Intelligent Multifunction Meter

 IEC 62053-22 Class 0.5S  Large, Backlit Dot-Matrix LCD with


 True RMS Measurements Wide Viewing Angle
 THD with 31 Ind. Harmonics  I/O Expansion Capabilities
 K-Factor, Crest Factor and TDD  RS-485 Port with Modbus RTU
 Unbalance & Phase Angles  IP54 Enclosure with No Openings
 Demands and Peak Demands  Standard Tropicalization
 Max/Min Log with Timestamp  Industrial Grade Components
 Multi-Tariff TOU  Extended Temperature Range
 12 Monthly Energy Log & SOE Log  Extended Warranty

Designed For Reliability Manufactured To Last


PMC-53A
Intelligent Multifunction Meter
Ease of use
 Large, backlit, Dot-Matrix LCD display with wide viewing angle
 Easy to navigate with an intuitive user interface
 kWh and kvarh LED pulse outputs for accuracy testing
 LED indicator for communication activities
 Password-protected setup via front panel or free PMC Setup software
 Easy installation with mounting clips, no tools required
Setpoints
 9 user programmable setpoints with extensive list of monitoring
parameters including Voltage, Current, Power and THD, … etc.
 Configurable thresholds, time delays and DO triggers
SOE Log
 64 events time-stamped to ±1ms resolution
 Setup changes, Setpoint and DI status changes and DO operations
The PMC-53A Intelligent Multifunction Meter is CET’s latest offer for the Max/Min Log
low-cost digital power/energy metering market. Housed in a standard DIN
 Max/Min Log with Timestamp for real-time measurements such as
form factor measuring 96x96x74mm, it is perfectly suited for industrial, Voltage, Current, In, I4, Freq., kW, kvar, kVA, PF, Unbalance, K-factor,
commercial and utility applications. The PMC-53A features quality Crest Factor and THD.
construction, multifunction measurements and a large, backlit, Dot-Matrix  Configurable for This Month/Last Month or Before/Since Last Reset
LCD that is easy to navigate and user friendly. Compliance with the IEC
Diagnostics
62053-22 Class 0.5S Standard, it is a cost effective replacement for analog
 Frequency Out-of-Range, Loss of Voltage / Current
instrumentation that is capable of displaying 4 measurements at once. It
 kW Direction per phase and Total, Possible incorrect CT Polarity
optionally provides I4 input for Neutral Current measurement, a second
 Incorrect V & I Phase Sequence,
RS485 port, four Digital Inputs for status monitoring, two Relay Outputs for
control and alarm applications as well as other I/O options for different Communications
applications.  Optically isolated RS485 port at max. 38,400 bps
 Optional 2nd RS485 port
Typical Applications  Standard Modbus RTU
 Industrial, Commercial and Utility Substation Metering System Integration
 Building, Factory and Process Automation
 Supported by CET’s PecStar® iEMS and iEEM
 Sub-metering and Cost Allocation  Easy integration into 3rd-party Energy Management, Automation or
 Energy Management and Power Quality Monitoring SCADA systems via Modbus RTU

Features Summary Inputs and Outputs


Basic Measurements Digital Inputs (Optional)
 VLN, VLL per phase and Average  4 channels, volts free dry contact, 24VDC internally wetted
 Current per phase and Average with calculated Neutral  1000Hz sampling
 kW, kvar, kVA, PF per phase and Total  External status monitoring with programmable debounce
 kWh, kvarh Import / Export / Net / Total and kVAh Total  Pulse counting with programmable weight for each channel for collecting
 Frequency WAGES (Water, Air, Gas, Electricity, Steam) information
 Optional I4 measurements Digital Outputs (Optional)
Enhanced Measurements  2 Form A mechanical relays for alarming and general purpose control
 THD, TOHD, TEHD and Individual Harmonics up to 31st  2 Solid State Pulse Outputs for kWh and kvarh pulsing
 TDD, K-Factor, Crest Factor and Displacement PF
 V and I Unbalance and Phase Angles
Expansion Modules
 Demands, Predicted Demands and Peak Demands for kW Total, kvar Total, The PMC-53A supports two optional, factory-installed modules that provide
kVA Total and per phase Current with Timestamp users with additional flexibility.
 Max/Min Log for real-time measurements Expansion Module A
 Two TOU schedules, each providing
 I4 Input
o 12 Seasons
 2nd RS485 port
o 20 Daily Profiles, each with 12 Periods in 15-minute interval
o 90 Holidays or Alternate Days Expansion Module B
o 8 Tariffs, each providing the following information
 2xDigital Inputs and 2xRelay Outputs
o kWh/kvarh Import/Export, kVAh
o kW/kvar/kVA Max. Demands  2xRTD Input (PT100 sensor not included)
 12 monthly recording of kWh/kvarh Import/Export/Total/Net, kVAh,  1xAI and 1xAO (0/4-20mA)
kvarh Q1-Q4 as well as kWh/kvarh Import/Export and kVAh per Tariff

Designed For Reliability Manufactured To Last


PMC-53A
Intelligent Multifunction Meter
Accuracy Standards of Compliance
Parameters Accuracy Resolution Safety Requirements
Voltage ±0.2% reading 0.1V CE LVD 2014 / 35 / EU EN61010-1 Edition 3
Current ±0.2% reading 0.001A Electrical safety in low voltage IEC 61557-12: 2008
I4 (measurement) 1.0% 0.001A distribution systems up to 1000Vac
kW, kVA IEC 62053-22 Class 0.5S 0.001k and 1500 Vdc
kWh, kVAh IEC 62053-22 Class 0.5S 0.1kXh
Insulation IEC 60255-5-2000
kvar / kvarh IEC 62053-21 Class 2 0.001k / 0.1kvarh
Dielectric test: 2kV @ 1 minute
P.F. ±1.0% 0.001
Insulation resistance: >100MΩ
Frequency ±0.02 Hz 0.01Hz
Impulse voltage: 6kV, 1.2/50µs
THD IEC 61000-4-7 Class B 0.01%
Electromagnetic Compatibility
K-Factor IEC 61000-4-7 Class B 0.1
Phase angles ±1° 0.1° CE EMC Directive 2014 / 30 / EU (EN 61326: 2013)
Immunity Tests
Technical Specifications Electrostatic discharge IEC 61000-4-2: 2001 Level IV
Radiated fields IEC 61000-4-3: 2002 (10 V/m)
Voltage Inputs (V1, V2, V3, VN)
Standard Un 400VLN/690VLL Fast transients IEC 61000-4-4: 2004 Level III
Range 10V to 1.2Un Surges IEC 61000-4-5: 2005 Level IV
Overload 1.2xUn continuous, 2xUn for 1s Conducted disturbances IEC 61000-4-6: 2006 Level III
Burden <0.02VA per phase Magnetic Fields IEC 61000-4-8: 2001 Level IV
Measurement Category CAT III up to 600VLL
Oscillatory waves IEC 61000-4-12: 2006 Level III
Frequency 45-65Hz
Current Inputs (I11, I12, I21, I22, I31, I32) Radio Disturbances CISPR 22:2006, Level B
Standard In 5A Emission Tests
Range 0.1% to 200% In Limits and methods of measurement
Starting Current 0.1% In of electromagnetic disturbance
Overload 2xIn continuous, 20xIn for 1s EN 55011: 2009 (CISPR 11)
characteristics of industrial, scientific
Measurement Category CAT III up to 600VLL
Burden <0.15VA per phase and medical (ISM) radio-frequency
Power Supply (L+, N-, GND) equipment
Standard 95-250VAC/DC, ±10%, 47-440Hz Limits and methods of measurement EN 55022: 2006+A1: 2007
Burden <2W of radio disturbance characteristics of (CISPR 22)
Overvoltage Category CAT III up to 300VLN information technology equipment
Digital Inputs (DI1, DI2, DI3, DI4, DIC) Limits for harmonic current emissions
Type Dry contact, 24VDC internally wetted for equipment with rated current ≤16 EN 61000-3-2: 2006+A1: 2009
Sampling 1000Hz
A
Hysteresis 40ms minimum
Limitation of voltage fluctuations and
Digital Outputs (DO11, DO12, DO21, DO22)
Type Form A Mechanical Relay flicker in low-voltage supply systems
EN 61000-3-3: 2006
Loading 5A @ 250VAC or 30VDC for equipment with rated current ≤16
Pulse Outputs (kWh, kvarh) A
Type Form A Solid State Relay Emission standard for residential,
Isolation Optical commercial and light-industrial EN 61000-6-3: 2007
Max. Load Voltage 80V
environments
Max. Forward Current 50mA
Electromagnetic Emission Tests for
Installation Torque
Measuring Relays and Protection IEC 60255-25: 2000
Voltage / Current Inputs 1.3 N.m
Power Supply, RS485, I/O 0.5 N.m Equipment
Environmental Conditions Mechanical Tests
Operating Temp. -25°C to 70°C Response IEC 60255-21-1:1998 Level I
Vibration Test
Storage Temp. -40°C to 85°C Endurance IEC 60255-21-1:1998 Level I
Humidity 5% to 95% non-condensing
Response IEC 60255-21-2:1998 Level I
Atmospheric Pressure 70 kPa to 106 kPa Shock Test
Endurance IEC 60255-21-2:1998 Level I
Mechanical Characteristics
Panel Cutout 92x92 mm (3.62”x3.62”) Bump Test IEC 60255-21-2:1998 Level I
Unit Dimensions 96x96x74 mm
IP Rating 54 (Front Panel), 30 (Body)
Shipping Weight TBD
Shipping Dimensions TBD

Designed For Reliability Manufactured To Last


PMC-53A
Intelligent Multifunction Meter
Device View and Dimensions Ordering Information

Your Local Representative

Ceiec Electric Technology Inc.


A: 8/F, WestSide, Building 201, Terra Industrial & Tradepark
Che Gong Miao, Shenzhen, Guangdong, P. R. China 518040
T: +86.755.8341.5187
F: +86.755.8341.0291
E: sales@cet-global.com
W: www.cet-global.com Revision Date: August 3, 2016

Designed For Reliability Manufactured To Last

S-ar putea să vă placă și