FLSS/FLS/FHS ISOLATORS AND RESTRAINTS

TABLE OF CONTENTS

General Descriptions and Specifications P3.1

KINETICS ™ Seismic Design Manual


Submittal Data P3.2

FLSS P3.2.1

FLS P3.2.2

FHS P3.2.3

Selection Information P3.3

Load Spreader Plate Data P3.4

Installation Instructions P3.5

TABLE OF CONTENTS (CHAPTER P3)


FLSS / FLS / FHS ISOLATORS/RESTRAINTS RELEASE DATE: 10/20/03

Toll Free (USA only): 800-959-1229 PAGE:


International:
Fax:
614-889-0480
614-889-0540 P3.0
World Wide Web: www.kineticsnoise.com
DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA Email: sales@kineticsnoise.com MEMBER

Kinetics Noise Control © 2003


Kinetics Model FLSS
Seismic control restrained spring vibration isolators consist of free-
standing, large diameter, laterally stable steel springs assembled
into welded steel housing assemblies that are designed to limit
vertical movement of the isolated equipment if equipment loads are
reduced or if the equipment is subjected to large external forces
such as seismic events. The housings also provide a constant free
and operating height to facilitate installation. Spring elements are
complete with internal noise isolation pads and have an adjusting
and leveling bolt as a part of the top load plate assembly. Large
holes are provided in all isolators for bolting to the structure and to
the supported equipment. To assure stability, the springs have a

KINETICS ™ Seismic Design Manual


lateral spring stiffness greater than 1.2 times the rated vertical
stiffness and are designed to provide a minimum of 50% overload
capacity. FLSS springs are available with deflections to 4 inches
(100 mm) and with load capacities to 11,800 lbs. (5364 kg) as
standard products. Custom isolators with higher deflection and
greater load capabilities are also available. Kinetics Model FLSS
spring isolators are recommended for the isolation of vibration
produced by equipment carrying a large fluid load which may be
drained, such as boilers and chillers, and for the isolation of
cooling towers, air-cooled condensers, etc., where motion due to
wind loads must be minimized.
Specification
Vibration isolators shall be seismically rated restrained spring isolators for equipment that is
subject to load variations and large external forces. Isolators shall consist of large diameter,
laterally stable steel springs assembled into welded steel housing assemblies designed to
limit movement of the supported equipment in all directions.

Housing assembly shall be of fabricated steel members and shall consist of a top load plate
complete with adjusting and leveling bolts, adjustable vertical restraints, isolation washers,
and a bottom plate with internal non-skid noise isolation pads and holes for anchoring of
the housing to the supporting structure. Housing shall be electro-zinc plated or hot-dip
galvanized for corrosion resistance. Housing shall be designed to provide a constant free
and operating height within 1/8 inch (3 mm).

The isolator housing shall provide a minimum of 1g restraint in all directions if attached with
through bolts. Spring elements shall be selected to provide static deflections as shown on
the vibration isolation schedule or as indicated or required in the project documents.
Springs shall be color coded or otherwise identified.

Spring elements shall have a lateral stiffness greater than 1.0 times the rated vertical
stiffness and shall be designed to provide a minimum of 50% overload capacity. Spring
elements shall be epoxy powder coated, and shall have a 1000-hour rating when tested in
accordance with ASTM B-117.
FLSS ISOLATORS DESCRIPTION AND SPECIFICATION
PAGE 1 OF 3 RELEASE DATE: 10/31/03

Toll Free (USA only): 800-959-1229 DOCUMENT:


International:
Fax:
614-889-0480
614-889-0540 P3.1
World Wide Web: www.kineticsnoise.com
DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA Email: sales@kineticsnoise.com MEMBER

Kinetics Noise Control ©2003


Kinetics Model FLS
Vibration isolators consist of free-standing large diameter
laterally stable steel springs assembled into welded steel
housing assemblies that are designed to limit vertical
movement of the isolated equipment if equipment loads are
reduced or if the equipment is subjected to large external
forces. The housings also provide a constant free and
operating height to facilitate installation. Spring elements are
complete with internal noise isolation pads and have an
adjusting and leveling bolt as a part of the top load plate

KINETICS ™ Seismic Design Manual


assembly. Springs are epoxy powder coated, with a 1000-hour
salt spray rating per ASTM B-117. Holes are provided in all
isolators for bolting to the structure and to the supported
equipment. The isolator can be welded to the structure as well.
To assure stability, the springs have a lateral spring stiffness
greater than 1.0 times the rated vertical stiffness, and are
designed to provide a minimum of 50% overload capacity. FLS
springs are available with deflections to 2.03 inches (52 mm)
and with load capacities to 15,600 lbs. (7076 kg) as standard
products. Custom isolators with higher deflection and greater
load capabilities are also available. Kinetics Model FLS spring
isolators are recommended for the isolation of vibration
produced by equipment carrying a large fluid load which may
be drained, such as boilers, cooling towers and chillers, and for
the isolation of cooling towers, air-cooled condensers, etc.,
where motion due to wind loads must be minimized.
Specification
Vibration isolators for equipment which is subject to load variations and large external
or torque forces shall consist of large diameter laterally stabile steel springs
assembled into welded steel housing assemblies designed to limit vertical movement
of the supported equipment.

Housing assembly shall be of fabricated steel members and shall consist of a top load
plate complete with adjusting and leveling bolts, vertical restraints, isolation washers,
and a bottom plate with internal non-skid noise isolation pads and holes provided for
anchoring to the supporting structure. Housing shall be hot dip galvanized for
corrosion resistance. Housing should be designed to provide a constant free and
operating height within 1/8 inch (0.06 mm).

Spring elements shall have a lateral stiffness greater than 1.0 times the rated vertical
stiffness and shall be designed to provide a minimum of 50% overload capacity.
Spring elements shall be epoxy powder coated, and shall have a 1000-hour rating
when tested in accordance with ASTM B-117.

FLS ISOLATORS DESCRIPTION AND SPECIFICATION


PAGE 2 OF 3 RELEASE DATE: 10/31/03

Toll Free (USA only): 800-959-1229 DOCUMENT:


International:
Fax:
614-889-0480
614-889-0540 P3.1
World Wide Web: www.kineticsnoise.com
DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA Email: sales@kineticsnoise.com MEMBER

Kinetics Noise Control ©2003


Kinetics Model FHS
Seismic control restrained spring isolators meet specifications for
Kinetics Model FDS isolators and include a steel housing assembly
to limit both lateral and vertical movement of the supported
equipment during an earthquake without degrading the vibration
isolation of the spring during normal equipment operating conditions.
Standard FHS isolators incorporate a steel housing which encloses a
neoprene snubber. Depending on the load and seismic zone, an
optional steel load spreader plate to distribute the load among
concrete anchors may be applied. A neoprene pad fitted in series
with the spring is provided. Equipment attachment is by way of a bolt
screwed downward through the equipment foot. Removal of the

KINETICS ™ Seismic Design Manual


isolator for servicing can be easily accomplished as the isolator is not
fitted with a protruding stud. In conformance with all current building
code standards, the restraining system is designed to withstand a
minimum 1.0g acceleration force. Motion is limited to approximately
0.2" in any direction.
Specification
Spring isolators shall be seismic control restrained spring isolators, incorporating a
single or multiple coil spring element, having all of the characteristics of free-standing
coil spring isolators as specified in the vibration isolation portion of this specification.
Springs shall be restrained using a housing engineered to limit both lateral and vertical
movement of the supported equipment during an earthquake without degrading the
vibration isolation capabilities of the spring during normal equipment operating
conditions.

Vibration isolators shall incorporate a steel housing and neoprene snubbing grommet
system designed to limit motion to no more than 1/4" (6 mm) in any direction and to
prevent any direct metal-to-metal contact between the supported member and the
fixed restraint housing. The restraining system shall be designed to withstand the
seismic design forces in any lateral or vertical direction without yield or failure. Where
the capacity of the anchorage hardware in concrete is inadequate for the required
seismic loadings, an adapter base plate to allow the addition of more or larger anchors
will be fitted to fulfill these requirements. In addition to the primary isolation coil spring,
the load path will include a minimum 1/4" (6 mm) thick neoprene pad.

Spring elements shall be color coded or otherwise easily identified. Springs shall have
a lateral stiffness greater than 1.2 times the rated vertical stiffness and shall be
designed to provide a minimum of 50% overload capacity. Non-welded spring
elements shall be epoxy powder coated and shall have a minimum of a 1000-hour
rating when tested in accordance with ASTM B-117.

To facilitate servicing, the isolator will be designed in such a way that the coil spring
element can be removed without the requirement to lift or otherwise disturb the
supported equipment.
FHS ISOLATORS DESCRIPTION AND SPECIFICATION
PAGE 3 OF 3 RELEASE DATE: 10/31/03

Toll Free (USA only): 800-959-1229 DOCUMENT:


International:
Fax:
614-889-0480
614-889-0540 P3.1
World Wide Web: www.kineticsnoise.com
DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA Email: sales@kineticsnoise.com MEMBER

Kinetics Noise Control ©2003


FLSS 1" DEFLECTION SEISMIC ISOLATOR A2, B2, L2, T2, D2 DIMENSIONS
IP UNITS (INCHES AND POUNDS) REFER TO OPTIONAL BASE-
PLATE USED TO INCREASE
TYPE L W T A B D E F d H VERTICAL RESTRAINT RATING WHEN ATTACHED
1-250/3500 9.00 4.00 0.31 0.75 0.75 0.69 2.75 2.75 0.56 6.25 BOLT TO CONCRETE

STANDARD SPRING COIL REMOVABLE


RATINGS COLOR FREE RATED E* F* BLOCKING
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL.
FLSS 1-250 BLUE 4.20 3.00 250 1.79 H - FR / OP
HEIGHT
FLSS 1-450 GREEN 4.20 3.00 450 1.54 d
FLSS 1-625 BLACK 4.20 3.00 625 1.44 T D
FLSS 1-800 GRAY 4.20 3.00 800 1.31
FLSS 1-1000 RED 4.20 3.00 1000 1.15 T2
D2

FLSS Submittal Drawings


FLSS 1-1250 BROWN 4.20 3.00 1250 1.09

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLSS 1-1700 ORANGE 4.20 3.00 1700 0.95
FLSS 1-2200 ORANGE GRAY 4.20 3.00 2200 1.00

Fax:
FLSS 1-2465 BLUE 4.20 3.00 2465 1.00

Email:
FLSS 1-2865 BLUE GRAY 4.20 3.00 2865 1.00 L
B*
FLSS 1-3500 BLUE BROWN 4.20 3.00 3500 1.00
A*
1-250/3500 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE W

International:
L2

DRAWING #S-01-22.11S – FLSS 1-250/3500


(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)
B2 L2
1-250/3500 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB A2

World Wide Web:


Toll Free (USA only):
8
IF EQUIP SUPPORT STEEL IS
90° TO THE LONG ISOLATOR VERT FORCE
AXIS, AN ADD'L PLATE EQUAL 7 = 12100 LBS *ALL MOUNTING BOLT PATTERNS
IN THICKNESS TO THE TOP PLATE SYMMETRICAL ABOUT ISOLATOR
IS REQUIRED CENTER-LINE
6

614-889-0540
614-889-0480
800-959-1229
5

www.kineticsnoise.com
3

sales@kineticsnoise.com
SPECIFICATIONS: WELDED TO STEEL
2
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH THROUGH BOLTED
VERTICAL FORCE LBS X 1000

CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE


NEOPRENE SNUBBING ELEMENTS. 1 ANCHORED TO CONCRETE
MINIMUM COIL OVERLOAD OF 50%.
MINIMUM Kx/Ky RATIO OF 1.0. 0
ALL ELEMENTS SAFE AT SOLID LOADING.
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET 0 1 2 3 4

HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT


ERECTION HORIZONTAL FORCE LBS X 1000
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.1-1
MEMBER
RELEASE DATE: : 2/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLSS 1" DEFLECTION SEISMIC ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
1-2500/7000 15.25 5.00 0.38 0.75 0.75 0.69 2.75 2.75 0.56 6.88 TO CONCRETE

STANDARD SPRING COIL VERTICAL RESTRAINT


RATINGS COLOR FREE RATED d BOLT
H - FR/OP F* REMOVABLE
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL. HEIGHT
FLSS 1-2500 BROWN 4.20 3.00 2500 1.09 BLOCKING
FLSS 1-3400 ORANGE 4.20 3.00 3400 0.95 T
FLSS 1-4400 ORANGE GRAY 4.20 3.00 4400 1.00
E*
D
FLSS 1-4930 BLUE 4.20 3.00 4930 1.00
FLSS 1-5730 BLUE GRAY 4.20 3.00 5730 1.00 D2 T2
FLSS 1-7000 BLUE BROWN 4.20 3.00 7000 1.00

FLSS Submittal Drawings

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


1-2500/7000 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)
1-2500/7000 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB

Fax:
L

Email:
B* A* W

International:
L2 L2
IF EQUIP SUPPORT STEEL IS

DRAWING #S-01-22.12S – FLSS 1-2500/7000


A2

World Wide Web:


90° TO THE LONG ISOLATOR B2
AXIS, AN ADD'L PLATE EQUAL

Toll Free (USA only):


IN THICKNESS TO THE TOP PLATE
IS REQUIRED
*ALL MOUNTING BOLT PATTERNS
9
VERT FORCE
SYMMETRICAL ABOUT ISOLATOR
= 26000 LBS
8 CENTER-LINE

614-889-0540
614-889-0480
800-959-1229
6

www.kineticsnoise.com
sales@kineticsnoise.com
4

WELDED TO STEEL
SPECIFICATIONS: 3
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH THROUGH BOLTED
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE 2

NEOPRENE SNUBBING ELEMENTS. ANCHORED TO CONCRETE


1
VERTICAL FORCE LBS X 1000

MINIMUM COIL OVERLOAD OF 50 %.


MINIMUM Kx/Ky RATIO OF 1.0.
0
ALL ELEMENTS SAFE AT SOLID LOADING.
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET 0 1 2 3 4 5 6 7
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT
HORIZONTAL FORCE LBS X 1000
ERECTION
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.1-2
MEMBER
RELEASE DATE: : 2/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLSS 1" DEFLECTION SEISMIC ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
TO CONCRETE
1-5000/14000 15.75 8.00 0.50 1.00 1.00 0.81 5.50 5.50 0.69 7.50

F*
STANDARD SPRING COIL E* VERTICAL RESTRAINT
RATINGS COLOR FREE RATED d BOLT
H - FR / OP REMOVABLE
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL. HEIGHT BLOCKING
FLSS 1-5000 BROWN 4.20 3.00 5000 1.09
FLSS 1-6800 ORANGE 4.20 3.00 6800 0.95 T D
FLSS 1-8800 ORANGE GRAY 4.20 3.00 8800 1.00 D2 T2
FLSS 1-9860 BLUE 4.20 3.00 9860 1.00
FLSS 1-11460 BLUE GRAY 4.20 3.00 11460 1.00

FLSS Submittal Drawings

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLSS 1-14000 BLUE BROWN 4.20 3.00 14000 1.00
1-5000/14000 REQUIRES 0.75 DIA. x 4.75 MIN. EMBED ANCHORS IN CONCRETE
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE) L

Fax:
1-5000/14000 ANCHOR BOLT TORQUE - 150 FT-LB, PULL TEST - 3625 LB

Email:
B*
A* W
L2
L2

International:
B2
A2

World Wide Web:


DRAWING #S-01-22.13S – FLSS 1-5000/14000
IF EQUIP SUPPORT STEEL IS
90° TO THE LONG ISOLATOR

Toll Free (USA only):


AXIS, AN ADD'L PLATE EQUAL VERT. FORCE VERT. FORCE
IN THICKNESS TO THE TOP PLATE
= 24800 LBS = 33000 LBS
IS REQUIRED
12 *ALL MOUNTING BOLT PATTERNS
11
SYMMETRICAL ABOUT ISOLATOR
CENTER-LINE
10

614-889-0540
614-889-0480
800-959-1229
9

WELDED TO STEEL
7

www.kineticsnoise.com
6 THROUGH BOLTED

sales@kineticsnoise.com
5 ANCHORED TO CONCRETE
SPECIFICATIONS:
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH 4

CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE 3


NEOPRENE SNUBBING ELEMENTS.
VERTICAL FORCE LBS X 1000

2
MINIMUM COIL OVERLOAD OF 50 %.
MINIMUM Kx/Ky RATIO OF 1.0. 1

ALL ELEMENTS SAFE AT SOLID LOADING. 0


POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET
0 1 2 3 4 5 6 7 8 9 10 11 12 13
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT
ERECTION HORIZONTAL FORCE LBS X 1000
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.1-3
MEMBER
RELEASE DATE: : 2/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
FLSS 2" DEFLECTION SEISMIC ISOLATOR A2, B2, L2, T2, D2 DIMENSIONS
IP UNITS (INCHES AND POUNDS) REFER TO OPTIONAL BASE-
VERTICAL RESTRAINT PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
2-100/1975 10.00 5.00 0.31 0.75 0.75 0.69 2.75 2.75 0.56 8.00
BOLT
TO CONCRETE

REMOVABLE
STANDARD SPRING COIL E* F*
RATINGS COLOR FREE RATED BLOCKING
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL. H - FR / OP
FLSS 2-100 GRAY 6.09 3.50 100 2.00 HEIGHT
d
FLSS 2-250 BLUE 6.09 3.50 250 2.00 D
T
FLSS 2-500 GREEN 6.09 3.50 500 2.00
FLSS 2-750 BLACK 6.09 3.50 750 2.00
T2
FLSS 2-995 ORANGE 6.09 3.50 995 2.00 D2

FLSS Submittal Drawings


FLSS 2-1400 ORANGE GREEN 6.09 3.50 1400 2.01

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLSS 2-1600 RED 6.09 3.50 1600 2.00
FLSS 2-1975 RED GREEN 6.09 3.50 1975 1.98
2-100/1975 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE

Fax:
L

Email:
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE) B*
2-100/1975 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB A*
W
L2

International:
B2

DRAWING #S-01-22.21S – FLSS 2-100/1975


A2 L2

World Wide Web:


IF EQUIP SUPPORT STEEL IS

Toll Free (USA only):


90° TO THE LONG ISOLATOR
10
AXIS, AN ADD'L PLATE EQUAL
IN THICKNESS TO THE TOP PLATE VERT FORCE
9
IS REQUIRED = 21300 LBS *ALL MOUNTING BOLT PATTERNS
8 SYMMETRICAL ABOUT ISOLATOR
CENTER-LINE
7

614-889-0540
614-889-0480
800-959-1229
6

www.kineticsnoise.com
4

sales@kineticsnoise.com
SPECIFICATIONS: 3 WELDED TO STEEL
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH
VERTICAL FORCE LBS X 1000

2
THROUGH BOLTED
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE
NEOPRENE SNUBBING ELEMENTS. ANCHORED TO CONCRETE
1
MINIMUM COIL OVERLOAD OF 50 %.
MINIMUM Kx/Ky RATIO OF 1.0.
0
ALL ELEMENTS SAFE AT SOLID LOADING.
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET 0 1 2 3 4

HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT HORIZONTAL FORCE LBS X 1000
ERECTION
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.1-4
MEMBER
RELEASE DATE: : 2/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
FLSS 2" DEFLECTION SEISMIC ISOLATOR A2, B2, L2, T2, D2 DIMENSIONS
IP UNITS (INCHES AND POUNDS) VERTICAL RESTRAINT REFER TO OPTIONAL BASE-
BOLT PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
2-2000/4500 11.00 5.00 0.31 0.75 0.75 0.69 2.75 2.75 0.56 10.00 TO CONCRETE

REMOVABLE
E* F* BLOCKING
STANDARD SPRING COIL
RATINGS COLOR FREE RATED H - FR/OP
TYPE SIZE OUTER INNER1 INNER2 HT. O.D. LOAD DEFL. HEIGHT
FLSS 2-2000 ORANGE 7.00 5.00 2000 2.00
d
T D
FLSS 2-2500 BLUE 7.00 5.00 2500 2.00
FLSS 2-2750 BLUE BLUE 7.00 5.00 2750 2.00
T2
FLSS 2-3025 BLUE GREEN 7.00 5.00 3025 2.02 D2
FLSS 2-3250 BLUE BLACK 7.00 5.00 3250 2.00

FLSS Submittal Drawings


FLSS 2-3500 BLUE ORANGE 7.00 5.00 3500 2.00

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLSS 2-3900 BLUE ORANGE GREEN 7.00 5.00 3900 2.00
FLSS 2-4100 BLUE RED 7.00 5.00 4100 2.00
L

Fax:
FLSS 2-4500 BLUE RED GREEN 7.00 5.00 4500 2.00 B*

Email:
2-2000/4500 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE A*
W
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE) L2
2-2000/4500 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB B2 L2

International:
A2

DRAWING #S-01-22.22S – FLSS 2-2000/4500

World Wide Web:


IF EQUIP SUPPORT STEEL IS

Toll Free (USA only):


*ALL MOUNTING BOLT PATTERNS
90° TO THE LONG ISOLATOR 10 VERT FORCE
AXIS, AN ADDT'L PLATE EQUAL SYMMETRICAL ABOUT ISOLATOR
= 23800 LBS
IN THICKNESS TO THE TOP PLATE 9
CENTER-LINE
IS REQUIRED
8

614-889-0540
614-889-0480
800-959-1229
6

www.kineticsnoise.com
sales@kineticsnoise.com
4

SPECIFICATIONS: 3
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH WELDED TO STEEL
VERTICAL FORCE LBS X 1000

CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE 2


THROUGH BOLTED
NEOPRENE SNUBBING ELEMENTS.
ISOLATORS MUST BE BOLTED OR WELDED TOP AND BOTTOM IN AN 1
ANCHORED TO CONCRETE
APPROVED MANNER
MINIMUM COIL OVERLOAD OF 50 %. 0

MINIMUM Kx/Ky RATIO OF 1.0. 0 1 2 3


ALL ELEMENTS SAFE AT SOLID LOADING.
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET HORIZONTAL FORCE LBS X 1000
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
ERECTION capacity envelope. Contact KNC for bolted to steel data.

P3.2.1-5
MEMBER
RELEASE DATE: : 2/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLSS 2" DEFLECTION SEISMIC ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
TO CONCRETE
2-4000/9000 17.50 6.00 0.50 0.75 0.75 0.69 2.75 2.75 0.56 10.13

STANDARD SPRING COIL


RATINGS COLOR FREE RATED
TYPE SIZE OUTER INNER1 INNER2 HT. O.D. LOAD DEFL.
FLSS 2-4000 ORANGE 7.00 5.00 4000 2.00
FLSS 2-5000 BLUE 7.00 5.00 5000 2.00
FLSS 2-5500 BLUE BLUE 7.00 5.00 5500 2.00
FLSS 2-6050 BLUE GREEN 7.00 5.00 6050 2.02
FLSS 2-6500 BLUE BLACK 7.00 5.00 6500 2.00

FLSS Submittal Drawings

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLSS 2-7000 BLUE ORANGE 7.00 5.00 7000 2.00
FLSS 2-7800 BLUE ORANGE GREEN 7.00 5.00 7800 2.00
FLSS 2-8200 BLUE RED 7.00 5.00 8200 2.00

Fax:
FLSS 2-9000 BLUE RED GREEN 7.00 5.00 9000 2.00

Email:
2-4000/9000 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)
2-4000/9000 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB

International:
DRAWING #S-01-22.23S – FLSS 2-4000/9000

World Wide Web:


VERT. FORCE
= 16700 LBS

Toll Free (USA only):


IF EQUIP SUPPORT STEEL IS
90° TO THE LONG ISOLATOR 10 VERT. FORCE
AXIS, AN ADD'L PLATE EQUAL = 28000 LBS
IN THICKNESS TO THE TOP PLATE 9 *ALL MOUNTING BOLT PATTERNS
IS REQUIRED SYMMETRICAL ABOUT ISOLATOR
8
CENTER-LINE
7

614-889-0540
614-889-0480
800-959-1229
6

www.kineticsnoise.com
4

sales@kineticsnoise.com
WELDED TO STEEL
SPECIFICATIONS: 3 THROUGH BOLTED
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH
VERTICAL FORCE LBS X 1000

CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE 2 ANCHORED TO CONCRETE


NEOPRENE SNUBBING ELEMENTS.
1
MINIMUM COIL OVERLOAD OF 50 %.
MINIMUM Kx/Ky RATIO OF 1.0.
0
ALL ELEMENTS SAFE AT SOLID LOADING.
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET 0 1 2 3 4 5 6 7

HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT


ERECTION HORIZONTAL FORCE LBS X 1000
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.1-6
MEMBER
RELEASE DATE: : 2/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
REFER TO OPTIONAL BASE-
FLSS 2" DEFLECTION SEISMIC ISOLATOR PLATE USED TO INCREASE
IP UNITS (INCHES AND POUNDS) RATING WHEN ATTACHED
TYPE L W T A B D E F d H TO CONCRETE
2-8000/18000 21.50 11.00 0.50 1.00 1.00 0.81 5.50 5.50 0.69 11.00

STANDARD SPRING COIL


RATINGS COLOR FREE RATED
TYPE SIZE OUTER INNER1 INNER2 HT. O.D. LOAD DEFL.
FLSS 2-8000 ORANGE 7.00 5.00 8000 2.00
FLSS 2-10000 BLUE 7.00 5.00 10000 2.00
FLSS 2-11000 BLUE BLUE 7.00 5.00 11000 2.00
FLSS 2-12100 BLUE GREEN 7.00 5.00 12100 2.02

FLSS Submittal Drawings


FLSS 2-13000 BLUE BLACK 7.00 5.00 13000 2.00

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLSS 2-14000 BLUE ORANGE 7.00 5.00 14000 2.00
FLSS 2-15600 BLUE ORANGE GREEN 7.00 5.00 15600 2.00

Fax:
FLSS 2-16400 BLUE RED 7.00 5.00 16400 2.00

Email:
FLSS 2-18000 BLUE RED GREEN 7.00 5.00 18000 2.00
2-8000/18000 REQUIRES 0.75 DIA. x 4.75 MIN. EMBED ANCHORS IN CONCRETE
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)

International:
2-8000/18000 ANCHOR BOLT TORQUE - 150 FT-LB, PULL TEST - 3625 LB

World Wide Web:


DRAWING #S-01-22.24S – FLSS 2-8000/18000
IF EQUIP SUPPORT STEEL IS

Toll Free (USA only):


90° TO THE LONG ISOLATOR VERT. FORCE
AXIS, AN ADD'L PLATE EQUAL VERT. FORCE = 38000 LBS *ALL MOUNTING BOLT PATTERNS
IN THICKNESS TO THE TOP PLATE = 24400 LBS SYMMETRICAL ABOUT ISOLATOR
IS REQUIRED CENTER-LINE
10

614-889-0540
614-889-0480
800-959-1229
8 WELDED TO STEEL
7 THROUGH BOLTED
6 ANCHORED TO CONCRETE

www.kineticsnoise.com
5

sales@kineticsnoise.com
SPECIFICATIONS: 4

VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH


3
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE
NEOPRENE SNUBBING ELEMENTS. 2
MINIMUM COIL OVERLOAD OF 50 %.
1
VERTICAL FORCE LBS X 1000

MINIMUM Kx/Ky RATIO OF 1.0.


ALL ELEMENTS SAFE AT SOLID LOADING. 0
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET
0 1 2 3 4 5 6 7 8 9 10 11
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT
ERECTION HORIZONTAL FORCE LBS X 1000
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.1-7
MEMBER
RELEASE DATE: : 2/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLSS 4" DEFLECTION SEISMIC ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
TO CONCRETE
4-100/1600 11.00 6.00 0.38 0.75 0.75 0.69 2.75 2.75 0.56 13.00

STANDARD SPRING COIL


RATINGS FREE RATED
TYPE SIZE COLOR HT. O.D. LOAD DEFL.
FLSS 4-100 GRAY 10.00 5.63 100 4.00
FLSS 4-250 BLUE 10.00 5.63 250 4.00
FLSS 4-500 GREEN 10.00 5.63 500 4.00
FLSS 4-750 BLACK 10.00 5.63 750 4.00
FLSS 4-1000 RED 10.00 5.63 1000 4.00

FLSS Submittal Drawings

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLSS 4-1250 BROWN 10.00 5.63 1250 4.00
FLSS 4-1600 ORANGE 10.00 5.63 1600 4.00
4-100/1600 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE

Fax:
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)

Email:
4-100/1600 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB

International:
DRAWING #S-01-22.41S – FLSS 4-100/1600
VERT. FORCE
IF EQUIP SUPPORT STEEL IS = 23500 LBS

World Wide Web:


90° TO THE LONG ISOLATOR VERT. FORCE

Toll Free (USA only):


AXIS, AN ADD'L PLATE EQUAL = 16500 LBS
IN THICKNESS TO THE TOP PLATE
10
IS REQUIRED
*ALL MOUNTING BOLT PATTERNS
9
SYMMETRICAL ABOUT ISOLATOR
8
CENTER-LINE

614-889-0540
614-889-0480
800-959-1229
6

www.kineticsnoise.com
WELDED TO STEEL

sales@kineticsnoise.com
4
THROUGH BOLTED
SPECIFICATIONS: 3
ANCHORED TO CONCRETE
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH
VERTICAL FORCE LBS X 1000

CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE 2

NEOPRENE SNUBBING ELEMENTS.


1
MINIMUM COIL OVERLOAD OF 50 %.
MINIMUM Kx/Ky RATIO OF 1.0.
0
ALL ELEMENTS SAFE AT SOLID LOADING.
0 1 2 3 4
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT
HORIZONTAL FORCE LBS X 1000
ERECTION
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.1-8
MEMBER
RELEASE DATE: : 2/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLSS 4" DEFLECTION SEISMIC ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
TO CONCRETE
4-2250/5800 16.25 8.00 0.50 1.00 1.00 0.69 5.50 5.50 0.69 15.00
E* VERTICAL RESTRAINT
F*
BOLT
STANDARD SPRING COIL
RATINGS COLOR FREE RATED d
REMOVABLE
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL. FR. OP.
H- BLOCKING
FLSS 4-2250 BEIGE 11.50 8.00 2250 4.00 HEIGHT
FLSS 4-2500 BEIGE BLUE 11.50 8.00 2500 4.00
FLSS 4-2750 BEIGE GREEN 11.50 8.00 2750 4.00
FLSS 4-3000 BEIGE BLACK 11.50 8.00 3000 4.00
FLSS 4-3250 BEIGE RED 11.50 8.00 3250 4.00 D

FLSS Submittal Drawings


T

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLSS 4-3500 BEIGE BROWN 11.50 8.00 3500 4.00 D2
FLSS 4-3850 BEIGE ORANGE 11.50 8.00 3850 4.00 T2
FLSS 4-4200 CHROME 11.50 8.00 4200 4.00

Fax:
FLSS 4-4450 CHROME BLUE 11.50 8.00 4450 4.00

Email:
FLSS 4-4700 CHROME GREEN 11.50 8.00 4700 4.00
L
FLSS 4-4950 CHROME BLACK 11.50 8.00 4950 4.00
FLSS 4-5200 CHROME RED 11.50 8.00 5200 4.00 B*

International:
L2 A* W
FLSS 4-5450 CHROME BROWN 11.50 8.00 5450 4.00

DRAWING #S-01-22.42S – FLSS 4-2250/5800


VERT. FORCE B2 L2

World Wide Web:


FLSS 4-5800 CHROME ORANGE 11.50 8.00 5800 4.00
= 18000 LBS
4-2250/5800 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE

Toll Free (USA only):


10
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)
A2
4-2250/5800 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB
9
VERT. FORCE
IF EQUIP SUPPORT STEEL IS
8 = 31700 LBS
90° TO THE LONG ISOLATOR
AXIS, AN ADD'L PLATE EQUAL *ALL MOUNTING BOLT PATTERNS
7
IN THICKNESS TO THE TOP PLATE SYMMETRICAL ABOUT ISOLATOR

614-889-0540
614-889-0480
800-959-1229
IS REQUIRED CENTER-LINE
6

www.kineticsnoise.com
4 WELDED TO STEEL

sales@kineticsnoise.com
3
THROUGH BOLTED
VERTICAL FORCE LBS X 1000

ANCHORED TO CONCRETE
SPECIFICATIONS: 2

VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH


1
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE
NEOPRENE SNUBBING ELEMENTS.
0
MINIMUM COIL OVERLOAD OF 50 %.
MINIMUM Kx/Ky RATIO OF 1.0. 0 1 2 3 4

ALL ELEMENTS SAFE AT SOLID LOADING.


POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET HORIZONTAL FORCE LBS X 1000
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
ERECTION
capacity envelope. Contact KNC for bolted to steel data.

P3.2.1-9
MEMBER
RELEASE DATE: : 2/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLSS 4" DEFLECTION SEISMIC ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
RATING WHEN ATTACHED
TYPE L W T A B D E F d H
TO CONCRETE
4-5500/11600 26.00 8.00 0.50 1.00 1.00 0.69 5.50 5.50 0.69 15.25
REMOVABLE
BLOCKING
STANDARD SPRING COIL E*
RATINGS COLOR FREE RATED VERTICAL
FR / OP d F*
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL. H- RESTRAINT
FLSS 4-5500 BEIGE GREEN 11.50 8.00 5500 4.00 HEIGHT
BOLT
FLSS 4-6000 BEIGE BLACK 11.50 8.00 6000 4.00
FLSS 4-6500 BEIGE RED 11.50 8.00 6500 4.00 T
FLSS 4-7000 BEIGE BROWN 11.50 8.00 7000 4.00
FLSS 4-7700 BEIGE ORANGE 11.50 8.00 7700 4.00 D

FLSS Submittal Drawings

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLSS 4-8400 CHROME 11.50 8.00 8400 4.00 D2 T2
FLSS 4-8900 CHROME BLUE 11.50 8.00 8900 4.00
FLSS 4-9400 CHROME GREEN 11.50 8.00 9400 4.00

Fax:
FLSS 4-9900 CHROME BLACK 11.50 8.00 9900 4.00

Email:
FLSS 4-10400 CHROME RED 11.50 8.00 10400 4.00 L
FLSS 4-10900 CHROME BROWN 11.50 8.00 10900 4.00
B*

International:
FLSS 4-11600 CHROME ORANGE 11.50 8.00 11600 4.00 A* W
4-5500/11600 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE
L2
L2

World Wide Web:


DRAWING #S-01-22.43S – FLSS 4-5500/11600
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE) VERT. FORCE
4-5500/11600 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB = 16900 LBS B2

Toll Free (USA only):


A2
9

IF EQUIP SUPPORT STEEL IS VERT. FORCE


8
90° TO THE LONG ISOLATOR = 31700 LBS *ALL MOUNTING BOLT PATTERNS
AXIS, AN ADD'L PLATE EQUAL SYMMETRICAL ABOUT ISOLATOR
7
IN THICKNESS TO THE TOP PLATE CENTER-LINE
IS REQUIRED
6

614-889-0540
614-889-0480
800-959-1229
5

www.kineticsnoise.com
sales@kineticsnoise.com
3
WELDED TO STEEL
2
THROUGH BOLTED
SPECIFICATIONS:
VERTICAL FORCE LBS X 1000

1
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH ANCHORED TO CONCRETE
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE
0
NEOPRENE SNUBBING ELEMENTS.
MINIMUM COIL OVERLOAD OF 50 %. 0 1 2 3 4 5 6 7 8

MINIMUM Kx/Ky RATIO OF 1.0.


ALL ELEMENTS SAFE AT SOLID LOADING. HORIZONTAL FORCE LBS X 1000
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET

DOCUMENT:
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT Computed horiz and vert seismic load combinations must fall within the restraint
ERECTION capacity envelope. Contact KNC for bolted to steel data.

P3.2.1-10
MEMBER
RELEASE DATE: : 2/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLSS 4" DEFLECTION SEISMIC ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H REMOVABLE BLOCKING RATING WHEN ATTACHED
TO CONCRETE
4-11000/23200 27.00 17.00 0.75 1.00 1.00 0.81 9.00 9.00 0.69 15.25

F*
SPRING COIL
VERTICAL
STANDARD E*
RATINGS COLOR FREE RATED RESTRAINT
H-
FR / OP
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL. BOLT
HEIGHT d
FLSS 4-11000 BEIGE GREEN 11.50 8.00 11000 4.00
FLSS 4-12000 BEIGE BLACK 11.50 8.00 12000 4.00 T D
D2
FLSS 4-13000 BEIGE RED 11.50 8.00 13000 4.00
FLSS 4-14000 BEIGE BROWN 11.50 8.00 14000 4.00 T2
FLSS 4-15400 BEIGE ORANGE 11.50 8.00 15400 4.00

FLSS Submittal Drawings


FLSS 4-16800 CHROME 11.50 8.00 16800 4.00

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLSS 4-17800 CHROME BLUE 11.50 8.00 17800 4.00
FLSS 4-18800 CHROME GREEN 11.50 8.00 18800 4.00 L
FLSS 4-19800 CHROME BLACK 11.50 8.00 19800 4.00

Fax:

Email:
FLSS 4-20800 CHROME RED 11.50 8.00 20800 4.00 B* A* W
FLSS 4-21800 CHROME BROWN 11.50 8.00 21800 4.00
FLSS 4-23200 CHROME ORANGE 11.50 8.00 23200 4.00 L2
L2

International:
4-11000/23200 REQUIRES 0.75 DIA. x 4.75 MIN. EMBED ANCHORS IN CONCRETE B2 A2
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)

World Wide Web:


4-11000/23200 ANCHOR BOLT TORQUE - 150 FT-LB, PULL TEST - 3625 LB

DRAWING #S-01-22.44S – FLSS 4-11000/23200


Toll Free (USA only):
VERT. FORCE
= 26800 LBS VERT. FORCE
IF EQUIP SUPPORT STEEL IS 11 = 47500 LBS
90° TO THE LONG ISOLATOR
*ALL MOUNTING BOLT PATTERNS
AXIS, AN ADDT'L PLATE EQUAL 10
IN THICKNESS TO THE TOP PLATE SYMMETRICAL ABOUT ISOLATOR
IS REQUIRED 9 CENTER-LINE
8

614-889-0540
614-889-0480
800-959-1229
7
WELDED TO STEEL
6
THROUGH BOLTED

www.kineticsnoise.com
5
ANCHORED TO CONCRETE

sales@kineticsnoise.com
4
SPECIFICATIONS:
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH 3

CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE


VERTICAL FORCE LBS X 1000

2
NEOPRENE SNUBBING ELEMENTS.
ISOLATORS MUST BE BOLTED OR WELDED TOP AND BOTTOM IN AN 1
APPROVED MANNER
MINIMUM COIL OVERLOAD OF 50 %. 0

MINIMUM Kx/Ky RATIO OF 1.0. 0 1 2 3 4 5 6 7 8 9 10 11 12

ALL ELEMENTS SAFE AT SOLID LOADING.


POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET HORIZONTAL FORCE LBS X 1000
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
ERECTION capacity envelope. Contact KNC for bolted to steel data.

P3.2.1-11
MEMBER
RELEASE DATE: 2/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLS 1" DEFLECTION ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
F* TO CONCRETE
1-250/3500 8.75 4.00 0.25 0.75 1.13 0.69 2.75 2.75 0.56 6.25 E*
REMOVABLE
BLOCKING
FR / OP
STANDARD SPRING COIL H- d
HEIGHT
RATINGS COLOR FREE RATED
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL.
FLS 1-250 BLUE 4.20 3.00 250 1.79 D2
FLS 1-450 GREEN 4.20 3.00 450 1.54
FLS 1-625 BLACK 4.20 3.00 625 1.44 T2 D
FLS 1-800 GRAY 4.20 3.00 800 1.31

FLS Submittal Drawings


FLS 1-1000 RED 4.20 3.00 1000 1.15 T

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLS 1-1250 BROWN 4.20 3.00 1250 1.09
FLS 1-1700 ORANGE 4.20 3.00 1700 0.95
FLS 1-2200 ORANGE GRAY 4.20 3.00 2200 1.00

Fax:
FLS 1-2465 BLUE 4.20 3.00 2465 1.00 L

Email:
FLS 1-2865 BLUE GRAY 4.20 3.00 2865 1.00 B*
A*

DRAWING #S-01-22.11 – FLS 1-250/3500


FLS 1-3500 BLUE BROWN 4.20 3.00 3500 1.00 W
L2

International:
1-250/3500 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE L2
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE) B2
A2

World Wide Web:


1-250/3500 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB
VERT FORCE

Toll Free (USA only):


= 12100 LBS
IF EQUIP SUPPORT STEEL IS
8
90° TO THE LONG ISOLATOR
AXIS, AN ADD'L PLATE EQUAL *ALL MOUNTING BOLT PATTERNS
IN THICKNESS TO THE TOP PLATE 7 SYMMETRICAL ABOUT ISOLATOR
IS REQUIRED CENTER-LINE
6

614-889-0540
614-889-0480
800-959-1229
5

www.kineticsnoise.com
sales@kineticsnoise.com
WELDED TO STEEL
3
SPECIFICATIONS:
THROUGH BOLTED
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH
2
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE
VERTICAL FORCE LBS X 1000

ANCHORED TO CONCRETE
NEOPRENE SNUBBING ELEMENTS.
MINIMUM COIL OVERLOAD OF 50 %.
MINIMUM Kx/Ky RATIO OF 1.0.
ALL ELEMENTS SAFE AT SOLID LOADING. 0
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET 0 1 2 3 4
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT
HORIZONTAL FORCE LBS X 1000
ERECTION
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.2-1
MEMBER
RELEASE DATE: 02/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLS 1" DEFLECTION ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H REMOVABLE RATING WHEN ATTACHED
1-2500/7000 14.00 4.00 0.38 1.00 0.50 0.69 2.75 2.75 0.56 6.88 TO CONCRETE
BLOCKING

SPRING COIL E* F*
STANDARD VERTICAL RESTRAINT
RATINGS COLOR FREE RATED
H - FR / OP d
HEIGHT BOLT
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL.
FLS 1-2500 BROWN 4.20 3.00 2500 1.09 T
D2
FLS 1-3400 ORANGE 4.20 3.00 3400 0.95 D
FLS 1-4400 ORANGE GRAY 4.20 3.00 4400 0.50
T2
FLS 1-4930 BLUE 4.20 3.00 4930 0.50

FLS Submittal Drawings


FLS 1-5730 BLUE GRAY 4.20 3.00 5730 0.50

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLS 1-7000 BLUE BROWN 4.20 3.00 7000 0.50
1-2500/7000 REQUIRES 0.62 DIA x 4.00 MIN EMBED ANCHORS IN CONCRETE
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE) L

Fax:
1-2500/7000 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB

Email:
B* A*
W

DRAWING #S-01-22.12 – FLS 1-2500/7000


L2

International:
L2
IF EQUIP SUPPORT STEEL IS B2
90° TO THE LONG ISOLATOR A2

World Wide Web:


AXIS, AN ADD'L PLATE EQUAL

Toll Free (USA only):


IN THICKNESS TO THE TOP PLATE
IS REQUIRED

VERT FORCE
*ALL MOUNTING BOLT PATTERNS
= 14650 LBS
SYMMETRICAL ABOUT ISOLATOR
CENTER-LINE

614-889-0540
614-889-0480
800-959-1229
WELDED TO STEEL

www.kineticsnoise.com
sales@kineticsnoise.com
THROUGH BOLTED
SPECIFICATIONS:
ANCHORED TO CONCRETE
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE
NEOPRENE SNUBBING ELEMENTS.
MINIMUM COIL OVERLOAD OF 50%.
VERTICAL FORCE LBS X 1000

MINIMUM Kx/Ky RATIO OF 1.0.


ALL ELEMENTS SAFE AT SOLID LOADING.
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT
ERECTION HORIZONTAL FORCE LBS X 1000
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.2-2
MEMBER
RELEASE DATE: 02/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLS 1" DEFLECTION ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
1-5000/14000 16.50 8.00 0.38 1.00 2.00 0.81 5.50 5.50 0.69 7.50 TO CONCRETE

REMOVABLE
STANDARD SPRING COIL BLOCKING
RATINGS COLOR FREE RATED
FR / OP
F* VERTICAL RESTRAINT
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL. E*
H-
FLS 1-5000 BROWN 4.20 3.00 5000 1.09 HEIGHT BOLT
FLS 1-6800 ORANGE 4.20 3.00 6800 0.95 T
d
FLS 1-8800 ORANGE GRAY 4.20 3.00 8800 1.00
D
FLS 1-9860 BLUE 4.20 3.00 9860 1.00 T2

FLS Submittal Drawings


FLS 1-11460 BLUE GRAY 4.20 3.00 11460 1.00 D2
FLS 1-14000 BLUE BROWN 4.20 3.00 14000 1.00

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


1-5000/14000 REQUIRES 0.75 DIA. x 4.75 MIN. EMBED ANCHORS IN CONCRETE
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE) L

Fax:
1-5000/14000 ANCHOR BOLT TORQUE - 150 FT-LB, PULL TEST - 3625 LB
B*

Email:
A*
L2 W
B2 L2

International:
DRAWING #S-01-22.13 – FLS 1-5000/14000
A2
IF EQUIP SUPPORT STEEL IS

World Wide Web:


90° TO THE LONG ISOLATOR
AXIS, AN ADD'L PLATE EQUAL

Toll Free (USA only):


VERT. FORCE
IN THICKNESS TO THE TOP PLATE
VERT. FORCE =23500 LBS
IS REQUIRED *ALL MOUNTING BOLT PATTERNS
=13300 LBS
SYMMETRICAL ABOUT ISOLATOR
7 CENTER-LINE

614-889-0540
614-889-0480
800-959-1229
WELDED TO STEEL
5

THROUGH BOLTED
4

www.kineticsnoise.com
ANCHORED TO CONCRETE

sales@kineticsnoise.com
SPECIFICATIONS: 3

VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH


CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE 2

NEOPRENE SNUBBING ELEMENTS.


VERTICAL FORCE LBS X 1000

MINIMUM COIL OVERLOAD OF 50%. 1


MINIMUM Kx/Ky RATIO OF 1.0.
ALL ELEMENTS SAFE AT SOLID LOADING.
0
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET
0 1 2 3 4 5 6
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT
ERECTION HORIZONTAL FORCE LBS X 1000
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.2-3
MEMBER
RELEASE DATE: 02/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
REFER TO OPTIONAL BASE-
FLS 2" DEFLECTION ISOLATOR PLATE USED TO INCREASE
IP UNITS (INCHES AND POUNDS) RATING WHEN ATTACHED
TO CONCRETE
TYPE L W T A B D E F d H
2-100/1975 9.00 5.00 0.25 0.75 0.75 0.69 2.75 2.75 0.56 8.00

STANDARD SPRING COIL


RATINGS COLOR FREE RATED
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL.
FLS 2-100 GRAY 6.09 3.50 100 2.00
FLS 2-250 BLUE 6.09 3.50 250 2.00
FLS 2-500 GREEN 6.09 3.50 500 2.00

FLS Submittal Drawings


FLS 2-750 BLACK 6.09 3.50 750 2.00

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLS 2-995 ORANGE 6.09 3.50 995 2.00
FLS 2-1400 ORANGE GREEN 6.09 3.50 1400 2.01
FLS 2-1600 RED 6.09 3.50 1600 2.00

Fax:
FLS 2-1975 RED GREEN 6.09 3.50 1975 1.98

Email:
2-100/1975 REQUIRES 0.62 DIA x 4.00 MIN EMBED ANCHORS IN CONCRETE

DRAWING #S-01-22.21 – FLS 2-100/1975


(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)

International:
2-100/1975 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB

World Wide Web:


9

Toll Free (USA only):


IF EQUIP SUPPORT STEEL IS
90° TO THE LONG ISOLATOR
AXIS, AN ADD'L PLATE EQUAL
8
IN THICKNESS TO THE TOP PLATE
IS REQUIRED *ALL MOUNTING BOLT PATTERNS
7 SYMMETRICAL ABOUT ISOLATOR
CENTER-LINE
6

614-889-0540
614-889-0480
800-959-1229
5

www.kineticsnoise.com
WELDED TO STEEL
4

sales@kineticsnoise.com
THROUGH BOLTED
SPECIFICATIONS: 3
ANCHORED TO CONCRETE
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE 2
VERTICAL FORCE LBS X 1000

NEOPRENE SNUBBING ELEMENTS.


MINIMUM COIL OVERLOAD OF 50 %. 1
MINIMUM Kx/Ky RATIO OF 1.0.
ALL ELEMENTS SAFE AT SOLID LOADING.
0
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET
0 1 2 3 4
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT
ERECTION HORIZONTAL FORCE LBS X 1000

DOCUMENT:
Computed horiz and vert seismic load combinations must fall within the restraint
capacity envelope. Contact KNC for bolted to steel data.

P3.2.2-4
MEMBER
RELEASE DATE: 02/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLS 2" DEFLECTION ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
TO CONCRETE
2-2000/4500 10.75 5.00 0.25 0.75 1.38 0.69 2.75 2.75 0.56 10.00

STANDARD SPRING COIL


RATINGS COLOR FREE RATED
TYPE SIZE OUTER INNER1 INNER2 HT. O.D. LOAD DEFL.
FLS 2-2000 ORANGE 7.00 5.00 2000 2.00
FLS 2-2500 BLUE 7.00 5.00 2500 2.00
FLS 2-2750 BLUE BLUE 7.00 5.00 2750 2.00
FLS 2-3025 BLUE GREEN 7.00 5.00 3025 2.02

FLS Submittal Drawings


FLS 2-3250 BLUE BLACK 7.00 5.00 3250 2.00

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLS 2-3500 BLUE ORANGE 7.00 5.00 3500 2.00
FLS 2-3900 BLUE ORANGE GREEN 7.00 5.00 3900 2.00
FLS 2-4100 BLUE RED 7.00 5.00 4100 2.00

Fax:
FLS 2-4500 BLUE RED GREEN 7.00 5.00 4500 2.00

Email:
2-2000/4500 REQUIRES 0.62 DIA x 4.00 MIN EMBED ANCHORS IN CONCRETE
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)

DRAWING #S-01-22.22 – FLS 2-2000/4500

International:
2-2000/4500 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB

World Wide Web:


Toll Free (USA only):
IF EQUIP SUPPORT STEEL IS
90° TO THE LONG ISOLATOR 8
AXIS, AN ADD'L PLATE EQUAL
IN THICKNESS TO THE TOP PLATE
IS REQUIRED 7

VERT FORCE
6
= 14300 LBS *ALL MOUNTING BOLT PATTERNS

614-889-0540
614-889-0480
800-959-1229
SYMMETRICAL ABOUT ISOLATOR
5 CENTER-LINE

www.kineticsnoise.com
sales@kineticsnoise.com
3
SPECIFICATIONS:
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH WELDED TO STEEL
2
VERTICAL FORCE LBS X 1000

CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE


NEOPRENE SNUBBING ELEMENTS. THROUGH BOLTED
1
MINIMUM COIL OVERLOAD OF 50 %.
MINIMUM Kx/Ky RATIO OF 1.0. ANCHORED TO CONCRETE
ALL ELEMENTS SAFE AT SOLID LOADING. 0
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET 0 1 2 2 3

HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT HORIZONTAL FORCE LBS X 1000
ERECTION
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.2-5
MEMBER
RELEASE DATE: 02/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLS 2" DEFLECTION ISOLATOR REFER TO OPTIONAL BASE-
PLATE USED TO INCREASE
IP UNITS (INCHES AND POUNDS)
RATING WHEN ATTACHED
TYPE L W T A B D E F d H TO CONCRETE
2-4000/9000 17.50 6.00 0.38 1.25 1.00 0.69 2.75 2.75 0.56 10.00

STANDARD SPRING COIL


RATINGS COLOR FREE RATED
TYPE SIZE OUTER INNER1 INNER2 HT. O.D. LOAD DEFL.
FLS 2-4000 ORANGE 7.00 5.00 4000 2.00
FLS 2-5000 BLUE 7.00 5.00 5000 2.00
FLS 2-5500 BLUE BLUE 7.00 5.00 5500 2.00

FLS Submittal Drawings


FLS 2-6050 BLUE GREEN 7.00 5.00 6050 2.02
FLS 2-6500 BLUE BLACK 7.00 5.00 6500 2.00

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLS 2-7000 BLUE ORANGE 7.00 5.00 7000 2.00
FLS 2-7800 BLUE ORANGE GREEN 7.00 5.00 7800 2.00
FLS 2-8200 BLUE RED 7.00 5.00 8200 2.00

Fax:

Email:
FLS 2-9000 BLUE RED GREEN 7.00 5.00 9000 2.00
2-4000/9000 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)

DRAWING #S-01-22.23 – FLS 2-4000/9000

International:
2-4000/9000 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB

World Wide Web:


9

Toll Free (USA only):


IF EQUIP SUPPORT STEEL IS
90° TO THE LONG ISOLATOR
AXIS, AN ADD'L PLATE EQUAL 8 VERT FORCE *ALL MOUNTING BOLT PATTERNS
IN THICKNESS TO THE TOP PLATE = 19500 LBS
IS REQUIRED SYMMETRICAL ABOUT ISOLATOR
7 CENTER-LINE

614-889-0540
614-889-0480
800-959-1229
5

www.kineticsnoise.com
4 WELDED TO STEEL

sales@kineticsnoise.com
THROUGH BOLTED
SPECIFICATIONS: 3

VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH ANCHORED TO CONCRETE


VERTICAL FORCE LBS X 1000

CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE 2


NEOPRENE SNUBBING ELEMENTS.
MINIMUM COIL OVERLOAD OF 50 %.
1
MINIMUM Kx/Ky RATIO OF 1.0.
ALL ELEMENTS SAFE AT SOLID LOADING.
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET 0
0 1 2 3
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT
ERECTION HORIZONTAL FORCE LBS X 1000
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.2-6
MEMBER
RELEASE DATE: 02/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
REFER TO OPTIONAL BASE-
FLS 2" DEFLECTION ISOLATOR PLATE USED TO INCREASE
IP UNITS (INCHES AND POUNDS) RATING WHEN ATTACHED
TYPE L W T A B D E F d H TO CONCRETE
2-8000/18000 21.50 11.00 0.38 1.50 1.50 1.06 5.50 5.50 0.69 11.00

STANDARD SPRING COIL


VERTICAL RESTRAINT
RATINGS COLOR FREE RATED E*
F* BOLT
TYPE SIZE OUTER INNER1 INNER2 HT. O.D. LOAD DEFL. H -FR / OP
HEIGHT REMOVABLE
FLS 2-8000 ORANGE 7.00 5.00 8000 2.00
d BLOCKING
FLS 2-10000 BLUE 7.00 5.00 10000 2.00
FLS 2-11000 BLUE BLUE 7.00 5.00 11000 2.00 T D

FLS Submittal Drawings


FLS 2-12100 BLUE GREEN 7.00 5.00 12100 2.02 D2 T2
FLS 2-13000 BLUE BLACK 7.00 5.00 13000 2.00

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLS 2-14000 BLUE ORANGE 7.00 5.00 14000 2.00
FLS 2-15600 BLUE ORANGE GREEN 7.00 5.00 15600 2.00

Fax:
FLS 2-16400 BLUE RED 7.00 5.00 16400 2.00

Email:
FLS 2-18000 BLUE RED GREEN 7.00 5.00 18000 2.00 L
2-8000/18000 REQUIRES 0.75 DIA. x 4.75 MIN. EMBED ANCHORS IN CONCRETE B*
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE) A* W

International:
DRAWING #S-01-22.24 – FLS 2-8000/18000
2-8000/18000 ANCHOR BOLT TORQUE - 150 FT-LB, PULL TEST - 3625 LB L2
B2 L2

World Wide Web:


VERT. FORCE A2

Toll Free (USA only):


= 16400 LBS
IF EQUIP SUPPORT STEEL IS
90° TO THE LONG ISOLATOR
AXIS, AN ADD'L PLATE EQUAL VERT. FORCE *ALL MOUNTING BOLT PATTERNS
IN THICKNESS TO THE TOP PLATE = 26800 LBS
IS REQUIRED SYMMETRICAL ABOUT ISOLATOR
CENTER-LINE

614-889-0540
614-889-0480
800-959-1229
WELDED TO STEEL

www.kineticsnoise.com
sales@kineticsnoise.com
THROUGH BOLTED
SPECIFICATIONS:
ANCHORED TO CONCRETE
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE
NEOPRENE SNUBBING ELEMENTS.
MINIMUM COIL OVERLOAD OF 50 %.
VERTICAL FORCE LBS X 1000

MINIMUM Kx/Ky RATIO OF 1.0.


ALL ELEMENTS SAFE AT SOLID LOADING.
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT
ERECTION HORIZONTAL FORCE LBS X 1000
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.2-7
MEMBER
RELEASE DATE: 02/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLS 4" DEFLECTION ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
TO CONCRETE
4-100/1600 10.75 6.00 0.25 0.75 0.75 0.69 2.75 2.75 0.56 13.00

F* VERTICAL RESTRAINT
E* BOLT
STANDARD SPRING COIL
RATINGS FREE RATED REMOVABLE
TYPE SIZE COLOR HT. O.D. LOAD DEFL. d
BLOCKING
FLS 4-100 GRAY 10.00 5.63 100 4.00 H - FR / OP
FLS 4-250 BLUE 10.00 5.63 250 4.00 HEIGHT
FLS 4-500 GREEN 10.00 5.63 500 4.00
FLS 4-750 BLACK 10.00 5.63 750 4.00

FLS Submittal Drawings


D
FLS 4-1000 RED 10.00 5.63 1000 4.00 T

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLS 4-1250 BROWN 10.00 5.63 1250 4.00
FLS 4-1600 ORANGE 10.00 5.63 1600 4.00 D2 T2
4-100/1600 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE

Fax:
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)

Email:
4-100/1600 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB
L

DRAWING #S-01-22.41 – FLS 4-100/1600


B*

International:
L2
A*
IF EQUIP SUPPORT STEEL IS
W
VERT FORCE B2

World Wide Web:


90° TO THE LONG ISOLATOR = 12100 LBS L2

Toll Free (USA only):


AXIS, AN ADD'L PLATE EQUAL A2
IN THICKNESS TO THE TOP PLATE 8
IS REQUIRED
7
*ALL MOUNTING BOLT PATTERNS
SYMMETRICAL ABOUT ISOLATOR
6 CENTER-LINE

614-889-0540
614-889-0480
800-959-1229
5

www.kineticsnoise.com
sales@kineticsnoise.com
3 WELDED TO STEEL

SPECIFICATIONS: THROUGH BOLTED


2
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH
VERTICAL FORCE LBS X 1000

CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE ANCHORED TO CONCRETE


NEOPRENE SNUBBING ELEMENTS. 1

MINIMUM COIL OVERLOAD OF 50 %.


MINIMUM Kx/Ky RATIO OF 1.0. 0
ALL ELEMENTS SAFE AT SOLID LOADING. 0 1 2
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET HORIZONTAL FORCE LBS X 1000
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT
ERECTION Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.2-8
MEMBER
RELEASE DATE: 02/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLS 4" DEFLECTION ISOLATOR
REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
4-2250/5800 15.50 8.00 0.25 0.75 1.75 0.69 5.50 5.50 0.69 14.88 TO CONCRETE

F* VERTICAL RESTRAINT
STANDARD SPRING COIL E* BOLT
RATINGS COLOR FREE RATED
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL. d REMOVABLE
FLS 4-2250 BEIGE 11.50 8.00 2250 4.00 BLOCKING
FLS 4-2500 BEIGE BLUE 11.50 8.00 2500 4.00 H - FR / OP
HEIGHT
FLS 4-2750 BEIGE GREEN 11.50 8.00 2750 4.00
FLS 4-3000 BEIGE BLACK 11.50 8.00 3000 4.00

FLS Submittal Drawings


FLS 4-3250 BEIGE RED 11.50 8.00 3250 4.00 D
FLS 4-3500 BEIGE BROWN 11.50 8.00 3500 4.00 T

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLS 4-3850 BEIGE ORANGE 11.50 8.00 3850 4.00 T2
FLS 4-4200 CHROME 11.50 8.00 4200 4.00 D2

Fax:
FLS 4-4450 CHROME BLUE 11.50 8.00 4450 4.00

Email:
FLS 4-4700 CHROME GREEN 11.50 8.00 4700 4.00
FLS 4-4950 CHROME BLACK 11.50 8.00 4950 4.00 L

DRAWING #S-01-22.42 – FLS 4-2250/5800


FLS 4-5200 CHROME RED 11.50 8.00 5200 4.00

International:
B*
FLS 4-5450 CHROME BROWN 11.50 8.00 5450 4.00 L2
A*
W

World Wide Web:


FLS 4-5800 CHROME ORANGE 11.50 8.00 5800 4.00 B2
9
L2

Toll Free (USA only):


4-2250/5800 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE A2
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)
4-2250/5800 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB 8
VERT FORCE
IF EQUIP SUPPORT STEEL IS
= 19500 LBS *ALL MOUNTING BOLT PATTERNS
90° TO THE LONG ISOLATOR 7
AXIS, AN ADD'L PLATE EQUAL SYMMETRICAL ABOUT ISOLATOR
IN THICKNESS TO THE TOP PLATE CENTER-LINE
6

614-889-0540
614-889-0480
800-959-1229
IS REQUIRED

www.kineticsnoise.com
4

sales@kineticsnoise.com
WELDED TO STEEL
3

SPECIFICATIONS: THROUGH BOLTED


VERTICAL FORCE LBS X 1000

VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH 2 ANCHORED TO CONCRETE


CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE
NEOPRENE SNUBBING ELEMENTS. 1
MINIMUM COIL OVERLOAD OF 50 %.
MINIMUM Kx/Ky RATIO OF 1.0.
0
ALL ELEMENTS SAFE AT SOLID LOADING.
0 1 2 3
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET
HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT HORIZONTAL FORCE LBS X 1000
ERECTION

DOCUMENT:
Computed horiz and vert seismic load combinations must fall within the restraint
capacity envelope. Contact KNC for bolted to steel data.

P3.2.2-9
MEMBER
RELEASE DATE: 02/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLS 4" DEFLECTION ISOLATOR REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) PLATE USED TO INCREASE
TYPE L W T A B D E F d H RATING WHEN ATTACHED
TO CONCRETE
4-5500/11600 25.50 8.00 0.38 1.13 1.75 0.81 5.50 5.50 0.69 14.88

STANDARD SPRING COIL


RATINGS COLOR FREE RATED
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL.
FLS 4-5500 BEIGE GREEN 11.50 8.00 5500 4.00
FLS 4-6000 BEIGE BLACK 11.50 8.00 6000 4.00
FLS 4-6500 BEIGE RED 11.50 8.00 6500 4.00
FLS 4-7000 BEIGE BROWN 11.50 8.00 7000 4.00

FLS Submittal Drawings


FLS 4-7700 BEIGE ORANGE 11.50 8.00 7700 4.00

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLS 4-8400 CHROME 11.50 8.00 8400 4.00
FLS 4-8900 CHROME BLUE 11.50 8.00 8900 4.00
FLS 4-9400 CHROME GREEN 11.50 8.00 9400 4.00

Fax:
FLS 4-9900 CHROME BLACK 11.50 8.00 9900 4.00

Email:
FLS 4-10400 CHROME RED 11.50 8.00 10400 4.00
FLS 4-10900 CHROME BROWN 11.50 8.00 10900 4.00

International:
FLS 4-11600 CHROME ORANGE 11.50 8.00 11600 4.00

DRAWING #S-01-22.43 – FLS 4-5500/11600


4-5500/11600 REQUIRES 0.62 DIA. x 4.00 MIN. EMBED ANCHORS IN CONCRETE

World Wide Web:


(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)
4-5500/11600 ANCHOR BOLT TORQUE - 75 FT-LB, PULL TEST - 2670 LB

Toll Free (USA only):


VERT. FORCE VERT. FORCE
IF EQUIP SUPPORT STEEL IS = 13300 LBS = 24500 LBS *ALL MOUNTING BOLT PATTERNS
90° TO THE LONG ISOLATOR SYMMETRICAL ABOUT ISOLATOR
AXIS, AN ADD'L PLATE EQUAL 7
CENTER-LINE
IN THICKNESS TO THE TOP PLATE
IS REQUIRED 6

614-889-0540
614-889-0480
800-959-1229
5

www.kineticsnoise.com
sales@kineticsnoise.com
3 WELDED TO STEEL
SPECIFICATIONS:
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH THROUGH BOLTED
2
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE ANCHORED TO CONCRETE
NEOPRENE SNUBBING ELEMENTS.
VERTICAL FORCE LBS X 1000

1
MINIMUM COIL OVERLOAD OF 50 %.
MINIMUM Kx/Ky RATIO OF 1.0.
ALL ELEMENTS SAFE AT SOLID LOADING. 0
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET 0 1 2 3

HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT HORIZONTAL FORCE LBS X 1000
ERECTION
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.2-10
MEMBER
RELEASE DATE: 02/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
A2, B2, L2, T2, D2 DIMENSIONS
FLS 4" DEFLECTION ISOLATOR REMOVABLE REFER TO OPTIONAL BASE-
IP UNITS (INCHES AND POUNDS) BLOCKING PLATE USED TO INCREASE
d RATING WHEN ATTACHED
TYPE L W T A B D E F H
TO CONCRETE
4-11000/23200 27.00 17.00 0.75 1.00 1.00 0.81 9.00 9.00 0.69 15.00
F* VERTICAL
E* RESTRAINT
d
STANDARD SPRING COIL BOLT
RATINGS COLOR FREE RATED H - FR / OP
HEIGHT D
TYPE SIZE OUTER INNER HT. O.D. LOAD DEFL.
FLS 4-11000 BEIGE GREEN 11.50 8.00 11000 4.00 T
D2
FLS 4-12000 BEIGE BLACK 11.50 8.00 12000 4.00
FLS 4-13000 BEIGE RED 11.50 8.00 13000 4.00 T2
FLS 4-14000 BEIGE BROWN 11.50 8.00 14000 4.00

FLS Submittal Drawings


FLS 4-15400 BEIGE ORANGE 11.50 8.00 15400 4.00
FLS 4-16800 CHROME 11.50 8.00 16800 4.00

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


FLS 4-17800 CHROME BLUE 11.50 8.00 17800 4.00 L
FLS 4-18800 CHROME GREEN 11.50 8.00 18800 4.00

Fax:
FLS 4-19800 CHROME BLACK 11.50 8.00 19800 4.00 B* A* W

Email:
FLS 4-20800 CHROME RED 11.50 8.00 20800 4.00
FLS 4-21800 CHROME BROWN 11.50 8.00 21800 4.00
L2 L2
FLS 4-23200 CHROME ORANGE 11.50 8.00 23200 4.00 B2 A2

International:
DRAWING #S-01-22.44 – FLS 4-11000/23200
4-11000/23200 REQUIRES 0.75 DIA. x 4.75 MIN. EMBED ANCHORS IN CONCRETE

World Wide Web:


(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE) VERT. FORCE
4-11000/23200 ANCHOR BOLT TORQUE - 150 FT-LB, PULL TEST - 3625 LB = 21150 LBS VERT. FORCE

Toll Free (USA only):


= 47000 LBS *ALL MOUNTING BOLT PATTERNS
IF EQUIP SUPPORT STEEL IS SYMMETRICAL ABOUT ISOLATOR
10
90° TO THE LONG ISOLATOR CENTER-LINE
AXIS, AN ADD'L PLATE EQUAL
9
IN THICKNESS TO THE TOP PLATE
IS REQUIRED
8

614-889-0540
614-889-0480
800-959-1229
7

WELDED TO STEEL
5

www.kineticsnoise.com
THROUGH BOLTED

sales@kineticsnoise.com
4
ANCHORED TO CONCRETE
SPECIFICATIONS:
3
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE
2
VERTICAL FORCE LBS X 1000

NEOPRENE SNUBBING ELEMENTS.


MINIMUM COIL OVERLOAD OF 50 %. 1
MINIMUM Kx/Ky RATIO OF 1.0.
ALL ELEMENTS SAFE AT SOLID LOADING. 0
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET 0 1 2 3 4 5 6 7

HOUSINGS MAY BE USED FOR BLOCKING DURING EQUIPMENT HORIZONTAL FORCE LBS X 1000
ERECTION Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
capacity envelope. Contact KNC for bolted to steel data.

P3.2.2-11
MEMBER
RELEASE DATE: 02/01/05

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
FHS 1" DEFLECTION SEISMIC ISOLATOR A2, L2, T2, D2 DIMENSIONS
NEOPRENE 3-AXIS REFER TO OPTIONAL
TYPE L W H D Z T A E Z BOLT BASEPLATE USED TO
SNUBBER
1-35/805 7.32 3.00 5.86 0.44 0.50 0.38 0.69 1.50 INCREASE RATING WHEN
ATTACHED TO CONCRETE
1-250/2200 9.56 5.00 7.36 0.81 0.62 0.38 0.88 2.50
1-2465/3500 9.56 5.00 7.36 0.81 0.62 0.38 0.88 2.50
H WELDED
I-P UNITS (INCHES AND POUNDS)
Op. Ht GUSSET
STANDARD RATINGS NOMINAL
COIL O.D. CAPACITY
TYPE SIZE FREE HT
1-35/805 1-35 BLUE 3.00 1.75 35 2 HOLES - D DIA
1-70 GREEN 3.00 1.75 70 4 x D2
1-120 GRAY 3.00 1.75 120 T2 T
1-220 BROWN 3.00 1.75 220

FHS Submittal Drawings


1-370 ORANGE 3.00 1.75 370

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


1-500 BEIGE 3.00 1.75 500
1-600 CHROME 3.00 1.75 600

Fax:
1-700 BGE/WHT 3.00 1.75 700

Email:
CHR/WHT L E
1-805 3.00 1.75 800
1-250/2200 1-250 BLUE 4.00 3.00 250 L2 A W
L2
1-450 GREEN 4.00 3.00 450

International:
1-625 BLACK 4.00 3.00 625

World Wide Web:


1-800 GRAY 4.00 3.00 800

Toll Free (USA only):


1-1000 RED 4.00 3.00 1000
A2
1-1250 BROWN 4.00 3.00 1250
ORANGE CONCRETE ANCHORS (SPEC INSPECTION) WELDED TO STEEL
1-1700 4.00 3.00 1700 STANDARD HOUSING ONLY
1-2200 ORG/GRY 4.00 3.00 2200 6000 6000
BLUE CAN BE INCREASED TO
1-2465/3500
1-2465/3500 * 1-2465 4.00 3.00 2465
WELDED RATING WITH
1-2865 BLU/GRY 4.00 3.00 2865 OVERSIZED BASEPLATE 1-250/2200
5000 5000

614-889-0540
614-889-0480
800-959-1229
1-3500 BLU/BRN 4.00 3.00 3500
* INCLUDES WELDED GUSSET AS SHOWN
1-35/805
4000
1-2465/3500 4000

DRAWING # S-01.35-1A – FHS 1-35/805 1-250/2200 1-2465/3500


1-35/805 REQUIRES 0.38 DIA x 2.50 MIN EMBED ANCHORS IN CONCRETE
1-250/3500 REQUIRES 0.75 DIA x 4.75 MIN EMBED ANCHORS IN CONCRETE

www.kineticsnoise.com
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)

sales@kineticsnoise.com
3000 1-250/2200 3000
1-35/805 ANCHOR BOLT TORQUE - 25 FT LB, PULL TEST - 1210 LB
1-250/3500 ANCHOR BOLT TORQUE - 150 FT LB, PULL TEST - 3625 LB
2000 2000
SPECIFICATIONS:
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH 1-35/805
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE 1000 1000
VERTICAL RESTRAINT CAPACITY (LBS)
VERTICAL RESTRAINT CAPACITY (LBS)

NEOPRENE SNUBBING ELEMENTS.


0.25 NOMINAL CLEARANCE IN SNUBBING ELEMENTS.
MINIMUM OVERLOAD OF 50%. 0 0
0 1000 2000 0 1000 2000 3000 4000 5000
MINIMUM Kx/Ky RATIO OF 1.0. HORIZONTAL RESTRAINT CAPACITY (LBS) HORIZONTAL RESTRAINT CAPACITY (LBS)
ALL ELEMENTS SAFE AT SOLID LOADING.
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
OSHPD APPROVAL NUMBER R-0433
capacity envelope. Contact KNC for bolted to steel data.

P3.2.3-1
MEMBER
RELEASE DATE: 11/3/03

Kinetics Noise Control ©2003


KINETICS ™ Seismic Design Manual
FHS 2" DEFLECTION SEISMIC ISOLATOR A2, L2, T2, D2 DIMENSIONS
NEOPRENE 3-AXIS REFER TO OPTIONAL
TYPE L W H D Z T A E Z BOLT BASEPLATE USED TO
SNUBBER
2-100/1600 10.38 5.00 8.72 0.69 0.50 0.50 0.75 2.50 INCREASE RATING WHEN
ATTACHED TO CONCRETE
2-1975 10.38 5.00 8.72 0.69 0.50 0.50 0.75 2.50
2-2000/4500 11.50 6.00 11.13 1.06 0.75 0.50 0.88 3.00
H WELDED
I-P UNITS (INCHES AND POUNDS)
Op. Ht GUSSET
STANDARD RATINGS
COIL NOMINAL O.D. CAPACITY
TYPE SIZE FREE HT
2-100/1600 2-100 GRAY 5.75 3.50 100 2 HOLES - D DIA
2-250 BLUE 5.75 3.50 250 4 x D2
2-500 GREEN 5.75 3.50 500 T2 T
2-750 BLACK 5.75 3.50 750

FHS Submittal Drawings


2-995 ORANGE 5.75 3.50 995

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


2-1400 ORG/GRN 5.75 3.50 1400
2-1600 RED 5.75 3.50 1600

Fax:
2-1975 * 2-1975 RED/GRN 5.75 3.50 1975

Email:
L E
2-2000/4500* 2-2000 ORANGE 7.00 5.00 2000
2-2500 BLUE 7.00 5.00 2500 L2 A W
L2
2-2750 BLU/BLU 7.00 5.00 2750

International:
2-3025 BLU/GRN 7.00 5.00 3025

World Wide Web:


2-3500 BLU/ORG 7.00 5.00 3500

Toll Free (USA only):


2-3900 BLU/ORG/GRN 7.00 5.00 3900
A2
2-4100 BLU/RED 7.00 5.00 4100
CONCRETE ANCHORS (SPEC INSPECTION) WELDED TO STEEL
2-4500 BLU/RED/GRN 7.00 5.00 4500 STANDARD HOUSING ONLY
* INCLUDES WELDED GUSSET AS SHOWN 6000 6000
CAN BE INCREASED TO
2-2000/4500
WELDED RATING WITH
OVERSIZED BASEPLATE 2-1975
5000 5000

614-889-0540
614-889-0480
800-959-1229
2-100/1600

DRAWING # S-01.35-2A – FHS 2-100/1600 2-1975 2-2000/4500


2-100/1975 REQUIRES 0.62 DIA x 4.0 MIN EMBED ANCHORS IN CONCRETE 4000 4000
2-2000/4500 REQUIRES 1.0 DIA x 6.0 MIN EMBED ANCHORS IN CONCRETE

www.kineticsnoise.com
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)

sales@kineticsnoise.com
3000 2-2000/4500 3000
2-100/1975 ANCHOR BOLT TORQUE - 75 FT LB, PULL TEST - 2670 LB
2-2000/4500 ANCHOR BOLT TORQUE - 200 FT LB, PULL TEST - 5310 LB
2000 2000
SPECIFICATIONS:
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH 2-100/1975
CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE 1000 1000
VERTICAL RESTRAINT CAPACITY (LBS)
VERTICAL RESTRAINT CAPACITY (LBS)

NEOPRENE SNUBBING ELEMENTS.


0.25 NOMINAL CLEARANCE IN SNUBBING ELEMENTS.
MINIMUM OVERLOAD OF 50%. 0 0
0 1000 2000 0 1000 2000 3000 4000 5000
MINIMUM Kx/Ky RATIO OF 1.0. HORIZONTAL RESTRAINT CAPACITY (LBS) HORIZONTAL RESTRAINT CAPACITY (LBS)
ALL ELEMENTS SAFE AT SOLID LOADING.
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET
Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
OSHPD APPROVAL NUMBER R-0433
capacity envelope. Contact KNC for bolted to steel data.

P3.2.3-2
MEMBER
RELEASE DATE: 11/3/03

Kinetics Noise Control ©2003


KINETICS ™ Seismic Design Manual
FHS 4" DEFLECTION SEISMIC ISOLATOR A2, L2, T2, D2 DIMENSIONS
NEOPRENE 3-AXIS REFER TO OPTIONAL
TYPE L W H D Z T A E Z BOLT BASEPLATE USED TO
SNUBBER
4-100/1600 12.25 7.00 13.85 0.69 0.62 0.50 0.81 3.50 INCREASE RATING WHEN
ATTACHED TO CONCRETE
4-2250/5800 14.76 10.00 16.00 1.06 0.88 0.50 0.94 5.00
I-P UNITS (INCHES AND POUNDS)
H WELDED
STANDARD RATINGS Op. Ht GUSSET
COIL NOMINAL O.D. CAPACITY
TYPE SIZE FREE HT
4-100/1600 4-100 GRAY 10.00 5.63 100
4-250 BLUE 10.00 5.63 250 2 HOLES - D DIA
4 x D2
4-500 GREEN 10.00 5.63 500
T2 T
4-750 BLACK 10.00 5.63 750

FHS Submittal Drawings


4-1000 RED 10.00 5.63 1000

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


4-1250 BROWN 10.00 5.63 1250
4-1600 ORANGE 10.00 5.63 1600
2-2250/5800 * 4-2250 BEIGE 11.50 8.00 2250

Fax:
4-2500 BGE/BLU 11.50 8.00 2500

Email:
L E
4-2750 BGE/GRN 11.50 8.00 2750 L2 A W
4-3000 BGE/BLK 11.50 8.00 3000 L2

International:
4-3250 BGE/RED 11.50 8.00 3250
4-3500 BGE/BRN 11.50 8.00 3500

World Wide Web:


4-3850 BGE/ORG 11.50 8.00 3850

Toll Free (USA only):


4-4200 CHROME 11.50 8.00 4200 A2
CONCRETE ANCHORS (SPEC INSPECTION)
4-4450 CHR/BLU 11.50 8.00 4450 STANDARD HOUSING ONLY WELDED TO STEEL
4-4700 CHR/GRN 11.50 8.00 4700

DRAWING # S-01.35-3A – FHS 4-100/1600 4-2250/5800


CHR/BLK CAN BE INCREASED TO 4-2250/5800
4-4950 11.50 8.00 4950 WELDED RATING WITH
CHR/RED 7000 OVERSIZED BASEPLATE 7000 4-100/1600
4-5200 11.50 8.00 5200
CHR/BRN

614-889-0540
614-889-0480
800-959-1229
4-5450 11.50 8.00 5450 6000 6000
CHR/ORG
4-2250/5800
4-5800 11.50 8.00 5800
* INCLUDES WELDED GUSSET AS SHOWN 5000 5000
4-100/1600
4-100/1600 REQUIRES 0.62 DIA x 4.0 MIN EMBED ANCHORS IN CONCRETE

www.kineticsnoise.com
4-2250/5800 REQUIRES 1.0 DIA x 9.0 MIN EMBED ANCHORS IN CONCRETE 4000 4000

sales@kineticsnoise.com
(ALLOWABLE LOADS BASED ON 3000 PSI MIN CONCRETE)
4-100/1600 ANCHOR BOLT TORQUE - 75 FT LB, PULL TEST - 2670 LB 3000 3000
4-2250/5800 ANCHOR BOLT TORQUE - 200 FT LB, PULL TEST - 5310 LB
SPECIFICATIONS: 2000 2000
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH
VERTICAL RESTRAINT CAPACITY (LBS)

VERTICAL RESTRAINT CAPACITY (LBS)

CONSTANT FREE AND OPERATING HEIGHT AND REPLACEABLE 1000 1000


NEOPRENE SNUBBING ELEMENTS.
0.25 NOMINAL CLEARANCE IN SNUBBING ELEMENTS. 0 0
MINIMUM OVERLOAD OF 50%. 0 1000 2000 3000 0 1000 2000 3000 4000 5000 6000 7000
MINIMUM Kx/Ky RATIO OF 1.0. HORIZONTAL RESTRAINT CAPACITY (LBS) HORIZONTAL RESTRAINT CAPACITY (LBS)
ALL ELEMENTS SAFE AT SOLID LOADING.
POWDER COATED COILS AND HOT DIPPED GALVANIZED BRACKET Computed horiz and vert seismic load combinations must fall within the restraint

DOCUMENT:
OSHPD APPROVAL NUMBER R-0433 capacity envelope. Contact KNC for bolted to steel data.

P3.2.3-3
MEMBER
RELEASE DATE: 11/3/03

Kinetics Noise Control ©2003


KINETICS ™ Seismic Design Manual
INSTALLATION INSTRUCTIONS
KINETICS MODEL ( FLS & FLSS) SPRING ISOLATOR
PR Y A PART BLOCKING
E LEMEN T AFTER NO TE:
EQUIPMENT
LEVELING KINET ICS NOI SE CONTROL SUG GESTS T HAT MODEL FLS & F LSS
OU TLINE
ISOLATORS BE ON THE JOBSI TE PRIOR TO ARRI VAL
OF THE EQUIPMENT .

Drawing # SS-900915
RE MOVA BLE
BLOCKIN G ELEMENT 1. COORDI NATE THE LOCATI ON OF EACH ISOLATOR WIT H THE APPROPRIATE
(PVC PIPE) SUBMIT TAL DRAWING AND WIT H THE CO LOR CO DE CHART PROVIDED
FOR THE SPRINGS.
LEVELING
BOLT 2. PLACE THE I SOLAT ORS IN THEIR PROPER LOCATION AND ATT ACH

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


BOT TOM PLATE TO THE BUI LDING SUPPO RT STEEL.

3. SET THE EQUIPMENT FOO T, BRACKET OR SUPPORT ST EEL ON TOP

Fax:
TOP PLATE

Email:
O F THE ISOLATORS AND ATT ACH TO THE FLS TOP PLAT E PER
PROJECT SPECIFICATIONS.

FLSS / FLS Installation Instructions

International:
VER TIC AL 4. LOOSEN THE VERT ICAL REST RAINT JAM NUTS T O T HE END O F
R ESTRAINT THE RESTRAI NT BO LTS.

World Wide Web:


J AM N UTS
BOTTOM PLATE

Toll Free (USA only):


5. I N TURN, ROT ATE THE LEVELING BOLTS COUNT ER-CLOCKWISE SEVERAL
RESTRAINT COMPLETE TURNS ON EACH ISOLAT OR UNT IL THE BLOCKING ELEMENT CAN
B OLT BE REMOVED BY PRYING APART WITH A SCREW DRI VER. I T WILL BE
NECESSARY TO MAKE SEVERAL CI RCUIT S OF THE I SOLATO RS IN
ORDER TO UNIFO RMLY RAISE THE EQUI PMENT . DO NOT AT TEMPT
T O PLACE ALL THE WEIG HT O N ANY ONE ISOLATOR, T HIS MAY
RESULT IN DAMAG E TO THE ISOLATO R.

614-889-0540
614-889-0480
800-959-1229
6. DO NOT ATTEMPT TO MO VE ISO LAT ORS LATERALLY WI TH THE WEIGHT
OF THE EQUIPMENT ON T HEM. I F IT I S NECESSARY TO MOVE THE
EQUIPMENT, REMO VE T HE EQ UI PMENT F ROM THE I SO LAT ORS FI RST .

www.kineticsnoise.com
F AI LURE TO FOLLOW THI S PROCEDURE COULD RESULT IN DAMAGE

sales@kineticsnoise.com
TO THE I SOLAT ORS.

7. WHEN THE EQUI PMENT I S LEVEL PER THE EQUIPMENT MANUFACTURER'S


BU ILDING SUPPORT T OLERANCE, TIG HTEN THE VERTICAL RESTRAINING NUTS F INGER T IGHT ,
STEE L OU TLINE THE BACK OFF ONE F ULL TURN. LOCK THE BOLTS WIT H JAM NUTS
PROVIDED.

8. DISCARD ALL BLO CKI NG ELEMENTS.

DOCUMENT:

P3.5-1
MEMBER
RELEASE DATE: 11/3/03

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual
INSTALLATION INSTRUCTIONS
FOR
TYPE FHS KINETICS SPRING ISOLATION MOUNT
ATTACH MENT BOLT

Drawing # SS-960892
1. COORDINATE THE LO CATION O F EACH ISOLATOR WITH
WASH ERS THE APPROPRIATE SUBMITTAL DRAWING .
2. REMOVE THE ATTACHMENT BO LT AND ONE WASHER FROM
THE TOP OF THE LEVELING NUT. INSERT I T INTO
EQU IPMENT BRAC KET THE EQUIPMENT BRACKET (IT IS NOT NECE SSARY
TO INSTALL THE SPRING AT THIS POINT)

DUBLIN, OHIO, USA • MISSISSAUGA, ONTARIO, CANADA


3. ALIGN THE EQUIPMENT AND CE NTER THE ISOLATOR

FHS Installation Instructions


ISO LATOR HOUSING ANCHOR BO LT LOCATIONS.

Fax:
4. RAISE THE EQUIPMENT OR EQUIPMENT B ASE AND INSTALL

Email:
THE ISOLATO R ANCHORS IN THE FLOOR.
5. LOCATE THE SPRINGS AND LOWER THE E QUIPMENT. NOTE
RUBBER SNUBBING PADS

International:
WITH APPROXIMATELY THE DESIRED FLOO R CLEARANCE.
(TAKE CARE NOT TO PUSH THE E QUIPMENT SIDEWAYS.)

World Wide Web:


6. INS TALL ANCHOR NUTS TO FIRMLY ATTA CH THE FHS

Toll Free (USA only):


HOUSING TO THE FLOOR OR HO USEKEEPING PAD.
7. LO OSELY BOLT EQUIPMENT TO THE ISOLATOR USING THE
LEVELING NUT ATTACHMENT BOLT.
8. ADJUST THE ISOLATOR BY TURNING THE LEVELING NUT CCW
UNTIL THE FHS HOUS ING TOP P LATE IS CENTERED BETWEEN
TOP LOAD CAP THE RUBBER SNUBBING PADS ON THE LEVELING SCREW.

614-889-0540
614-889-0480
800-959-1229
IN A SIMILAR MANNER, CONTINUE WITH THE ADJUSTMENT
FHS H OUSING
OF THE REMAINING ISO LATORS.
9. TIGHTEN THE ADJUSTMENT BO LT, THUS BOLTING
THE SPRING TO THE SUPPORTED EQUIPMENT AND

www.kineticsnoise.com
LOCKING THE LEVELING BOLT AGAINST TURNING

sales@kineticsnoise.com
10. DO NOT ATTEMPT TO MOVE THE ISOLATO RS LATERALLY
WI TH THE WEIGHT OF THE EQUIPMENT ON THEM. IF IT
IS NECESSARY TO MOVE THE EQUIPMENT, REMOVE THE
INSTALLATION WEIGHT FRO M THE IS OLATORS BY RAISING THE
EQUIPMENT BEFORE MOVING.
DRAWING

DOCUMENT:

P3.5-2
MEMBER
RELEASE DATE: 11/3/03

Kinetics Noise Control © 2003


KINETICS ™ Seismic Design Manual