Copper Conductor PVC Insulated Building Wire

Cu/PVC 450/750 V (NYA)

Specification :
SNI 04-6629.3 : 2006

Constructions:

Conductor Applications:
Annealed plain copper round circular stranded or according to Permanent Installation in conduit or exposed wiring in dry location.
SNI IEC 60228
Note : [re] round solid conductor
Insulation [rm] circular stranded conductor
Extruded layer of Polyvinyl Chloride (PVC) complied with
SNI 6629.1 ; SNI 04-6629.3 Packing : [C] Coil
[D] Drum
Colour :
- Yellow Strip Green or Light Blue or Black or Yellow or Red

Current Carrying
Conductor Nominal Overall Weight Min. Insulation Short Circuit Standard
Capacity at 30°C
Nominal Thickness of Diameter of Cable DC. Resistance Current Delivery
Cross-section Insulation (approx) (approx) at 20°C Capacity at
Length
Area In Pipe In Air 1.0 Second
sq.mm mm mm kg/km M.Ohm. A A kA mm
1.5 re 0.7 3.3 19 50 15 24 0.17 100/C
1.5 rm 0.7 3.4 20 50 15 24 0.17 100/C
2.5 re 0.8 3.9 31 50 19 32 0.29 100/C
2.5 rm 0.8 4.2 33 50 19 32 0.29 100/C
4 re 0.8 4.4 45 50 25 42 0.46 100/C
4 rm 0.8 4.7 48 50 25 42 0.46 100/C
6 re 0.8 4.9 65 50 33 54 0.69 100/C
6 rm 0.8 5.4 71 50 33 54 0.69 100/C
10 re 1.0 6.1 92 40 45 73 1.15 100/C
10 rm 1.0 6.8 108 40 45 73 1.15 100/C
16 rm 1.0 8.0 175 40 61 98 1.84 3000/D
25 rm 1.2 9.8 273 40 83 129 2.88 3000/D
35 rm 1.2 11 367 40 103 158 4.03 2000/D
50 rm 1.4 13 523 30 132 197 5.75 1000/D
70 rm 1.4 15 692 30 165 245 8.05 1000/D
95 rm 1.6 17 962 30 197 290 10.93 1000/D
120 rm 1.6 19 1192 30 235 345 13.80 500/D
150 rm 1.8 21 1511 20 - 390 17.25 500/D
185 rm 2.0 23.5 1844 20 - 445 21.28 500/D
240 rm 2.2 26.5 2430 20 - 525 27.60 500/D
300 rm 2.4 29.5 3015 20 - 605 34.50 500/D
400 rm 2.6 33.5 3863 20 - 725 46.00 500/D

sales@kabelindo.co.id 1
Single Core Flexible Copper Conductor PVC Insulated

Cu/PVC-f 450/750 V (NYAF)

Specification :
SNI 04-6629.5 : 2006

Constructions:

Conductor Applications:
Annealed plain copper wires bunch stranded, according toSNI Used for fixed Installation inside appliances,switchgear and controlgear.
IEC 60228
Note : [f] Flexible bunched wire
Insulation
Extruded layer of Polyvinyl Chloride (PVC) complied with Packing : [C] Coil
SNI 6629.1 ; SNI 04-6629.5 [D] Drum

Colour :
- Yellow Strip Green or Light Blue or Black or Yellow or Red

Conductor Nominal Overall Weight Min. Insulation Current Carrying Short Circuit Standard
thickness Diameter of Cable DC. Resistance Capacity at 30°C Current Delivery
Nominal No. of wire
crosssection and Insulation at 20°C Capacity at Length
(approx) (approx) In Pipe In Air 1.0 Second
area Diameter
sq.mm mm mm mm kg/km M.Ohm.km A A kA m
0.5 f 16/0.2 0.6 2.6 10 50 2.5 - 0.06 100/C
0.75 f 24/0.2 0.6 2.8 13 50 7 - 0.09 100/C
1.0 f 32/0.2 0.6 3 16 50 11 19 0.12 100/C
1.5 f 30/0.25 0.7 3.5 23 50 15 24 0.17 100/C
2.5 f 50/0.25 0.8 4.2 36 50 20 32 0.29 100/C
4f 56/0.3 0.8 5 51 50 25 41 0.46 100/C
6f 84/0.3 0.8 6.3 73 50 33 53 0.69 100/C
10 f 84/0.4 1.0 7.4 116 50 45 72 1.15 100/C
16 f 126/0.4 1.0 8.6 180 40 61 97 1.84 100/C
25 f 196/0.4 1.2 10.8 275 40 82 128 2.88 500/D
35 f 278/0.4 1.2 12 385 40 102 156 4.03 500/D
50 f 398/0.4 1.4 14.5 550 40 131 195 5.75 500/D
70 f 360/0.5 1.4 16.5 750 30 164 243 8.05 500/D
95 f 475/0.5 1.6 19.5 1000 30 205 287 10.93 500/D
120 f 608/0.5 1.6 21 1240 30 233 342 13.80 500/D
150 f 760/0.5 1.8 23.5 1550 30 - 386 17.25 500/D
185 f 925/0.5 2 26 1900 20 - 441 21.28 500/D
240 f 1221/0.5 2.2 29.5 2450 20 - 525 27.60 500/D
300 f 1517/0.5 2.4 32.5 3025 20 - 605 34.50 500/D

sales@kabelindo.co.id 5