Sunteți pe pagina 1din 28

INTERFACE A

MEDIUM VOLTAGE SEPARABLE


CONNECTORS AND BUSHINGS
CATALOGUE 2017
NEXANS NETWORK SOLUTIONS DIV. EUROMOLD

COMPANY PRESENTATION

EUROMOLD International standards Laboratory accreditation


Nexans is the leading European All our products meet the Since June 2000, Nexans'
specialised designer, manufacturer International standards like independent ELAB laboratory
and distributor of prefabricated CENELEC HD 629.1, CENELEC EN obtained the BELAC accreditation
cable accessories for medium 50180, IEC 60137, IEC 60502- no.144-TEST conform with
voltage energy distribution. 4… or country specifications. the European standards for
Under its tradename Euromold, Official certificates, CESI, KEMA, laboratories ISO 17025 for
it provides a complete range ATEX… prove the conformity of electrical testing of low and
of accessories for underground our products. Long duration tests medium voltage cable accessories
cables: premoulded EPDM of existing or new products are according to the international
rubber connectors for cables and continuously performed in our test standards EN 50393, IEC 60502-
epoxy bushings for transformers fields. 4, IEC 61442 and HD 629.
and switchgear, as well as a
large range of cold-shrinkable
terminations and joints from 12 to
42 kV.
Nexans division Euromold is also
the manufacturer of electrical
components for the high voltage
accessories of the Nexans group.

ISO 9001 Certificate


Since 1992, Nexans'
commitment to quality is
demonstrated by its ISO 9001
certification. We are also certified
in the important sectors of
environmental protection and
occupational safety.

While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility
can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or
modify the characteristics of its products described in this catalogue as standards and technology evolve.
SEPARABLE CONNECTORS
INTERFACE A

TABLE OF CONTENTS INTERFACE A1


158LR - elbow connector Dimensions according to European
152SR - straight connector CENELEC EN 50180 and 50181
151SP - straight plug (in mm).
156SA - surge arrester
180AR-1 /-2 /-3 and 180AR-1-G /-3-G - equipment bushings
180A-24P-O - in-air bushing
PITO-E - plug-in termination
Accessories
Bail restraints

Dia. 32.5±0.2

Dia. 31+0.1
- 0.3

Dia. for
+0.02
pin 7.9 - 0.05

0
48 -0.2

9
min

Dia. 48.5±0.2

In mm.

09/2017
CONNECTING POSSIBILITIES

BUSHINGS / ACCESSORIES / CONNECTION CONNECTORS /


CONNECTOR ACCESSORIES

Equipment interface dead-ending of equipment (K)150DR


Dead-end receptacle
two cables to equipment
(K)180AR-1(-G),-2 & -3(-G) (K)200T
Equipment bushing three cables to equipment Tee connector

one line to equipment


180A-24P-O
In-air bushing
one cable to (K)200X
Cross connector
equipment

(K)200T in-line junction PITO-E


Plug-in termination
Tee connector + tap-off

(K)200X in-line junction


Cross connector + 2 tap-offs

(K)150DP
Dead-end plug
cable
insulation (K)152SR(/G)
(K)151SOP Straight connector
Stand-off plug

250GP cable
Earthing plug earthing
(K)158LR(/G)
Elbow connector
(K)400RTPA tap-off
Reducing tap plug 630/250 A

(K)676RTPA tap-off
Reducing tap plug 1250/250 A

(K)152SR(/G)
Straight connector
disconnectable joint

(K)158LR(/G)
(K)151SP Elbow connector
Straight plug

(K)200T
in-line junction + tap-off Tee connector

in-line junction + 2 tap-offs


(K)200X
Cross connector

cable isolation (K)150DR


Dead-end receptacle

09/2017
158LR INTERFACE A
ELBOW CONNECTOR

APPLICATION TECHNICAL
Separable elbow connector CHARACTERISTICS
designed to connect polymeric • The thick conductive EPDM jacket
insulated cable to equipment provides a total safe to touch
(transformers, switchgear, screen which ensures safety for
motors...). personnel.
Also connects cable to cable, • Each separable connector is
using the appropriate mating tested for AC withstand and
part. partial discharge prior to leaving
the factory.

DESIGN 160 mm

Separable connector
comprising: 6/10 (12) kV
1. Conductive EPDM insert. 6.35/11 (12) kV
2. Conductive EPDM jacket. 8.7/15 (17.5) kV
3. Insulating EPDM layer 4 12/20 (24) kV
moulded between the insert 1
12.7/22 (24) kV
and the jacket. 221 mm 5
4. Type A - 250 A interface 2 Up to 24 kV - 250 A
6
as described by CENELEC 3
EN 50180 and 50181.
5. Conductor connector. 7
6. Voltage test point.
7. Earthing lead
(-/G version only).

SPECIFICATIONS AND
STANDARDS
The separable connector 158LR
meets the requirements of
CENELEC HD 629.1.

Separable Voltage Current


Conductor sizes (mm2)
connector Um Ir
type (kV) (A) min max
158LR/G 12 250 16 95
158LR 12 250 70 95
K158LR/G 24 250 16 70
K158LR 24 250 25 95
09/2017

4
KIT CONTENTS
The complete (K)158LR or The kit also comprises lubricant, wipers,
(K)158LR/G elbow connector installation instructions and crimp chart.
kit comprises the following
components:
(K)158LR/G-W-X
connector kit for
smaller sizes
Connector housing Cable reducer
(K)158BLR/G-W 211CA

Conductor Pin contact Bail


(K)158LR-W-X+11TL
contact + hex key restraint
connector kit for
164LRC-X 154LRF 150BA-B1
larger sizes
or Connector housing Cable adaptor
164LRMC-X (K)158BLR-W 11TL

ORDERING INSTRUCTIONS TABLE W


Select the part number which gives
Ordering Dia. over core insulation (mm)
the best centring to the cable core
part number min max
insulation diameter and substitute
158LR/G-11-X 12.6 16.1
X using table X, according to the
158LR/G-13-X 14.6 18.7
conductor size and type. 158LR-FB-X+11TL 17.5 20.2
Add a 'K' for use up to 24 kV. 158LR-FG-X+11TL 18.4 21.2
158LR-GA-X+11TL 19.7 22.5
EXAMPLE: 158LR-GAB-X+11TL 21.0 23.8
The copper wire screened cable 158LR-GH-X+11TL 23.6 26.4

is 24 kV, 50 mm2 stranded


TABLE X
aluminium with a diameter over
core insulation of 20.4 mm. Conductor Aluminium Copper
Order a K158LR-FG-50(K)M- sizes
12-2+11TL elbow connector kit. (mm²) DIN hexagonal Deep indent DIN hexagonal
16 - - 16(K)M-11-2
25 25(K)M-12-2 25KM-12-1 25(K)M-11-2
35 35(K)M-12-2 35KM-12-1 35(K)M-11-2
For an option with a bolted
50 50(K)M-12-2 50(K)M-12-1* 50(K)M-11-2
conductor contact, 70 70(K)M-12-2 70(K)M-12-1* 70(K)M-11-2
specify the ordering part number 95 95(K)M-12-2 * 95(K)M-12-1* 95(K)M-11-2*
below.
* The 158LR-FB is not compatible with these conductor contacts.

Ordering part number Dia. over core insulation (mm) Conductor sizes (mm²)
158LR/G-13-25.95-14-5 14.6 - 22.7 35 - 70
158LR-GAS-50.95-14-5+11TL 19.7 - 25.4 25 - 95

For use with For use with Alupe or For use with For adapted For outdoor Components can be
copper tape C 33-226 cables. other cable types. bail restraints: applications. ordered individually.
screened cables. Please contact our Please contact our see 'Bail restraints and Order: +MWS.
Order: Kit MT. representative. representative. typical applications'.
5
152SR INTERFACE A
STRAIGHT CONNECTOR

APPLICATION TECHNICAL
Separable straight connector CHARACTERISTICS
designed to connect polymeric • The thick conductive EPDM jacket
insulated cable to equipment provides a total safe to touch
(transformers, switchgear, screen which ensures safety for
motors...). personnel.
Also connects cable to cable, • Each separable connector is
using the appropriate mating tested for AC withstand and
part. partial discharge prior to leaving
the factory.

DESIGN
Separable connector 6/10 (12) kV
comprising: 6.35/11 (12) kV
1. Conductive EPDM insert. 100 mm 8.7/15 (17.5) kV
2. Conductive EPDM jacket. 12/20 (24) kV
3. Insulating EPDM layer 12.7/22 (24) kV
moulded between the insert
and the jacket. Up to 24 kV - 250 A
4. Type A - 250 A interface
as described by CENELEC 7

EN 50180 and 50181.


5. Conductor connector.
6. Voltage test point. 1
7. Earthing lead 255 mm 2
(-/G version only).
5

3
6

SPECIFICATIONS AND
STANDARDS 4
The separable connector 152SR
meets the requirements of
CENELEC HD 629.1.

Separable Voltage Current


Conductor sizes (mm2)
connector Um Ir
type (kV) (A) min max
152SR/G 12 250 16 70
152SR 12 250 70 95
K152SR/G 24 250 16 25
K152SR 24 250 25 95
09/2017

6
KIT CONTENTS
The complete (K)152SR or The kit also comprises lubricant, wipers,
(K)152SR/G straight connector installation instructions and crimp chart.
kit comprises the following
components: (K)152SR/G-W-X
connector kit for
Connector housing Cable reducer smaller sizes
(K)152SRH/G-W 211CA

Conductor
contact (K)152SR-W-X+11TL
151SRC-X connector kit for
or Bail restraint Connector housing Cable adaptor larger sizes
151SRMC-X 151BA (K)152SRH-W 11TL

ORDERING TABLE W
INSTRUCTIONS
Ordering Dia. over core insulation (mm)
Select the part number which
part number min max
gives the best centring to the
cable core insulation diameter 152SR/G-11-X 12.6 16.1
152SR/G-13-X 14.6 18.7
and substitute X using table X,
152SR-FB-X+11TL 17.5 20.2
according to the conductor size 152SR-FG-X+11TL 18.4 21.2
and type. 152SR-GA-X+11TL 19.7 22.5
Add a 'K' for use up to 24 kV. 152SR-GAB-X+11TL 21.0 23.8
152SR-GH-X+11TL 23.6 26.4
EXAMPLE:
The copper wire screened cable TABLE X
is 24 kV, 50 mm2 stranded
aluminium with a diameter over Conductor Aluminium Copper
sizes
core insulation of 20.4 mm. (mm²) DIN hexagonal Deep indent DIN hexagonal
Order a K152SR-FG-50(K)M-
16 - - 16(K)M-11-2
12-2+11TL straight connector 25 25(K)M-12-2 25KM-12-1 25(K)M-11-2
kit. 35 35(K)M-12-2 35KM-12-1 35(K)M-11-2
50 50(K)M-12-2 50(K)M-12-1* 50(K)M-11-2
70 70(K)M-12-2 70(K)M-12-1* 70(K)M-11-2
95 95(K)M-12-2 * 95(K)M-12-1* 95(K)M-11-2*
For an option with a bolted
conductor contact, * The 152SR-FB is not compatible with these conductor contacts.
specify the ordering part
number below.

Ordering part number Dia. over core insulation (mm) Conductor sizes (mm²)
152SR/G-13-25.95-14-5 14.6 - 22.7 35 - 70
152SR-GAS-50.95-14-5+11TL 19.7 - 25.4 25 - 95

For use with For use with Alupe or For use with For adapted For outdoor Components can be
copper tape C 33-226 cables. other cable types. bail restraints: applications. ordered individually.
screened cables. Please contact our Please contact our see 'Bail restraints and Order: +MWS.
Order: Kit MT. representative. representative. typical applications'.
7
151SP INTERFACE A
STRAIGHT PLUG

APPLICATION TECHNICAL
Separable straight plug designed CHARACTERISTICS
to connect polymeric insulated • The thick conductive EPDM jacket
cable to cable. provides a total safe to touch
Mates with the elbow, straight and screen which ensures safety for
branch joint connectors. personnel.
• Each straight plug is tested for AC
withstand and partial discharge
prior to leaving the factory.

DESIGN
Separable connector
comprising:
1. Conductive EPDM insert. 6/10 (12) kV
2. Conductive EPDM jacket. 6.35/11 (12) kV
3. Insulating EPDM layer 8.7/15 (17.5) kV
moulded between the insert 12/20 (24) kV
and the jacket. 12.7/22 (24) kV
4. Type A interface as described
by CENELEC EN 50180 and Up to 24 kV - 200 A
50181.
5. Conductor connector.

223 mm

5
1
3

Dia.
54 mm

Separable Voltage Current


Conductor sizes (mm2)
plug Um Ir
type (kV) (A) min max
151SP 12 200 16 95
K151SP 24 200 16 95
09/2017

8
KIT CONTENTS
The kit also comprises lubricant, wipers,
The complete (K)151SP straight
installation instructions and crimp chart.
plug kit comprises the following
components:

(K)151SP-W-X+11TL
straight plug kit

Straight plug housing Conductor Cable


(K)151SPH-W contact adaptor
151SPC-X 11TL

ORDERING INSTRUCTIONS TABLE W


Select the part number
which gives the best centring to Ordering Dia. over core insulation (mm)
the cable core insulation diameter part number min max
and substitute X using table X, 151SP-A-X+11TL-FA/FAB 14.6 18.7
according to the conductor size 151SP-B-X+11TL-FB/FG 17.2 21.2
and type. 151SP-B-X+11TL-GA/GAB 19.7 23.0
Add a 'K' for use up to 24 kV. 151SP-C-X+11TL-GB/GH 22.2 26.4

TABLE X
EXAMPLE:
The copper wire screened cable Conductor Aluminium Copper
is 12 kV, 50 mm2 stranded sizes
(mm²) DIN hexagonal Deep indent DIN hexagonal
aluminium with a diameter over
core insulation of 16.9 mm. 16 - - 16(K)M-11-2
Order a 151SP-A-50(K)M-12- 25 25(K)M-12-2 25KM-12-1 25(K)M-11-2
2+11TL-FA/FAB straight plug kit. 35 35(K)M-12-2 35KM-12-1 35(K)M-11-2
50 50(K)M-12-2 50(K)M-12-1 50(K)M-11-2
70 70(K)M-12-2 70(K)M-12-1 70(K)M-11-2
95 95(K)M-12-2 95(K)M-12-1 95(K)M-11-2

For use with For use with Alupe or For use with For adapted For outdoor Components can be
copper tape C 33-226 cables. other cable types. bail restraints: applications. ordered individually.
screened cables. Please contact our Please contact our see 'Bail restraints and Order: +MWS.
Order: Kit MT. representative. representative. typical applications'.
9
156SA INTERFACE A
SURGE ARRESTER

APPLICATION TECHNICAL
Surge arrester designed to protect CHARACTERISTICS
12 and 24 kV class components, • This surge arrester is a metal
including transformers, oxide varistor surge arrester in an
equipment, cable and accessories elbow configuration.
from high voltage surges resulting • Each arrester is tested for AC
from lightning or switching. withstand and partial discharge
prior to leaving the factory.

DESIGN 2 1

Surge arrester comprising:


1. Bail restraint. 3 6/10 (12) kV
2. Conductive EPDM insert. 6.35/11 (12) kV
3. Type A - 250 A interface 4 8.7/15 (17.5) kV
as described by CENELEC 12/20 (24) kV
EN 50180 and 50181. 12.7/22 (24) kV
4. Pin contact. 5
5. Contact disc.
Up to 24 kV
6. Copper shunt. 6
7. Metal oxide valve elements.
8. Aluminium spacer.
9. Steel cap.
10. Earth connection.
11. Insulating EPDM layer 7 12
moulded between the insert
11
and the jacket.
12. Conductive EPDM jacket.
5

8
6

10

Nominal Rated Max continuous Steep current Lightning current High current
Surge
discharge voltage operating residual residual impulse
arrester
current Ur voltage voltage @ 5 kA voltage @ 5 kA withstand
type
In (kA) (kV) Uc (kV) [1/20 µs] (kV) [8/20 µs] (kV) (kA)

156SA-12 5 15 12.5 62.5 54.5 40


156SA-15 5 19 15.5 77.0 69.0 40
156SA-18 5 22 18.0 87.0 79.0 40
156SA-21 5 26 21.0 101.5 93.5 40
156SA-24 5 30 24.5 116.5 108.5 40
09/2017

10
TYPICAL APPLICATION AND
DIMENSIONS
415

220 195
156

131

K400RTPA
reducing tap plug

K400TE/G,
K400TB/G or
K440TB/G
connector
330
Surge arrester
156SA-24

Note: the surge arrester body


needs to be positioned vertically
after installation.

In mm.

ORDERING INSTRUCTIONS
To order the surge arrester,
specify the surge arrester type, as
described on previous page.

EXAMPLE:
For a maximum continuous
operating voltage (r.m.s.) of 21 kV.
Order a 156SA-21 surge arrester.

11
180AR-1/180AR-2/180AR-3 INTERFACE A1
EQUIPMENT BUSHINGS

APPLICATION SPECIFICATIONS AND


For use in equipment insulated STANDARDS
with oil fluid, typically for The plug-in type equipment
transformers, switchgear, bushings 180AR-… meet the
capacitors... requirements of CENELEC EN
50180 and IEC 60137.
TECHNICAL
CHARACTERISTICS
Each bushing is tested for AC Type 180AR-1 /-2 /-3
withstand and partial discharge
prior to leaving the factory.

DESIGN
• The equipment bushings are 6/10 (12) kV
6.35/11 (12) kV
28

moulded epoxy insulated parts


in accordance with CENELEC EN
8
8.7/15 (17.5) kV
50180.
A
12/20 (24) kV
The 180AR-2 bushing has a 12.7/22 (24) kV
length B outside this standard. B

• The standard bushings, Minimum oil level:


- 12 kV: 40 mm
Dia.
16 Up to 24 kV - 250 A
(K)180AR-1 /-2 /-3, are - 24 kV: 50 mm

equipped with 6 tabs for the bail


19
restraint.
• The (K)180AR-1-G and Dia. 75
M10

(K)180AR-3-G are equipped with Dia. 110

4 tabs and 2 threaded inserts M6 Type 180AR-1-G /-3-G


(-G version).

ORDERING INSTRUCTIONS M6

To order the equipment bushing,


specify the type. 11

The bushings are supplied with an


earth jumper (/J) or an earth plate
(/GS). This earth connection must
be specified when ordering.
E.g. K180AR-1/J.
In mm.

Equipment Voltage Current Dimensions (mm)


bushing Um Ir
type (kV) (A) A B
180AR-1 12 250 222 106
K180AR-1 24 250 222 106
180AR-2 12 250 284 168
K180AR-2 24 250 284 168
180AR-3 12 250 171 55
K180AR-3 24 250 171 55 09/2017

12
FIXINGS FOR EQUIPMENT BUSHINGS
180AR-1/GS 180AR-1/J
180AR-1-G/GS 180AR-1-G/J
180AR-2/GS 180AR-2/J
180AR-3/GS AND 180AR-3/J AND
180AR-3-G/GS BUSHINGS 180AR-3-G/J BUSHINGS
bushing interface
fixing studs

NF C 52-053
clamp E DIN 42 538
stud clamp

equipment

sealing gasket

equipment
connection

A DIN 42 538
tabs for bail restraint fixing flange

earth jumper
earth plate

BUSHING CLAMPING KIT BUSHING CLAMPING KIT


To order the bushing clamping kit,
To order the bushing clamping kit,
according to DIN 42 538 stand-
according to NF C 52-053
ards, simply specify: KBCD-200.
standards, simply specify KBC-
Contents: - 1 x fixing flange A
NF1-200.
- 4 x stud clamp E
Contents: - 3 x claw clamp NF
- 1 x sealing gasket.
- 1 x sealing gasket.

FIXING DIMENSIONS FIXING DIMENSIONS


STANDARDS NF C 52-053 STANDARDS DIN 42 538
French standards. German standards.
M8 or
M10
M10

Min. 55 Min. 55
Max. 30 Max. 30

3 fixing 4 fixing 13
studs Dia. 78 studs Dia. 78
Dia. 126 Dia. 123 In mm.
180A-24P-O INTERFACE A1
IN-AIR BUSHING

APPLICATION TECHNICAL
For use in equipment insulated CHARACTERISTICS
with air, typically for dry type Each bushing is tested for
transformers, motors, switchgear, AC withstand and partial
capacitors... discharge prior to leaving the
factory.

SPECIFICATIONS AND
STANDARDS
The plug-in type equipment 59
bushings 180A-24P-O are
moulded epoxy insulated parts 6/10 (12) kV
and meet the requirements of 20 6.35/11 (12) kV
CENELEC EN 50181, IEC 60071 8.7/15 (17.5) kV
and IEC 60137.
Dia. 70
12/20 (24) kV
A
Dia. 110 12.7/22 (24) kV

Up to 24 kV - 250 A

ORDERING INSTRUCTIONS 351


To order the equipment bushing,
specify the type.
250
The bushings are supplied with an
earth jumper.
To include the ring clamp, add:
• /B, if per British standards
• /D, if per German standards
Dia.
• /F, if per French standards. 16
E.g. 180A-24P-O/F.

20

M10
B Dia. 80

In mm.

Equipment Voltage Current Creepage distance


bushing Um Ir A-B
type (kV) (A) (mm)
180A-24P-O 12 250 630
180A-24P-O 24 250 630
09/2017

14
FIXINGS FOR EQUIPMENT BUSHINGS
180A-24P-O IN-AIR BUSHING
bushing interface
fixing studs and
nuts M10
earth jumper

equipment

gasket

equipment
connection

fixing flange
fixing flange
BCA-B or
BCA-D BCA-F

tabs for bail


restraint
Dia.12 Dia.12
Dia. 94.5 Dia. 94.5
4 4
10 10
Dia. 111 Dia. 111

120°

126

120°
BS 2562 stand.: 120
DIN 42 538 stand.: 123 Dia. 150
Dia. 150
Type BCA-B : BS 2562 British standards Type BCA-F : NF C 52-053 French standards
Type BCA-D : DIN 42 538 German standards

FIXING DIMENSIONS FIXING DIMENSIONS


STANDARDS DIN 42 538 STANDARDS NF C 52-053
German standards. French standards.

M10 M10

Min. 55
Min. 55
Max. 20
Max. 20

4 fixing
3 fixing
studs 15
studs
Dia. 82
Dia. 82
Dia. 126
Dia. 123
In mm.
PITO-E PLUG-IN TERMINATION

APPLICATION TECHNICAL
• Separable termination designed CHARACTERISTICS
to connect overhead lines or bus Each plug-in termination is tested
bars to equipment. for AC withstand prior to leaving
• Is suitable for indoor and the factory.
outdoor use for medium polluted
atmosphere.

DESIGN
The plug-in termination is a
moulded epoxy insulated part. 6/10 (12) kV
It meets the type A - 250 A 6.35/11 (12) kV
interface as described in 8.7/15 (17.5) kV
CENELEC EN 50180 and 50181. 12/20 (24) kV
12.7/22 (24) kV

Up to 24 kV - 250 A

SPECIFICATIONS AND
STANDARDS
The separable termination PITO-E
meets the requirements of IEC
60137.

ORDERING INSTRUCTIONS
To order the plug-in termination
for 12 or 24 kV, specify PITO-E.
The kit includes the bail restraint
and 2 brass nuts.

In mm.

Plug-in Voltage Current Creepage distance


termination Ur Ir A-B
type (kV) (A) (mm)
PITO-E 12 250 510
PITO-E 24 250 510
09/2017

16
ACCESSORIES INTERFACE A

APPLICATION TECHNICAL 6/10 (12) kV


For use with connectors and CHARACTERISTICS 6.35/11 (12) kV
bushings with an interface A as All these products, except the 8.7/15 (17.5) kV
described by CENELEC EN 50180 earthing plug, are tested for 12/20 (24) kV
and 50181. AC withstand and partial 12.7/22 (24) kV
discharge prior to leaving the
factory.
Up to 24 kV

150DR ORDERING INSTRUCTIONS


DEAD-END RECEPTACLE Order
Fits over a bushing with a type A 150DR for 12 kV or
interface to provide 'dead-end' K150DR for 24 kV
facility. applications.
Renders the assembly watertight. The dead-end receptacle can
be supplied with an earth lead.
Order: -/G. E.g. K150DR/G.

150DP ORDERING INSTRUCTIONS


DEAD-END PLUG Order
Plugs into connectors or 150DP for 12 kV or
receptacles to provide 'dead-end' K150DP for 24 kV
facility. applications.
Renders the assembly watertight.

151SOP ORDERING INSTRUCTIONS


STAND-OFF PLUG Order
Is designed to support and 'dead- 151SOP for 12 kV or
end' connectors with a type A K151SOP for 24 kV
interface when removed from applications.
equipment.

250GP ORDERING INSTRUCTIONS


EARTHING PLUG Order
Is designed to support and earth 250GP for 12 kV or 24 kV
connectors with a type A interface applications.
when removed from equipment. 09/2017

17
200T ORDERING INSTRUCTIONS
SEPARABLE TEE CONNECTOR Order
Is designed to connect three cables 200T for 12 kV or
of the same or varying sizes or two K200T for 24 kV
cables to equipment. applications.
For an adapted bail, please refer
to the catalogue or contact our
representative.

200X ORDERING INSTRUCTIONS


SEPARABLE CROSS Order
CONNECTOR 200X for 12 kV or
Is designed to connect four cables K200X for 24 kV
of the same or varying sizes or applications.
three cables to equipment.
For an adapted bail, please refer
to the catalogue or contact our
representative.

1501J3-U-8 ORDERING INSTRUCTIONS


THREE-WAY JUNCTION Order
Provides a flexible means of 1501J3-U-8 for 12 kV or
connecting two or three cables of K1501J3-U-8 for 24 kV
the same or varying sizes. applications.
For an adapted bail, please refer
to the catalogue or contact our
representative.

KIT MT ORDERING INSTRUCTIONS


EARTHING KIT FOR COPPER Order
TAPE SCREENED CABLES Kit MT for 12 kV or 24 kV
Contains a tinned copper braid applications.
(25 mm² - L=500 mm), a tinned
copper wire for cleating and water
sealing mastic.

18

09/2017
BAIL RESTRAINTS INTERFACE A

APPLICATION ORDERING INSTRUCTIONS


For use with connectors, The type of bail restraint is defined
receptacles and bushings with by its intended use with different
an interface A as described by types of connector, receptacle and/
CENELEC EN 50180 and 50181. or bushing.
To order the bail restraint, specify
the type needed.

147BA 149BA
For use with: For use with:
1. (K)152SR straight connector, 1. (K)158LR elbow connector,
2. (K)200T tee connector and 2. (K)200T tee connector and
3. (K)150DR dead-end 3. (K)150DR dead-end
receptacle. receptacle.

1 3 3 1

2 2

148BA
For use with:
1. (K)158LR elbow connector and
2. (K)150DP dead-end plug. 150BA-B1
For use with:
1. (K)158LR elbow connector
1 and
2. an interface A equipment
bushing (shown), 250GP
earthing plug, (K)151SOP
stand-off plug (shown) or
(K)1501J3-U-8 three-way
2 junction.

1 1

2 2

09/2017

19
150TB-1 153BA
For use with: For use with:
1. (K)200T tee connector and 1. (K)152SR straight connector
2. an interface A equipment and
bushing (shown), 250GP 2. (K)150DP dead-end plug.
earthing plug, (K)151SOP
stand-off plug (shown) or
(K)1501J3-U-8 three way 1
junction.

1 1

2 2 154BA-CS180
For use with:
1. (K)151SP straight plug and
151BA 2. (K)150DR dead-end
For use with: receptacle.
1. (K)152SR straight connector 2 1
and
2. an interface A equipment
bushing (shown), 250GP
earthing plug, (K)151SOP
stand-off plug (shown) or
(K)1501J3-U-8 three-way 155BA-1
junction. For use with:
1. 2 x (K)152SR straight
connector and
1 1
2. (K)200T tee connector.

1 1

2 2
2

152BA 155BA-2 - CS180


For use with: For use with:
1. (K)150DR dead-end 1. (K)151SP straight plug and
receptacle and 2. (K)158LR elbow connector or
2. an interface A equipment 3. (K)200T tee connector.
bushing (shown) or
(K)1501J3-U-8 three-way
junction.
3
2
1
1 1
20
2

09/2017
156BA-1 159BA
For use with: For use with:
1. (K)200T tee connector and 1. 2 x (K)158LR elbow connector
2. (K)150DP dead-end plug. and
2. (K)200T tee connector.

1 1

2 2

157BA - CS181
For use with:
1. (K)152SR straight connector
and 200BA
2. (K)151SP straight plug. For use with:
1. (K)152SR straight connector
and
2. (K)200X cross connector.
1 2

158BA
For use with:
1. (K)152SR straight connector,
2. (K)200T tee connector
and
3. (K)158LR elbow connector.

2
1 3

201BA
For use with:
2
1. (K)158LR elbow connector
and
2. (K)200X cross connector.

21
2
202BA 206BA
For use with: For use with:
1. (K)152SR straight connector, 1. (K)152SR straight connector,
2. (K)200X cross connector and 2. (K)200X cross connector and
3. (K)150DR dead-end 3. (K)158LR elbow connector.
receptacle.

1 3 1 3

2 2

203BA
For use with:
1. (K)158LR elbow connector,
2. (K)200X cross connector and
3. (K)150DR dead-end 207BA
receptacle. For use with:
1. 2 x (K)158LR elbow
3 1 connector and
2. (K)200X cross connector.

1 1
2

204BA 2
For use with:
1. (K)200X cross connector and
2. (K)151SP straight plug.

1 2 208BA
For use with:
1. (K)200X cross connector and
2. (K)150DR dead-end
receptacle.

205BA
For use with:
1. (K)200X cross connector and 2
2. 2 x (K)152SR straight
connector.

2 2
1

22
1

09/2017
NOTES

23
Nexans Network Solutions N.V. - Div. Euromold
Zuid III, Industrielaan 12, B-9320 Erembodegem
Tel.: +32(0)53 85 02 11 • sales.euromold@nexans.com • www.euromold.be

Catalogue also available on Website and Mobile Apps

Find out more about Nexans Power Accessories.


09/2017