This document describes functioning of ARCODE elevator controller in fire evacuation and
firefighter service modes.
Section 1 gives a general description of the controller's behavior in fire evacuation and
firefighter service modes.
Section 2 describes how a fire exit floor is selected in fire evacuation mode.
Section 3 describes in detail the working of the doors in firefighter service mode.
Sections 4 and 5 gives a description of each parameter related to fire evacuation and
firefighter service operation and the meanings of their options.
Section 6 and 7 lists the inputs and outputs which are related to fire operations.
To ease selection of correct parameters for some of the frequently used standards,
compatibility settings for the following standards have been included as presets, selectable
by the parameter "(P0613) Standard compatibility":
- User defined
- EN81-73 (fire evacuation only)
- EN81-72 (firefighter elevator without key in the car)
- EN81-72 (firefighter elevator with key in the car)
Selecting any of the options except "User defined" will hide some of the fire related
parameters from the menu and will set them to the appropriate values enforced by the
selected standard. Other parameters will be left for the user to set.
Section 8 gives lists of enforced preset parameters for each standard-compatibility option.
References to articles in standard documents are given where possible.
In the future, other standard-compatibility presets may be added to newer versions of the
firmware by requests and feedback from our customers.
1. Operation of ARCODE Controller in Fire
Fire Phase-1 Operation mode is intended to carry the passengers inside the lift to a safe
evacuation floor when a fire is detected in the building. Upon arrival to the evacuation floor,
the elevator is taken out of service.
a) Entry to Phase-1:
Fire evacuation operation is initiated on the following conditions:
if "(P0844) Fire floor selection method" is set to
- "Main fire evacuation floor":
if (FES1), (FFKL) or (FFKC) input is activated.
Note: (FFKC) is ignored if (P0843) is set to "Not installed"
-"Main or alternate fire evacuation floor":
Only if (FES1) or (FES2) inputs are activated.
-"Fire detected floor" or "Lowest floor without fire"
Any input (FDLx) from a floor is activated.
b) Operation in Phase-1:
When Fire Evacuation Operation is activated:
- Photocell inputs are disabled.
- All landing call buttons are disabled.
- Outputs (FRA1) and (FRA3) are activated.
- Controller is disconnected from group communications.
- Relevelling and door preopening is disabled.
- Behavior of door-open button and car command from the current floor depends on
the parameters: P0866
- If the car was moving on the direction of the selected fire-evacuation floor:
- The travel is shortened or lengthened accordingly to move to the fire
selected fire evacuation floor as soon as possible.
- If the car was moving on the opposite direction of the selected fire-evacuation floor:
- The car is stopped at the nearest possible stop. Then, without opening the
doors, it is sent to the selected fire evacuation floor.
c) Exiting Phase-1:
Condition for returning to normal service is determined by the parameter P0614.
1.2. Fire Phase-2 Operation Mode (firefighting):
Fire Phase-2 Operation mode is intended for use by the fire service personnel during fire.
a) Entry to Phase-2:
Fire Phase-2 Operation is initiated when all of the following conditions are true:
- Fire Phase-1 Operation is completed (car waiting on selected fire evacuation floor)
- (FFKL) or (FFKC) input is activated.
Operation in Phase-2:
During Phase-2 Operation:
- Photocell inputs are disabled
- All landing call buttons are disabled.
- Outputs (FRA2) and (FRA3) are activated.
- Controller is disconnected from group communications.
- Relevelling and door preopening is disabled.
- Only one car command can be registered at a time. When a car command is already
registered, pressing the car command button of another floor clears the previous
registration and the new command gets registered.
- Behavior of the door(s) are described in the section "Behavior of the Doors in Fire
Phase-2 Operation Mode"
- If the parameter "(P0863) Car commands in firefighter operation" is set to the value
"Only when firefighter key inside car is active":
- When the key input (FFKC) is inactive:
- the car will open its doors and will not close the door(s) in any
condition. Also car calls will not be registered.
- When the key input (FFKC) is active:
- A single car command can be given. The door(s) will close if there is a
car command or door-close button is pressed.
- If the parameter "(P0864) When the landing-key turned OFF and ON (5 sec)" is set
to the value "Fire evacuation (Phase-1) is restarted":
The car may be recalled to the fire evacuation floor by toggling the firefighter
key in the landing from ON to OFF and then back to ON again within 5
seconds. In this case, the controller will shift back to Fire Phase-1 Operation
Mode, which will cause the car to close the doors, move to the fire
evacuation floor, open the doors and wait. After opening of the doors,
Fire Phase-2 Operation continues.
If the key was turned to OFF for more than 5 seconds, it will continue
operation in firefighter service mode. If the car is sent to the fire evacuation
floor by car commands while the landing firefighter key is OFF, the controller
returns to normal service mode.
2. Selection of the Fire Evacuation Floor in Phase-1
Selection of the fire evacuation floor in Phase-1 is made according to the following
parameters:
Selecting an option other than "User defined" for this parameter will enforce some of the
other parameters under "Fire evacuation and firefighting settings" branch to predefined
values. The predefined parameters will not be visible on the menu tree.
A list of enforced parameter settings for each of the standard-compatibilities is given in the
tables below.
The Vis(ibility) column in the tables indicates whether a parameter is enforced to a specific
value and hidden, or it should be set by the user.
Where possible, the standard document and article number related to the parameter is
given in the Reference column.
Note: Some of the inputs/outputs can only be used as NC or NO type contacts according to
some standards. Selecting a compatibility-mode cannot not change the contact type of the
inputs/outputs.
It is left to the user to check the contact type required by the standard and to set the correct
contact type (NC or NO) in the programmable input/output selection parameters.
EN81-73 (Fire evacuation only):