E HIDRANTES
Based on NFPA 25
1 Adopted 7-1-14
Item Activity Description References/Date Fail N/A Pass
2.1 T Waterflow alarm devices 5.3.3 ☐ ☐ ☐
(Inspectors test – 90 sec. max.)
2.2 T Valve supervisory alarm devices Table 13.1.1.2 ☐ ☐ ☐
(Functioning)
2.3 T Supervisory signal devices Table 13.1.1.2 ☐ ☐ ☐
(Functioning)
2.4 T Main drain Table 13.1.1.2 ☐ ☐ ☐
(Static and residual pressure within tolerance)
2.5 T Antifreeze solution 5.3.4 ☐ ☐ ☐
(Within tolerance)
2.6 T Gauges 5.3.2 ☐ ☐ ☐
(Replaced or tested every 5 years, within 3%) Date of last test/replacement:
Click here to enter a date.
2.7 T Sprinklers – Extra high temperature 5.3.1.1.1.4 ☐ ☐ ☐
(5 –year testing) Date of last test/replacement:
Click here to enter a date.
2.8 T Sprinklers – Fast / Quick response 5.3.1.1.1.3 ☐ ☐ ☐
(Tested after 20 years at 10-year intervals) Date of last test/replacement:
Click here to enter a date.
2.9 T Sprinklers – At 50 years and thereafter 5.3.1.1.1 ☐ ☐ ☐
(Replaced or tested at 10-year intervals) Date of last test/replacement:
Click here to enter a date.
2.10 T Sprinklers – At 75 years and thereafter 5.3.1.1.1.5 ☐ ☐ ☐
(Replaced or tested at 5-year intervals, replace prior 1920) Date of last test/replacement:
Click here to enter a date.
2.11 T Sprinklers – Dry at 10 years and thereafter 5.3.1.1.1.6 ☐ ☐ ☐
(Replaced or tested at 10-year intervals) Date of last test/replacement:
Click here to enter a date.
3.1 I&M Valves (all types) Table 13.1.1.2 ☐ ☐ ☐
( 5-year internal inspection) Date of last internal inspection:
Click here to enter a date.
3.2 Dry Pipe/Preaction Valves Table 13.1.1.2 ☐ ☐ ☐
(Trip test, quick-opening device, low pressure alarm, 5-year Date of last internal inspection:
internal inspection) Click here to enter a date.
2 Adopted 7-1-14
1. Deficiencies and Comments (Explain any “Fail” answers)
2. Note any Changes in Hazard, Occupancy, Use, Process, or Materials (Sec. 4.1.5 and 4.1.6)
3 Adopted 7-1-14