ELECTRONIC HEAD FOR GAS PUMPS

C-100

INSTRUCTIONS FOR SETTING


PARAMETERS
C 100 has been developed as a flexible programmable counting device which
can be connected to all existing mechanical counting gas pumps. For that
purpose there are several parameters which must be set according to the
configuration of the mechanic counting system and to the particular
requirements of the client. Setting these parameters (registers) can be done only
by authorized specialist and requires switching the electronic head over in
special mode. Beneath is described the sequences of the operations for switching
over the mode and setting parameters, as well as description of each parameters
and its function.

SETTING PARAMETERS AND REVERSE IN “MODE SALE”

 Switch off the power supply of the gas pump


 Remove the front glass cover
 Remove the front panel
 Remove the cap of the micro keys
 Switch over the first key in position “1”.( install jumper)
 Put the front panel in its place
 Switch on the power supply of the gas pump
 Set the parameters (see t.2)
 Switch off the power supply of the gas pump
 Remove the front panel
 Switch over the first key in position “0”.( remove jumper)
 Put the cap of the micro keys
 Put the front panel in its place
 Put and lock the glass cover
 Switch on the power supply of the gas pump

SETTING PARAMETERS

After switching on the power supply you will hear a sound signal as well as the
first display will indicate “C-100”, the second – the software version and the
third – “PROG”.After a several minutes the third (at the bottom) display will
indicate”REG:01”- this is the number of the parameter(register) while the first
and second display indicate its value. Setting can be done via the small 4-buttons
keyboard placed onto the front panel as the buttons have the following function:

 “TOTAL EURO” – selecting register. Each pressing of this button leads


to record the value of the current register and then switching over to the
next one.

 “+” – increases the register’s value. Advanced increasing can be done by


simultaneous pressing and button “TOTAL LITRES”.
 “-“ - decreases the register’s value. Advanced decreasing can be done by
simultaneous pressing and button “TOTAL LITRES”.
 “+” and “-“ loads the register with its standard value.

MODE “SALE” – IN SYSTEM

 Switch off the power supply of the gas pump


 Remove the front glass cover
 Remove the front panel
 Remove the cap of the micro keys
 For autonomous mode, switch over the second key in position “1” (install
jumper)
 For operation in system switch over the second key in position “0” (
remove jumper)
 Put the cap of the micro keys
 Put the front panel in its place
 Put and lock the glass cover
 Switch on the power supply of the gas pump

TABLE 2
№ DESCRIPTION OF PARAMETERS

01 Number of gas pump (1…16)


02 Type of fuel(1…5)
03 Number of impulses coming from the sensor for one
liter (1…10000)
04 Price per liter of fuel (0.01…9999.00)
05 Max. acceptable time for waiting for pulling out the
pistol till starting refuel in steps in 15 seconds (1..15)
06 Max. acceptable interruption during refuel in steps in
15 seconds (0…15,0 – is not tracked)
07 Remaining quantity of fuel for refuel at which the
intake butterfly valve turns off.( 0.00….5.00)
08 Remaining impulses at which the pump and the
valve.(0….100)
09 Status of the key when the pistol is pulled out (0- open,
1 – closed)
10 Setting limit by amount from the cash register (0- in lv,
1 –in coins)
11 Setting limit by quantity from the cash register (0- in
litres, 1 – in decimal signs)
12 Operation with coins -1, operation without coins - 0
16 Max. acceptable number of non-synchronized impulses
from sensor’s phases(1…200)
18 Monitoring the impulses after switching the pump off
(1- allowed,0 – forbidden)
20 Value of fore selecting button 1 in leva
21 Value of fore selecting button 2 in leva
22 Value of fore selecting button 1 in litres
23 Value of fore selecting button 2 in litres
24 Function –relay 3( 0 – valve – 1 – lightening)
25 Max. quantity for one refuel (0.00….9999.99 l)
26 Method of limits(0- to 10,000.00 l, 1 - to 1.000,000.00
lv. 2 – up to the quantity set in register 25)
27 Final amount at refuel with preselecting in leva.(0 –
actual amount, 1 - set amount)
28 Control amount of the communication protocol(0 –
XOR control amount, 1 - 16- bit CRC)
ACCUMULATING COUNTERS
A1 Total litres
A3 Total litres in autonomous mode of operation
A4 Total amount in autonomous mode
A5 Customer counter for displaying quantity
A6 Customer counter for counting amount
A7 Quantity of last refuel
A9 “Lost” impulses
ADDITIONAL PARAMETERS
B2 Min.quantity for refuel (0.00…1.00)