Documente Academic
Documente Profesional
Documente Cultură
Electrical
Engineering Standard
EP 03 00 00 01 TI
Disclaimer
This document was prepared for use on the RailCorp Network only.
RailCorp makes no warranties, express or implied, that compliance with the contents of this document shall be
sufficient to ensure safe systems or work or operation. It is the document user’s sole responsibility to ensure that the
copy of the document it is viewing is the current version of the document as in use by RailCorp.
RailCorp accepts no liability whatsoever in relation to the use of this document by any party, and RailCorp excludes
any liability which arises in any manner by the use of this document.
Copyright
The information in this document is protected by Copyright and no part of this document may be reproduced, altered,
stored or transmitted by any person without the prior consent of RailCorp.
Document control
Version Date Summary of change
November 2001 Last Technical Review
3.0 May 2010 Application of TMA 400 format
3.1 May 2013 Update template
© RailCorp Page 2 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
Contents
1 Introduction .............................................................................................................................4
2 Symbols ...................................................................................................................................4
3 General .....................................................................................................................................5
4 RailCorp Rectifier Connections.............................................................................................5
4.1 Connection Types .....................................................................................................................5
4.2 Series, Full Wave Bridge...........................................................................................................5
4.3 Full Wave Bridge.......................................................................................................................6
4.4 Double Star Transformers.........................................................................................................7
4.5 Quadruple Zig Zag ....................................................................................................................8
5 Simple Model of Rectifier and Transformer at ‘Normal’ Loads ..........................................9
6 Rectifier Transformer Impedances......................................................................................10
6.1 Resistance ..............................................................................................................................10
6.2 Reactance ...............................................................................................................................10
6.3 Short Circuit 'Resistance' ........................................................................................................11
6.4 Fault Current Approximations .................................................................................................12
7 Rectifier Resistance..............................................................................................................12
8 Voltage Regulation................................................................................................................13
9 Power Factor .........................................................................................................................13
10 Harmonics..............................................................................................................................14
10.1 General....................................................................................................................................14
10.2 Levels of DC Harmonic Voltage..............................................................................................14
10.3 Levels of AC Harmonic Currents ............................................................................................15
10.4 DC Harmonic Filter..................................................................................................................15
11 DC Reactor.............................................................................................................................15
12 Protection ..............................................................................................................................16
13 Typical Values .......................................................................................................................17
13.1 Double Star- 2.5MW / 1.5MVA................................................................................................17
13.2 Three Phase Bridge - 4MW / 4.2MVA....................................................................................18
13.3 Quad Zig Zag - 4MW / 4.2MVA.............................................................................................19
13.4 Series Bridge - 4MW / 4.2 MVA ............................................................................................20
© RailCorp Page 3 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
1 Introduction
This document presents the electrical characteristics of RailCorp rectifiers and rectifier
transformers. Detailed investigations are available in Australian Standard AS1955 and
the 'classical' paper by J C Read titled "The Calculation of Rectifier and Inverter
Performance Characteristics".
This document will attempt to simplify these detailed documents and specially look at
RailCorp rectifiers.
2 Symbols
CT transf. Copper loss (Watts)
ID dc current
L Reactor Inductance
VA ac phase-phase volts
© RailCorp Page 4 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
VD dc volts
3 General
The RailCorp has only 4 types of traction rectifier (see Section 4) with by far the majority
being 12 pulse output. The most common rating is 4MW continuous and with a typical
power factor of 0.95, transformer ratings are 4.2 MVA.
The reactance of rectifier transformers is specified to be the same for different rated
rectifiers so that the fault level at the rectifier is relatively constant for different rated
rectifiers (about 35 MVA). Typical reactances as a percentage of the transformer ratings
are 12% on 4MW; 14% on 5MW and 8% on 2.5MW. These are much higher impedances
than would be expected in large power transformers. They are specified high to reduce
the fault level to make protection of the rectifier easier. It is possible to use this high
value without causing excessive voltage drop because the rectifier has a good power
factor (0.95 or higher).
All RailCorp rectifiers are uncontrolled - the output voltage is directly related to input
voltage and load and cannot be "controlled". All RailCorp rectifiers use silicon diodes.
In general, the primary windings may be either star or delta but the majority of RailCorp
types have star connected primary.
© RailCorp Page 5 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
Figure 1
© RailCorp Page 6 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
Figure 2
© RailCorp Page 7 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
Figure 3
This required a very complicated transformer but was a preferred type with mercury arc
rectifiers which had a high voltage/low current requirement for each tank.
© RailCorp Page 8 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
Figure 4
The impedance of the transformer is (Ra + jXa) and the voltage drop through the
transformer is thus
The term qf/pf is constant at about 0.33 for normal load levels, so that now Tx volts drop
are
The rectifier can be considered as a resistance and a constant voltage drop of about 5
volts (see Section 6.)
© RailCorp Page 9 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
Where Req includes the transf., rectifier, ac & dc cables & reactor.
6.1 Resistance
Given the impedance voltage W (on Tx base) (%) and the copper loss CT(Watts) at full
load.
If S is rating of transf. in MVA, pf is load power factor and VA is the voltage that Ra refers
to:-
6.2 Reactance
The reactance per phase Xa is
VA* W * 1 EQN.8
√3 *100 rated amps/phase
Note:
RailCorp specifies the impedance voltage dependant on the rating i.e. 12% for 4.2 MVA;
14% for 5.3 MVA etc. This means W/S is a 'constant' for all ratings of rectifier
transformers = 2.8 approx.
Therefore Xa = j 30 ohms @ 33kV & j120 ohms @ 66kV for all ratings.
Typical values are CT = 35kW; .. for 4MW and 0.95pf, so Ra = 2.1 ohms @ 33kV
© RailCorp Page 10 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
115 * I DO
I DC s / c terminals = EQN. 10a
( Xa % + Xs % )
where Xa% and Xs% are based on the transformer rating. eg 12%
Note that the above does not take into account the rectifier and cable resistances. It is
very theoretical. To calculate the actual fault current for a short circuit on the DC side we
need to include the dc resistances to the fault.
Rsc = 1625/ ( IDC s/c terminals) = 0.021*(Xa+Xs)% (in ohms) EQN. 10d
P
Example:
For a 4.3 MVA transformer with 12% impedance the theoretical max dc fault current is:
115*2600/12 = 24,900A
Note:
© RailCorp Page 11 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
Example:
For a 4.3 MVA transformer with 12% impedance and other dc resistances as given in
Section 6 of 0.0035 ohms, the actual fault current for a fault on the dc bus is:
VD REF * P
I SCO = EQN. 10f
0.021 * ( Xa + Xs )%
1650 ⎛ ⎛
⎜ −
tL ⎞
⎟ ⎞
I = * ⎜1 − e ⎝ R ⎠ ⎟ EQN. 10g
SC
R ⎜ ⎟
⎝ ⎠
7 Rectifier Resistance
Tests usually give losses CR (Watts) at full load. As an approximation, the rectifier can
be represented as resistance and a constant voltage drop in the diodes. [In addition
there are cable & reactor resistances.] At full load the resistance voltage drop and diode
drops are about equal. An equivalent resistance for the rectifier is
2 2 2 12
RReq = CR/rated amps = CR * VDREF /P /10 EQN.11
© RailCorp Page 12 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
8 Voltage Regulation
The total voltage drop through the transformer/rectifier/cables and reactor can be
obtained more exactly than from EQN.5 by using EQN.4 and Section 6.
Example: with VA = 1625, ID = 2600A and using other typical values given.
VD = 1546 volts
9 Power Factor
The power factor caused by rectifiers is relatively constant and can be taken as 0.95 for
most applications. It is relatively independent of load.
Because of the non-sinusoidal waveform power factor is NOT the usual cosine of the
angle between the fundamental voltage and current but is defined as:
cos φ = cosine of angle between fundamental AC line current and line to neutral voltage.
© RailCorp Page 13 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
1/(12+0.0452+0.032+.012+0.0082) = 0.99692
So it does not affect the simple calculation of cos φ very much.
10 Harmonics
10.1 General
The harmonics produced by rectifiers depend on the number of pulses.
i.e. for 6 pulse - 250Hz, 350Hz, 550Hz, 650Hz, 850Hz, 950 Hz etc.
i.e. for 12 pulse - 550Hz, 650Hz, 1150Hz, 1250Hz etc.
The ac side harmonic currents can cause harmonic voltages to appear at other points in
the AC System.
The power flow of harmonics is from the load out into the AC system! Therefore energy
meters will subtract the harmonic energy from the consumed energy thus reducing the
electricity bill !
Harmonic levels are a function of supply inductances and the following tables show
typical RailCorp values.
© RailCorp Page 14 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
These voltages do not vary appreciably with load or rectifier rating. Filtering of the dc
voltage harmonics DOES NOT affect the level of ac harmonic currents.
5 250 18 -
7 350 11 -
13 650 3 3
17 850 1.5 -
19 950 1.0 -
The DC harmonic filter has very little effect on the production of harmonic currents in ac
side, ie filtering the dc harmonics does not filter the ac harmonics.
11 DC Reactor
A reactor is placed in series with the negative connection to the rectifier. Typical values
are 0.25 to 1 mH. The main purpose of the reactor is to limit the initial rate of rise of
current for a dc fault close to a substation. It also "contributes" to reducing he harmonic
current flowing to the overhead wiring (ie it helps 'smooth' the dc) and the harmonic filter
current.
and this must be kept below 6 x 106 A/s to stay within dccb ratings. (This defines the
min. value of 0.25 mH.)
The impedance of the reactor is given by 2π fL and substitution shows the typical values
are 0.5 - 2 ohms - the same order of magnitude of the train loads. Therefore the reactor
is not particularly effective in smoothing the dc.
© RailCorp Page 15 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
12 Protection
Because the dc system is unearthed, it presents special protection problems.
The rectifier and transformer are protected against faults within these units by
instantaneous ac overcurrent relays on the rectifier accb (to detect ac fault current flowing
into the trans/rect) and by a dccb which detects current flowing into the rectifier from the
dc bus bar.
The instantaneous ac overcurrent relays are set at about 5 times full load current.
Instantaneous relays operate in about 5 cycles and the rectifier diodes can withstand 5
times overload for this length of time. With rectifiers less than 4MW rating, this setting of
5 times full load allows incorrect operation on dc faults close to the SS, ie, the ac
protection does not discriminate with the feeder dccb. An additional time delay is used in
these cases.
The ac protection also includes an earth fault element but because the transf. secondary
is unearthed, this can only detect earth faults between the accb and transf. and internal
transf. faults to the tank.
The rectifier dccb is usually set at about 1000A for current flowing into the rectifier. Note
that although this is called 'reverse current' protection, the rectifier dccb is actually tripping
in its normal direction i.e. current flow away from the 1500V bus bar.
A 'frame leakage' relay is also connected to detect current flow from the rectifier
enclosure ('frame') and earth.
© RailCorp Page 16 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
13 Typical Values
EQN. Values
HV ph - ph Volts - 33kV
LV ph - ph Volts -
Tx. Cu Loss -
Tx. Fe Loss -
Tx. Impedance -
Rect. Loss -
DC no Load Volts 1a
Equiv. DC Resistance of
Kingsgrove
© RailCorp Page 17 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
EQN. Values
HV ph - ph Volts - 33kV
LV ph - ph Volts - 1210V
Tx. Cu Loss -
Tx. Fe Loss -
Equiv. DC Resistance of
(5MW)
Hurstville
© RailCorp Page 18 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
Tx. Fe Loss -
Equiv. DC Resistance of
Blacktown to Oakey Pk
Cowan to Gosford
© RailCorp Page 19 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1
RailCorp Engineering Standard — Electrical
Rectifier Transformer & Rectifier Characteristics EP 03 00 00 01 TI
Equiv. DC Resistance of
Ourimbah to Booragul
© RailCorp Page 20 of 20
Issued May 2013 UNCONTROLLED WHEN PRINTED Version 3.1