Sunteți pe pagina 1din 5

Ecolibrium

JULY 2018 · VOLUME 17.6


RRP $14.95
PRINT POST APPROVAL
NUMBER PP352532/00001

Natural
selection
The benefits of
biophilic design.
FORUM
P EER - R E V I E W ED T ECH N I C A L PA P ER S

Simulating the effect of a


building fire on ventilation systems
Ulf Johansson, senior fire engineer RED Fire Engineers

ABSTRACT
Typically fire safety design of ventilation systems use fire and smoke dampers on ducts to each fire compartment or separate
ventilation systems for each fire compartment. These solutions are generally referred to as prescriptive solutions (also known
as deemed-to-satisfy solutions under the National Construction Code).

Less known are analytical methods that use simulations to allow a designer to predict the fire’s effect on the building’s ventilation
system. These methods predict the flow and temperature of hot gases entering the ventilation system. This allows a ventilation
system design with the fan(s) operating during a fire and where the operation of the fan is able to prevent fire and smoke spread
in the building via the ventilation system.

This paper uses a case study for a single-storey building to demonstrate how such simulations were used to justify the omission
of smoke and fire dampers from the ventilation system design. The construction cost savings associated with the engineered design
was approximately $200–$300K.

1. INTRODUCTION via leakage in the façade and internal walls. The ratio of the
fire-induced flow being pushed into the ducts, leakage or other
A building is typically divided into multiple fire compartments. paths will depend on the pressure drop (resistance) for each
Different fire compartments are separated from each other using of the components. The part that is pushed into the ducts
fire-resistant construction intended to maintain the structural is called the fire flow.
adequacy, integrity and insulation. Ventilation systems that serve
multiple fire compartments also need to be adequately protected The fire-induced flow for compartments up to 200m2 can
against fire and smoke spread. Typically, this is achieved by be calculated using Equation 1 (Backvik, Fagergren, & Jensen,
fire and/or smoke dampers fitted to the ducts to each fire 2008):
compartment that close upon detection of fire and stopping
the fan(s) during a fire. q f  = 0.0081 ∙ a0.4231 ∙ A0.5009 ∙ h1.0394 (1)

Although less known, alternative methods to adequately where:


protect against fire and smoke spread exist. Such methods
typically involve maintaining fans operating throughout
qf Fire-induced flow [m3/s]
a fire instead of installing fire/smoke dampers. In order to a Fire growth rate [W/s2]
verify that smoke and fire does not spread during a fire scenario, A Floor area of fire compartment [m2]
a model of the ventilation system can be created and the effects
of the fire can be modelled. This paper will briefly describe the h Ceiling height of fire compartment [m]
fire science relevant to ventilation systems, what acceptance In the early phase of a fire, temperatures are generally
criteria are typically applied to a fire engineering design of low because the fire has not reached flashover. The Swedish
a ventilation system and the tools that may be used to simulate guidelines for engineering assessments related to ventilation
the fire-induced effects on the ventilation system. systems recommend that a maximum temperature of 350°C
may be used to approximate the room temperatures in the early
2. THEORY phase of a fire (Boverket, 2013).

2.1 The effects of fire – Early, pressurised phase 2.2 The effects of fire


A fire in a room will generate heat which in turn causes – Late phase (fully developed fire)
volumetric expansion. This is called the fire-induced flow. The late phase of an enclosure fire is characterised by greatly
If the room is enclosed and relatively air tight, this will cause elevated temperatures, often in the range of 800°C–1,200°C
the pressure to rise in the room. This is why the early stages (Karlsson & Quintiere, 2000). This is often referred to as
of a fire is sometimes referred to as the pressurised phase. a fully developed fire which means the fire has gone through
The increased pressure will lead to the air/smoke mixture a transition called flashover where all combustible material
in the room being pushed out via ventilation ducts and in the room becomes involved in the fire.

50 ECO L I BR I U M  •  J U LY 2018
FORUM

In the late phase, pressure relief of the room where the fire that for openings with the top part of the opening being located
has originated has occurred. This typically happens because a maximum of 360mm above floor level (scale 1:1), negligible
of window breakage due to the greatly elevated temperatures. amounts of smoke were spread. When a fan (19Pa positive
pressure) was connected to the supply air opening, negligible
2.3 Smoke spread via ventilation systems smoke spread was observed up to 800mm above floor level
The conditions required to cause smoke spread will differ for (scale 1:1).
supply and exhaust systems. For supply systems, smoke will
spread downstream through the ductwork when the fire flow For exhaust systems, a conservative criterion for avoiding
causes the pressure in the room to be equal to the pressure drop smoke spread is to maintain at least 0Pa in branches between
between the main supply duct and the room. E.g., if the pressure ducts serving different fire compartments (for example, see
drop between the main supply duct and the room is 100Pa, the Point A in Figure 2) (Bengtson, Jönsson, & Frantzich, 2005).
fire needs to create at least a pressure of 100Pa before smoke is If the pressure in this point is 0Pa or less, it is physically
spread via the supply system. It is possible for a fire to create impossible for smoke to spread between the different
pressures up to 1,000–2,000Pa (Backvik, Fagergren, & Jensen, compartments. The criteria is conservative because in reality
2008; Kallada Janardhan & Hostikka, 2017). Therefore, the the pressure in the branching between fire compartments must
supply air system typically needs to be protected by backflow be greater than the dynamic pressure generated at this point.
protection dampers or by placing the supply air openings near Swedish guidelines for engineering assessments related to
floor level or by installing a sprinkler system in the building. ventilation systems suggest that a maximum volume of smoke
spread equivalent to 1% of the receiving fire compartment’s
volume is acceptable for occupancies with sleeping occupants
(Boverket, 2013).
A

BASIC-1, 4 Figure 2:  Point A illustrates branching between different


fire compartments. Used with permission from Hagab.

2.4  Fire spread via ventilation systems


The risk of fire spread is mainly concerned with the late phase
of the fire when temperatures are greatly elevated.
Because ducts are passing through fire resistant construction
and not fitted with fire dampers (which protect against heat
transfer between fire compartments), metal ducts may be heated
in the room of fire origin and conduct heat to the parts of the
BRANDCELL SCHAKT duct in another fire compartment. Because hot gases also are
entering and being transported away from the room of fire
Figure 1:  Illustration with solution using backflow prevention damper.
origin, the temperature inside a duct far from the room of fire
Used with permission from Hagab. origin may be sufficient to cause fire spread. Depending on the
temperatures inside the ducts, the ducts will need to be provided
Backflow prevention dampers are a special type of with fire rated insulation.
“passive” damper that allow air to flow in one direction
but automatically close when the airflow changes direction
(see Figure 1). Because this is the major risk for the supply air 3. DESIGN CONSIDERATIONS
ducts in the pressurised phase, such dampers provide protection AND ACCEPTANCE CRITERIA
against smoke spread. The design of the ventilation system must demonstrate
The Swedish design guide for ventilation systems suggests the following:
that by placing the top of supply air openings a maximum • The spread of smoke between different fire compartments
of 50mm above the floor level provides adequate protection is less than 1 % of the receiving compartment’s volume
against smoke spread (Backvik, Fagergren, & Jensen, 2008). when exposed to the worst credible fire.
However, the justification for the 50mm criteria appears
to be lacking. In a recent research report using 1:2 scale tests, • Mixing temperatures at the fan does not exceed
it was demonstrated that low level supply openings appear the fan’s temperature rating.
to provide protection against smoke spread (Nyman & Ingason, • The provided fire rated insulation is appropriate for
2014). For tests involving low level supply air openings without the calculated/simulated mixing temperatures in the ducts
any fan connected to the opening, it could be demonstrated to prevent fire spread.

J U LY 2018 • ECO L I BR I U M 51
FORUM

• The negative pressures generated in the building 4.3  Protection of exhaust system
do not cause door opening forces to exceed accepted To ensure that no smoke spread occurs, a simulation of
values (typically this is in the order of 110 to 150N). the ventilation system was carried out using the modelling
software Program Flow System (PFS) (Jensen, 2015). A model
In addition to the above, systems utilising fans operating
of the network of ducts was created for the ventilation system.
through the fire scenario will require:
Fans were described by pressure altering elements within PFS.
• Metal ducts with appropriate seals that maintain The model is used to adjust the pressures within the system
their integrity at temperatures above 1,000°C to achieve the minimum 10Pa pressure drop between the
main duct and the room located furthest from the exhaust fan.
• Fans required to operate during a fire must be located
in a separate fire compartment. Such a fire compartment Using the equation for maximum fire-induced flow,
may not be served by the fan(s) or must be provided the maximum values were calculated using the actual floor
with fire and/or smoke dampers. and ceiling heights for the different types of rooms and using
a “fast” fire growth rate which is recommended by the Swedish
• The power supply to the fan(s) required to operate guidelines for such engineering assessments (Boverket, 2013).
during a fire must be adequately protected. Essential The maximum fire-induced flow was determined as follows:
switchboards, etc., must be located in a fire compartment
not served by the fan or protected with fire and smoke • Normal sized room (9m2): 390L/s
dampers. Power supply cables must be protected when • Accessible room (14m2): 500L/s
located in areas served by the fans.
Leakage from the rooms to the outside was assumed to be
10L/s at 15Pa pressure difference based on recommendations
4.  CASE STUDY from the mechanical design engineer.
A simulation of the nominal operation of the ventilation
4.1 The building and its ventilation system
system using PFS is shown in Figure 3 (located in Appendix A).
This case study involves a single storey Class 3 building where It can be seen that the pressure drop over between the main
the ventilation system serves each Sole-Occupancy Unit (room). duct and “Room 8” is approximately 10Pa. The simulation
The eight rooms are provided with mechanical supply and shows that the fan must be able to generate a pressure of at
exhaust. The airflows to the rooms were as follows: least 69Pa at 760L/s to achieve the 10Pa pressure drop between
• Normal sized room (9m2): 95L/s the main duct and “Room 8”.

• Accessible room (14m2): 135L/s In Figure 4 (located in Appendix A), the early, pressurised
phase of a fire is simulated in “Room 7” which is the worst
For the supply and exhaust system, the lowest pressure drop case scenario for the ventilation system. The fire-induced flow
between the main duct and a room is 10Pa. is introduced into “Room 7”. The temperature of the hot gases
in “Room 7” is assumed to be 350°C. The ratio of flow of ambient
The exhaust fan is able to operate for a minimum of 60 minutes
temperature air into the supply duct and hot gases into the
when exposed to temperatures up to 200°C.
exhaust duct is solved by iterating the fire-induced pressure
Each room is a fire compartment. Under the prescriptive within the room.
regulations of the NCC, the room would have to be fitted with
The simulation shows that a positive pressure of about 7Pa
smoke dampers as well as fire dampers. The engineered solution occurs in the branch between fire compartments, however,
allows the omission of both the smoke and fire dampers from no smoke is spread. The model is adjusted for the fan’s operation
the supply and exhaust ducts to the rooms. in fire mode as the total flow at the fan is 830L/s (less than
A smoke-detection system in the building forces the 10% increase from 760L/s) and is calculated to 69Pa by
ventilation system(s) in the building to operate in “fire mode”. adjusting the fan’s ability to increase the pressure for the
For this particular case study, the exhaust fans were to ramp mixing temperature. No smoke spread occurs due to the
up to maximum speed. The exhaust fans are designed to dynamic pressure in this point created by the flow. As such,
have a 10% additional capacity to what is required for normal the ventilation system is able to prevent smoke spread between
operation. The supply air fan is set to operate at a speed that fire compartments. The pressure generated by the fan has been
provides the nominal airflows in “fire mode” but operating converted to account for the mixing temperature at the fan.
at a fixed fan speed (no variable speed drive permitted). The maximum mixing temperature at the fan in the early
phase is 71°C which does not exceed the fan’s temperature
4.2  Protection of supply system rating. As such, the fan will not fail due to elevated temperatures
Protection of smoke spread via the supply air system is in the early phase.
achieved by locating the topmost part of the supply air opening In Figure 5 (located in Appendix A), the late, flashover phase
at 250mm above the fixed floor level. As the supply air fan of a fire is simulated in “Room 7”. The temperature in the
produces a minimum of 10Pa positive pressure from the main fully developed phase is conservatively assumed to be 1,200°C.
duct, research illustrates that a negligible amount of smoke may The simulation shows that the mixing temperature at the fan is
spread via the supply air duct at this height (Nyman & Ingason, calculated to approximately 75°C which does not exceed the fan’s
2014). Adequate protection against spread of smoke and fire temperature rating. As such, the fan will not fail due to elevated
via the supply air system is therefore achieved. temperatures in the late fully developed fire phase.

52 ECO L I BR I U M  •  J U LY 2018
FORUM

The fan will therefore maintain the integrity between REFERENCES


the fire compartments throughout the fire.
Backvik, B., Fagergren, T., & Jensen, L. (2008). Installationsbrandskydd:
The mixing temperature is calculated in different parts ventilation, rör, el. Stockholm: Brandskyddslaget.
of the main ductwork for the late phase in the simulation. Bengtson, S., Jönsson, R., & Frantzich, H. (2005). Brandskyddshandboken:
The temperature decreases closer to the fan as more ambient en handbok för projektering av brandskydd i byggnader. Lund: Wallin & Dalholm.
temperature air is mixed with the hot gases. Based on the worst Boverket. (2013). The Swedish National Board of Housing, Building and
credible mixing temperatures, the main duct and associated Planning’s general recommendations on the analytical design of a building’s
insulation was provided with a Fire Resistance Level (FRL) fire protection, BBRAD 3. Karlskrona: Swedish National Board of Housing,
of -/30/30 which will limit the surface temperature to 160°C Building and Planning.
and prevent fire spread to the degree necessary (Backvik, Jensen, L. (2015). PFS++ Reference Manual. Lund: Lund University.
Fagergren, & Jensen, 2008). Ducts serving a single room Kallada Janardhan, R., & Hostikka, S. (2017). Experiments and Numerical
was provided with an FRL of -/60/60. Simulations of Pressure Effects in Apartment Fires. Fire Technology, 53,
1353–1377.
The simulations illustrate only one out of several similar
Karlsson, B., & Quintiere, J. (2000). Enclosure Fire Dynamics. Boca Raton,
ventilation systems for the case study building. In total, the FL: CRC Press.
case study building had 70 rooms. The engineered method
Nyman, H., & Ingason, H. (2014). Rumsbrand med lågt placerade
allowed fire and smoke dampers to be omitted from each
ventilationsdon – modellskaleförsök. Borås: SP Fire Research.
room. Based on indicative pricing from manufacturers, this
results in a cost savings of approximately $200K–$300K for
the construction of the building. Fire and smoke dampers
require ongoing maintenance and replacement for the lifetime ABOUT THE AUTHOR
of the building. The engineered assessment leads to significantly
lower costs for maintenance for the case study building. A Chartered Professional Engineer, Ulf Johansson has over
five years of experience as a consulting fire safety engineer
in both Australia and Sweden. He is also a registered building
5. CONCLUSION practitioner (RBP) in the category of engineer – fire safety.
The available fire science related to fire development and One of Johansson’s passions is alternative fire safety designs
behaviour of ventilation system components allows modelling of ventilation and smoke-control systems. He has used
of the effects from fire on a building’s ventilation system. engineering methods to carry out analytical fire safety design
By applying fire safety engineering methods and tools, it is of ventilation systems for numerous projects, including
possible to justify designs where fire and smoke dampers are apartment buildings, offices, hospitals, aged care and heritage
buildings. He is also a specialist in performance-based
omitted and replaced by fans that operate through during a
assessments such as advanced smoke spread modelling
fire. The cost savings associated with such engineered designs
(e.g., CFD), egress modelling and structural fire assessments.
for the construction phase are significant and result in reduced
maintenance for fire safety systems over the building’s lifetime.  ❚

S-ar putea să vă placă și