 1 mA on 1 mA 1 mA
- pointer movement : ≈ 0.5 mm below limit off 3 mA on 1 mA
- float movement : ≈ 0.8 mm
lower MAX above limit off 3 mA on 1 mA 1 mA
Max-contact
- pointer movement : ≈ 0.5 mm below limit off 3 mA off 3 mA
- float movement : ≈ 0.6 mm
Tab. 1.3. Function of limit switches as Max-Max contact
in fail safe version
According FM-Global (option XA)
Explosion proof : C1I, Division 0, Groups IIC T6
(Ta = 60°C)
Entity parameters : Vmax = 16 V; Imax = 20 mA;
Ci = 100 nF; Li = 150 µH

POWER SUPPLY FOR LIMIT SWITCHES


Type : Transformer isolated barrier acc.
DIN EN 50227 (NAMUR)
Power supply : 230 V AC +10 %/-15 %, 50/60Hz
: 24 V DC ± 20 %
Relay output : 1 potential-free changeover
contact
: 2 potential-free changeover
contacts
Switching capacity : max. 250V AC, max. 2A
Control circuit : intrinsically safe [EEx ia] IIC
Entity parameters : acc. certificate of conformity
PTB 00 ATEX 2081 (230 V AC)
PTB 00 ATEX 2080 (24 V DC)
(See fig. 8 on page 16)

GS 1R1B2-E-H
5

Fig. 1. RAMC 2-wire unit with inductive limit switches in conjunction with transformer isolated barrier

Fig. 2. RAMC 3-wire unit with inductive limit switches in conjunction with transformer isolated barrier

GS 1R1B1-E-H
6

Fig. 3. RAMC 4-wire unit with pulse output

Fig. 4. Ex-version according to ATEX (option XE): RAMC with electric transmitter in conjunction with power supply unit plus
additional limit switches in conjunction with transformer isolated barrier

GS 1R1B2-E-H
7

Fig. 5. RAMC - 2 Wire unit with HART communication, with inductive limit switches in conjunction with transformer
isolated barrier.

GS 1R1B1-E-H
8

Temperature graphs

450

400
max operation temperature [ºC]

350

300

250

200

150

100

50

0
20 30 40 50 60 70 80 90 100 110
Ambient temperature [ºC]
without option A2 with option A2, no insulation with option A2 and insulation

Fig. 6a. RAMC: - local indicator Minimum ambient temperature: -25°C


Housing material: - stainless steel; aluminium

450

400
max operation temperature [ºC]

350

300

250

200

150

100

50

0
20 30 40 50 60 70
Ambient temperature [ºC]
without option A2 with option A2, no insulation with option A2 and insulation

Fig. 6b. RAMC: - local indicator with limit switch (SC 3.5; SJ 3.5) Minimum ambient temperature: -25°C
- electric transmitter (WT-MAG)
- pneumatic transmitter
Housing material: - stainless steel; aluminium

GS 1R1B2-E-H
9

Temperature graphs

120
max operation temperature [ºC]

100

80

60

40

20

0
20 30 40 50 60 70
Ambient temperature [ºC]

Fig. 6c. RAMC: - local indicator with/without limit switch Minimum ambient temperature: -25°C
- electric transmitter (WT-MAG)
Housing material: - plastic

These temperature specifications do not consider the influence of additional heat sources which may change the ambient
conditions significantly!

GS 1R1B1-E-H
10

Model and suffix codes

Model Suffixcode Optioncode Description


RAMC01 ............................................................................................. Size DN 15 (1/2 inch), for: D4, A1, A2, T4, R4
RAMC23 ............................................................................................. Size DN 20 (3/4 inch), for: D4, A1, A2, T4, R4
RAMC02 ............................................................................................. Size DN 25 (1 inch), for: D4, A1, A2, T4, S2, S4, R4
RAMC03 ............................................................................................. Size DN 32 (11/4 inch), for: D4, A1, A2, T4, S4, R4
RAMC04 ............................................................................................. Size DN 40 (11/2 inch), for: D4, A1, A2, S4
RAMC05 ............................................................................................. Size DN 50 (2 inch), for: D4, A1, A2, T4, S2, S4, R4
RAMC06 ............................................................................................. Size DN 65 (21/2 inch), for: D4, A1, A2, T4, S2, R4
RAMC08 ............................................................................................. Size DN 80 (3 inch), for: D4, A1, A2, S2, S4
RAMC10 ............................................................................................. Size DN 100 (4 inch), for: D2, D4, A1, A2, S2, S4

Process- -D2 .................................................................................. DIN flange PN 16 (only for DN100)


connection -D4 .................................................................................. DIN flange PN 40
-A1 .................................................................................. ASME flange 150 lbs
-A2 .................................................................................. ASME flange 300 lbs
-T4 .................................................................................. NPT-F, PN 40*
-R4 .................................................................................. RP, PN 40*
-S2 .................................................................................. External thread DIN 11851 PN 40/PN 25
-S4 .................................................................................. Tri clamp PN16 / PN10

Material SS ............................................................................ 1.4571, AISI 316 Ti


wetted parts PF ............................................................................ Teflon (PTFE)

Cone/float -nnnn....................................................................... Refer to table 2 and 3

Indicator/transmitter -T ...................................................................... Local indicator


-E ...................................................................... Electronic transmitter without HART (WT-MAG)
-H...................................................................... Electronic transmitter with HART (WT-MAG)
-P ...................................................................... Pneumatic transmitter

Housing type 61 ............................................................... Aluminium (only for transmitter -P),


65 ............................................................... Aluminium
66 ............................................................... Polyamid
90 ............................................................... Stainless steel

Power supply NNN ..................................................... Without power supply


Output 24n....................................................... 230 V AC - 4-wire
14n....................................................... 115 V AC - 4-wire
n=0: 0 - 20 mA 430....................................................... 24 V DC - 3-wire
n=4: 4 - 20 mA 424....................................................... 24 V DC - 2-wire
BAR...................................................... Pneumatic output 0.2 - 1 bar g (only type -P)
PSI ....................................................... Pneumatic output 3 - 15 psi g (only type-P)

Style *B................................................... ROTA YOKOGAWA version (yellow)


*C................................................... Yokogawa version (green)
*D................................................... Round indicator housing (stainless steel)

Options /[ ] ........................ see separate table on next page

* - gasket material Perbunan


- inserted parts stainless steel
- swivel unit carbon steel

GS 1R1B2-E-H
11

Options

Options Optioncode Description

Indicator /A2 Insulating distance version 60 mm between tube and indicator


/A12 US engineering units, only for electronic transmitter
/A13 Screwing M20 x 1.5

Marking /B1 Stainless steel tag plate with customer specification


/BG Customer specification notes on scale
/BD Dual scale

Limit switches /K1 MIN-contact


/K2 MAX-contact
/K3 MIN-MAX-contact, MIN-MIN-contact, MAX-MAX-contact
/K6 FAIL-SAFE-version MIN-contact
/K7 FAIL-SAFE-version MAX-contact
/K8 FAIL-SAFE-version MIN-MAX-contact
/K9 FAIL-SAFE-version MIN-MIN-contact
/K10 FAIL-SAFE-version MAX-MAX-contact

Pulse output /CP Pulse output, potential off (only for 4-wire units)

Ex-proof type /XE Intrinsically safe acc. ATEX EN 50020


WT-MAG /XN Protection type „n“ (non incendive) acc. EN 50021

Tests and /H1 Certificate of degrease


certificates /P2 Test certificate “2.1” acc. EN 10204 (DIN 50049)
/P3 Test certificate “2.2” acc. EN 10204 (DIN 50049)
/P6 Inspection certificate 3.1.B acc. EN 10204 (DIN 50049) for pressurised parts

Damping /SD For gas applications a damping unit is recommended below the following pressure
only for stainless steel (See sizing programm edition 2.7 or higher editions)
In general you can specify without damping above following limits:
- Float type L: 1 bar g
- Float type M: 5 bar g
- Float type S: 10 bar g

Heating /T1 Heating with process connection R1/4”


/T2 Heating with DIN flange DN 15/PN40
/T3 Heating with DIN flange DN 25/PN40

Transmitter /U2F SINEAX B811-14, 230 V AC, with galvanic isolation,


power supply output 0/4-20 mA, for Ex version
unit /U3F SINEAX B811-13, 24 V AC/DC, with galvanic isolation,
output 0/4-20 mA, for Ex version

Transformer /W2A KFA6-SR2-Ex1.W / 230 V AC, 1 channel, 1 changeover contact


isolated barrier /W2B KFA6-SR2-Ex2.W / 230 V AC, 2 channel, 2 changeover contacts
/W2E KHA6-SH-EX1 / 230 V AC, 1 channel, 1 changeover contact
/W4A KFD2-SR2-Ex1.W / 24 V DC, 1 channel, 1 changeover contact
/W4B KFD2-SR2-Ex2.W / 24 V DC, 2 channel, 2 changeover contacts
/W4E KFD2-SH-EX1 / 24 V DC, 1 channel, 1 changeover contact

Instruction manuals /IDn Quantity of instruction manuals in German (possible 1 to 9) standard 0


/IEn Quantity of instruction manuals in English (possible 1 to 9) standard 0
n = 1-9 /IFn Quantity of instruction manuals in French (possible 1 to 9) standard 0

GS 1R1B2-E-H
12

FLOWTABLE FOR METAL TUBES

Setting of the right metering tube specification:


- specify cone / float combination acc. to the requested
flowrate depending for liquid or gas
- specify then the available process connection type and size

Table 2.
Process connection
Water / Liquids
Flange Male Thread Clamp Female Thread
Type
Position DIN ANSI DIN 11851 Clamp NPT RP Recommended Solution
Maximum
Pressure Flowrate Cone/float Pressure Viscosity(c
rate PN 16 PN 40 150 lbs 300 lbs PN 40/25 PN 16/10 PN 16/10 PN 16/10 combination drop (b
Ms-code D2 D4 A1 A2 S2 (a S4 (a T4 (a R4 (a [m3/h] (e gpm (f Ms-code [mbar] [mPas]
DN 15 1/2“ 1/2“ DN 25 DN 25 / 1“ 1/2“ 1/2“ 0.025 0.11 43 S0 40 2.9
1 DN 20 3/4“ 3/4“ PN 40 DN 32 3/4“ 3/4“ 0.04 0.18 44 S0 40 4.5
DN 25 1“ 1“ DN 40 / 1-1/2“ PN 25 PN 25 0.063 0.28 47 S0 40 6.4
DN 32 PN 16 0.1 0.45 51 S0 40 9.2
DN 15 1/2“ (a 1/2“ (a DN 25 DN 25 / 1“ 1/2“ 1/2“ 0.1 0.45 - - -
DN 20 3/4“ 3/4“ PN 40 DN 32 3/4“ 3/4“ 0.16 0.7 53 M1 15 8.2
DN 25 1“ 1“ DN 40 / 1-1/2“ PN 25 PN 25 0.25 1.12 53 S1 40 13
2 DN 32 1-1/4“ 1-1/4“ PN 16 0.4 1.8 54 S1 40 18
DN 40 1-1/2“ 1-1/2“ 0.63 2.8 57 S1 40 23
DN 50 2“ 2“ 1.0 4.5 61 S1 40 27
1.6 7.0 62 S1 40 31
2.3 10.4 62 V1 45 - (d
DN 25 1“ (a 1“ (a DN 50 DN 50 / 2“ 1“ 1“ 1.0 4.5 - - -
Size DN 32 1-1/4“ 1-1/4“ PN 25 PN 16 1-1/4“ 1-1/4“ 1.6 7.0 - - -
3 DN 40 1-1/2“ 1-1/2“ PN 16 PN 16 2.5 11.2 63 S2 41 44
DN 50 2“ 2“ 4 18 64 S2 41 50
6 27 64 V2 43 - (d
DN 50 2“ (a 2“ (a DN 65 DN 65 2“ 2“ 2.5 11.2 - - -
DN 65 2-1/2“ 2-1/2“ DN 80 3“ 2-1/2“ 2-1/2“ 4 18 - - -
4 DN 80 3“ 3“ PN 25 PN 10 PN 10 PN 10 6.3 28 67 S5 47 72
10 45 71 S5 47 82
16 70 72 S5 47 92
25 110 72 V5 63 - (d
DN 100 DN 80 3“ 3“ DN 100 DN 100 / 4“ 25 110 73 V8 60 - (d
5 DN 100 4“ 4“ PN 25 PN 10 40 180 74 V8 60 - (d
63 280 77 V8 60 - (d
DN 100 DN 100 4“ 4“ 100 450 81 11 70 - (d
6 130 570 82 11 70 - (d

a) No heat jacket possible (option /T…).


b) Calculated pressure drop caused by the float.
c) Limitation of the linear scaling. Up to these values no influence of viscosity on the specified maximum flowrate.
d) This cone/float combination shows always viscosity dependency.
e) Flow at reference conditions 20 °C and 1.013 bar abs.
f) Flow US gallons per minute (reference condition 70 °F).
g) Flow converted to 0 °C and 1.013 bar abs. when operated at 20 °C and 1.013 bar abs.
h) Flow in standard cubic feet per minute converted to 60 °F and 14.7 psia when operated at 70 °F and 14.7 psia.
i) Specification of float type should be avoided for gas applications.

NOTE
Pressure rating of the several process connections are mentionned for a temerature of 20°C. Shall the process temperature vary,
kindly refer to DIN or ASME allowed max process pressure as a funktion of the process temperature.

GS 1R1B2-E-H
13

NOTES
- The recommended combinations should be preferred.
However if a lower pressure drop is necessary the
alternative combination can be selected.
- For float type V the scale is always non linear.

Air / Gases

Alternative Solution Recommended Solution Alternative Solution


Cone/float Pressure (c Pressure Cone/float Pressure Cone/float
combination drop (b Viscosity Maximum Flowrate combination drop (b Maximum Flowrate combination drop
Ms-code [mbar] [mPas] [m3/h] (e [m3/h i. N.] (g scfm (h Ms-code [mbar] [m3/h] (e [m3/h i. N.] (g scfm (h Ms-code [mbar]
- - - 0.75 0.7 0.44 43 S0 45 - - - - -
- - - 1.2 1.12 0.7 44 S0 45 - - - - -
- - - 1.8 1.7 1.05 47 S0 45 - - - - -
- - - 3 2.8 1.75 51 S0 45 - - - - -
53 L1 6 5.1 - - - - - - - - - -
54 L1 6 7.1 4 3.6 2.3 53 L1 11 - - - - -
57 L1 6 8.8 5.5 5.0 3.2 53 M1 20 - - - - -
61 L1 6 10 6.5 6.0 3.8 54 L1 11 - - - - -
61 M1 15 17 10 9.0 5.7 57 L1 11 9 8.5 5.0 54 M1 20
62 M1 15 19 16 15 9.0 61 L1 11 15 14 8.7 57 M1 20
61 V1 45 - (d 25 23 14 62 L1 11 22 20 12.5 61 M1 20
- - - 35 33 20 62 M1 20 30 28 17.5 61 S1 45
63 L2 7 17 40 36 23 63 L2 12 50 47 29 63 M2 22
64 L2 7 20 70 60 38 64 L2 12 - - - - -
64 M2 16 16 90 85 50 64 M2 22 - - - - -
63 V2 43 - (d 130 120 75 64 S2 47 - - - - -
- - - - - - - - - - - - -
67 L5 8 29 100 90 59 67 L5 14 130 120 75 67 M5 25
71 L5 8 33 160 150 90 71 L5 14 - - - - -
72 L5 8 37 200 180 115 71 M5 25 200 180 115 67 S5 54
72 M5 19 58 280 250 160 72 L5 14 360 340 210 72 M5 25
71 V5 63 - (d - - - - - 500 470 290 72 S5 54
- - - - - - - - - - - - -
- - - 550 500 320 73 L8 30 750 700 440 73 V8 (i 65
- - - 850 800 500 74 L8 30 1200 1120 700 74 V8 (i 65
- - - 1400 1300 800 77 L8 30 1800 1700 1050 77 V8 (i 65
- - - - - - - - - - - -
- - - - - - - - - - - -

ORDERING INSTRUCTIONS

Specify the following when ordering:


1. Model, suffix codes and option codes
2. a. Fluid name
b. Temperature
c. Pressure
d. Viscosity
e. Density
3. For gases
Condition of the scale (st. or actual)
4. Options
a. Tag No.
b. Customer specification notes

GS 1R1B2-E-H
14

FLOW TABLE FOR PTFE-LINING


Setting of the right metering tube specification:
- specify cone / float combination acc. to the requested
flowrate depending for liquid or gas
- specify then the available process connection type and size

Table 3.
Process connection
Flange Water / Liquids
Type
Position DIN ANSI
Pressure Cone/float Pressure
Maximum Flowrate combination drop (b Viscosity
(c
PN 16 PN 40 150 lbs 300 lbs
rate
Ms-code D2 D4 A1 A2 [m3/h] (e
gpm (f Ms-code [mbar] [mPas]
DN 15 (a 3/4“ (a 3/4“ (a 0.1 0.45 51 A1 16 - (d
DN 25 1“ 1“ 0.16 0.7 52 A1 16 - (d
2 0.25 1.12 53 A1 16 - (d
0.4 1.8 54 A1 16 - (d
0.63 2.8 57 A1 16 - (d
1.0 4.5 61 V1 18 - (d
DN 25 (a 1-1/4“ (a 1-1/4“(a 1.6 7.0 62 A2 20 30
3 DN 40 1-1/2“ 1-1/2“ 2.5 11.2 63 A2 20 35
DN 50 (a 4 18 63 A2 22 - (d
Size DN 50 (a 2-1/2“ 2-1/2“ 4 18 64 A5 20 47
4 DN 65 3“ (a 3“(a 6.3 28 67 A5 20 54
DN 80 (a 10 45 71 A5 20 60
16 70 71 V5 22 - (d
DN 100 DN 80 (a
4“ (a
4“(a 16 70 72 V8 25 - (d
5 25 110 73 V8 25 - (d
40 180 74 V8 25 - (d
6 DN 100 DN 100 (a
4“ (a
4“* 63 280 77 10 30 - (d

a) No heat jacket possible (option /T…).


b) Calculated pressure drop caused by the float.
c) Limitation of the linear scaling. Up to these values no influence of viscosity on the specified maximum flowrate.
d) This cone/float combination shows always viscosity dependency.
e) Flow at reference conditions 20 °C and 1.013 bar abs.
f) Flow US gallons per minute (reference condition 70 °F).
g) Flow converted to 0 °C and 1.013 bar abs. when operated at 20 °C and 1.013 bar abs.
h) Flow in standard cubic feet per minute converted to 60 °F and 14.7 psia when operated at 70 °F and 14.7 psia.

GS 1R1B2-E-H
15

Air / Gases

Cone/float Pressure
Maximum Flowrate combination drop (b
[m3/h] (e
[m3/h i.N.](g scfm(h Ms-code [mbar]
3.5 3.3 51 A1 20
5 4.7 52 A1 20
8.5 8.0 53 A1 20
13 12 54 A1 20
20 18 57 A1 20
34 32 61 V1 12
50 47 62 A2 25
85 80 63 A2 25
- - - -
130 120 64 A5 25
200 180 67 A5 25
350 330 71 A5 25
- - - -
500 470 72 V8 27
850 800 73 V8 27
- - - -
- - - -

ORDERING INSTRUCTIONS

Specify the following when ordering:


1. Model, suffix codes and option codes
2. a. Fluid name
b. Temperature
c. Pressure
d. Viscosity
e. Density
3. For gases
Condition of the scale (st. or actual)
4. Options
a. Tag No.
b. Customer specification notes

GS 1R1B2-E-H
16

DIMENSIONS AND WEIGHT

Fig. 7a. Front view in style *B resp. *C Fig. 7b. Front view in style *D.
L

Fig. 8. Metal version Fig. 9. Metal version with lining

GS 1R1B2-E-H
17

Fig. 10. RAMC type 90 with option A2 Fig. 11. RAMC type 65 with option A2 and heat jacket

Fig. 12. With connection T4/R4 Fig. 13. With connection S2

GS 1R1B1-E-H
18

DIMENSIONS AND WEIGHT

Position Size di da
[mm] [mm] [mm]

1 DN 25 / 1" 36 50.5
DN 32 36 50.5
DN 40 / 1-1/2" 36 50.5
2 DN 25 / 1" 36 50.5
DN 32 36 50.5
DN 40 / 1-1/2" 36 50.5
3 DN 50 / 2" 47.8 64
4 DN 65 72.1 91
3" 72.1 91
5 DN 100 / 4" 97.6 119

Table 4. Diameter for connection size S4.

Fig. 14. With connection S4

ADVICE FOR PROJECT WORK

- The real working pressure has to be less than the specified pressure limits of the Rotameter.

- Make sure that the wetted material is resistant to the medium.

- Ambient and operation temperature has to be less than the specified maximum value.

- If dirt accumulation is to be expected we recommend to install a bypass pipe.

- To avoid float bouncing in case of gas application notice the recommandations of VDI/VDE 3513 Sheet 3.

- To avoid mutual magnetic influence in case of a parallel design of several Rotameters take care that the
distance between the tube middle axes is not less than 300 mm. The distance to other ferrictic materials
should not be less than 60 mm.

- The strength of external magnetic fields close by the Rotameter should be approximately 0mT.

GS 1R1B2-E-H
19

Ms-code D2 D4 A1 A2 S2 S4 T4 / R4
Position Size L [mm] Size L [mm] Size L [mm] Size L [mm] Size L [mm] Size L [mm] Size L [mm]

1 DN 15 250 1/2" 250 1/2" 250 DN 25 275 DN 25/1“ 250 1/2" 295
DN 20 250 3/4" 250 3/4" 250 DN 32 250 3/4" 295
DN 25 250 1" 250 1" 250 DN 40/1-1/2" 250
DN 32 250
2 DN 15 250 1/2" 250 1/2" 250 DN 25 275 DN 25 / 1" 250 1/2" 295
DN 20 250 3/4" 250 3/4" 250 DN 32 250 3/4" 295
DN 25 250 1" 250 1" 250 DN 40/1-1/2" 250
DN 32 250 1-1/4" 250 1-1/4" 250
DN 40 250 1-1/2" 250 1-1/2" 250
DN 50 250 2" 250 2" 250
3 DN 25 250 1" 250 1" 250 DN 50 275 DN 50/2" 250 1" 310
DN 32 250 1-1/4" 250 1-1/4" 250 1-1/4" 310
DN 40 250 1-1/2" 250 1-1/2" 250
DN 50 250 2" 250 2" 250
4 DN 50 250 2" 250 2" 250 DN 65 275 DN 65 300 2" 325
DN 65 250 2-1/2" 250 2-1/2" 260 DN 80 275 3" 300 2-1/2" 325
DN 80 250 3" 250 3" 260
5 DN 100 250 DN 80 250 3" 250 3" 250 DN 100 300 DN 100/4" 250
DN 100 250 4" 250 4" 270
6 DN 100 250 DN 100 250 4" 250 4" 270

Table 5. Face to face lengths for stainless steel tubes.

Ms-code D2 D4 A1 A2

Position Size L [mm] Size L [mm] Size L [mm] Size L [mm]

2 DN 15 250 3/4" 250 3/4" 250


DN 25 250 1" 250 1" 250
3 DN 25 250 1-1/4" 250 1-1/4" 250
DN 40 250 1-1/2" 250 1-1/2" 250
DN 50 250 1-1/2" 250 1-1/2" 250
4 DN 50 250 2-1/2" 250 2-1/2" 260
DN 65 250 3" 250 3" 260
DN 80 250
5 DN 100 250 DN 80 250 4" 250 4" 270
6 DN 100 250 DN 100 250 4" 250 4" 270

Table 6. Face to face lengths for tubes with PTFE-lining.

Stainless steel PTFE-lining


Position Weigth
D1 D2 D1 D2
[mm] [mm] [mm] [mm] [kg]
1 30 30 ca. 3 - 5
2 32 40 38 44.5 ca. 3 - 5
3 47 57 57 70 ca. 6.5 - 8
4 78 88.9 90 101.6 ca. 8.5 - 11
5 104 114.3 121 132 ca. 13 - 16
6 124 139.7 140 ca. 17 - 20

Table 7. Dimensions D1 (no heat jacket) and D2 (in case of heat jackets) and weights.

GS 1R1B1-E-H
HUNGARY AUSTRALIA UNITED STATES OF AMERICA
YOKOGAWA Yokogawa Hungaria Ltd.
Alkotas Center 39 C
1123 BUDAPEST
Yokogawa Australia Pty Ltd.
Private mail bag 24
Centre Court D3
Yokogawa Corporation of
America
2 Dart Road
Tel. +36-1-355 3938 25-27 Paul Street North NEWNAN, GA 30265-1040
Fax +36-1-355 3897 NORTH RYDE, N.S.W. 2113 Tel. +1-770-253 70 00
EUROPEAN HEADQUARTERS Tel. +61-2-805 0699 Fax +1-770-251 28 00
Yokogawa Europe B.V. Fax +61-2-888 1844
Databankweg 20 ITALY
Yokogawa Italia S.r.l. ISO 9001
3821 AL AMERSFOORT BELGIUM SINGAPORE
The Netherlands Yokogawa Belgium N.V./S.A. Vicolo D. Pantaleoni, 4
20161 MILANO Yokogawa Engineering Asia Pte. Ltd.
Tel. +31-33-4641 611 Minervastraat 16 11, Tampines Street 92
Fax +31-33-4641 610 1930 ZAVENTEM Tel. +39-02-66 24 11
Fax +39-02-645 57 02 SINGAPORE, 528872
E-mail: info@yokogawa.nl Tel. +32-2-719 55 11 Tel. +65-783 9537
Fax +32-2-725 34 99 CERTIFICATED
www.yokogawa-europe.com Fax +65-786 2606 FIRM
SPAIN
THE NETHERLANDS FRANCE Yokogawa España S.A.
C/Francisco Remiro, N°2, Edif. H Manufactured by:
Yokogawa Nederland B.V. Yokogawa France S.A. GERMANY
Hoofdveste 11 Vélizy Valley 28028 MADRID
Tel. +34-91-724 20 80 Rota Yokogawa GmbH & Co. KG CENTRAL/EAST REGION
3992 DH HOUTEN 18-20 Rue Grange Dame Rose Rheinstrasse 8 Via Yokogawa Austria: Czechia,
Tel. +31-30-635 77 77 78140 VELIZY VILLACOUBLAY Fax +34-91-355 31 40
D-79664 WEHR Slovakia, Poland, Croatia,
Fax +31-30-635 77 70 Tel. +33-1-39 26 10 00 Tel. +49-7761-567 0 Slovenia, Jugoslavia, Bulgaria,
Fax +33-1-39 26 10 30 UNITED KINGDOM
Yokogawa United Kingdom Ltd. Fax +49-7761-567 126 Romania, Macedonia, Bosnia &
AUSTRIA Herzegovina
Yokogawa Austria Ges.m.b.H. GERMANY Stuart Road, Manor Park,
RUNCORN SOUTH AFRICA
Franzensbrückenstrasse 26 Yokogawa Deutschland GmbH Yokogawa South Africa (Pty) ltd. Distributors in:
A-1021 WIEN Berliner Strasse 101-103 Cheshire WA7 1TR
Tel. +44-1-928 597100 67 Port Road, Robertsham Denmark, Finland, Greece,
Tel. +43-1-2165 043 0 D-40880 RATINGEN Southdale 2135, JOHANNESBURG Norway, Portugal, Russian
Fax +43-1-2165 043 33 Tel. +49-2102-4983 0 Fax +44-1-928 597101
Tel. +27-11-680-5420 Federation, Sweden,
Fax +49-2102-4983 22 Fax +27-11-680-2922 Switzerland and Turkey.

Block 03, 10-00


GS 1R1B2-E-H
Subject to modifications without notice Printed in The Netherlands, 09-111 (A) Q