EST Catalog u Small Building Fire Alarm Solutions

iO500 Intelligent
Life Safety System
COA 6020

7165-1657:
0244

S3000

Overview Features
The EST iO500 intelligent life safety system offers the power of • Comes standard with one loop (expandable to two) that
high-end intelligent processing in a configuration that delivers an supports up to 250 (expandable to 500) intelligent devices:
uncomplicated solution for small to mid-sized applications. With each iO500 loop supports up to 125 detectors and up to 125
intelligent detection, electronic addressing, automatic device map- modules.
ping, optional Ethernet® connectivity, and a full line of easily-con- • Supports Signature Series intelligent modules and detectors
figured option cards and modules, this flexible system offers offers
versatility that benefits building owners and contractors alike. • Combines the Signature intelligent releasing module with
Signature multisensor detectors for reliable suppression
The iO500 provides one Class A or Class B analog device loop
• Four Class B NACs or two Class A NACs.
that supports up to 250 device addresses. A second 250-point
loop may be added to the iO500 to expand total system capacity • Form C contacts for alarm and trouble, Form A for supervisory
to up to 500 device addresses. The panel includes four NACs that • Electronic addressing with automatic device mapping
may be wired for either Class A or Class B operation.
• Optional Ethernet port for diagnostics, programming and a
The iO500 supports a wide range of accessories and related variety of system reports
equipment, including:
• Two programmable switches with LEDs and custom labeling
• Signature Series intelligent modules, detectors, and bases
• Supports Genesis horn silence over two wires and UL
• R-Series remote annunciators 1971-compliant strobe synchronization
• option cards that expand system capacity and extend system • Supports up to eight serial annunciators, (LCD, LED-only, and
capabilities graphic interface).
• Listed for releasing applications using SIGA-REL • 1,000 event panel history log
• Fully integrated CO detection using Signature Series 2 detec- • Can use existing wiring for most retrofit applications
tors with or w/o audible signaling • Upload/download remotely or locally
• Two-level maintenance alert reporting
• Pre-alarm and alarm verification by point
• Adjustable detector sensitivity
• 4 x 20 character backlit LCD display
• Optional earthquake hardening: OSHPD seismic pre-approval
for component Importance Factor 1.5

Page 1 of 10 D ATA S H E E T 85005-0130


Not to be used for installation purposes. Issue 7.1
Application Operation
The iO500 life safety system is a powerful intelligent solution for The front panel provides
small to mid-sized buildings. Advanced analog technology delivers an easy-to-use operator’s
the benefits of flexible system installation, while a clean and easy- interface, as well as all
to-operatate user interface makes panel operation and system the necessary controls for
maintenance quick and intuitive. front panel programming.
A large back-lit 80-char-
The smart choice acter LCD displays
Signature Series electronic addressing eliminates the tedium of system status, event
setting dipswitches, and automatic device mapping ensures that details, and programming
each device resides on the system at its correct location. Mean- prompts. Large tactile
while, innovative programming allows the designer to customize control buttons are easy
the system to precisely suit the needs of the building owner. to see in low light condi-
tions, and bright multi-color LEDs offer at-a-glance status indica-
Flexibility built right in tion.
Two fully-programmable front panel switch/LED combinations pro-
vide an added measure of flexibility. Their slide-in labels take the
mystery out of custom applications, and present a clean finished Control buttons
appearance.
Button Description
Reset Initiates a system reset.
Perfect for retrofits
ACK/Panel Silences the panel and remote annunciators during
The iO500 is particularly well-suited to retrofit applications. All Silence an active trouble, supervisory, or alarm event and
connections are made over standard wiring – no shielded cable acknowledges new event activations.
required. This means that in most situations existing wiring can Signal Silence Alarm mode: Silences active notification appliances.
be used to upgrade a legacy control panel to iO500 technology Pressing Signal Silence a second time turns NACs back
without the expense or disruption of rewiring the entire building. on.
Drill Initiates a drill confirmation. Pressing drill a second time
Signals with a difference turns off the drill function.
iO500 NACs are configurable to fully support the advanced signal- Remote Dialer: Disables or enables dialer.
ing technology of Edwards Genesis and Enhanced Integrity notifi- Disconnect Dialer set to modem only: Disables or enables the
common alarm relay.
cation appliances. These devices offer precision synchronization of
Left arrow Display mode: Moves the cursor to the left.
strobes to UL 1971 standards. For Genesis devices, enabling this Menu mode: Toggles between programming
feature allows connected horns to be silenced while strobes on selections.
the same two-wire circuit continue to flash until the panel is reset. Right arrow Display mode: Moves the cursor to the right.
Menu mode: Retrieves a programming option’s sub
Clear-cut remote annunciation menu and toggles between a programming option’s
Remote annunciation is a strong suit of the iO500. Up to eight an- selections.
nunciators can be installed on a single system. Compatible annun- Up arrow Display mode: Advances to the previous event.
ciators include a range of LED and LCD models that provide zone Menu mode: Moves the cursor up.
or point annunciation, as well as common control capabilities. Down arrow Display mode: Advances to the next event.
Menu mode: Moves the cursor down.
The iO500 also supports graphic annunciation with optional Enter Display mode: Displays selected event details.
graphic annunciator interface modules. Each interface provides Menu mode: Retrieves a programming option’s sub
common control, indicators, and LED drivers. Consult the Order- menu or jumps to the Save function in the menu.
ing Information section for details. Entry mode: Enters the selected data into the system.
Cancel Display mode: Exits the detailed information display.
Menu mode: Exits the current menu level.
A complete line of accessories Entry mode: Clears the current entry.
The iO500 life safety system is supported by a complete line of Menu Display mode: Enters the menu mode
intelligent detectors, modules and related equipment. Consult the Menu mode: Exits menu mode
Ordering Information section for details. Space Enters a space, such as a space between words.
Alphanumeric Entry mode: Pressing a button once enters the number
keypad on the button. Pressing the button twice enters the
secondary value.
Programmable These buttons can be programmed to control outputs,
buttons disable devices or unlatch system outputs. The buttons
can be labeled with a slip-in insert.

Page 2 of 10 D ATA S H E E T 85005-0130


Not to be used for installation purposes. Issue 7.1
System LEDs Panel Operation Options
LED Description Language English or French
Alarm Red LED. On steady when there is an active Marketplace U.S. or Canada
alarm. AC fail delay Off: Off-premise notification of an AC power failure
Trouble Yellow LED. Flashes when there is a fault on a is immediate.
monitored circuit or system component, or when a 1 to 15 hours: Delays the off-premise notification of
an AC power failure by the time period selected.
circuit is disabled.
Zone resound On: NACs resound each time a device in the zone
Sup Yellow LED. On steady when there is an active goes into alarm even if they were silenced
supervisory event. Off: Inhibits the NACs from turning on again (after
AC Power Green LED. On when the panel has AC power. they were silenced) when a second device in the
Disable Yellow LED. Double-flashes when there is a dis- zone goes into alarm.
abled circuit, alarm relay, or remote annunciator. Reset inhibit after Off: Panel reset is operational immediately.
Ground Yellow LED. On steady during an active ground fault. NACs turn on 1 minute: Panel reset is inhibited for one minute.
Fault Auto signal Off: Allows immediate silencing of signals from an
silence off-normal condition using the Signal Silence button
Test Yellow LED. Flashes when performing an audible
5 to 30 minutes: Delays the silencing of signals
walk test. Steady indicates a silent test. from an off-normal condition by disabling the Signal
Monitor Yellow LED. On steady when there is an active Silence button for the time period selected.
monitor event. Day start Start time for daytime sensitivity
Service Yellow LED. Indicates that detector needs servicing. Night start Start time for nighttime sensitivity
Detector Date U.S.: MM/DD/YYYY, Canada: DD/MM/YYYY
Signal Yellow LED. On steady indicates that NAC circuits Sounder Base Six configuration settings
Silence are turned off but the panel is still in alarm. Mapping Disabled: Device mapping is not available
Remote Yellow LED. On steady indicates that the dialer Enabled: Device mapping is available
Disconnect is disabled or that the alarm relay is enabled or LCD banner Banner text for line one and line two. Each line is
disabled when the dialer is set to modem only. capable of up to 20 characters.
Drill Yellow LED. Indicates that the panel is in drill. Event notification Zone: When a device is a member of a zone, only
the zone information is sent to the LCD display,
Reset Yellow LED. Indicates that the panel is resetting.
LEDs, printer, and dialer.
Panel Yellow LED. Indicates that the panel has been Zone/device: Zone information is sent to the LCD
Silence silenced during an active trouble, supervisory, or display and LEDs. Device information is sent to the
alarm event and indicates that new event activa- printer and dialer.
tions have been acknowledged. Device: Only device information is reported.
User Keys Yellow LED. Programmable.

Programming Dimensions
iO500 life safety systems are simple to set up, yet also offer ad- Surface mounting holes
vanced programming features that put these small building panels D2 D3
into a class of their own. The auto programming feature quickly
gets the panel operational using factory default settings. Basic
zone and point settings can be programmed easily through the
front panel interface, so the system is up and running in no time.

Semi-flush mounting holes


For more advanced system configuration and correlation groups
programming, iO500 systems interface to a PC running compat-
ible iO-CU software. This option offers full system configuration
in the familiar Windows® operating environment. Connection is
D1 D4
typically made to a laptop through the panel’s optional RS-232
communications port, which can also be used to connect a sys-
tem printer.
Among the many innovative features of iO500 control panels is the
optional network card. This module provides a standard 10/100
Base T Ethernet® network connection that permits access to the Surface mounting holes
control panel from any remote location with the correct commu-
nications protocols. The connection can be used to download
to the panel from the iO-CU, or upload and view system reports D6
using the iO-CU. D5
Available system reports include:
•  Correlation groups •  Device details Panel dimensions, in (cm)
• Device maintenance • History Model D1* D2 D3 D4 D5* D6
•  Internal status •  System configuration 28.0 3.85 9.0 22.0 15.75 10.25
iO500
•  System status •  Walk test (71.1) (9.8) (22.8) (55.8) (40.0) (26.0)
• Dialer • CO runtime * Add 1-1/2 in. (3.81 cm) to D1 and D5 dimensions for trim kit.

Page 3 of 10 D ATA S H E E T 85005-0130


Not to be used for installation purposes. Issue 7.1
Wiring & Configuration
Notification appliance circuits (TB2) Signature Device loop
iO500 control panels come equipped with four notification ap- The system provides one device loop circuit with a total capacity
pliance circuits. Each circuit can be individually configured for of 125 detectors and 125 module addresses. The loop circuit is
continuous, temporal, synchronized, latching, and coded output. supervised for opens, shorts, and grounds.

Circuit specifications The Signature Loop Controller uses broadcast polling and ad-
Circuit
Class Type
B wiring 4 Class B or 2 Class A, 2.5 amps each vanced communications formats to regularly check the entire
Voltage - 24 VFWR device circuit for anomalies. If a change of state is detected at the
NAC1
Current + 2.5 A max.
6.0 A total, + per circuit at 120/230 VAC 60 Hz circuit level, the Loop Controller then uses a direct address search
NAC1+
5.0 A
- total at 230VAC
- 50 Hz, 2.5 A max. per circuit to find the reporting device. This two-staged technique ensures
Impedance
NAC2 -
+ 26 Ω
+ total,
EOLR
0.35 µF max that only new information is transmitted, thus allowing for a re-
EOLR NAC2+ 15 K Ω, ½W duced baud rate while still achieving nearly instant device reporting.
- -
TB2 Class B wiring
Circuit specifications
Device loops 1 loop, expandable to 2, Class A or B, each loop
Class B wiring supporting
-
Loop 1 SEC up to 250 device addresses
Data Line
+
NAC1 -
+ + Communication Maximum 20 V peak-to-peak
NAC1+ line voltage Loop 1 PRI
- + +
- - Circuit current + 0.5 A max - -
EOLR
NAC2 - Loop Loop
+ + Circuit 66Ω total, 0.5 µF, max
device device
Loop card
NAC2+
- - impedance
TB2 Isolators 64 maximum
NAC3 - Class B wiring Class A wiring
+ +
Class B Wiring Class A Wiring
NAC3+
- - EOLR - -
NAC4 - Marking indicates Loop 1 SEC Loop 1 SEC
Data Line
+ + output signal polarity + +
NAC4+
- - when the circuit is ac- - + +- + +
Loop 1 PRI Loop 1 PRI
tive. Polarity reverses
TB6 + - -+ - -Terminal wiring location
when the circuit is not Loop Loop Loop Loop
active. Wire notification device Loopdevice
card device device
Loop card Data Line
Class A wiring appliances accordingly.
Notification appliance
NAC1 -
+ + polarity shown in ac- Class A wiring
NAC1+ tive state. Annunciator loop (TB4)
- -
NAC2 - The control- panel provides a connection for up to eight serially
+ + driven and +supervised remote annunciators.
Loop 1 SEC
Channel 1 Channel 2
NAC2+
- - – –
+

+
Circuit specifications
- + + TB4
TB2 Loop 1 PRI
- Device loops
+
Class B -
(Style Y) -
or Class A (Style Z)Annunciator
Loop Loop
+ Circuit
Loopvoltage
card 2.55 Vdevice device CH1 (+) IN
Data Line
- Circuit current 30 mA max CH1 (-) IN
Circuit Up to 8 annunciators or 4000 feet
+ impedance CH2 (+) IN
TB6 CH2 (-) IN
Class B Class A
Channel 1 Channel 2 Channel 1 Channel 2
– – – –
+

+
+

TB4 TB4
Auxiliary & Smoke power outputs (TB3)
The control panel provides two auxiliary power outputs which can Annunciator Annunciator
CH1 (+) IN CH1 (+) IN
be used for powering ancillary equipment such as remote an-
CH1 (-) IN CH1 (-) IN
nunciators and two wire smoke detectors. Aux 2 can be software
selected to operate continuous. The circuit is supervised for shorts
CH2 (+) IN CH2 (+) IN
and grounds. CH2 (-) IN CH2 (-) IN

Note: For a complete list of devices that can be connected to this


Channel 1 Channel 2
circuit, refer to the iO Series compatibility list (p/n 3101064). Alarm,–trouble,
– and supervisory relay (TB3)
+

TB4
Circuit specifications The trouble relay is normally-open, held closed, and opens on any
Circuit voltage range 21.9 to 28.3 V trouble event or whenAnnunciator
the panel is de-energized. The supervisory
Resettable circuit 24 VDC nominal at 500 mA relay is normally-open, CH1
and(+)closes
IN
on any supervisory event. The
CH1 (-) IN
(Aux power 2) alarm relay changes over on any alarm event.
Continuous circuit 24 VDC nominal at 500 mA. Use this circuit for
(Aux power 1) powering two-wire smoke detectors. Relay specifications CH2 (+) IN
CH2 (-) IN
Alarm Trouble Supervisory
Note: Any current above 0.5 amp connected to both Aux 1 and 2 will reduce the total
available NAC power by that amount. Type Form C Form A
Voltage 24 VDC at 1 A resistive 24 VDC at 1 A resistive
Relay circuits can only be connected to power-limited sources.

Page 4 of 10 D ATA S H E E T 85005-0130


Not to be used for installation purposes. Issue 7.1
Option Cards
iO500 panels are supported by a complete line of modules and SMK Smoke Power Converter
related equipment that enhance performance and extend system The SMK Smoke Power Convert-
24 VDC
capabilities. Option cards plug directly into the control panel main er Module provides a regulated auxilliary
power
+
_
circuit board or are connected to it with a ribbon cable. After in- power source for two-wire smoke (not resettable)

stallation, terminals remain accessible. The cabinet provides ample circuits connected to a Signature
room for wire routing, keeping wiring neat at all times. data circuit. The SMK moni-
tors the operating power from SMK
8 7 6 5
+ +
Power in

SA-ETH Ethernet Interface Card the power supply. When power Power out
+ +
SA-ETH wiring The SA-ETH card provides a begins to degrade, the SMK 4 3 2 1

To network provides the necessary operating


connection standard 10/100 Base T Ethernet
Network cable
network connection for connect- voltage to the two-wire smoke Two-wire smoke

ing to an intranet, a local net- detection circuits. detectors

work, or the Internet. The card 16 15 14 13 3 2 1 12 11 10 9

can be used to download JP1


+

configuration programming from 8 7 6 5 4 3 2 1


the iO-CU to the panel over the
network. Data in +

The Ethernet card is installed on Two-wire smoke


detectors
the plastic assembly and con-
Ethernet card
nects to the main circuit board 16 15 14 13 3 2 1 12 11 10 9

via a ribbon cable. JP1


+
Terminate
or to next
UM

SA-ETH specifications 8 7 6 5 4 3 2 1

Ethernet 10/100 Base T


Data out
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Humidity 0 to 93% RH, noncondensing at 90°F SMK specifications
(32°C) Input voltage 21.9 to 28.3 VDC (not resettable)
Output voltage 24 VDC nom. at 200 mA, max., special
Class B wiring applications
XAL250 Loop Expander Card Ground fault 10 k ohm
The XAL250 Loop Expander Card provides- an additional Signature impedance
Series device loop on the control panel.
Loop 1 SEC
The card expands the
Data Line Operating environment
+
control panel’s device capacity to 500 Temperature 32 to 120°F (0 to 49°C)
- total device addresses,
+ + 250
Loop 1 PRI Humidity 0 to 93% RH, noncondensing at 90°F (32°C)
per loop. The card is compatible with + Class B or Class- A wiring.
- It
Storage temperature –4 to 140°F (–20 to 60°C)
is compatible with iO500 control panels only. Loop Loop
Loop card device device Compatible electrical North American 4 inch square x 2-1/2 in.
The loop expander card connects to connector J7 on the main boxes (64 mm) deep 2 gang box or Standard 4 in.
circuit board.
Class B wiring Class A wiring
square box 1-1/2 in. (38 mm) deep
Wire size 14, 16, or 18 AWG wire (1.5, 1.0, or 0.75 sq.
Class B Wiring Class A Wiring
mm) (Sizes 16 and 18 AWG are preferred)
- -
Loop 1 SEC Loop 1 SEC
Data Line
+ +
- + +- + +
Loop 1 PRI Loop 1 PRI
+ - -+ - - SA-232 RS-232 interface
Loop Loop Loop Loop SA-232 wiring
device Loopdevice
card device device The SA-232 card provides an RS-232
Loop card Data Line GND (black wire)
interface with iO500 panels. It can be TXD (white wire)
used for connecting a printer to the RXD (red wire)
XAL250
Class specifications
A wiring
control panel to print system events. The
Device addresses on loop 125 detectors and 125 modules card also can be used for connecting a
Wiring - Class B (Style Y) or Class A (Style Z) computer to download a configuration
Loop 1 SEC
Operating voltage
+ 20 V peak-to-peak program from the iO-CU to the control
Operating
Loop 1 PRI
current
- + 0.5 A total
+ panel.
Circuit impedance
+ - 66 Ω, 0.5- µF, max
Terminal rating Loop
12 to 18 AWG (0.75 to 2.5 sq mm)
Loop The RS-232 card is installed on the plastic assembly and con-
device device
Loop card
Operating environment
Data Line nects to the main circuit board via a ribbon cable.
Temperature 32 to 120°F (0 to 49°C)
Humidity 0 to 93% RH, noncondensing at 90°F SA-232 specifications
(32°C) Operating voltage Standard EIA-232
Terminal rating 12 to18 AWG (0.75 to 2.5 sq mm)
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Humidity 0 to 93% RH, noncondensing at 90°F (32°C)

Page 5 of 10 D ATA S H E E T 85005-0130


Not to be used for installation purposes. Issue 7.1
SA-DACT Dialer SIGA-REL Releasing Module
The SA-DACT provides communications between the control The SIGA-REL is an analog addressable module that communi-
panel and the central station over a telephone line system. It cates directly with the fire alarm panel Signature loop controller. The
transmits system status changes (events) to a compatible digital SIGA-REL controls sprinkler, pre-action and deluge systems, and
alarm communicator receiver over the public switched telephone may also be used to release extinguishing agents such as CO2,
network. The dialer is capable of single, dual, or split reporting Halon, or foam. The module is easily configured in the field and of-
of events to two different account and telephone numbers. The fers a wide range of options that ensure dependable service, while
modem feature of the SA-DACT can also be used for uploading preventing the unnecessary release of extinguishing agent.
and downloading panel configuration, history, and current status
to a PC running the iO-CU. SIGA-REL specifications
SA-DACT Phone line 2 Input voltage 24 Vdc (power limited)
wiring
To wall Supervisory current 25 mA, max.
Phone line 1 phone jack Power riser
Riser input current 4 amps maximum
Phone cables
Alarm 170 mA min.; 4 A max.
(supplied) RJ31 jacks Output rating 2 A @ 24 Vdc (per circuit)
Valves per circuit 4 valves, max.
Release Max. supervisory current 0.4 mA (short circuit)
circuits Nominal supervisory current 0.18 mA
The dialer phone lines connect
Supervisory voltage 26 Vdc, max. (open circuit)
to connectors on the dialer’s
End of line device 47k Ohm EOL
main circuit board. Phone line 1
connects to connector J4 and 2 A @ 24 Vdc (for each
Output rating
phone line 2 connects to circuit)
Max. supervisory current
connector J1. Pre-release 0.4 mA (short circuit)
Nominal supervisory current
alarm circuits 0.18 mA
Supervisory voltage
26 Vdc, max. (open circuit)
End of line device
47k Ohm resistor
Max. supervisory current 0.4 mA (short circuit)
Nominal supervisory current 0.18 mA
Manual
Supervisory voltage 26 Vdc, max. (open circuit)
The SA-DACT queues messages and transmits them based on release input
End of line device 47k Ohm resistor
circuit
priority (alarm, supervisory, trouble, and monitor). Activations are Circuit type Class B N.O. latching
transmitted before restorations. Circuit capacitance 0.1 µF, max
Max. supervisory current 0.4 mA (short circuit)
The SA-DACT is installed on the plastic assembly and connects to Nominal supervisory current 0.18 mA
the main circuit board via a ribbon cable. Supervisory voltage 26 Vdc, max. (open circuit)
Abort circuit
End of line device 47k Ohm resistor
SA-DACT specifications Circuit type Class B N.O. non- latching
Phone line type One or two loop-start lines on a public, Circuit capacitance 0.1 µF, max
switched network First alarm 3 A @ 24 Vdc
Contact rating
Phone line connector RJ-31/38X (C31/38X) output relay (0.6 power factor) Form C
Communication formats Contact ID (SIA DC-05) Operating voltage 5.2 to 19.95 Vdc
Signature
Operating environment Supervisory current 1000 µA
Data line
Temperature 32 to 120°F (0 to 49°C) Alarm current 1000 µA
Humidity 0 to 93% RH, noncondensing at 90°F Note: Output circuits are power-limited when the riser circuit is power-limited.
(32°C)
iO500 Control Panel Signature Series smoke detectors
Compatible DACRs
Receiver Models Formats Loop Controller M Signature Series modules

Ademco 685 Contact ID Horn circuit

FBII CP220 Contact ID Strobe circuit


Osborne-Hoffman OH 2000 Contact ID M
SD Service Disconnect Station
Radionics D6600 Contact ID A Manual Abort Station
Silent Knight 9800 Contact ID MR Manual Release Station

Sur-Gard SG-MLR1, MLR2 Contact ID Fire Alarm Control Panel


First Alarm Output Relay

Auxiliary Releasing Module SD RELA-EOL Release Circuit1


Power Supply (SIGA-REL)
SD RELA-EOL Release Circuit2

A MR

For detailed specification and ordering information on the SIGA-REL, refer


to Data Sheet 85001-0531 -- Releasing Module.

Page 6 of 10 D ATA S H E E T 85005-0130


Not to be used for installation purposes. Issue 7.1
Specifications
Device loops 1 loop, expandable to 2, Class A or B, each loop Battery placement iO500 cabinets accommodate up to 18 A/H
supporting up to 250 device addresses batteries. Use a external cabinet for larger battery
NAC circuits 4 Class B or 2 Class A, 2.5 amps each sizes.
Power supply 6.0 A total, 2.5 A max. per circuit at 120/230 VAC Batteries Batteries must be sealed lead acid type only.
60 Hz Maximum charging capacity = 26 Ah.
5.0 A total at 230VAC 50 Hz, 2.5 A max. per Loop circuit Maximum loop resistance: 66 Ω. Maximum loop
circuit capacitance: 0.5 µF. Style 4, 6, and 7 wiring. 64
0.5 amps aux power isolators maximum.
NAC Operating 24 VDC. NAC minimum voltage: 19.5 VDC @ 20.4 SIGA-UM/SIGA- 1.5 mA (see the UL and ULC compatibility list for
voltage V battery voltage MAB for the maximum quantity of detectors per circuit)
Loop circuit 20 V peak-to-peak Compatibility ID 100
operating voltage Alarm contact Form C 24 VDC @ 1 A (resistive load)
SLC Primary power 120 VAC, 60 Hz, 230 VAC 50-60 Hz Trouble contact Form C 24 VDC @ 1 A (resistive load)
Aux Power 1 24 VDC nominal at 500 mA. A SMK module is Supervisory contact Form A 24 VDC @ 1 A (resistive load)
(Continuous circuit) required when using the SIGA-UM module to Environmental Temperature: 0 to 49°C (32 to 120°F).
support two-wire smoke detectors. Humidity: 0 to 93% RH, noncondensing
Aux Power 2 24 VDC nominal at 500 mA Terminal rating All terminals rated for 12 to 18 AWG (0.75 to 2.5 mm²)
(Resettable circuit) Serial Voltage: 2.55 V. Current: 30 mA max
Auxiliary output 19 to 25.7 VDC communications
Base panel Standby: 172 mA Remote annunciator 8 drops max, RS-485 Class A or B
current draw Alarm: 267 mA Input zones 32 max.
Panel History Log 1,000 events Agency Listing UL864, UL2017, CSFM, ULC and NYFD #6020,
FM approved

Ordering Information
Part Description
iO500 Intelligent Multi-Loop Analog Systems
iO500G 1 Loop system, 500 point capacity, 4 NACs, gray door, surface mount enclosure, 115 Vac, English.
iO500G-2 1 Loop system, 500 point capacity, 4 NACs, gray door, surface mount enclosure, 230 Vac, English.
iO500GC Canada only: 1 Loop system, 500 point capacity, 4 NACs, 16-zone LED display, grey door, surface mount, 115 Vac, English.
iO500G-F Canada only: 1 Loop system, 500 point capacity, 4 NACs, 16-zone LED display, grey door, surface mount, 115VAC, French.
iO500GD 1 Loop system, 500 point capacity, two-line dialer, 4 NACs, Gray door, surface mount enclosure, 115VAC transformer, English.
iO500R 1 Loop system, 500 point capacity, 4 NACs, red Door, surface mount enclosure, 115VAC transformer, English.
iO500R-2 1 Loop system, 500 point capacity, 4 NACs, red door, surface mount enclosure, 230VAC transformer, English.
iO500RD 1 Loop system, 500 point capacity, two-line dialer, 4 NACs, Red Door, surface mount enclosure, 115VAC transformer, English.
iO500G-SP 1 Loop system, 500 point capacity, 4 NACs, gray door, surface mount enclosure, 115vac, Spanish.
iO500G-2-SP 1 Loop system, 500 point capacity, 4 NACs, gray door, surface mount enclosure, 230vac, Spanish.
iO500G-PG 1 Loop system, 500 point capacity, 4 NACs, gray door, surface mount enclosure, 115vac, Portuguese.
iO500G-2-PG 1 Loop system, 500 point capacity, 4 NACs, gray door, surface mount enclosure,, 230vac, Portuguese.
SA-TRIM2 Flush mount trim, black

Replacement Electronics
500elec-iO Replacement electronics kit, complete motherboard and user interface, English
500elec-iO-SP Replacement electronics kit, complete motherboard and user interface, Spanish
500elec-iO-PG Replacement electronics kit, complete motherboard and user interface, Portuguese
500elec-iO-FR Replacement electronics kit, complete motherboard and user interface, Canadian French

Option Cards
SA-DACT Dual Line Dialer/Modem, supports Contact ID, mounts in cabinet on base plate.
SA-232 Serial Port (RS-232), for connection to printers & computers, mounts in cabinet to base plate
SA-ETH Ethernet Port, Slave, mounts in cabinet on base plate.
XAL250 Signature Loop Expansion Module. Adds second loop to iO500 systems, 250 point capacity. Mounts in cabinet on main board.
D16L-iO-2 LED Annunciator module, 16 X 2-LED zones (4 programmable for sup). Mounts in cabinet to right of LCD display for zones 17-32.
D16L-iO-1 LED Annunciator module, 16 X 2-LED zones (4 programmable for sup). Mounts in cabinet to left of LCD display for zones 1-16.
D8RY-iO-2 Canada only: LED Annunciator module, two LEDs per zone, 16 zones (4 alarm only, 8 supervisory only, 4 alarm or supervisory).
Mounts in cabinet to right of LCD display for zones 17-32.
D8RY-iO-1 Canada only: LED Annunciator module, two LEDs per zone, 16 zones (4 alarm only, 8 supervisory only, 4 alarm or supervisory).
Mounts in cabinet to left of LCD display for zones 1-16.

Page 7 of 10 D ATA S H E E T 85005-0130


Not to be used for installation purposes. Issue 7.1
Remote Annunciators (refer to Data Sheet 85005-0128)
LCD Remote Annunciators (mount to standard 4” square electrical box)
RLCD Remote Annunciator, 4X20 LCD & Common Indicators for displaying system status. Gray housing.
RLCD-R Remote Annunciator, 4X20 LCD & Common Indicators for displaying system status. Red housing.
RLCD-C Remote Annunciator, 4X20 LCD. Common controls and status indicators. Gray housing.
RLCD-CR Remote Annunciator, 4X20 LCD. Common controls and status indicators. Red housing.
RLCD-SP Remote Annunciator, 4X20 LCD. Common system status indicators. White housing. Spanish.
RLCD-PG Remote Annunciator, 4X20 LCD. Common system status indicators. White housing. Portuguese.
RLCD-C-SP Remote Annunciator, 4X20 LCD. Common controls and status indicators. White housing. Spanish.
RLCD-C-PG Remote Annunciator, 4X20 LCD. Common controls and status indicators. White housing. Portuguese.
RLED-C-SP Remote Annunciator, common controls and status indicators. 16 groups w/2 LEDs each for zone display. White housing. Spanish.
RLED-C-PG Remote Annunciator, common controls and status indicators. 16 groups w/2 LEDs each for zone display. White housing. Portuguese.
GCI Graphic Annunciator Driver Master for R-Series annunciators. Outputs for 32 LEDs, connection to common control switches and LEDs.
GCIX Graphic Annunciator Driver Expander for use with GCI Masters. Outputs for 48 LEDs, 24 switch inputs for R-Series annunciators.
For French common control, add suffix F to model number.
LED Remote Annunciators & Expander (mount to standard 4” square electrical box)
RLED-C Remote Annunciator. Common controls and status indicators with 16 X 2-LED groups for zone display. Gray housing.
RLED-CF Remote Annunciator. Common controls and status indicators with 16 X 2-LED groups for zone display. Gray housing, French.
RLED-CR Remote Annunciator. Common controls and status indicators with 16 X 2-LED groups for zone display. Red housing.
RLED24 Remote Annunciator Zone expander. 24 X 2-LED groups with custom label areas for display of alarm and trouble. Gray housing.
RLED24R Remote Annunciator Zone expander. 24 X 2-LED groups with custom label areas for display of alarm and trouble. Red housing.
Remote Annunciator Cabinets & Accessories
RA-ENC1 Remote Annunciator Enclosure, key locked with plexiglass window for one RLCD(C) or RLED(C).
RA-ENC2 Remote Annunciator Enclosure, key locked with plexiglass window with space for 2 of either RLCDx, RLEDx or RLED24.
RA-ENC3 Remote Annunciator Enclosure, key locked with plexiglass window with space for 3 of either RLCDx, RLEDx or RLED25.
RKEY Keyswitch, single gang, provides key operated enable or disable of common controls on RLCD or RLED units.
LSRA-SB Surface Mount Box - for R Series single units.

Programming Tools
iO-CU EST Series configuration and diagnostics utility.
260097 RS232 cable, 4 conductor, DB9 PC interface

Intelligent Analog Addressable Devices & Accessories


Part # Description Ship wt.

Intelligent Detectors & Bases


SIGA2-PHCOS Intelligent Multisensor Photoelectric/Heat Detector with carbon monoxide sensor
SIGA2-PHS Intelligent Multisensor Photoelectric/Heat Detector
SIGA2-PHSB Intelligent 4D Multisensor Detector (Black) - UL/ULC Listed
SIGA2-PCOS Intelligent Photoelectric Detector with carbon monoxide sensor
SIGA2-PS Intelligent Photoelectric Detector 0.4 (0.16)
SIGA2-HRS Intelligent combination fixed temperature/rate-of-rise heat detector
SIGA2-HFS Intelligent fixed temperature heat detector
SIGA2-HCOS Intelligent fixed temperature heat detector with CO sensor
SIGA2-COS Intelligent Carbon Monoxide Detector
SIGA-HFS Intelligent Fixed Temperature Heat Detector
SIGA-HRS Intelligent Fixed Temperature/Rate-of-Rise Heat Detector
SIGA-IPHS Intelligent 4D Multisensor Detector
SIGA-IPHSB Intelligent 4D Multisensor Detector (Black) 0.5 (0.23)
SIGA-PHS Intelligent 3D Multisensor Detector
SIGA-PS Intelligent Photoelectric Detector
SIGA-SD Intelligent Duct Detector
SIGA-SB Detector Mounting Base
SIGA-SB4 4-inch Detector Mounting Base c/w SIGA-TS Trim Skirt
SIGA-RB Detector Mounting Base w/Relay
SIGA-RB4 4-inch Detector Mounting Base /w Relay c/w SIGA-TS Trim Skirt 0.2 (0.09)
SIGA-IB Detector Mounting Base w/Fault Isolator
SIGA-IB4 4-inch Detector Mounting Base w/ Fault Isolator c/w SIGA-TS Trim Skirt
SIGA-LED Remote Alarm LED
SIGA-AB4G Audible (Sounder) Base 0.3 (0.15)

Page 8 of 10 D ATA S H E E T 85005-0130


Not to be used for installation purposes. Issue 7.1
SIGA-TS4 Trim Skirt (supplied with 4-inch bases) 0.1 (.04)
SIGA-AB4GT Audible (Sounder) Base for CO and Fire Detectors 0.3 (0.15)
SIGA-TCDR Temporal Pattern Generator 0.3 (0.15)

Modules
SIGA-CC1 Single Input Signal Module (Standard Mount) 0.5 (0.23)
SIGA-MCC1 Single Input Signal Module (UIO Mount) 0.18 (0.08)
SIGA-CC1S Synchronization Output Module (Standard Mount) 0.5 (0.23)
SIGA-MCC1S Synchronization Output Module (UIO Mount) 0.18 (0.08)
SIGA-CC2 Dual Input Signal Module (Standard Mount) 0.5 (0.23)
SIGA-MCC2 Dual Input Signal Module (UIO Mount) 0.18 (0.08)
SIGA-CR Control Relay Module (Standard Mount) 0.4 (0.15)
SIGA-MCR Control Relay Module (UIO Mount) 0.18 (0.08)
SIGA-CRR Polarity Reversal Relay Module (Standard Mount) 0.4 (0.15)
SIGA-MCRR Polarity Reversal Relay Module (UIO Mount) 0.18 (0.08)
SIGA-RM1 Riser Monitor Module (Standard Mount) 0.5 (0.23)
SIGA-MRM1 Riser Monitor Module (Plug-in) 0.18 (0.08)
SIGA-IO Input/Output Module (Standard Mount) 0.34 (0.15)
SIGA-MIO Input/Output Module (Plug-in) 0.22 (0.10)
SIGA-MAB Universal Class A/B Module (Plug-in) 0.18 (0.08)
SIGA-CT1 Single Input Module 0.4 (0.15)
SIGA-CT2 Dual Input Module 0.4 (0.15)
SIGA-MCT2 Dual Input Plug-in (UIO) Module 0.1 (0.05)
SIGA-IM Fault Isolator Module 0.5 (0.23)
SIGA-MM1 Monitor Module 0.4 (.15)
SIGA-WTM Waterflow/Tamper Module 0.4 (.15)
SMK Smoke Power Converter Module 0.4 (0.15)
SIGA-UIO2R Universal Module Board w/Riser Inputs - Two Module Positions 0.32 (0.15)
SIGA-UIO6R Universal Module Board w/Riser Inputs - Six Module Positions 0.62 (0.28)
SIGA-UIO6 Universal Module Board - Six Module Positions 0.56 (0.25)
SIGA-REL Analog addressable releasing module 0.5 (0.23)
276A-REL Manual releasing station (single-action). English markings, black text on yellow polycarbonate body. 1.0 (0.45)
278A-REL Manual releasing station (double-action). English markings, black text on yellow polycarbonate body. 1.0 (0.45)
RELA-ABT Manual Abort Station. English markings, black text on yellow polycarbonate body. 1.0 (0.45)
Service Disconnect Switch. One n/c contact and one n/o contact. English markings, white text on blue
RELA-SRV-1 1.0 (0.45)
polycarbonate body.
RELA-EOL Polarized end-of-line relay. English markings on stainless steel cover. 0.2 (0.1)

Accessories
GCI Graphic Annunciator Driver, provides outputs for common indicators and 32 alarm/supv zones as well as
inputs for common switches. Provided with a snap track for mounting in custom graphic enclosures.
CTM City Tie Module. Provides connection to a local energy fire alarm box. 0.6 (0.3)
RPM Reverse Polarity Module 3.0 (1.36)
BC-1 Battery Cabinet. 14.0" x 18.25" x 7.25". Holds 2 12V24A batteries. 50.0 (22.7)
BC-1R Battery Cabinet - Red. 14.0" x 18.25" x 7.25". Holds 2 12V24A batteries. 50.0 (22.7)
BC-1EQ Seismic hardening Kit for iO series panels. Includes battery hardening for BC-1 enclosure and components
to harden panel internal components. See note below.
MFC-A Multifunction Fire Cabinet, 8" x 14" x 3.5" - RED. 20.6 (9.4)
PT-1S System Printer - Desktop style. 36.6 (16.6)

Note:
For earthquake anchorage, including detailed mounting weights and center of gravity detail, please refer to Seismic Application Guide 3101676-EN.
Approval of panel anchorage to site structure may require local AHJ, structural, or civil engineer review.

Standby batteries must be mounted externally from fire panel in separately mounted BC-1 enclosure. Order BC-1 and BC-1EQ separately.

Page 9 of 10 D ATA S H E E T 85005-0130


Not to be used for installation purposes. Issue 7.1
Contact us...
Email: edwards.fire@fs.utc.com
Web: www.est-fire.com

EST is an EDWARDS brand.


1016 Corporate Park Drive
Mebane, NC 27302

In Canada, contact Chubb Edwards...


Email: inquiries@chubbedwards.com
Web: www.chubbedwards.com

© 2013 UTC Fire & Security Americas


Corporation, Inc. All rights reserved.
Specifications subject to change
without notice. Edwards is part of UTC
Climate, Controls & Security, a unit of
United Technologies Corporation.

11-04-14

Page 10 of 10 D ATA S H E E T 85005-0130


Not to be used for installation purposes. Issue 7.1