Sunteți pe pagina 1din 24

Inverter

MICROMASTER 430
3/2 Description

3/4 Circuit diagrams

3/6 Technical data

3/9 Selection and ordering data

3/10 Options

3/17 Dimension drawings

Siemens DA 51.2 · 2003/2004 3/1


MICROMASTER 430

Description

■ Applications ■ Main characteristics ■ Options (overview) ■ International standards


The MICROMASTER 430 in- ■ Easy, guided start-up ■ Line commutating chokes ■ The MICROMASTER 430
verter is suitable for a variety ■ Modular construction al- ■ Output chokes inverter complies with the
of variable-speed drive appli- lows maximum configura- ■ LC filter
requirements of the EU low-
cations. Its flexibility provides tion flexibility voltage guideline
■ Gland plates
for a wide spectrum of appli- ■ Six programmable isolated ■ The MICROMASTER 430
cations. It is especially suit- ■ Basic Operator Panel 2
digital inputs inverter has the > mark-
3 able for use with industrial
pumps and fans. The inverter ■ Two scaleable analog in-
puts (0 V to 10 V, 0 mA to
(BOP-2) for parameterizing
the inverter
ing
■ acc. to u and cu certified
is especially characterized by ■ Communication modules
20 mA) can also be used as ■ c-tick ●

its customer-oriented perfor- – PROFIBUS
mance and ease-of-use. It has a 7th/8th digital input
– DeviceNet Note:
more inputs and outputs than ■ Two programmable analog
the MICROMASTER 420, an outputs (0 mA to 20 mA) – CANopen See Appendix for standards.
optimized operator panel with ■ Three programmable relay ■ PC connection kits
manual/automatic switchover outputs (30 V DC/5 A resis- ■ Mounting kits for installing
and adapted software func- tive load; 250 V AC/2A in- the operator panels in the
tionality. ductive load) control cabinet doors
■ Low-noise motor operation ■ PC start-up tools execut-
■ Design thanks to high pulse fre- able under Windows 95/98
The MICROMASTER 430 in- quencies, adjustable (ob- and NT/2000/
verter has a modular design. serve derating if necessary) XP Professional.
■ Complete protection for ■ TIA integration with
The operator panels and com- motor and inverter Drive ES
munication modules can be
■ Control of up to three addi-
easily exchanged.
tional drives on the basis of
PID control (motor staging)
■ Operation of drive directly
on mains (with external by-
pass circuit)
■ Low-energy mode
■ Detects dry run of pumps
(belt failure detection).

3/2 Siemens DA 51.2 · 2003/2004


MICROMASTER 430

Description

■ Mechanical features ■ Performance features ■ Protection features


■ Modular design ■ Latest IGBT technology ■ High-grade internal PID ■ Overload capability
■ Operating temperature ■ Digital microprocessor controller for simple pro- 7.5 kW to 90 kW:
–10 °C to +40 °C control cess control Overload current 1.4 x rat-
(+14 °F to +104 °F) ■ Flux Current Control (FCC) ■ Programmable accelera- ed output current (i.e.
■ Compact housing as a re- for improved dynamic re- tion/deceleration times +140 % overload capabili-
sult of high power density sponse and optimized mo- from 0 s to 650 s ty) for 3 s, and 1.1 x rated
tor control ■ Ramp smoothing output current (i.e. 110 %
■ Easy cable connection, overload capability) for
mains and motor connec- ■ Linear V/f characteristic ■ Fast Current Limit (FCL) for 60 s, cycle time 300 s
tions are separated for opti- ■ Quadratic V/f characteristic trip-free operation 110 kW to 250 kW:
mum electromagnetic com- ■ Multipoint characteristic ■ Fast, repeatable digital in- Overload current 1.5 x rat-
patibility (programmable V/f charac- put response time ed output current (i.e.
■ Detachable operator teristic) ■ Fine adjustment using two 150 % overload capability)
panels ■ Flying restart high-resolution 10-bit ana- for 1 s, and 1.1 x rated out-
■ Screwless control terminal log inputs put current (i.e. 110 % over-
■ Slip compensation
strip on detachable I/O ■ Compound braking for con- load capability) for 59 s,
board. ■ Automatic restart following cycle time 300 s
mains failure or fault trolled rapid braking
■ Four skip frequencies ■ Overvoltage/undervoltage
■ Energy saving mode (stop-
■ Removable “Y” capacitor for protection
ping e.g. of a pump at low
use on IT systems (with ■ Inverter overtemperature
speeds)
non-grounded mains sup- protection
■ Motor staging (connection
and disconnection of addi- plies, the “Y” capacitor ■ Special direct connection
tional motors, use of invert- must be removed and an for PTC or KTY to protect
er as control drive in a output choke installed). the motor
pump cascade) ■ Earth fault protection
■ Manual/automatic mode ■ Short-circuit protection
■ Load torque monitoring ■ I2t motor thermal protection
(detects dry run of pumps) ■ Locked motor protection
■ Stall prevention
■ Parameter interlock

Siemens DA 51.2 · 2003/2004 3/3


MICROMASTER 430

Circuit diagrams

■ General circuit diagram


O p e r a to r p a n e l ( O p tio n )

3 8 0 to 4 8 0 V 3 A C
P E

F S 1

+ 1 0 V P E F o r a d d itio n a l d ig ita l in p u ts
B O P
1 S e r ia l L 1 , L 2 , L 3 (D IN 7 , D IN 8 ) e x te rn a l
P ro to c o l c o n n e c tio n s s h o u ld b e m a d e :
0 V
2
A IN 1 +
-> 4 , 7 k 9 A
3
1 1
A IN 1 - D
4 2 2

A IN 2 + A 3 1 0
1 0
D 4 1 1
A IN 2 - D IN 7 D IN 8
1 1
D IN 1
5 N o te s :
D IN 2 W h e n a n a n a lo g in p u t is
A C c o n fig u re d a s a d ig ita l in p u t
6
D IN 3 th e th re s h o ld v a lu e s a r e a s
O p to is o la tio n

fo llo w s :
7 D C
D IN 4 1 .7 5 V D C = o ff
3 .7 V D C = o n
8
D IN 5
A IN 1 : 0 V to 1 0 V , 0 m A to 2 0 m A
1 6 a n d -1 0 V to + 1 0 V
D IN 6 A IN 2 : 0 V to 1 0 V
1 7 a n d 0 m A to 2 0 m A
P N P O u tp u t + 2 4 V
( is o la te d )
o r 9
N P N O u tp u t 0 V
( is o la te d )
2 8
P T C A
3 M o to r
P T C /K T Y P T C B
1 4
A
D
1 5 C P U
A O U T 1 +
0 - 2 0 m A , A D C
1 2
m a x . 5 0 0 9 A O U T 1 - D
1 3
A C
A O U T 2 +
A
0 - 2 0 m A , 2 6
m a x . 5 0 0 9 A O U T 2 - D
2 7
R L 1
R L 1 - C 6 0 H z
2 0 N o t
R L 1 - B u s e d 5 0 H z
1 9 1 2
R L 1 - A D IP S w itc h e s
1 8
O u tp u t re la y R L 2 (o n C o n tro l B o a rd )
c o n ta c ts
2 5 0 V A C , m a x . 2 A R L 2 - C
2 2
( in d u c tiv e lo a d ) R L 2 - B
3 0 V D C , m a x . 5 A 2 1
( r e s is tiv e lo a d ) A IN 1 A IN 2
R L 3
0 - 2 0 m A
R L 3 - C
2 5 0 - 1 0 V
R L 3 - B
2 4 1 2
R L 3 - A D IP S w itc h e s
2 3 (o n I/O B o a rd )
W h e n a c o m m u n ic a tio n s
P +
m o d u le is c o n n e c te d , 2 9 R S 4 8 5
th e s e r ia l in te r fa c e
N -
d o e s n 't w o rk . 3 0 P E U , V , W
A D A 5 1 -5 0 4 8 c

M
3 ~

3/4 Siemens DA 51.2 · 2003/2004


MICROMASTER 430

Circuit diagrams

■ Terminal connection diagram

Example, frame size C

View A

Mains connections

Motor connections

View A
AIN1 AIN2 RL1-A RL1-B RL1-C RL2-B RL2-C RL3-A RL3-B RL3-C

A DA51-5025
S1 S2
18 19 20 21 22 23 24 25

DIP Switches:
0 mA to 20 mA
or Output relay contacts
0 V to 10 V
3
AOUT1+ AOUT1- PTC PTC DIN5 DIN6 AOUT2+ AOUT2- PE P+ N-
A B 0V

12 13 14 18
15 16 17 26 27 28 29 30

NPN *)

Analog output 1 Digital inputs Analog output 2 RS-485


(USS-protocol)

(DIN7) (DIN8)
+10 V 0V AIN1+ AIN1- DIN1 DIN2 DIN3 DIN4 +24 V AIN2+ AIN2-

1 2 3 18
4 5 6 7 8 9 10 11

PNP *)

Voltage Analog input 1 Digital inputs Analog input 2


supply 10 V

*) PNP or NPN possible

Siemens DA 51.2 · 2003/2004 3/5


MICROMASTER 430

Technical data

■ MICROMASTER 430 inverter


Mains voltage and 3 AC 380 V to 480 V ± 10% 7.5 kW to 250 kW (variable torque)
Power ranges
Power frequency 47 Hz to 63 Hz
Output frequency 7.5 kW to 90 kW 0 Hz to 650 Hz
110 kW to 250 kW 0 Hz to 267 Hz
Power factor ˜ 0.95
Inverter efficiency
7.5 kW to 90 kW 96 % to 97 %
110 kW to 250 kW 97 % to 98 %
Overload capability 7.5 kW to 90 kW Overload current 1.4 x rated output current (i.e. +140 % overload capability) for 3 s, and
1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s
110 kW to 250 kW Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 1 s and
1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s
Inrush current Less than rated input current
Control method Linear V/f characteristic; quadratic V/f characteristic; multipoint characteristic
(programmable V/f characteristic); flux current control (FCC), energy saving mode
Pulse frequency 7.5 kW to 90 kW 4 kHz (standard)
2 kHz to 16 kHz (in 2 kHz steps)
110 kW to 250 kW 2 kHz (standard)
2 kHz to 4 kHz (in 2 kHz steps)
Fixed frequencies 15, programmable
Skip frequency ranges 4, programmable
Setpoint resolution 0.01 Hz digital
0.01 Hz serial
10 bit analog
Digital inputs 6 fully programmable isolated digital inputs; switchable PNP/NPN
Analog inputs 2 programmable analog inputs
• 0 V to 10 V, 0 mA to 20 mA and –10 V to +10 V (AIN1)
• 0 V to 10 V and 0 mA to 20 mA (AIN2)
• both can be used as 7th/8th digital input
Relay outputs 3, programmable, 30 V DC/5 A (resistive load); 250 V AC/2A (inductive load)
Analog outputs 2, programmable (0/4 mA to 20 mA)
Serial interfaces RS-485, optional RS-232
Motor cable length 7.5 kW to 90 kW
without output choke max. 50 m (shielded)
max. 100 m (unshielded)

3 without output choke see variant dependent options


110 kW to 250 kW
without output choke max. 100 m (shielded)
max. 150 m (unshielded)
with output choke Available soon
Electromagnetic compatibility
7.5 kW to 90 kW Inverter with internal filter Class A available
For inverters without filter
7.5 kW to 15 kW EMC filter, Class B to EN 55 011 available as an option
18.5 kW to 90 kW EMC filter, Class B from Schaffner available as an option
110 kW to 250 kW EMC filter, Class A available as an option
Braking DC braking, compound braking
Degree of protection IP20
Operating temperature range
7.5 kW to 90 kW –10 °C to +40 °C (+14 °F to +104 °F)
110 kW to 250 kW 0 °C to +40 °C (+32 °F to +104 °F)
Storage temperature –40 °C to +70 °C (–40 °F to +158 °F)
Relative humidity 95 % (non-condensing)
Installation altitude 7.5 kW to 90 kW Up to 1000 m above sea level without derating
110 kW to 250 kW Up to 2000 m above sea level without derating
Protection features for undervoltage, overvoltage, overload, earth faults, short-circuits, stall prevention, locked motor protection,
motor overtemperature, inverter overtemperature, parameter change protection
Conformity with standards
7.5 kW to 90 kW u, cu, >, c-tick ● ✔
110 kW to 250 kW u available soon, cu available soon, >
> marking Conformity with low-voltage directive 73/23/EEC
Dimensions and weights Frame size (FS) H x W x D (mm) Weight, approx. (kg)
(without options) C 245 x 185 x 195 5.7
D 520 x 275 x 245 17
E 650 x 275 x 245 22
F without filter 850 x 350 x 320 56
F with filter 1150 x 350 x 320 75
FX 1400 x 326 x 356 116
GX 1533 x 326 x 545 176

3/6 Siemens DA 51.2 · 2003/2004


MICROMASTER 430

Technical data

■ Derating data
Pulse frequency

Output Rated output current in A


(for 3 AC 400 V) for a pulse frequency of
kW 2 kHz 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz 14 kHz 16 kHz
7.5 19.0 19.0 17.1 15.2 13.3 11.4 9.5 7.6
11.0 26.0 26.0 24.7 23.4 20.8 18.2 15.6 13.0
15.0 32.0 32.0 28.8 25.6 22.4 19.2 16.0 12.8
18.5 38.0 38.0 36.1 34.2 30.4 26.6 22.8 19.0
22 45.0 45.0 40.5 36.0 31.5 27.0 22.5 18.0
30 62.0 62.0 55.8 49.6 43.4 37.2 31.0 24.8
37 75.0 75.0 71.3 67.5 60.0 52.5 45.0 37.5
45 90.0 90.0 81.0 72.0 63.0 54.0 45.0 36.0
55 110.0 110.0 93.5 77.0 63.3 49.5 41.3 33.0
75 145.0 145.0 123.3 101.5 83.4 65.3 54.4 43.5
90 178.0 178.0 138.0 97.9 84.6 71.2 62.3 53.4
110 205.0 180.4 – – – – – –
132 250.0 220.0 – – – – – –
160 302.0 265.8 – – – – – –
200 370.0 325.6 – – – – – –
250 477.0 419.8 – – – – – –

Operating temperature

Inverter 7.5 kW to 90 kW Inverter 110 kW to 250 kW


G_DA51_EN_05045b A D A 5 1 -5 0 4 7 a

100 1 0 0
Rated output current

R a te d o u tp u t c u rre n t

% 8 5
80 8 0
%
60 6 0

40 4 0

20 2 0 3
0 0
-10 0 10 20 30 40 °C 50 0 1 0 2 0 3 0 4 0 4 5 °C 5 5
Operating temperature O p e r a tin g te m p e r a tu r e

Siemens DA 51.2 · 2003/2004 3/7


MICROMASTER 430

Technical data

■ Derating data (continued)


Installation height above sea level

Permissible output current


in % of the rated output current
Inverter 7.5 kW to 90 kW Inverter 110 kW to 250 kW
ADA51-5018c ADA51-5046

100 100
Rated output current

Rated output current


% 85
80 80
%
60 60

40 40

20 20

0 0
0 1000 2000 3000 m 4000 0 1000 2000 3000 m 4000
Operational altitude Operational altitude

Permissible mains voltage


in % of the max. possible mains voltage
Inverter 7.5 kW to 90 kW Inverter 110 kW to 250 kW
ADA51-5019b ADA51-5019b

100 100
Mains voltage
Mains voltage

% %
80 80
77 77
60 60

40 40

20 20

0 0
0 1000 2000 3000 m 4000 0 1000 2000 3000 m 4000
Operational altitude Operational altitude

3/8 Siemens DA 51.2 · 2003/2004


MICROMASTER 430

Selection and ordering data

■ MICROMASTER 430 inverter


Output Rated input Rated output Frame size Order No.
current current
MICROMASTER 430 MICROMASTER 430
without filter 4) with internal filter
kW hp A A (FS) Class A 3)

Mains operating voltage 3 AC 380 V to 480 V


7.5 10 20.2 1) 19 C 6SE6430-2UD27-5CA0 6SE6430-2AD27-5CA0
11.0 15 29.0 1) 26 C 6SE6430-2UD31-1CA0 6SE6430-2AD31-1CA0
15.0 20 39.0 1) 32 C 6SE6430-2UD31-5CA0 6SE6430-2AD31-5CA0
18.5 25 45.2 1) 38 D 6SE6430-2UD31-8DA0 6SE6430-2AD31-8DA0
22 30 54.7 1) 45 D 6SE6430-2UD32-2DA0 6SE6430-2AD32-2DA0
30 40 74.8 1) 62 D 6SE6430-2UD33-0DA0 6SE6430-2AD33-0DA0
37 50 91.0 1) 75 E 6SE6430-2UD33-7EA0 6SE6430-2AD33-7EA0
45 60 111.0 1) 90 E 6SE6430-2UD34-5EA0 6SE6430-2AD34-5EA0
55 75 143.0 1) 110 F 6SE6430-2UD35-5FA0 6SE6430-2AD35-5FA0
75 100 190.0 1) 145 F 6SE6430-2UD37-5FA0 6SE6430-2AD37-5FA0
90 120 223.0 1) 178 F 6SE6430-2UD38-8FA0 6SE6430-2AD38-8FA0
110 150 204.5 2) 205 FX 6SE6430-2UD41-1FA0 –
132 200 244.5 2) 250 FX 6SE6430-2UD41-3FA0 –
160 250 296.4 2) 302 GX 6SE6430-2UD41-6GA0 –
200 300 354.0 2) 370 GX 6SE6430-2UD42-0GA0 –
250 350 442.0 2) 477 GX 6SE6430-2UD42-5GA0 –

See Appendix for note on or-


dering.
■ Motors for
MICROMASTER 430
All MICROMASTER 430 invert- Catalog M 11 contains selec-
ers are supplied with a Status tion and ordering data for mo-
Display Panel (SDP). A BOP-2 tors which are particularly suit-
or other options have to be able for operation with the
ordered separately (see MICROMASTER 430 inverters
Pages 3/11 to 3/13). (see Appendix for overview).
This catalog is suitable for IEC
motors. For motors according
3
to US standards (NEMA)
please refer to:
http://www.sea.siemens.com/
motors

1) Supplementary conditions: If a line commutating choke is 2) Supplementary conditions: 3) Use of MICROMASTER invert-
Input current at rated operating used, the specified values at Input current at rated operating ers with internal filter is not per-
point, applicable at short-cir- 380 V to 480 V are reduced to point, applicable at short-cir- missible on non-grounded
cuit voltage of the supply between 70% and 80% cuit voltage of the supply mains supplies.
USC = 1 % with reference to the USC $ 2.33 % with reference to
4) Generally suited to heavy
inverter rated power and rated the inverter rated power and
industrial applications. For
mains operating voltage of rated mains voltage of 400 V.
details please refer to Appen-
400 V without a line commutat-
dix on page A/4.
ing choke.

Siemens DA 51.2 · 2003/2004 3/9


MICROMASTER 430
Options
Variant dependent options

■ Overview
EMC filter, Class A 50 mA. The exact values de- • Frame sizes D to F: This means that the inverters
pend on the design, environ- The LC filters, frame sizes D with an output power
All 7.5 kW to 90 kW inverters
ment and cable lengths. Inter- to F, are designed for ˜ 0.75 kW comply with the
are supplied with an internal
ference-free operation with mounting upright in the con- EN 61 000-3-2 standard.
filter Class A.
residual current operated de- trol cabinet. Due to leakage
For inverters 110 kW to
vices with a trigger value of flux lines caused by physical Output choke
250 kW, EMC filters Class A
30 mA cannot be guaranteed. sources, a minimum dis-
are available. In this perfor- Output chokes can be sup-
tance of 50 mm to adjacent
mance range, the EMC filters However, operation with resid- plied for reducing the capaci-
modules and metal parts is
are only permitted to be used ual current operated devices tive compensation currents
recommended.
in combination with a line with a trigger value of 300 mA and dV/dt in the case of motor
commutating choke. is possible. Please refer to the Please note when using cables >50 m (shielded) or
Instruction Manual for details. LC filters: > 100 m (unshielded).
The requirements are fulfilled
using shielded cables with a • Only V/f, FCC control per- For max. permissible cable
LC filter
max. length of 25 m. missible lengths, see Technical Data.
The LC filter limits the rate of • Increased inverter load: ap-
EMC filter, Class B rise of voltage and the capac- prox. 10 % to 15 % Gland plate
itive charge/discharge cur- • Operation only permissible
Available for inverters 7.5 kW Gland plates are available for
rents which usually occur with with 4 kHz pulse frequency
to 15 kW with an internal Class inverters of frame size C. In
inverter operation. This means • The output frequency is lim-
A EMC filter. frame sizes D, E and F, the
that much longer shielded mo- ited to 150 Hz.
gland plates are integrated.
The requirements are fulfilled tor cables are possible when
using shielded cables with a using LC filters and the ser- Line commutating choke The gland plate facilitates the
max. length of 25 m. vice life of the motor achieves shield connection of power
Line commutating chokes are
values similar to those with di- and control cables and thus
For inverters 18.5 kW to 90 kW used to smooth voltage peaks
rect mains operation. ensure optimum EMC perfor-
without filters, EMC filters of or to bridge commutating
mance.
Class B from Schaffner can be The LC filters can be used for dips.
used. all MICROMASTER 430 invert- In addition, line commutating
ers of frame sizes C to F. chokes reduce the effects of
The requirements are fulfilled
harmonics on the inverter and
using shielded cables with a • Frame size C:
the power supply. If the line
max. length of 25 m to 50 m Only one footprint compo-
impedance is < 1 %, a line
(depending on the type, de- nent is permissible for frame
commutating choke must be
tails on request). size C. If a line choke and LC
used in order to reduce the
filter are used, the line choke
3 With this filter, the inverter
complies with the emission
must be located on the left of
current peaks.
the inverter. Required spac- No limits are currently defined
standard EN 55 011, Class B.
ing: 75 mm. in the EN 61 000-3-2 standard
Leakage currents: for professionally used devic-
es with a connected load
The leakage currents of the in-
> 1 kW.
verters with/without filter (inter-
nal/external) may exceed
30 mA. Typical values in prac-
tice are between 10 mA and

3/10 Siemens DA 51.2 · 2003/2004


MICROMASTER 430
Options
Variant dependent options

■ Technical data
LC filter

Mains voltage 3 AC 380 V to 480 V


Current at (40 °C / 50 °C)
For frame size C (7.5 to 15 kW) 32.6 A/ 29.7 A
For frame size D (18.5 kW) 38.8 A/ 32 A
For frame size D (22 kW) 45.9 A/ 38 A
For frame size D (30 kW) 63.2 A/ 45 A
For frame size E (37 kW) 76.5 A/ 62 A
For frame size E (45 kW) 112.2 A/ 90 A
For frame size F (55 kW) 112.2 A/ 90 A
For frame size F (75 kW) 147.9 A/110 A
For frame size F (90 kW) 181.6 A/145 A
Limiting of motor overvoltage ˆ 1078 V
dV/dt limiting ˆ 500 V/ms
Pulse frequency 4 kHz
Max. motor frequency 150 Hz
Max. permissible motor cable lengths Shielded 200 m
Unshielded 300 m
Insulation strength Overvoltage category III to VDE 0110
Electromagnetic compatibility Up to 200 m motor cable length with emissions to Class A according to EN 55 011 in conjunc-
tion with filtered inverters and unshielded cables
Conformity CE according to the low-voltage directive 73/23/EEC
Approvals UL available soon
Strain resistance EN 60 068-2-31
Humidity 95 % humidity, non-condensing
Degree of protection Frame size C IP20 (to EN 60 529)
Frame sizes D to F IP00 / IP20 (to EN 60 529 with terminal covers)
Insulation class H (180 °C)
Temperature range Operation –10 °C to +40 °C (+14 °F to +104 °F) 100 % Pn
to +50 °C (to +122 °F) 80 % Pn
Storage –25 °C to +70 °C (–13 °F to +158 °F)
Installation altitude Frame size C Up to 2000 m: 100 % Pn
2000 to 4000 m: 62.5 % Pn
Frame sizes D to F to 1000 m: 100 % Pn
1000 to 4000 m: 12.5 % derating for each 1000 m
Mounting position
Free space
Vertical
100 mm 3
100 mm
100 mm
Connection system Input, litz wire or terminal 1U1, 1V1, 1W1
Output, terminals 1U2, 1V2, 1W2
Torque for Terminal cross-section Torque
conductor connections Frame size C – 1.5 Nm to 1.8 Nm
Frame sizes D to F 16 mm2 2.0 Nm to 4.0 Nm
35 mm2 2.5 Nm to 5.0 Nm
50 mm2 3.0 Nm to 6.0 Nm
95 mm2 6.0 Nm to 12.0 Nm
150 mm2 10.0 Nm to 20.0 Nm
Weight, approx. for frame size C 29 kg
for frame size D 21 kg to 34 kg
for frame size E 49.5 kg to 67 kg
for frame size F 67 kg to 77.5 kg

Max. permissible cable lengths from the motor to the inverter when using output chokes
The following table shows the
maximum permissible cable
lengths from the motor to the
inverter when using output
chokes.
Frame size Output choke Max. permissible motor cable lengths (shielded/unshielded)
for a mains voltage of
(FS) Type 380 V to 400 V ± 10 % 401 V to 480 V ± 10 %
C 6SE6400-3TC03-2CD3 200 m/300 m 100 m/150 m
D to F 6SE6400-3TC . . -. . D0 200 m/300 m 200 m/300 m
FX/GX Available soon

Siemens DA 51.2 · 2003/2004 3/11


MICROMASTER 430
Options
Variant dependent options

■ Selection and ordering data


The options listed here (filters, The inverter and the associat- All options are certified to l Use in America requires u-listed
chokes, gland plates, fuses ed options have the same volt- u, except fuses. fuses such as the Class NON
and circuit-breakers) must be age ratings. The 3NE1 fuses are u-listed range from Bussmann.
selected to match the inverter. (equivalent to U).

Mains voltage Output Inverter Order No. of the options


kW hp without filter EMC filter, Class A EMC filter, Class B LC filter
3 AC 380 V to 480 V 7.5 10 6SE6430-2UD27-5CA0 – – 6SE6400-3TD03-2CD0
11.0 15 6SE6430-2UD31-1CA0 – –
15.0 20 6SE6430-2UD31-5CA0 – –
18.5 25 6SE6430-2UD31-8DA0 – EMC filter, Class B, 6SE6400-3TD03-7DD0
22 30 6SE6430-2UD32-2DA0 – available from Schaffner 6SE6400-3TD04-8DD0
30 40 6SE6430-2UD33-0DA0 – 6SE6400-3TD06-1DD0
37 50 6SE6430-2UD33-7EA0 – 6SE6400-3TD07-2ED0
45 60 6SE6430-2UD34-5EA0 – 6SE6400-3TD11-5FD0
55 75 6SE6430-2UD35-5FA0 –
75 100 6SE6430-2UD37-5FA0 – 6SE6400-3TD15-0FD0
90 120 6SE6430-2UD38-8FA0 – 6SE6400-3TD18-0FD0
110 150 6SE6430-2UD41-1FA0 6SL3000-0BE32-5AA0 *) – Available soon
132 200 6SE6430-2UD41-3FA0 6SL3000-0BE34-4AA0 *) –
160 250 6SE6430-2UD41-6GA0 –
*) Must be used in com-
bination with a line 200 300 6SE6430-2UD42-0GA0 –
commutating choke. 250 350 6SE6430-2UD42-5GA0 6SL3000-0BE36-0AA0 *) –

Mains voltage Output Inverter Order No. of the options


without filter Line commutating Output choke Gland plate
kW hp choke
3 AC 380 V to 480 V 7.5 10 6SE6430-2UD27-5CA0 6SE6400-3CC02-2CD3 6SE6400-3TC03-2CD3 6SE6400-0GP00-0CA0
11.0 15 6SE6430-2UD31-1CA0
15.0 20 6SE6430-2UD31-5CA0 6SE6400-3CC03-5CD3
18.5 25 6SE6430-2UD31-8DA0 6SE6400-3CC04-4DD0 6SE6400-3TC05-4DD0 Integrated as standard
22 30 6SE6430-2UD32-2DA0 6SE6400-3TC03-8DD0
30 40 6SE6430-2UD33-0DA0 6SE6400-3CC05-2DD0 6SE6400-3TC05-4DD0
37 50 6SE6430-2UD33-7EA0 6SE6400-3CC08-3ED0 6SE6400-3TC08-0ED0
3 45
55
60
75
6SE6430-2UD34-5EA0
6SE6430-2UD35-5FA0 6SE6400-3CC11-2FD0
6SE6400-3TC07-5ED0
6SE6400-3TC14-5FD0
75 100 6SE6430-2UD37-5FA0 6SE6400-3TC15-4FD0
90 120 6SE6430-2UD38-8FA0 6SE6400-3CC11-7FD0 6SE6400-3TC14-5FD0
110 150 6SE6430-2UD41-1FA0 6SL3000-0CE32-3AA0 Available soon
132 200 6SE6430-2UD41-3FA0 6SL3000-0CE32-8AA0
160 250 6SE6430-2UD41-6GA0 6SL3000-0CE33-3AA0
200 300 6SE6430-2UD42-0GA0 6SL3000-0CE35-1AA0
250 350 6SE6430-2UD42-5GA0

Mains voltage Output Inverter Order No. of the options


without filter Fuses (see Catalog LV 10) Circuit-breaker
kW hp 3NA3 3NE1 (U) (see Catalog LV 10)
3 AC 380 V to 480 V 7.5 10 6SE6430-2UD27-5CA0 3NA3807 l 3RV1031-4EA10
11.0 15 6SE6430-2UD31-1CA0 3NA3812 3RV1031-4FA10
15.0 20 6SE6430-2UD31-5CA0 3NA3814 3RV1031-4HA10
18.5 25 6SE6430-2UD31-8DA0 3NA3820 3NE1817-0 3RV1042-4KA10
22 30 6SE6430-2UD32-2DA0 3NA3822 3NE1818-0
30 40 6SE6430-2UD33-0DA0 3NA3824 3NE1820-0 3RV1042-4MA10
37 50 6SE6430-2UD33-7EA0 3NA3830 3NE1021-0 3VL1712- . DD33- . . . .
45 60 6SE6430-2UD34-5EA0 3NA3832 3NE1022-0 3VL1716- . DD33- . . . .
55 75 6SE6430-2UD35-5FA0 3NA3836 3NE1224-0 3VL3720- . DC36- . . . .
75 100 6SE6430-2UD37-5FA0 3NA3140 3NE1225-0 3VL3725- . DC36- . . . .
90 120 6SE6430-2UD38-8FA0 3NA3144 3NE1227-0 3VL4731- . DC36- . . . .
110 150 6SE6430-2UD41-1FA0 – On request
132 200 6SE6430-2UD41-3FA0 – 3NE1230-0
160 250 6SE6430-2UD41-6GA0 – 3NE1332-0
200 300 6SE6430-2UD42-0GA0 – 3NE1333-0
250 350 6SE6430-2UD42-5GA0 – 3NE1435-0

3/12 Siemens DA 51.2 · 2003/2004


MICROMASTER 430
Options
Variant dependent options

■ Selection and ordering data (continued)

Mains voltage Output Inverter Order No. of the options


with internal filter LC filter Line commutating Output choke
kW hp Class A choke
3 AC 380 V to 480 V 7.5 10 6SE6430-2AD27-5CA0 6SE6400-3TD03-2CD0 6SE6400-3CC02-2CD3 6SE6400-3TC03-2CD3
11.0 15 6SE6430-2AD31-1CA0
15.0 20 6SE6430-2AD31-5CA0 6SE6400-3CC03-5CD3
18.5 25 6SE6430-2AD31-8DA0 6SE6400-3TD03-7DD0 6SE6400-3CC04-4DD0 6SE6400-3TC05-4DD0
22 30 6SE6430-2AD32-2DA0 6SE6400-3TD04-8DD0 6SE6400-3TC03-8DD0
30 40 6SE6430-2AD33-0DA0 6SE6400-3TD06-1DD0 6SE6400-3CC05-2DD0 6SE6400-3TC05-4DD0
37 50 6SE6430-2AD33-7EA0 6SE6400-3TD07-2ED0 6SE6400-3CC08-3ED0 6SE6400-3TC08-0ED0
45 60 6SE6430-2AD34-5EA0 6SE6400-3TD11-5FD0 6SE6400-3TC07-5ED0
55 75 6SE6430-2AD35-5FA0 6SE6400-3CC11-2FD0 6SE6400-3TC14-5FD0
75 100 6SE6430-2AD37-5FA0 6SE6400-3TD15-0FD0 6SE6400-3TC15-4FD0
90 120 6SE6430-2AD38-8FA0 6SE6400-3TD18-0FD0 6SE6400-3CC11-7FD0 6SE6400-3TC14-5FD0

Mains voltage Output Inverter Order No. of the options


with internal filter Additional EMC filter, Gland plate
Class A Class B
kW hp
3 AC 380 V to 480 V 7.5 10 6SE6430-2AD27-5CA0 6SE6400-2FS03-8CD0 6SE6400-0GP00-0CA0
11.0 15 6SE6430-2AD31-1CA0
15.0 20 6SE6430-2AD31-5CA0
18.5 25 6SE6430-2AD31-8DA0 An inverter without filter Integrated as standard
22 30 6SE6430-2AD32-2DA0 must be selected to sat-
isfy the EMC require-
30 40 6SE6430-2AD33-0DA0 ments of Class B. In
37 50 6SE6430-2AD33-7EA0 addition, an appropriate
EMC filter of Class B is
45 60 6SE6430-2AD34-5EA0
from Schaffner is
55 75 6SE6430-2AD35-5FA0 required.
75
90
100
120
6SE6430-2AD37-5FA0
6SE6430-2AD38-8FA0
3
Mains voltage Output Inverter with internal fil- Order No. of the options
ter Class A Fuses (see Catalog LV 10) Circuit-breaker
kW hp 3NA3 3NE1 (U) (see Catalog LV 10)
3 AC 380 V to 480 V 7.5 10 6SE6430-2AD27-5CA0 3NA3807 l 3RV1031-4EA10
11.0 15 6SE6430-2AD31-1CA0 3NA3812 3RV1031-4FA10
15.0 20 6SE6430-2AD31-5CA0 3NA3814 3RV1031-4HA10
18.5 25 6SE6430-2AD31-8DA0 3NA3820 3NE1817-0 3RV1042-4KA10
22 30 6SE6430-2AD32-2DA0 3NA3822 3NE1818-0
30 40 6SE6430-2AD33-0DA0 3NA3824 3NE1820-0 3RV1042-4MA10
37 50 6SE6430-2AD33-7EA0 3NA3830 3NE1021-0 3VL1712- . DD33- . . . .
45 60 6SE6430-2AD34-5EA0 3NA3832 3NE1022-0 3VL1716- . DD33- . . . .
55 75 6SE6430-2AD35-5FA0 3NA3836 3NE1224-0 3VL3720- . DC36- . . . .
75 100 6SE6430-2AD37-5FA0 3NA3140 3NE1225-0 3VL3725- . DC36- . . . .
90 120 6SE6430-2AD38-8FA0 3NA3144 3NE1227-0 3VL4731- . DC36- . . . .
l Use in America
requires u-listed fuses
such as the Class
NON range from
Bussmann.

Siemens DA 51.2 · 2003/2004 3/13


MICROMASTER 430
Options
Variant independent options

■ Overview
Basic Operator Panel 2 PROFIBUS module CANopen module Start-up tools
(BOP-2)
For a complete PROFIBUS Using the CANopen commu- • STARTER
With the BOP-2, individual pa- connection with up to nications module, an inverter is a graphic start-up soft-
rameter settings can be made. ˆ12 Mbaud. Remote control can be linked to the CANopen ware for guided start-up for
Values and units are shown on of the inverter is possible with fieldbus system and remote MICROMASTER 410/420/
a 5-digit display. the PROFIBUS module. Re- control is then possible. 430/440 frequency inverters
mote control and operation at under Windows NT/2000/
Remote control and operation
the inverter can be combined XP Professional. Parameter
at the inverter can be com-
using an operator panel lists can be read out, al-
bined using an operator panel
plugged onto the PROFIBUS tered, stored, entered and
plugged onto the CANopen
module. The PROFIBUS mod- printed.
module.
ule can be supplied by an ex-
• DriveMonitor
ternal 24 V DC power supply The module is connected to
is a start-up software for list-
and is thus also active when the bus system through a
oriented programming of
the inverter is disconnected 9-pin Sub-D connector.
frequency inverters. This
from the power supply.
program executes under
Connection kit for
Connection by means of a Windows 95/98/NT/2000/
PC to inverter
9-pin Sub-D connector (avail- XP Professional.
able as an option). For controlling an inverter di-
Both programs are included
rectly from a PC if the appro-
Basic Operator Panel (BOP-2) on the Docu CD which is pro-
DeviceNet module priate software has been in-
vided with every inverter.
stalled (e.g. STARTER).
A BOP-2 can be used for sev- For networking the inverters to
Isolated RS-232 adapter mod-
eral inverters. It can be direct- the DeviceNet fieldbus system
ule for reliable point-to-point
ly mounted on the inverter or in widely used on the American
connection to a PC. Includes a
a control cabinet door using a market. A maximum transmis-
Sub-D connector and an
mounting kit. sion rate of 500 kbaud is pos-
RS-232 standard cable (3 m).
sible. Remote control of the in-
verter is possible with the
Operator panel door mount-
DeviceNet module.
ing kit for single inverter
Remote control and operation
For mounting an operator pan-
at the inverter can be com-
el BOP-2 in a control cabinet
bined using an operator panel
door. Degree of protection
plugged onto the DeviceNet
3 module.
IP56. Contains a cable adapt-
er module with screwless ter- 1) A shielded cable of type
The connection to the minals for use with user’s own Belden 8132 (28 AWG) is
DeviceNet bus system is RS-232 cables 1). recommended.
The maximum cable length is
made using a 5-pin connector 5 m for RS-232.
with terminal strip.

■ Selection and ordering data


The options listed here are
suitable for all
MICROMASTER 430 inverters.

Options Order No.


Basic Operator Panel 2 (BOP-2) 6SE6400-0BE00-0AA0
PROFIBUS module 6SE6400-1PB00-0AA0
DeviceNet module 6SE6400-1DN00-0AA0
CANopen module 6SE6400-1CB00-0AA0
RS485/PROFIBUS bus connector 6GK1500-0FC00
Connection kit for PC to inverter 6SE6400-1PC00-0AA0
Operator panel door mounting kit for single inverter 6SE6400-0PM00-0AA0

3/14 Siemens DA 51.2 · 2003/2004


MICROMASTER 430
Options
Variant independent options

■ Technical data of the communication modules


PROFIBUS module DeviceNet module
6SE6400-1PB00-0AA0 6SE6400-1DN00-0AA0

Size (height x width x depth) 161 mm x 73 mm x 46 mm


Degree of protection IP20
Degree of pollution 2 to IEC 60 664-1 (DIN VDE 0110/T1), no condensation permitted during operation
Strain resistance to IEC 60 068-2-6 (if module is installed correctly)
• Stationary Deflection 0.15 mm in the frequency range of 10 Hz to 58 Hz
Acceleration 19.6 m/s2 in the frequency range of 58 Hz to 500 Hz
• Transport Deflection 3.5 mm in the frequency range of 5 Hz to 9 Hz
Acceleration 9.8 m/s2 in the frequency range of 9 Hz to 500 Hz
Climatic category (during operation) 3K3 to IEC 60 721-3-3
Cooling method Natural air cooling
Permissible ambient or cooling agent temperature
• Operation –10 °C to +50 °C (+14 °F to +122 °F)
• Storage and transport –25 °C to +70 °C (–13 °F to +158 °F)
Relative humidity
(permissible humidity rating)
• Operation
• Storage and transport
ˆ 85 % (non-condensing)
ˆ 95 %
3
Electromagnetic compatibility Emission to EN 55 011 (1991) Class A
Interference to IEC 60 801-3 and EN 61 000-4-3
Power supply 6.5 V ± 5 %, max. 300 mA, 6.5 V ± 5 %, max. 300 mA
internal from inverter or internal from inverter or
24 V ± 10 %, max. 350 mA, external 24 V, max. 60 mA from DeviceNet-Bus
Output voltage 5 V ± 10 %, max. 100 mA, –
galvanically isolated supply
• for terminating the serial interface bus or
• for supplying the OLP (Optical Link Plug)
Data transmission rate max. 12 Mbaud 125, 250 and 500 Kbaud

Siemens DA 51.2 · 2003/2004 3/15


MICROMASTER 430
Options
Variant independent options

■ Technical data of the communication modules (continued)


CANopen module
6SE6400-1CB00-0AA0

Size (height x width x depth) 161 mm x 73 mm x 46 mm


Degree of protection IP20
Degree of pollution 2 to IEC 60 664-1 (DIN VDE 0110/T1), no condensation permitted during operation
Strain resistance to IEC 60 068-2-6 (if module is installed correctly)
• Stationary Deflection 0.15 mm in the frequency range of 10 Hz to 58 Hz
Acceleration 19.6 m/s2 in the frequency range of 58 Hz to 500 Hz
• Transport Deflection 3.5 mm in the frequency range of 5 Hz to 9 Hz
Acceleration 9.8 m/s2 in the frequency range of 9 Hz to 500 Hz
Climatic category (during operation) 3K3 to IEC 60 721-3-3
Cooling method Natural air cooling
Permissible ambient or cooling agent temperature
• Operation –10 °C to +50 °C (+14 °F to +122 °F)
• Storage –40 °C to +70 °C (–40 °F to +158 °F)
• Transport –25 °C to +70 °C (–13 °F to +158 °F)
Relative humidity

3 (permissible humidity rating)


• Operation
• Storage and transport
ˆ 85 % (non-condensing)
ˆ 95 %
Power supply The CAN bus is supplied from the inverter power supply
Data transmission rate 10, 20, 50, 125, 250, 500, 800 Kbaud and 1 Mbaud

Documentation

■ Selection and ordering data


Type of documentation Language Order No.
Docu pack, Multilanguage 6SE6400-5AE00-1AP0
supplied with each inverter,
containing CD-ROM 1) and Getting
Started Guide 2)
(paper version)
Operating instructions2) German 6SE6400-5AE00-0AP0
(paper version) English 6SE6400-5AE00-0BP0
French 6SE6400-5AE00-0DP0
Italian 6SE6400-5AE00-0CP0
Spanish 6SE6400-5AE00-0EP0
Parameter list 2) German 6SE6400-5AF00-0AP0
(paper version) English 6SE6400-5AF00-0BP0
French 6SE6400-5AF00-0DP0
Italian 6SE6400-5AF00-0CP0
Spanish 6SE6400-5AF00-0EP0

1) The CD-ROM contains operat- and DriveMonitor, multilan- 2) Available on Internet at


ing instructions, parameter list, guage http://www.siemens.com/
commissioning tools STARTER micromaster

3/16 Siemens DA 51.2 · 2003/2004


MICROMASTER 430

Dimension drawings

■ MICROMASTER 430 inverter


Frame size 3 AC 380 V to 480 V
C 7.5 kW to 15 kW
D 18.5 kW to 30 kW
E 37 kW to 45 kW

Drill pattern

204 (8.03)

ADA51-5009b
245 (9.65)

309 (12.16)
ADA51-5002d

174 (6.85)
Fixing with
(7 195
8)

4 x M5 bolts
.6

4 x M5 nuts
185 (7.28) 4 x M5 washers
Inverter frame size C Tightening torque with washers fitted:
3.0 Nm
Inverter frame size C
Ventilation clearance required at top with gland plate
and bottom: 100 mm

Drill pattern

Drill pattern
3
616.4 (24.27)
650 (25.59)
520 (20.47)

486 (19.13)

ADA51-5021b
ADA51-5020b

235 (9.25)
235 (9.25)
(9 245
5)
(9 245
5)

.6

Fixing with 275 (10.82) Fixing with


.6

275 (10.82) 4 x M8 bolts 4 x M8 bolts


Inverter frame size D 4 x M8 nuts Inverter frame size E 4 x M8 nuts
4 x M8 washers 4 x M8 washers
Tightening torque with Tightening torque with
washers fitted: 3.0 Nm washers fitted: 3.0 Nm
Ventilation clearance Ventilation clearance
required at top and bottom: required at top and bottom:
300 mm 300 mm

With the communication module, the mounting depth increases


for frame size C by 23 mm (0.91 inches). All dimensions in mm (values in brackets are in inches)

Siemens DA 51.2 · 2003/2004 3/17


MICROMASTER 430

Dimension drawings

■ MICROMASTER 430 inverter


Frame size 3 AC 380 V to 480 V
F 55 kW to 90 kW

Drill pattern

Drill pattern

1110 (43.70)
1150 (45.28)
850 (33.46)

810 (31.89)

ADA51-5023b
ADA51-5022b

3 300 (11.81) 300 (11.81)

Fixing with Fixing with


(1 320

(1 320
6)

6)

4 x M8 bolts 4 x M8 bolts
2.

2.

350 (13.78) 4 x M8 nuts 350 (13.78) 4 x M8 nuts


4 x M8 washers 4 x M8 washers
Inverter frame size F without filter Inverter frame size F with filter
Tightening torque with Tightening torque with
washers fitted: 3.0 Nm washers fitted: 3.0 Nm
Ventilation clearance Ventilation clearance
required at top and bottom: required at top and bottom:
350 mm 350 mm

All dimensions in mm (values in brackets are in inches)

3/18 Siemens DA 51.2 · 2003/2004


MICROMASTER 430

Dimension drawings

■ MICROMASTER 430 inverter


Frame size 3 AC 380 V to 480 V
FX 110 kW to 132 kW
GX 160 kW to 250 kW

Drill pattern

Drill pattern
125 125
(4.92) (4.92)

125 125
(4.92) (4.92)

1508 (59.37)
1533 (60.35)
1375 (54.13)
1400 (55.12)

G_DA51_EN_05075
G_DA51_EN_05074

125 125
(4.92) (4.92)
3
125 125
1. 5
)

(4.92) (4.92)
46
(2 54
4. 6
)
06
(1 35

Fixing with
326 Fixing with 326 6 x M8 bolts
(12.83) 6 x M8 bolts (12.83) 6 x M8 nuts
6 x M8 nuts 6 x M8 washers
Inverter frame size FX 6 x M8 washers Inverter frame size GX
Tightening torque
Tightening torque with washers
with washers fitted: 13.0 Nm
fitted: 13.0 Nm Ventilation clearance
Ventilation clearance required:
required: at top: 250 mm
at top: 250 mm at bottom: 150 mm
at bottom: 150 mm in front: 100 mm
in front: 100 mm

All dimensions in mm (values in brackets are in inches)

Siemens DA 51.2 · 2003/2004 3/19


MICROMASTER 430

Dimension drawings

■ EMC filter

38 185 (7.28)
(1.5) 156 (6.14)

4 x M5
219 (8.62)
232 (9.13)
204 (8.03)
245 (9.65)

ADA51-5012c

174 54 (2.13)
(6.85)

EMC filter for frame size C

b1
n4
b
c
n3
a
a1
G_DA51_XX_05103

EMC filter for inverter Dimensions Weight,


Class A approx.
Type Frame size a a1 b b1 c n3 n4 kg
6SL3000- (FS)
0BE32-5AA0 FX 270 360 200 240 116 210 220 12.3
(10.63) (14.17) (7.87) (9.45) (4.57) (8.27) (8.66)
0BE34-4AA0 FX/GX 270 360 200 240 116 210 220 12.3
(10.63) (14.17) (7.87) (9.45) (4.57) (8.27) (8.66)
0BE36-0AA0 GX 310 400 215 265 140 250 240 19.0
(12.2) (15.75) (8.46) (10.43) (5.51) (9.84) (9.45)

EMC filter for frame sizes FX and GX

All dimensions in mm (values in brackets are in inches)

3/20 Siemens DA 51.2 · 2003/2004


MICROMASTER 430

Dimension drawings

■ LC filter

140 185 (7.28) Drill pattern


(5.51)

174 (6.85)

320 (12.6)
335 (13.19)
382 (15.04)

G_DA51_EN_05078a

G_DA51_EN_05081
156 (6.14)

Fixing with M5 bolts

LC filter 6SE6400-3TD03-2CD0 for frame size C

b LC filter for inverter Dimensions


c Type Frame size
3
G_DA51_XX_05082

(FS)
a b c n1 n2
6SE6400-3TD03-7DD0 D 278 240 230 115 190
(10.94) (9.45) (9.06) (4.53) (7.48)
6SE6400-3TD04-8DD0 D 290 240 240 125 190
(11.42) (9.45) (9.45) (4.92) (7.48)
6SE6400-3TD06-1DD0 D 345 300 220 120 240
(13.58) (11.81) (8.66) (4.72) (9.45)
a

6SE6400-3TD07-2ED0 E 355 300 235 145 240


(13.98) (11.81) (9.25) (5.71) (9.45)
6SE6400-3TD11-5FD0 E/F 460 360 235 125 264
(18.11) (14.17) (9.25) (4.92) (10.39)
6SE6400-3TD15-0FD0 F 460 360 250 140 264
(18.11) (14.17) (9.84) (5.51) (10.39)
n1
6SE6400-3TD18-0FD0 F 520 420 290 173 316
n2
(20.47) (16.54) (11.42) (6.81) (12.44)

Fixing with M10 bolts

LC filter for frame sizes D to F

All dimensions in mm (values in brackets are in inches)

Siemens DA 51.2 · 2003/2004 3/21


MICROMASTER 430

Dimension drawings

■ Line commutating chokes

c b c b

G_DA51_XX_05014e

a
a

DA51-5051
Line commutating Dimensions Weight Line commutating Dimensions Weight
choke for (max.) choke for (max.)
a b c kg a b c kg
Frame size C 245 185 50 2.3 Frame size D 520 275 85 9.5
(9.65) (7.28) (1.97) (20.47) (10.83) (3.35)
Frame size E 650 275 95 17.0
(25.59) (10.83) (3.74)

Line commutating choke for frame size C Line commutating choke for frame sizes D and E

b
c

3
DA51-5052

Line commutating for inverter Dimensions Weight


a

choke (max.)
type 6SE6400- Frame size a b c n1 n2 kg
3CC11-.... F 210 240 141 109 190 25.0
(8.27) (9.45) (5.55) (4.29) (7.48)
n1
n2

Line commutating choke for inverter frame size F

b
c

Line commu- for inverter Dimensions Weight


tating choke Frame size (max.)
type (FS)
6SL3000- a b c n1 n2 kg
DA51-5053
a

0CE32-.... FX 248 255 203 101 200 24.0


(9.76) (10.04) (7.99) (3.98) (7.87)
0CE33-.... GX 248 255 203 101 200 25.0
(9.76) (10.04) (7.99) (3.98) (7.87)
0CE35-.... GX 269 275 210 118 224 35.0
(10.59) (10.83) (8.27) (4.65) (8.82)
n1
n2

Line commutating choke for inverters of frame sizes FX and GX

All dimensions in mm (values in brackets are in inches)

3/22 Siemens DA 51.2 · 2003/2004


MICROMASTER 430

Dimension drawings

■ Output chokes

c b

G_DA51_XX_05050a

Output chokes for Dimensions Weight


a

(max.)
a b c kg
Frame size C 245 185 80 5.6
(9.65) (7.28) (3.15)

Line commutating choke


for frame size C

b
Output for inverter Dimensions Weight
c
choke (max.)
type Frame size a b c n1 n2 kg
6SE6400- (FS) (to DIN 41308)
3TC03-8DD0 D 210 225 179 76 176 16.1
DA51-5052

(8.27) (8.86) (7.05) (2.99) (6.93)


a

3TC05-4DD0 D 210 225 150 76 176 10.7


(8.27) (8.86) (5.91) (2.99) (6.93)
3TC07-5ED0 E 248 270 209 88 200 24.9

n1 3TC08-0ED0 E
(9.76)
210
(10.63)
225
(8.23)
150
(3.46)
76
(7.87)
176 10.4 3
n2 (8.27) (8.86) (5.91) (2.99) (6.93)
3TC14-5FD0 F 321 350 288 120 264 51.5
Output chokes (12.64) (13.78) (11.34) (4.72) (10.39)
for inverters of size D, E and F
3TC15-4FD0 F 210 225 150 76 176 11.2
(8.27) (8.86) (5.91) (2.99) (6.93)

All dimensions in mm (values in brackets are in inches)

Siemens DA 51.2 · 2003/2004 3/23


MICROMASTER 430

Dimension drawings

■ Assembly of inverter and options

G_DA51_XX_05042b
Example:
Assembly of
inverter, filter and choke
If additional options are
required, they must be
mounted on the side.

3/24 Siemens DA 51.2 · 2003/2004

S-ar putea să vă placă și