In the High impedance differential relay the simple current or voltage based
operated relay can be use as High impedance with the series of stabilizing resistor
and withe parallel connection of metrosil.
in this the setting of stabilizing resistor is based on the required operating voltage in
the relay and metrosil is provided for to avoid the relay to operate from through fault
current.
for a High impedance differential protection we should have same CT ratios, same
Knee point voltage, same class of CT s with same magnetizing current of the ct
should be use. if any changes is there in the CTs causes different burden across the
both end and it makes the change in set operating voltage across the relay.( in the
case of ideal transformers we can go for High impedance).
Low impedance:
in the Low impedance relay nothing but biased differential relay in this we have the
slopes to avoid relay operation from the through fault current and CT saturation
condition also.
i) CT ratio errors