Sunteți pe pagina 1din 7

Estimation of Population for Waste Water Purifier of Buildings

(JIS A 3302 - 2000)

Table 1
Population equivalent Guide line (ministry of
Construction Japan 1996)
No Building Use Waste water volume and BOD
(Joint treatment)
Formula Calculation unit Volume BOD
Pubic, hall, moving theater, n = 0.08 A n : PE 16 150
a
entertainment hall A : Area (m2) (L/m2-D) (mg/L)
Stadium, race track, speedboat course n = 16 C n : PE 2,400 260
1 Assembly hall b
C : total no.of toilets (L/units-D) (mg/L)
Gymnasium, admission stands n = 0.065 A n : PE 10 260
c
A : Area (m2) (L/m2-D) (mg/L)
A < 130 m2 n=5 n : PE 200 200
a house
130 m2 <=130 m2 n=7 A : Area (m2) (L/p - D) (mg/L)
n : PE 10 200
If n <=3.5 in one house, n (L/m2-D) (mg/L)
shall be 3.5, or if one
house made up by one
b apartment n = 0.05 A
room, n shall be 2. And if
2 Residential
more than 6 person will
live in one house, n shall
be 8
n : PE 14 140
c lodge, dormitory n = 0.07 A
A : Total Area (m2) (L/m2-D) (mg/L)
dormitory, army camp, home for the n : PE 200 200
d n=P
aged, nursing home P : person who occupy (L/m2-D) (mg/L)
a have wedding n : PE 30 200
hall or n = 0.15 A A : total area (m2) (L/m2-D) (mg/L)
banquet hall
hotel
no wedding n : PE 30 200
hall, or no n = 0.075 A A : total area (m2) (L/m2-D) (mg/L)
3 accommodation
banquet hall 1,000 50
n : PE
b motel n=5R R : no. of rooms (L/room-D) (mg/L)
n=P n : PE 200 200
c
lodge, training camp, youth hostel P : person who occupy (L/m2-D) (mg/L)
with kitchen <300 beds n = 8 B 300 beds < with kitchen
or washing >= 300 n=11.43(B- 1,000 and washing
a hospital, clinic, machine for beds 300)+2,400 (L/bed-D) equipment
4 medical hospital for infection business n : PE 320 (mg/L)
without kitchen <300 beds n = 8 B B : no. of beds 300 beds < without kitchen
or washing >= 300 n=11.43(B- 1,000 and washing
machine for beds 300)+2,400 (L/bed-D) equipment
business 320 (mg/L)
b clinic, doctor's office n = 0.19 A n : PE 25 300
A : total area (m2) (L/m2-D) (mg/L)
a shop, market n = 0.075 A 15 (L/m2-D) 150 (mg/L)
b department store n = 0.15 A 30 (L/m2-D) 150 (mg/L)
5 shop in general n = 0.72 A n : PE A:total area (m2) 130 220
c restaurant (L/m2-D) (mg/L)
high loading n = 2.04 A 260 450
(L/m2-D) (mg/L)
low loading n = 0.55 A 110 150
(L/m2-D) (mg/L)
6 amusement a Billiard saloon, table tennis club n = 0.075 A n : PE 15 (L/m2-D) 150 (mg/L)
b Pachinko game shop n = 0.11 A A : area (m2) 22 (L/m2-D) 150 (mg/L)
c Igo club, mah-jong club n = 0.15 A 30 (L/m2-D) 150 (mg/L)
d discotheque club n = 0.05 A 100 (L/m2-D) 150 (mg/L)
e golf practice range n = 0.25 S n : PE 50(L/box-D) 150 (mg/L)
S : no.of batter box
f bowling center n = 2.50L n : PE 500(L/lane-D) 150 (mg/L)
L : no. of lane
g Batting center n = 0.20S n : PE 40 (L/box - D) 150 (mg/L)
S : batter box
night n : PE 100(L/court-D) 150 (mg/L)
h Tennis club operation n = 3S S : no.of court
no night n : PE 400(L/court-D)
operation n = 2S S : no.of court
i amusement park, bathing beach n = 16C n : PE 2400(L/place-D) 260 (mg/L)
C : total no.toilet
general part n=3,60P
toilet sightseeing part n=3,83P
a service area 820 (L/units.D)

7 Car Park
toilet
a service area no kiosk n=2,55P n = PE 820 (L/units.D)
general part n=2,66P p = total no of car
kiosk
sightseeing part n=2,81P
7 Car Park n = PE
C = no. of toilet ( feces )
b car park, garage n=( 20C + 120 U ) /8 X t U = no.of toilet ( Urinal ) 170 (L/units.D)
t = occupied hour/day
t = 0,4 - 2,0
n = PE
c gas station n=20
per one station
nursary scholl, kindergarden n = PE 50 (L/p.D) 180 ( mg/L )
a n=0,20P
primary scholl,middle scholl P = no of person
8 School b high scholl, university, other scholl. n=0,25P 60 (L/p.D) 180 ( mg/L )
n = PE 16 (L/p.D) 150 ( mg/L )
c library n=0,08A
A = total area ( m2 )
with kitchen n=0,075A n = PE 15 (L/p.D) 300 ( mg/L )
9 Office a office
with out kotchen n= 0,06A A = total area ( m2 ) 15 (L/p.D) 150 ( mg/L )
with kitchen n=0,75 P n = PE 100 (L/p.D) 150 ( mg/L )
10 a factory, work shop, institute, laboratory.
Working Place with out kotchen n=0,30P P = no of person 60 (L/p.D) 150 ( mg/L )
a market n= 0,02A n = PE 4,20 (L/p.D) 200 ( mg/L )
b public bath n= 0,17A A = total area ( m2 ) 33 (L/p.D) 50 ( mg/L )
11 Other Facilities d public lavatory n= 16C n = PE
P<100,000 n=0,008P n = PE
c Station bus terminal
100,000<P<200,000 n=0,0010P P = no of passenger
RESEARCH AND DEVELOPMENT
ON BUILDING SANITATION SYSTEM
JAPAN - INDONESIA

DESIGN CRITERIA

NO ITEM Indonesia Standard Japan Standard


DISCHARGE BOD LOAD DISCHARGE BOD LOAD
(l/p/day) (g/p/day) (l/p/day) (g/p/day)

1 TOILET 10 10.5 50 13

2 KITCHEN 30 30 21

3 WASHING 50 19.5 40 4

4 BATH 70 80 2

TOTAL 160 30 200 40

NOTE:
DATA SOURCE 1994: NATIONAL URBAN DEVELOPMENT CORPORATION
MINISTRY OF CONSTRUCTION INFRASTRUCTURE DEVELOPMENT INSTITUTE JAPAN
National Regulation of
Effluent Standard of Domestic Waste Water Treatment
NO. 112 , 2003 Year

NO INDICATOR UNIT MAX.

1 PH mg/l 6--9

2 BOD mg/l 100

3 TSS mg/l 100

4 OIL & GREASE mg/l 10

Date : 10 July 2003


Ministry of Indonesia Environment

Nabiel Makarim,MPA,MSM
eatment
DKI Jakarta Regulation of
Effluent Standard of Domestic Waste Water Treatment
NO. ………………………

NO INDICATOR UNIT MAX.

1 PH mg/l 6--9
2 Organic (KMnO4) mg/l 85
3 TSS mg/l 50
4 Ammonia mg/l 10
5 Oil & Grease mg/l 10
6 Blue Metilen mg/l 2
7 COD mg/l 80
8 BOD mg/l 50

Date : …………………..
GOVERNOR OF DKI JAKARTA

SUTIYOSO
IPLC
PERMIT LIECENCE OF DOMESTIC WASTE WATER
NO. 30 , 1999 YEAR

1 SUBMISSION LETTER TO BAPEDALDA (BPLHD)

2 ATTACHMENT:
A. FORM DATA
B. FLOWCHART
C. NOTARIAT LICIENCE COMPANY
D. BUILDING LICIENCE (IMB)
E. BUILDING SYSTEM LICIENCE (IPB)
F. LICIENCE OF HO (UNDANG-UNDANG GANGGUAN)
G. DOMESTIC WASTE WATER DESIGN
H. UKL/UPL DOCUMENT
I. TEST LABORATORY
J. LETTER OF

3 VALIDATION FOR 5 YEARS

Jakarta, 19 April 1999


GOVERNOR OF DKI JAKARTA

SUTIYOSO