Documente Academic
Documente Profesional
Documente Cultură
1
Standards and recommendations
2
WRM – Why
3
WRM – When
Factory test
Installation/commissioning
Routine (Scheduled) Transformer Maintenance
Unscheduled Maintenance/Troubleshooting
Internal Transformer Inspections
4
WRM application and practices
5
WRM Basic theory
d flux
U R I
dt
L
t
di(t ) dL(i(t ), t )
U R i(t ) L(i, t ) i(t )
dt dt
Winding Inductance × current × change of
resistance change of inductance.
× current Inductance is a
current (=0 if current is function of current
constant) AND time
6
Principal relationship between applied voltage,
resistance and core saturation
OK
Avoid!
Time
7
Selecting Test Current Range
8
Current ratings for typical transformers
HV LV
MVA
Description Configuration
rating
kV A kV A
9
Winding resistance measurement – How
Decide if single or 2-ch measurement/current injection (SWM) is
appropriate
Connect current and voltage measurement cables to the actual
transformer winding(-s)
Select test current
Start test
Wait for measurement results to stabilize
When stable value, stop measurement/store result, discharging
starts automatically
Wait until discharging is finalized before disconnecting any cables!
Next measurement…
When finished - Demagnetize
10
Interpretation of Measurements
Field readings may vary more than this due to the many variables, in
particular the problem of determining exact winding temperature.
Suggested guidelines;
11
Temperature dependence
12
Demagnetization
Described in IEEE C57.152
Accomplished by switching the polarity of the DC current and then
repeating the same procedure while decreasing the current level
Only necessary to connect to one of the HV windings/legs (with
highest exiting current)
Important before SFRA and Excitation current measurements
May effect TTR measurements
Recommended in IEEE C57.152 to perform prior to excitation current
tests
Recommended in upcoming IEEE C57.152 (former IEEE 62) before
reconnecting the transformer back in service (to avoid potentially
dangerous in-rush currents)
+100% of
Test current +10% Positive
+0.1% polarity
Etc…
-0.01% Negative
-1% polarity
-100%
13
Adaptive demagnetization
Measure/calculate voltage-time integral (V*s) at high current (above
saturation current)
Create demagnetization cycles by reducing Vs value (typically 20%
reduction/step)
Effective
• Verified against true AC demagnetization. Similar results in excitation current and
magnetic balance verification measurements
Magnetic balance after AC demag b-n Magnetic balance after adaptive demag b-n
Fast
• Significantly faster than static demagnetization algorithms for smaller transformers
(40 cycles demagnetization in less than 1 minute for 0.5 MVA transformer)
14
Transformer magnetization influence
15
WRM field test guide
• Use a high accuracy dedicated winding resistance test set with
sufficient compliance voltage and test current
• Ground the instrument!
• Before you start measurements – Make a safety check
• Measure HV side (for all tap positions if LTC is on HV side)
• Continue with LV side (for all tap positions if LTC is on LV side). Use
dual injection technique if necessary to amplify magnetization
current
• Or use 2-ch and measure HV and LV simultaneously (SWM)
• Or use automated 3-w or 6-w measurement (MTO3xx)
• Never remove any cables before the transformer is fully discharged!
There is a lot of energy in a charged transformer!
• Demagnetize the core after test
16
Winding Resistance Measurements
17
Delta winding configuration
MTO
Solution:
Simultaneous winding
magnetization (SWM);
Incject test current on
HV and LV
simultaneously!
18
Increase magnetization and “effective test current”
Current Current
H0
H1 H0 H1
x1 x0 x1 x0
Electric
Current
Magnetic
Flux 10A ”110A”!
HV=1000 turns
LV=100 turns
Turn ratio=10
Single winding Dual winding
current injection current injection
10A test current X 10 Turn ratio = 110 A ”effective magnetization current” for the LV measurement!
WRM – LV delta measurement example (1)
220 MVA YNd11, LV 1-3, TTR=5.2, 10A test current (0.12% of rated)
mΩ
7.0
6.0
5.0
Single LV
injection
3.0 Dual ch
(out of
phase)
2.0
0.0
00:00 01:12 02:24 03:36 04:48 06:00 07:12 Minutes
20
WRM – LV delta measurement example (2)
1100 MVA YNd5, LV u-v, TTR=14.8, 8A test current (0.03% of rated)
Single measurement
Stabilization time > 25 minutes
SWM measurement
Stabilization time about 5 minutes
21
SWM Connection and Measurement
EXAMPLES ON TRANSFORMER CONNECTION SCHEMES FOR INJECTING TEST CURRENT AND MEASURING TWO WINDINGS SIMULTANEOUSLY
Measurement setup
Vector Group Current Connections Meas ch 1 Meas ch 2
+ Current Jumper - Current + - + -
H1 H3-X1 X3 H1 H3 X1 X3
Dd0 H2 H1-X2 X1 H2 H1 X2 X1
H3 H2-X3 X2 H3 H2 X3 X2
H1 H3-X0 X1 H1 H3 X0 X1
Dyn7 H2 H1-X0 X2 H2 H1 X0 X2
H3 H2-X0 X3 H3 H2 X0 X3
H1 H3-X1 X0 H1 H3 X1 X0
Dyn1 H2 H1-X2 X0 H2 H1 X2 X0
H3 H2-X3 X0 H3 H2 X3 X0
H1 H0-X1 X0 H1 H0 X1 X0
YNyn0 H2 H0-X2 X0 H2 H0 X2 X0
H3 H0-X3 X0 H3 H0 X3 X0
H1 H0-X1 X2 H1 H0 X1 X2
Ynd1 H2 H0-X2 X3 H2 H0 X2 X3
H3 H0-X3 X1 H3 H0 X3 X1
H1 H3-X1 X2 H1 H3 X3 X2
Dy1 H2 H1-X2 X3 H2 H1 X1 X3
H3 H2-X3 X1 H3 H2 X2 X1
H1 H0-X2 X1 H1 H0 X2 X1
YNd7 H2 H0-X3 X2 H2 H0 X3 X2
H3 H0-X1 X3 H3 H0 X1 X3
H1 H2-X0 X1 H1 H2 X0 X1
Dyn5 H2 H3-X0 X2 H2 H3 X0 X2
H3 H1-X0 X3 H3 H1 X0 X3
H1 H3-X1 X3 H1 H3 X1 X3
Dy11 H2 H1-X2 X1 H2 H1 X2 X1
H3 H2-X3 X2 H3 H2 X3 X2
H1 H2-X1 X0 H1 H2 X1 X0
Dyn11 H2 H3-X2 X0 H2 H3 X2 X0
H3 H1-X3 X0 H3 H1 X3 X0
22
The doctor is in...
23