BHEL TRICHY 14

PROJECT : BORL CFBC AS ON : 28.02.07


FBC & HRSG
CUST NO : 5308,5309,5310 PAGE 1 OF 2
DCS -PLC I/O ESTIMATION
BMS PLC IO ESTIMATION-
Process Signals(IS- Intrinsic Safe)- per CFBC boiler- applicable for hazardous area
AI Signals DI signals DO signals AO
15 100 40 10

DO's for SOV need powered output.


Process Signals( Non IS)-per CFBC boiler
AI Signals DI signals DO signals

MCC/MOV/Drive signals-per CFBC boiler


DI signals DO signals

Note: 1) Spares if any shall be seperately indicated in the estimation( for each type of signals)
2) 3 no's Separate independent PLC is provided for each CFBC boiler- BMS application

BOP PLC( 3 Nos) IO ESTIMATION-


Process Signals( IS)- per CFBC boiler
AI Signals DI signals DO signals
2 160 160

Process Signals( Non IS)-per CFBC boiler


AI Signals DI signals DO signals
SB CONT 6 150 150
BLR PRO 200 150

MCC/MOV/Drive signals-per CFBC boiler


DI signals DO signals
240 150

Note:1) All Non Burner/fuel operation related signals shall be covered in this PLC system.
2) All process interlock/drives/MOV signals are to included in this PLC system.

CFBC- DCS CONTROLLER IO ESTIMATION-


Process Signals( IS)- per CFBC Boiler
AI(NR) Signals-
FF-Foundation AI(NR)-
AI(R) signal AO(R) signals Fieldbus Ordinery RTD T/C DI signals

Process Signals(Non IS)-per CFBC Boiler


AI(NR) Signals-
FF-Foundation AI(NR)-
AI(R) signal AO(R) signals Fieldbus Ordinery RTD T/C DI signals
180 40 30 40 80 80 50

Note: 1) AI(R-Redundant) signals is applicable for all process instruments used in closed loops.
2) AO(R-Redundant) signals is applicable for all control Valves commands
3) AI-FF( Foundation Fieldbus) signals is analog tags for DCS monitoring and alarm only.
BHEL TRICHY 14
PROJECT : BORL CFBC AS ON : 28.02.07
FBC & HRSG
CUST NO : 5308,5309,5310 PAGE 2 OF 2
DCS -PLC I/O ESTIMATION
Please consider minimum 15% spare in all category.