Documente Academic
Documente Profesional
Documente Cultură
article info a b s t r a c t
Article history: A railway bridge with a double composite section has been proposed to enhance the structural
Received 23 June 2008 performance of existing twin-girder bridges, because the governing design parameter of railway bridges
Accepted 13 February 2009 is flexural stiffness. The concrete deck in negative moment regions is neglected in the design of continuous
composite bridges assuming the concrete slab has no resistance to tension. Therefore, the flexural stiffness
Keywords: of the composite section in the negative moment region is reduced, resulting in an increase of the
Double composite section
depth of the steel section. In this study, push-out tests on lying studs and mixed stud shear connection
Continuous twin-girder bridge
Lying stud
with lying and vertical studs were performed to investigate the behavior of the shear connection in
Mixed stud the double composite section. In addition, the static strength of the shear connection was evaluated.
Ultimate strength This study focuses on continuous two girder bridge models of 5m–5m span length with the proposed
double composite section. From the static tests on the bridge models, several design considerations
were investigated including the effective width, shear connection, and ultimate strength of the double
composite section. Based on the test results, design guidelines and innovative twin-girder bridges were
suggested.
© 2009 Elsevier Ltd. All rights reserved.
Fig. 3. Push-out specimens: (a) specimen of lying studs (STA22T3); (b) specimen of mixed studs (CSTA22B1).
Table 1
Test specimens.
Specimen Compressive strength Test variables
of concrete N/mm2
STA22T2-2
30 Two row
STA22T3-2
STA22D10-2
STA22D13-2 30 Two row
STA22D16-2
CSTA22A1 H1, V1 Arrangement of stud dc = 200 mm (H1: one lying stud, V1: one vertical stud, V2: two vertical studs)
30
CSTA22A2 H1, V2
CSTA22B1 H1, V1 Arrangement of stud dc = 400 mm (H1: one lying stud, H2: two lying stud, V1: one vertical stud, V2: two
vertical studs)
30
CSTA22B2 H1, V2
CSTA22B3 H2, V1
CSTA22B4 H2, V2
STB22T2
40 dc = 300 mm, 400 mm
STB22T3
STB16T2 Diameter of stud 16mm, 19 mm, 25 mm
STB19T2 40
STB25T2
CSTB22B1∼B3 H1, V1 Arrangement of stud dc = 400 mm: 3EA (H1: one lying stud, V1: one vertical stud)
40
CSTB16B1∼B3 H1, V1
Fig. 5. Failure modes: (a) stud/slab failure; (b) stud shank failure; (c) slab failure.
the effective use of the shear connectors. The compressive strength strength of the STB series specimens was higher than design
of the concrete and details of the reinforcements are important strength of the vertical stud shear connection in Eurocode-4 [5].
factors for preventing slab failure. The splitting strength of the However, the nominal strength from the push-out tests was lower
concrete slab can be calculated by Eqs. (4) and (5) [7]. than the design values of Eurocode-4 [5]. This is due to a weaker
confinement of the stud resulting from the relatively thin concrete
– Single row of studs;
slab. The shear connection with vertical studs has higher shear
2 strength than the lying stud shear connection, due to a higher
ba
Psplit(one) = 0.6bc ha fcb π 1− (4) constraint by the wider concrete slab and more reinforcements. In
bc
order to suggest the empirical equation for the design of the lying
– Two rows of studs: stud shear connection, we modified the current design equation of
vertical stud shear connection.
ba
Psplit(two) = 0.6bc ha fcb π 1− (5) When slab failure is prevented by the design provisions of
bc details and by checking the splitting failure of the concrete
where, Psplit is the splitting strength (kN), bc is the thickness of slab, we could design the lying stud shear connection using an
the concrete slab (mm), ba is the diameter empirical equation (6). This equation can only be used for the shear
√ of the stud (mm), ha
is the height of the stud (mm), fcb = 0.5 fc , and fc is the design connection with the stud shank failure mode. Fig. 6 shows the
compressive strength of concrete (N/mm2 ). comparison of the test results with values from AASHTO LRFD [8]
and Eurocode-4 [5].
As seen in Table 2, the STB series with a higher compressive
strength of concrete showed stud shank failure. The ultimate PL = 0.725fu (π d2 /4)/γv (6)
H.-H. Kim, C.-S. Shim / Journal of Constructional Steel Research 65 (2009) 1355–1365 1359
Table 2
Test results of lying stud.
Specimen Experiment EC-4 (1) EC-4 (2) Kuhlmann Failure mode
Ultimate strength (kN) Splitting strength (kN)
2.4. Static strength of mixed stud shear connection 3.1. Test specimen
In areas of high shear forces, lying studs and vertical studs Two double composite twin-girder (DCTG) bridge models were
need to be placed to resist the horizontal shear forces and the fabricated to study the behavior of the shear connection in the
tensile forces in the transverse direction. This mixed stud shear lower concrete slab and the inelastic behavior of the double
connection has not been previously investigated. For the design composite section. Fig. 8 illustrates the test specimen details. The
of this shear connection, we calculated the shear strength by bridge model had 10 m length and 800 mm girder height. The
adding the strength of lying studs and vertical studs. However, it is bottom of the section was closed using 80 mm deep precast slabs
necessary to ensure that this assumption is conserved throughout and these slabs work as formwork for the bottom concrete at the
the experiments, because the stress distribution according to the negative moment area near the internal support resulting in a
arrangement of studs can vary. 200 mm-thick bottom concrete slab. No bottom concrete was cast
Table 3 summarizes the test results of the push-out tests on at mid-span, and the bottom precast slabs were not connected
the mixed stud shear connection and calculated values obtained lengthwise. A 168 mm-wide and 200 mm-thick strip at both sides
by adding the shear strength of lying stud shear connection (PL ) of the slabs was needed to ensure the shear force transfer among
1360 H.-H. Kim, C.-S. Shim / Journal of Constructional Steel Research 65 (2009) 1355–1365
Table 3
Test results of mixed stud shear connection.
Specimen Experiment PL + PRd Failure mode
Ultimate strength (kN) Ultimate displacement (mm)
Fig. 8. Double composite beam specimens (mm): (a) composite section; (b) longitudinal layout.
the precast slabs, resulting in the torsion circuit for the strict box
section.
Based on the results of previous push-out tests, the shear
connection for the bottom concrete slab was designed to achieve
full composite action (degree of shear connection = 1.01). We
used 16 mm lying studs and 22 mm vertical studs for the shear
connection; it is preferable to use smaller studs for lying stud
shear connectors because of the relatively weak constraint of the
concrete slab in the direction of the thickness.
The DCTG1 model was designed to have SM490 steel only for
the flanges and the web, and the DCTG2 model was designed to
have SM520 steel for flanges and SM490 steel for the web (hybrid
combination).
In these specimens, there was no diaphragm because the deliv-
ery or the erection of the bridge model was performed after hav-
ing the composite section. In actual practice on double composite
twin-girder bridges, it is necessary to provide diaphragms for the
Fig. 9. Test setup.
stability of the girders during construction.
Static tests were conducted using two hydraulic testing
machines of 1000 kN capacity. As shown in Fig. 9, one end of the of the specimen was loaded by two actuators. Loads were applied
specimen was supported in the upper direction and the other end to simulate eccentric loading, uniform loading, and failure load.
H.-H. Kim, C.-S. Shim / Journal of Constructional Steel Research 65 (2009) 1355–1365 1361
Fig. 10. Measurement layout: (a) reinforcement strain; (b) concrete strain; (c) steel strain, slip and displacement measurement; (d) crack width measurement.
at four points with LVDTs to evaluate the flexural stiffness of At the time of static test (air curing) Standard curing
the composite sections. LVDTs were also installed to measure the Upper slab 40.8 43
relative displacements (slip) between the steel girder and the Lower slab 27.7 –
concrete slab, as presented in Fig. 10. Several strain gauges were Precast panel 39.8 32.6
installed on the steel beams, concrete slabs, and reinforcements to
observe the mechanical behavior of the specimens. Table 5
Material properties of steel girder.
Elastic modulus Yield stress Tensile strength
3.2. Material properties (GPa) (MPa) (MPa)
Fig. 14. Crack pattern of upper concrete slab: (a) DCTG1; (b) DCTG2.
Table 6 Table 7
Comparison of flexural stiffness. Comparison of ultimate strength.
Specimens Second moment of area (I) Specimens Design Experiment
Fig. 16. Load–strain curve of steel girder (negative moment section): (a) DCTG1; Fig. 17. Load–displacement curve: (a) DCTG1; (b) DCTG2.
(b) DCTG2.
4. Conclusion
(3) the flexural strength of the double composite section can be [3] Kuhlmann U, Kurschner K. Behaviour of lying shear studs in reinforced
evaluated by rigid-plastic analysis when the full shear connection concrete slabs. In: Symposium on connections between steel and concrete.
2001.
and the compact section requirements are achieved. [4] Breuninger U. Behaviour of lying studs with longitudinal shear force. In:
From the design applications, we conclude that the double Engineering foundation conference. Composite construction in steel and
composite action provides designers with an opportunity to design concrete IV. 2000.
[5] Eurocode 4. Design of composite steel and concrete structures. Part 1. General
more innovative and economic bridges. Because railway bridges rules and rules for buildings. ENV 1994-2. CEN; 1994.
are high impact structures, dynamic behavior of the composite [6] Eurocode 4. Design of composite steel and concrete structures. Part 2. General
girders and fatigue endurance of the connection need to be rules and rules for bridges. EN 1994-2. CEN; 2005.
[7] Oehlers DJ, Bradford MA. Composite steel and concrete structural members.
conducted. The double composite action using a bottom concrete Pergamon; 1995.
slab can also be applied to highway bridges. Further research is [8] AASHTO. AASHTO LRFD bridge design specifications. 3rd ed. Washington (DC):
needed to investigate the effective design solutions for highway American Association of State and Highway Transportation Officials; 2004.
[9] Shim C-S, Lee P-G, Yoon T-Y. Static behavior of large stud shear connectors.
bridges.
Engineering Structures 2004;26(12):1853–60.
[10] Lee P-G, Shim C-S, Chang S-P. Static and fatigue behavior of large stud shear
connectors for steel–concrete composite bridges. Journal of Constructional
References Steel Research 2005;61(9):1270–85.
[11] Slutter RG, Fisher JW. Fatigue strength of shear connectors. Highway research
[1] Shim C-S. Research on the double composite twin-girder railway bridges. record no. 147. New York; 1966.
In: Proceedings of the 8th Korea–China–Japan symposium on structural steel [12] AREMA manual for railway engineering. The American Railway Engineering
construction. 2005. p. 49–57. and Maintenance-of-way Association; 2008.
[2] Kuhlmann U, Kurschner K. Design of lying studs with longitudinal shear force. [13] DIANA user’s manual release 9.1. TNO building and construction research.
In: Symposium on connections between steel and concrete. 2001. Netherlands; 2005.