Product Information Bulletin

Unsafe VFD Control Cabinet

REFERENCE REFERENCE DESCRIPTION

This document contains proprietary and confidential information which NOV


belongs to National-Oilwell Varco, L.P., its affiliates or subsidiaries (all
collectively referred to hereinafter as "NOV"). It is loaned for limited 2800 N. Frazier Street
purposes only and remains the property of NOV. Reproduction, in whole Conroe, TX 77303
or in part, or use of this design or distribution of this information to others
is not permitted without the express written consent of NOV. This
Phone: 936-756-4800
document is to be returned to NOV upon request and in any event upon Fax: 936-523-2788
completion of the use for which it was loaned. This document and the
information contained and represented herein is the copyrighted property
of NOV.
© National Oilwell Varco
DOCUMENT NUMBER REV

PIB-01022 0

www.nov.com/brandt
Document number PIB-01022
Revision 0
Page 1 of 6

Revision History

0 10.01.2010 Initial Release JPW KED ES


Rev Date ECN Number Prepared Checked Approved

www.nov.com/brandt
Document number PIB-01022
Revision 0
Page 2 of 6

Product: VFD Control Cabinet

Problem: A VFD cabinet that does not meet Engineering's safety standards has
been found in the Conroe facility. These standards require all high
voltage terminals to be covered or finger safe.
Figure 1, Figure 2 and Figure 3 demonstrate examples of what
Conroe Engineering considers unsafe cabinets.
Solution: If you have similar cabinets, please do the following:
1. Cover any exposed high voltage components (terminals,
fuses, transformers, reactors, plugs, receptacles, etc.) with
Lexan glass. Figure 4 and Figure 5 show what Engineering
considers safe practice. Lexan glass can be commercially
bought at a local Home Depot.
2. NOV Engineering has developed a comparable unit at the
cost of $35,000. This cabinet is readily available to you and
we recommend using them in the future. The part number for
the cabinet is 23904. Figure 6 shows the new cabinet.
Drawings, wiring diagrams and spare parts are in Symix.
The unit is purged and pressurized, designed to meet NFPA
496 design safety standards and is suitable for use in
hazardous locations.

www.nov.com/brandt
Document number PIB-01022
Revision 0
Page 3 of 6

Figure 1. Incorrect Control Cabinet with exposed high voltage terminals and uncovered VFDs

www.nov.com/brandt
Document number PIB-01022
Revision 0
Page 4 of 6

Figure 2. Incorrect Exposed Fuses

Figure 3. Incorrect High Voltage Female Receptacle

www.nov.com/brandt
Document number PIB-01022
Revision 0
Page 5 of 6

Figure 4. Correct Power Terminals Covered or Shielded Behind Lexan Glass

Figure 5. Correct Fuses Covered and Finger Safe

www.nov.com/brandt
Document number PIB-01022
Revision 0
Page 6 of 6

Figure 6. Correct New Control Cabinet