While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility
can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or
modify the characteristics of its products described in this catalogue as standards and technology evolve.
SEPARABLE CONNECTORS
INTERFACE A
Dia. 32.5±0.2
Dia. 31+0.1
- 0.3
Dia. for
+0.02
pin 7.9 - 0.05
0
48 -0.2
9
min
Dia. 48.5±0.2
In mm.
09/2017
CONNECTING POSSIBILITIES
(K)150DP
Dead-end plug
cable
insulation (K)152SR(/G)
(K)151SOP Straight connector
Stand-off plug
250GP cable
Earthing plug earthing
(K)158LR(/G)
Elbow connector
(K)400RTPA tap-off
Reducing tap plug 630/250 A
(K)676RTPA tap-off
Reducing tap plug 1250/250 A
(K)152SR(/G)
Straight connector
disconnectable joint
(K)158LR(/G)
(K)151SP Elbow connector
Straight plug
(K)200T
in-line junction + tap-off Tee connector
09/2017
158LR INTERFACE A
ELBOW CONNECTOR
APPLICATION TECHNICAL
Separable elbow connector CHARACTERISTICS
designed to connect polymeric • The thick conductive EPDM jacket
insulated cable to equipment provides a total safe to touch
(transformers, switchgear, screen which ensures safety for
motors...). personnel.
Also connects cable to cable, • Each separable connector is
using the appropriate mating tested for AC withstand and
part. partial discharge prior to leaving
the factory.
DESIGN 160 mm
Separable connector
comprising: 6/10 (12) kV
1. Conductive EPDM insert. 6.35/11 (12) kV
2. Conductive EPDM jacket. 8.7/15 (17.5) kV
3. Insulating EPDM layer 4 12/20 (24) kV
moulded between the insert 1
12.7/22 (24) kV
and the jacket. 221 mm 5
4. Type A - 250 A interface 2 Up to 24 kV - 250 A
6
as described by CENELEC 3
EN 50180 and 50181.
5. Conductor connector. 7
6. Voltage test point.
7. Earthing lead
(-/G version only).
SPECIFICATIONS AND
STANDARDS
The separable connector 158LR
meets the requirements of
CENELEC HD 629.1.
4
KIT CONTENTS
The complete (K)158LR or The kit also comprises lubricant, wipers,
(K)158LR/G elbow connector installation instructions and crimp chart.
kit comprises the following
components:
(K)158LR/G-W-X
connector kit for
smaller sizes
Connector housing Cable reducer
(K)158BLR/G-W 211CA
Ordering part number Dia. over core insulation (mm) Conductor sizes (mm²)
158LR/G-13-25.95-14-5 14.6 - 22.7 35 - 70
158LR-GAS-50.95-14-5+11TL 19.7 - 25.4 25 - 95
For use with For use with Alupe or For use with For adapted For outdoor Components can be
copper tape C 33-226 cables. other cable types. bail restraints: applications. ordered individually.
screened cables. Please contact our Please contact our see 'Bail restraints and Order: +MWS.
Order: Kit MT. representative. representative. typical applications'.
5
152SR INTERFACE A
STRAIGHT CONNECTOR
APPLICATION TECHNICAL
Separable straight connector CHARACTERISTICS
designed to connect polymeric • The thick conductive EPDM jacket
insulated cable to equipment provides a total safe to touch
(transformers, switchgear, screen which ensures safety for
motors...). personnel.
Also connects cable to cable, • Each separable connector is
using the appropriate mating tested for AC withstand and
part. partial discharge prior to leaving
the factory.
DESIGN
Separable connector 6/10 (12) kV
comprising: 6.35/11 (12) kV
1. Conductive EPDM insert. 100 mm 8.7/15 (17.5) kV
2. Conductive EPDM jacket. 12/20 (24) kV
3. Insulating EPDM layer 12.7/22 (24) kV
moulded between the insert
and the jacket. Up to 24 kV - 250 A
4. Type A - 250 A interface
as described by CENELEC 7
3
6
SPECIFICATIONS AND
STANDARDS 4
The separable connector 152SR
meets the requirements of
CENELEC HD 629.1.
6
KIT CONTENTS
The complete (K)152SR or The kit also comprises lubricant, wipers,
(K)152SR/G straight connector installation instructions and crimp chart.
kit comprises the following
components: (K)152SR/G-W-X
connector kit for
Connector housing Cable reducer smaller sizes
(K)152SRH/G-W 211CA
Conductor
contact (K)152SR-W-X+11TL
151SRC-X connector kit for
or Bail restraint Connector housing Cable adaptor larger sizes
151SRMC-X 151BA (K)152SRH-W 11TL
ORDERING TABLE W
INSTRUCTIONS
Ordering Dia. over core insulation (mm)
Select the part number which
part number min max
gives the best centring to the
cable core insulation diameter 152SR/G-11-X 12.6 16.1
152SR/G-13-X 14.6 18.7
and substitute X using table X,
152SR-FB-X+11TL 17.5 20.2
according to the conductor size 152SR-FG-X+11TL 18.4 21.2
and type. 152SR-GA-X+11TL 19.7 22.5
Add a 'K' for use up to 24 kV. 152SR-GAB-X+11TL 21.0 23.8
152SR-GH-X+11TL 23.6 26.4
EXAMPLE:
The copper wire screened cable TABLE X
is 24 kV, 50 mm2 stranded
aluminium with a diameter over Conductor Aluminium Copper
sizes
core insulation of 20.4 mm. (mm²) DIN hexagonal Deep indent DIN hexagonal
Order a K152SR-FG-50(K)M-
16 - - 16(K)M-11-2
12-2+11TL straight connector 25 25(K)M-12-2 25KM-12-1 25(K)M-11-2
kit. 35 35(K)M-12-2 35KM-12-1 35(K)M-11-2
50 50(K)M-12-2 50(K)M-12-1* 50(K)M-11-2
70 70(K)M-12-2 70(K)M-12-1* 70(K)M-11-2
95 95(K)M-12-2 * 95(K)M-12-1* 95(K)M-11-2*
For an option with a bolted
conductor contact, * The 152SR-FB is not compatible with these conductor contacts.
specify the ordering part
number below.
Ordering part number Dia. over core insulation (mm) Conductor sizes (mm²)
152SR/G-13-25.95-14-5 14.6 - 22.7 35 - 70
152SR-GAS-50.95-14-5+11TL 19.7 - 25.4 25 - 95
For use with For use with Alupe or For use with For adapted For outdoor Components can be
copper tape C 33-226 cables. other cable types. bail restraints: applications. ordered individually.
screened cables. Please contact our Please contact our see 'Bail restraints and Order: +MWS.
Order: Kit MT. representative. representative. typical applications'.
7
151SP INTERFACE A
STRAIGHT PLUG
APPLICATION TECHNICAL
Separable straight plug designed CHARACTERISTICS
to connect polymeric insulated • The thick conductive EPDM jacket
cable to cable. provides a total safe to touch
Mates with the elbow, straight and screen which ensures safety for
branch joint connectors. personnel.
• Each straight plug is tested for AC
withstand and partial discharge
prior to leaving the factory.
DESIGN
Separable connector
comprising:
1. Conductive EPDM insert. 6/10 (12) kV
2. Conductive EPDM jacket. 6.35/11 (12) kV
3. Insulating EPDM layer 8.7/15 (17.5) kV
moulded between the insert 12/20 (24) kV
and the jacket. 12.7/22 (24) kV
4. Type A interface as described
by CENELEC EN 50180 and Up to 24 kV - 200 A
50181.
5. Conductor connector.
223 mm
5
1
3
Dia.
54 mm
8
KIT CONTENTS
The kit also comprises lubricant, wipers,
The complete (K)151SP straight
installation instructions and crimp chart.
plug kit comprises the following
components:
(K)151SP-W-X+11TL
straight plug kit
TABLE X
EXAMPLE:
The copper wire screened cable Conductor Aluminium Copper
is 12 kV, 50 mm2 stranded sizes
(mm²) DIN hexagonal Deep indent DIN hexagonal
aluminium with a diameter over
core insulation of 16.9 mm. 16 - - 16(K)M-11-2
Order a 151SP-A-50(K)M-12- 25 25(K)M-12-2 25KM-12-1 25(K)M-11-2
2+11TL-FA/FAB straight plug kit. 35 35(K)M-12-2 35KM-12-1 35(K)M-11-2
50 50(K)M-12-2 50(K)M-12-1 50(K)M-11-2
70 70(K)M-12-2 70(K)M-12-1 70(K)M-11-2
95 95(K)M-12-2 95(K)M-12-1 95(K)M-11-2
For use with For use with Alupe or For use with For adapted For outdoor Components can be
copper tape C 33-226 cables. other cable types. bail restraints: applications. ordered individually.
screened cables. Please contact our Please contact our see 'Bail restraints and Order: +MWS.
Order: Kit MT. representative. representative. typical applications'.
9
156SA INTERFACE A
SURGE ARRESTER
APPLICATION TECHNICAL
Surge arrester designed to protect CHARACTERISTICS
12 and 24 kV class components, • This surge arrester is a metal
including transformers, oxide varistor surge arrester in an
equipment, cable and accessories elbow configuration.
from high voltage surges resulting • Each arrester is tested for AC
from lightning or switching. withstand and partial discharge
prior to leaving the factory.
DESIGN 2 1
8
6
10
Nominal Rated Max continuous Steep current Lightning current High current
Surge
discharge voltage operating residual residual impulse
arrester
current Ur voltage voltage @ 5 kA voltage @ 5 kA withstand
type
In (kA) (kV) Uc (kV) [1/20 µs] (kV) [8/20 µs] (kV) (kA)
10
TYPICAL APPLICATION AND
DIMENSIONS
415
220 195
156
131
K400RTPA
reducing tap plug
K400TE/G,
K400TB/G or
K440TB/G
connector
330
Surge arrester
156SA-24
In mm.
ORDERING INSTRUCTIONS
To order the surge arrester,
specify the surge arrester type, as
described on previous page.
EXAMPLE:
For a maximum continuous
operating voltage (r.m.s.) of 21 kV.
Order a 156SA-21 surge arrester.
11
180AR-1/180AR-2/180AR-3 INTERFACE A1
EQUIPMENT BUSHINGS
DESIGN
• The equipment bushings are 6/10 (12) kV
6.35/11 (12) kV
28
ORDERING INSTRUCTIONS M6
12
FIXINGS FOR EQUIPMENT BUSHINGS
180AR-1/GS 180AR-1/J
180AR-1-G/GS 180AR-1-G/J
180AR-2/GS 180AR-2/J
180AR-3/GS AND 180AR-3/J AND
180AR-3-G/GS BUSHINGS 180AR-3-G/J BUSHINGS
bushing interface
fixing studs
NF C 52-053
clamp E DIN 42 538
stud clamp
equipment
sealing gasket
equipment
connection
A DIN 42 538
tabs for bail restraint fixing flange
earth jumper
earth plate
Min. 55 Min. 55
Max. 30 Max. 30
3 fixing 4 fixing 13
studs Dia. 78 studs Dia. 78
Dia. 126 Dia. 123 In mm.
180A-24P-O INTERFACE A1
IN-AIR BUSHING
APPLICATION TECHNICAL
For use in equipment insulated CHARACTERISTICS
with air, typically for dry type Each bushing is tested for
transformers, motors, switchgear, AC withstand and partial
capacitors... discharge prior to leaving the
factory.
SPECIFICATIONS AND
STANDARDS
The plug-in type equipment 59
bushings 180A-24P-O are
moulded epoxy insulated parts 6/10 (12) kV
and meet the requirements of 20 6.35/11 (12) kV
CENELEC EN 50181, IEC 60071 8.7/15 (17.5) kV
and IEC 60137.
Dia. 70
12/20 (24) kV
A
Dia. 110 12.7/22 (24) kV
Up to 24 kV - 250 A
20
M10
B Dia. 80
In mm.
14
FIXINGS FOR EQUIPMENT BUSHINGS
180A-24P-O IN-AIR BUSHING
bushing interface
fixing studs and
nuts M10
earth jumper
equipment
gasket
equipment
connection
fixing flange
fixing flange
BCA-B or
BCA-D BCA-F
120°
126
120°
BS 2562 stand.: 120
DIN 42 538 stand.: 123 Dia. 150
Dia. 150
Type BCA-B : BS 2562 British standards Type BCA-F : NF C 52-053 French standards
Type BCA-D : DIN 42 538 German standards
M10 M10
Min. 55
Min. 55
Max. 20
Max. 20
4 fixing
3 fixing
studs 15
studs
Dia. 82
Dia. 82
Dia. 126
Dia. 123
In mm.
PITO-E PLUG-IN TERMINATION
APPLICATION TECHNICAL
• Separable termination designed CHARACTERISTICS
to connect overhead lines or bus Each plug-in termination is tested
bars to equipment. for AC withstand prior to leaving
• Is suitable for indoor and the factory.
outdoor use for medium polluted
atmosphere.
DESIGN
The plug-in termination is a
moulded epoxy insulated part. 6/10 (12) kV
It meets the type A - 250 A 6.35/11 (12) kV
interface as described in 8.7/15 (17.5) kV
CENELEC EN 50180 and 50181. 12/20 (24) kV
12.7/22 (24) kV
Up to 24 kV - 250 A
SPECIFICATIONS AND
STANDARDS
The separable termination PITO-E
meets the requirements of IEC
60137.
ORDERING INSTRUCTIONS
To order the plug-in termination
for 12 or 24 kV, specify PITO-E.
The kit includes the bail restraint
and 2 brass nuts.
In mm.
16
ACCESSORIES INTERFACE A
17
200T ORDERING INSTRUCTIONS
SEPARABLE TEE CONNECTOR Order
Is designed to connect three cables 200T for 12 kV or
of the same or varying sizes or two K200T for 24 kV
cables to equipment. applications.
For an adapted bail, please refer
to the catalogue or contact our
representative.
18
09/2017
BAIL RESTRAINTS INTERFACE A
147BA 149BA
For use with: For use with:
1. (K)152SR straight connector, 1. (K)158LR elbow connector,
2. (K)200T tee connector and 2. (K)200T tee connector and
3. (K)150DR dead-end 3. (K)150DR dead-end
receptacle. receptacle.
1 3 3 1
2 2
148BA
For use with:
1. (K)158LR elbow connector and
2. (K)150DP dead-end plug. 150BA-B1
For use with:
1. (K)158LR elbow connector
1 and
2. an interface A equipment
bushing (shown), 250GP
earthing plug, (K)151SOP
stand-off plug (shown) or
(K)1501J3-U-8 three-way
2 junction.
1 1
2 2
09/2017
19
150TB-1 153BA
For use with: For use with:
1. (K)200T tee connector and 1. (K)152SR straight connector
2. an interface A equipment and
bushing (shown), 250GP 2. (K)150DP dead-end plug.
earthing plug, (K)151SOP
stand-off plug (shown) or
(K)1501J3-U-8 three way 1
junction.
1 1
2 2 154BA-CS180
For use with:
1. (K)151SP straight plug and
151BA 2. (K)150DR dead-end
For use with: receptacle.
1. (K)152SR straight connector 2 1
and
2. an interface A equipment
bushing (shown), 250GP
earthing plug, (K)151SOP
stand-off plug (shown) or
(K)1501J3-U-8 three-way 155BA-1
junction. For use with:
1. 2 x (K)152SR straight
connector and
1 1
2. (K)200T tee connector.
1 1
2 2
2
09/2017
156BA-1 159BA
For use with: For use with:
1. (K)200T tee connector and 1. 2 x (K)158LR elbow connector
2. (K)150DP dead-end plug. and
2. (K)200T tee connector.
1 1
2 2
157BA - CS181
For use with:
1. (K)152SR straight connector
and 200BA
2. (K)151SP straight plug. For use with:
1. (K)152SR straight connector
and
2. (K)200X cross connector.
1 2
158BA
For use with:
1. (K)152SR straight connector,
2. (K)200T tee connector
and
3. (K)158LR elbow connector.
2
1 3
201BA
For use with:
2
1. (K)158LR elbow connector
and
2. (K)200X cross connector.
21
2
202BA 206BA
For use with: For use with:
1. (K)152SR straight connector, 1. (K)152SR straight connector,
2. (K)200X cross connector and 2. (K)200X cross connector and
3. (K)150DR dead-end 3. (K)158LR elbow connector.
receptacle.
1 3 1 3
2 2
203BA
For use with:
1. (K)158LR elbow connector,
2. (K)200X cross connector and
3. (K)150DR dead-end 207BA
receptacle. For use with:
1. 2 x (K)158LR elbow
3 1 connector and
2. (K)200X cross connector.
1 1
2
204BA 2
For use with:
1. (K)200X cross connector and
2. (K)151SP straight plug.
1 2 208BA
For use with:
1. (K)200X cross connector and
2. (K)150DR dead-end
receptacle.
205BA
For use with:
1. (K)200X cross connector and 2
2. 2 x (K)152SR straight
connector.
2 2
1
22
1
09/2017
NOTES
23
Nexans Network Solutions N.V. - Div. Euromold
Zuid III, Industrielaan 12, B-9320 Erembodegem