iO500 Intelligent
Life Safety System
COA 6020
7165-1657:
0244
S3000
Overview Features
The EST iO500 intelligent life safety system offers the power of • Comes standard with one loop (expandable to two) that
high-end intelligent processing in a configuration that delivers an supports up to 250 (expandable to 500) intelligent devices:
uncomplicated solution for small to mid-sized applications. With each iO500 loop supports up to 125 detectors and up to 125
intelligent detection, electronic addressing, automatic device map- modules.
ping, optional Ethernet® connectivity, and a full line of easily-con- • Supports Signature Series intelligent modules and detectors
figured option cards and modules, this flexible system offers offers
versatility that benefits building owners and contractors alike. • Combines the Signature intelligent releasing module with
Signature multisensor detectors for reliable suppression
The iO500 provides one Class A or Class B analog device loop
• Four Class B NACs or two Class A NACs.
that supports up to 250 device addresses. A second 250-point
loop may be added to the iO500 to expand total system capacity • Form C contacts for alarm and trouble, Form A for supervisory
to up to 500 device addresses. The panel includes four NACs that • Electronic addressing with automatic device mapping
may be wired for either Class A or Class B operation.
• Optional Ethernet port for diagnostics, programming and a
The iO500 supports a wide range of accessories and related variety of system reports
equipment, including:
• Two programmable switches with LEDs and custom labeling
• Signature Series intelligent modules, detectors, and bases
• Supports Genesis horn silence over two wires and UL
• R-Series remote annunciators 1971-compliant strobe synchronization
• option cards that expand system capacity and extend system • Supports up to eight serial annunciators, (LCD, LED-only, and
capabilities graphic interface).
• Listed for releasing applications using SIGA-REL • 1,000 event panel history log
• Fully integrated CO detection using Signature Series 2 detec- • Can use existing wiring for most retrofit applications
tors with or w/o audible signaling • Upload/download remotely or locally
• Two-level maintenance alert reporting
• Pre-alarm and alarm verification by point
• Adjustable detector sensitivity
• 4 x 20 character backlit LCD display
• Optional earthquake hardening: OSHPD seismic pre-approval
for component Importance Factor 1.5
Programming Dimensions
iO500 life safety systems are simple to set up, yet also offer ad- Surface mounting holes
vanced programming features that put these small building panels D2 D3
into a class of their own. The auto programming feature quickly
gets the panel operational using factory default settings. Basic
zone and point settings can be programmed easily through the
front panel interface, so the system is up and running in no time.
Circuit specifications The Signature Loop Controller uses broadcast polling and ad-
Circuit
Class Type
B wiring 4 Class B or 2 Class A, 2.5 amps each vanced communications formats to regularly check the entire
Voltage - 24 VFWR device circuit for anomalies. If a change of state is detected at the
NAC1
Current + 2.5 A max.
6.0 A total, + per circuit at 120/230 VAC 60 Hz circuit level, the Loop Controller then uses a direct address search
NAC1+
5.0 A
- total at 230VAC
- 50 Hz, 2.5 A max. per circuit to find the reporting device. This two-staged technique ensures
Impedance
NAC2 -
+ 26 Ω
+ total,
EOLR
0.35 µF max that only new information is transmitted, thus allowing for a re-
EOLR NAC2+ 15 K Ω, ½W duced baud rate while still achieving nearly instant device reporting.
- -
TB2 Class B wiring
Circuit specifications
Device loops 1 loop, expandable to 2, Class A or B, each loop
Class B wiring supporting
-
Loop 1 SEC up to 250 device addresses
Data Line
+
NAC1 -
+ + Communication Maximum 20 V peak-to-peak
NAC1+ line voltage Loop 1 PRI
- + +
- - Circuit current + 0.5 A max - -
EOLR
NAC2 - Loop Loop
+ + Circuit 66Ω total, 0.5 µF, max
device device
Loop card
NAC2+
- - impedance
TB2 Isolators 64 maximum
NAC3 - Class B wiring Class A wiring
+ +
Class B Wiring Class A Wiring
NAC3+
- - EOLR - -
NAC4 - Marking indicates Loop 1 SEC Loop 1 SEC
Data Line
+ + output signal polarity + +
NAC4+
- - when the circuit is ac- - + +- + +
Loop 1 PRI Loop 1 PRI
tive. Polarity reverses
TB6 + - -+ - -Terminal wiring location
when the circuit is not Loop Loop Loop Loop
active. Wire notification device Loopdevice
card device device
Loop card Data Line
Class A wiring appliances accordingly.
Notification appliance
NAC1 -
+ + polarity shown in ac- Class A wiring
NAC1+ tive state. Annunciator loop (TB4)
- -
NAC2 - The control- panel provides a connection for up to eight serially
+ + driven and +supervised remote annunciators.
Loop 1 SEC
Channel 1 Channel 2
NAC2+
- - – –
+
+
Circuit specifications
- + + TB4
TB2 Loop 1 PRI
- Device loops
+
Class B -
(Style Y) -
or Class A (Style Z)Annunciator
Loop Loop
+ Circuit
Loopvoltage
card 2.55 Vdevice device CH1 (+) IN
Data Line
- Circuit current 30 mA max CH1 (-) IN
Circuit Up to 8 annunciators or 4000 feet
+ impedance CH2 (+) IN
TB6 CH2 (-) IN
Class B Class A
Channel 1 Channel 2 Channel 1 Channel 2
– – – –
+
+
+
TB4 TB4
Auxiliary & Smoke power outputs (TB3)
The control panel provides two auxiliary power outputs which can Annunciator Annunciator
CH1 (+) IN CH1 (+) IN
be used for powering ancillary equipment such as remote an-
CH1 (-) IN CH1 (-) IN
nunciators and two wire smoke detectors. Aux 2 can be software
selected to operate continuous. The circuit is supervised for shorts
CH2 (+) IN CH2 (+) IN
and grounds. CH2 (-) IN CH2 (-) IN
TB4
Circuit specifications The trouble relay is normally-open, held closed, and opens on any
Circuit voltage range 21.9 to 28.3 V trouble event or whenAnnunciator
the panel is de-energized. The supervisory
Resettable circuit 24 VDC nominal at 500 mA relay is normally-open, CH1
and(+)closes
IN
on any supervisory event. The
CH1 (-) IN
(Aux power 2) alarm relay changes over on any alarm event.
Continuous circuit 24 VDC nominal at 500 mA. Use this circuit for
(Aux power 1) powering two-wire smoke detectors. Relay specifications CH2 (+) IN
CH2 (-) IN
Alarm Trouble Supervisory
Note: Any current above 0.5 amp connected to both Aux 1 and 2 will reduce the total
available NAC power by that amount. Type Form C Form A
Voltage 24 VDC at 1 A resistive 24 VDC at 1 A resistive
Relay circuits can only be connected to power-limited sources.
stallation, terminals remain accessible. The cabinet provides ample circuits connected to a Signature
room for wire routing, keeping wiring neat at all times. data circuit. The SMK moni-
tors the operating power from SMK
8 7 6 5
+ +
Power in
SA-ETH Ethernet Interface Card the power supply. When power Power out
+ +
SA-ETH wiring The SA-ETH card provides a begins to degrade, the SMK 4 3 2 1
SA-ETH specifications 8 7 6 5 4 3 2 1
A MR
Ordering Information
Part Description
iO500 Intelligent Multi-Loop Analog Systems
iO500G 1 Loop system, 500 point capacity, 4 NACs, gray door, surface mount enclosure, 115 Vac, English.
iO500G-2 1 Loop system, 500 point capacity, 4 NACs, gray door, surface mount enclosure, 230 Vac, English.
iO500GC Canada only: 1 Loop system, 500 point capacity, 4 NACs, 16-zone LED display, grey door, surface mount, 115 Vac, English.
iO500G-F Canada only: 1 Loop system, 500 point capacity, 4 NACs, 16-zone LED display, grey door, surface mount, 115VAC, French.
iO500GD 1 Loop system, 500 point capacity, two-line dialer, 4 NACs, Gray door, surface mount enclosure, 115VAC transformer, English.
iO500R 1 Loop system, 500 point capacity, 4 NACs, red Door, surface mount enclosure, 115VAC transformer, English.
iO500R-2 1 Loop system, 500 point capacity, 4 NACs, red door, surface mount enclosure, 230VAC transformer, English.
iO500RD 1 Loop system, 500 point capacity, two-line dialer, 4 NACs, Red Door, surface mount enclosure, 115VAC transformer, English.
iO500G-SP 1 Loop system, 500 point capacity, 4 NACs, gray door, surface mount enclosure, 115vac, Spanish.
iO500G-2-SP 1 Loop system, 500 point capacity, 4 NACs, gray door, surface mount enclosure, 230vac, Spanish.
iO500G-PG 1 Loop system, 500 point capacity, 4 NACs, gray door, surface mount enclosure, 115vac, Portuguese.
iO500G-2-PG 1 Loop system, 500 point capacity, 4 NACs, gray door, surface mount enclosure,, 230vac, Portuguese.
SA-TRIM2 Flush mount trim, black
Replacement Electronics
500elec-iO Replacement electronics kit, complete motherboard and user interface, English
500elec-iO-SP Replacement electronics kit, complete motherboard and user interface, Spanish
500elec-iO-PG Replacement electronics kit, complete motherboard and user interface, Portuguese
500elec-iO-FR Replacement electronics kit, complete motherboard and user interface, Canadian French
Option Cards
SA-DACT Dual Line Dialer/Modem, supports Contact ID, mounts in cabinet on base plate.
SA-232 Serial Port (RS-232), for connection to printers & computers, mounts in cabinet to base plate
SA-ETH Ethernet Port, Slave, mounts in cabinet on base plate.
XAL250 Signature Loop Expansion Module. Adds second loop to iO500 systems, 250 point capacity. Mounts in cabinet on main board.
D16L-iO-2 LED Annunciator module, 16 X 2-LED zones (4 programmable for sup). Mounts in cabinet to right of LCD display for zones 17-32.
D16L-iO-1 LED Annunciator module, 16 X 2-LED zones (4 programmable for sup). Mounts in cabinet to left of LCD display for zones 1-16.
D8RY-iO-2 Canada only: LED Annunciator module, two LEDs per zone, 16 zones (4 alarm only, 8 supervisory only, 4 alarm or supervisory).
Mounts in cabinet to right of LCD display for zones 17-32.
D8RY-iO-1 Canada only: LED Annunciator module, two LEDs per zone, 16 zones (4 alarm only, 8 supervisory only, 4 alarm or supervisory).
Mounts in cabinet to left of LCD display for zones 1-16.
Programming Tools
iO-CU EST Series configuration and diagnostics utility.
260097 RS232 cable, 4 conductor, DB9 PC interface
Modules
SIGA-CC1 Single Input Signal Module (Standard Mount) 0.5 (0.23)
SIGA-MCC1 Single Input Signal Module (UIO Mount) 0.18 (0.08)
SIGA-CC1S Synchronization Output Module (Standard Mount) 0.5 (0.23)
SIGA-MCC1S Synchronization Output Module (UIO Mount) 0.18 (0.08)
SIGA-CC2 Dual Input Signal Module (Standard Mount) 0.5 (0.23)
SIGA-MCC2 Dual Input Signal Module (UIO Mount) 0.18 (0.08)
SIGA-CR Control Relay Module (Standard Mount) 0.4 (0.15)
SIGA-MCR Control Relay Module (UIO Mount) 0.18 (0.08)
SIGA-CRR Polarity Reversal Relay Module (Standard Mount) 0.4 (0.15)
SIGA-MCRR Polarity Reversal Relay Module (UIO Mount) 0.18 (0.08)
SIGA-RM1 Riser Monitor Module (Standard Mount) 0.5 (0.23)
SIGA-MRM1 Riser Monitor Module (Plug-in) 0.18 (0.08)
SIGA-IO Input/Output Module (Standard Mount) 0.34 (0.15)
SIGA-MIO Input/Output Module (Plug-in) 0.22 (0.10)
SIGA-MAB Universal Class A/B Module (Plug-in) 0.18 (0.08)
SIGA-CT1 Single Input Module 0.4 (0.15)
SIGA-CT2 Dual Input Module 0.4 (0.15)
SIGA-MCT2 Dual Input Plug-in (UIO) Module 0.1 (0.05)
SIGA-IM Fault Isolator Module 0.5 (0.23)
SIGA-MM1 Monitor Module 0.4 (.15)
SIGA-WTM Waterflow/Tamper Module 0.4 (.15)
SMK Smoke Power Converter Module 0.4 (0.15)
SIGA-UIO2R Universal Module Board w/Riser Inputs - Two Module Positions 0.32 (0.15)
SIGA-UIO6R Universal Module Board w/Riser Inputs - Six Module Positions 0.62 (0.28)
SIGA-UIO6 Universal Module Board - Six Module Positions 0.56 (0.25)
SIGA-REL Analog addressable releasing module 0.5 (0.23)
276A-REL Manual releasing station (single-action). English markings, black text on yellow polycarbonate body. 1.0 (0.45)
278A-REL Manual releasing station (double-action). English markings, black text on yellow polycarbonate body. 1.0 (0.45)
RELA-ABT Manual Abort Station. English markings, black text on yellow polycarbonate body. 1.0 (0.45)
Service Disconnect Switch. One n/c contact and one n/o contact. English markings, white text on blue
RELA-SRV-1 1.0 (0.45)
polycarbonate body.
RELA-EOL Polarized end-of-line relay. English markings on stainless steel cover. 0.2 (0.1)
Accessories
GCI Graphic Annunciator Driver, provides outputs for common indicators and 32 alarm/supv zones as well as
inputs for common switches. Provided with a snap track for mounting in custom graphic enclosures.
CTM City Tie Module. Provides connection to a local energy fire alarm box. 0.6 (0.3)
RPM Reverse Polarity Module 3.0 (1.36)
BC-1 Battery Cabinet. 14.0" x 18.25" x 7.25". Holds 2 12V24A batteries. 50.0 (22.7)
BC-1R Battery Cabinet - Red. 14.0" x 18.25" x 7.25". Holds 2 12V24A batteries. 50.0 (22.7)
BC-1EQ Seismic hardening Kit for iO series panels. Includes battery hardening for BC-1 enclosure and components
to harden panel internal components. See note below.
MFC-A Multifunction Fire Cabinet, 8" x 14" x 3.5" - RED. 20.6 (9.4)
PT-1S System Printer - Desktop style. 36.6 (16.6)
Note:
For earthquake anchorage, including detailed mounting weights and center of gravity detail, please refer to Seismic Application Guide 3101676-EN.
Approval of panel anchorage to site structure may require local AHJ, structural, or civil engineer review.
Standby batteries must be mounted externally from fire panel in separately mounted BC-1 enclosure. Order BC-1 and BC-1EQ separately.