Documente Academic
Documente Profesional
Documente Cultură
Natural
selection
The benefits of
biophilic design.
FORUM
P EER - R E V I E W ED T ECH N I C A L PA P ER S
ABSTRACT
Typically fire safety design of ventilation systems use fire and smoke dampers on ducts to each fire compartment or separate
ventilation systems for each fire compartment. These solutions are generally referred to as prescriptive solutions (also known
as deemed-to-satisfy solutions under the National Construction Code).
Less known are analytical methods that use simulations to allow a designer to predict the fire’s effect on the building’s ventilation
system. These methods predict the flow and temperature of hot gases entering the ventilation system. This allows a ventilation
system design with the fan(s) operating during a fire and where the operation of the fan is able to prevent fire and smoke spread
in the building via the ventilation system.
This paper uses a case study for a single-storey building to demonstrate how such simulations were used to justify the omission
of smoke and fire dampers from the ventilation system design. The construction cost savings associated with the engineered design
was approximately $200–$300K.
1. INTRODUCTION via leakage in the façade and internal walls. The ratio of the
fire-induced flow being pushed into the ducts, leakage or other
A building is typically divided into multiple fire compartments. paths will depend on the pressure drop (resistance) for each
Different fire compartments are separated from each other using of the components. The part that is pushed into the ducts
fire-resistant construction intended to maintain the structural is called the fire flow.
adequacy, integrity and insulation. Ventilation systems that serve
multiple fire compartments also need to be adequately protected The fire-induced flow for compartments up to 200m2 can
against fire and smoke spread. Typically, this is achieved by be calculated using Equation 1 (Backvik, Fagergren, & Jensen,
fire and/or smoke dampers fitted to the ducts to each fire 2008):
compartment that close upon detection of fire and stopping
the fan(s) during a fire. q f = 0.0081 ∙ a0.4231 ∙ A0.5009 ∙ h1.0394 (1)
50 ECO L I BR I U M • J U LY 2018
FORUM
In the late phase, pressure relief of the room where the fire that for openings with the top part of the opening being located
has originated has occurred. This typically happens because a maximum of 360mm above floor level (scale 1:1), negligible
of window breakage due to the greatly elevated temperatures. amounts of smoke were spread. When a fan (19Pa positive
pressure) was connected to the supply air opening, negligible
2.3 Smoke spread via ventilation systems smoke spread was observed up to 800mm above floor level
The conditions required to cause smoke spread will differ for (scale 1:1).
supply and exhaust systems. For supply systems, smoke will
spread downstream through the ductwork when the fire flow For exhaust systems, a conservative criterion for avoiding
causes the pressure in the room to be equal to the pressure drop smoke spread is to maintain at least 0Pa in branches between
between the main supply duct and the room. E.g., if the pressure ducts serving different fire compartments (for example, see
drop between the main supply duct and the room is 100Pa, the Point A in Figure 2) (Bengtson, Jönsson, & Frantzich, 2005).
fire needs to create at least a pressure of 100Pa before smoke is If the pressure in this point is 0Pa or less, it is physically
spread via the supply system. It is possible for a fire to create impossible for smoke to spread between the different
pressures up to 1,000–2,000Pa (Backvik, Fagergren, & Jensen, compartments. The criteria is conservative because in reality
2008; Kallada Janardhan & Hostikka, 2017). Therefore, the the pressure in the branching between fire compartments must
supply air system typically needs to be protected by backflow be greater than the dynamic pressure generated at this point.
protection dampers or by placing the supply air openings near Swedish guidelines for engineering assessments related to
floor level or by installing a sprinkler system in the building. ventilation systems suggest that a maximum volume of smoke
spread equivalent to 1% of the receiving fire compartment’s
volume is acceptable for occupancies with sleeping occupants
(Boverket, 2013).
A
J U LY 2018 • ECO L I BR I U M 51
FORUM
• The negative pressures generated in the building 4.3 Protection of exhaust system
do not cause door opening forces to exceed accepted To ensure that no smoke spread occurs, a simulation of
values (typically this is in the order of 110 to 150N). the ventilation system was carried out using the modelling
software Program Flow System (PFS) (Jensen, 2015). A model
In addition to the above, systems utilising fans operating
of the network of ducts was created for the ventilation system.
through the fire scenario will require:
Fans were described by pressure altering elements within PFS.
• Metal ducts with appropriate seals that maintain The model is used to adjust the pressures within the system
their integrity at temperatures above 1,000°C to achieve the minimum 10Pa pressure drop between the
main duct and the room located furthest from the exhaust fan.
• Fans required to operate during a fire must be located
in a separate fire compartment. Such a fire compartment Using the equation for maximum fire-induced flow,
may not be served by the fan(s) or must be provided the maximum values were calculated using the actual floor
with fire and/or smoke dampers. and ceiling heights for the different types of rooms and using
a “fast” fire growth rate which is recommended by the Swedish
• The power supply to the fan(s) required to operate guidelines for such engineering assessments (Boverket, 2013).
during a fire must be adequately protected. Essential The maximum fire-induced flow was determined as follows:
switchboards, etc., must be located in a fire compartment
not served by the fan or protected with fire and smoke • Normal sized room (9m2): 390L/s
dampers. Power supply cables must be protected when • Accessible room (14m2): 500L/s
located in areas served by the fans.
Leakage from the rooms to the outside was assumed to be
10L/s at 15Pa pressure difference based on recommendations
4. CASE STUDY from the mechanical design engineer.
A simulation of the nominal operation of the ventilation
4.1 The building and its ventilation system
system using PFS is shown in Figure 3 (located in Appendix A).
This case study involves a single storey Class 3 building where It can be seen that the pressure drop over between the main
the ventilation system serves each Sole-Occupancy Unit (room). duct and “Room 8” is approximately 10Pa. The simulation
The eight rooms are provided with mechanical supply and shows that the fan must be able to generate a pressure of at
exhaust. The airflows to the rooms were as follows: least 69Pa at 760L/s to achieve the 10Pa pressure drop between
• Normal sized room (9m2): 95L/s the main duct and “Room 8”.
• Accessible room (14m2): 135L/s In Figure 4 (located in Appendix A), the early, pressurised
phase of a fire is simulated in “Room 7” which is the worst
For the supply and exhaust system, the lowest pressure drop case scenario for the ventilation system. The fire-induced flow
between the main duct and a room is 10Pa. is introduced into “Room 7”. The temperature of the hot gases
in “Room 7” is assumed to be 350°C. The ratio of flow of ambient
The exhaust fan is able to operate for a minimum of 60 minutes
temperature air into the supply duct and hot gases into the
when exposed to temperatures up to 200°C.
exhaust duct is solved by iterating the fire-induced pressure
Each room is a fire compartment. Under the prescriptive within the room.
regulations of the NCC, the room would have to be fitted with
The simulation shows that a positive pressure of about 7Pa
smoke dampers as well as fire dampers. The engineered solution occurs in the branch between fire compartments, however,
allows the omission of both the smoke and fire dampers from no smoke is spread. The model is adjusted for the fan’s operation
the supply and exhaust ducts to the rooms. in fire mode as the total flow at the fan is 830L/s (less than
A smoke-detection system in the building forces the 10% increase from 760L/s) and is calculated to 69Pa by
ventilation system(s) in the building to operate in “fire mode”. adjusting the fan’s ability to increase the pressure for the
For this particular case study, the exhaust fans were to ramp mixing temperature. No smoke spread occurs due to the
up to maximum speed. The exhaust fans are designed to dynamic pressure in this point created by the flow. As such,
have a 10% additional capacity to what is required for normal the ventilation system is able to prevent smoke spread between
operation. The supply air fan is set to operate at a speed that fire compartments. The pressure generated by the fan has been
provides the nominal airflows in “fire mode” but operating converted to account for the mixing temperature at the fan.
at a fixed fan speed (no variable speed drive permitted). The maximum mixing temperature at the fan in the early
phase is 71°C which does not exceed the fan’s temperature
4.2 Protection of supply system rating. As such, the fan will not fail due to elevated temperatures
Protection of smoke spread via the supply air system is in the early phase.
achieved by locating the topmost part of the supply air opening In Figure 5 (located in Appendix A), the late, flashover phase
at 250mm above the fixed floor level. As the supply air fan of a fire is simulated in “Room 7”. The temperature in the
produces a minimum of 10Pa positive pressure from the main fully developed phase is conservatively assumed to be 1,200°C.
duct, research illustrates that a negligible amount of smoke may The simulation shows that the mixing temperature at the fan is
spread via the supply air duct at this height (Nyman & Ingason, calculated to approximately 75°C which does not exceed the fan’s
2014). Adequate protection against spread of smoke and fire temperature rating. As such, the fan will not fail due to elevated
via the supply air system is therefore achieved. temperatures in the late fully developed fire phase.
52 ECO L I BR I U M • J U LY 2018
FORUM