1. Line length = 25 Km
2. Total number of tower = 25x7/2 = 87.5 = 88 (approx.)
3. Weight of Mild Steel and Tension Steel.
Avg. Wt. Of mild steel per tower = 3.89 MT
Avg. Wt. Of tension steel per tower = (Avg. Wt. Of mild steel + 3) MT
Total number of Tension tower needed = 3x2 = 6.
Total steel including tower and stub with nut and bolt = (3.89x88 + 6x3) = 360.32 MT.
4. Tower type
No. of suspension tower (70%) = 62
No. of single suspension fitting = 56
No. of Double suspension fitting = 6
No. of High tension tower (30%) = 26
No. of single H.T. fitting = 22
No. of Double H.T. fitting = 4
5. Polymer Disc insulator 70 KN
Single Suspension fitting = 56 Tower x3 = 168.
Double suspension fitting = 6 Tower x 3x2 = 36
1 % of permitted extra consumption = 2
Total no.of Polymer Disc insulator = 168 + 36 + 2 = 206.
The above data has been taken from approved PGCIL Ara (PG) – jagdishpur S/C on D/C
Tower Transmission line.
10. Calculation sheet of Concreting for proposed 132 KV S/C Sonebarsa-Simri Bakhtiyarpur
DCSS Transmission.