Function overview
13
14
15
Siemens SIP · Edition No. 7 7/3
Line Differential Protection / 7SD60
Application, construction
Application
LSP2002-afpen.tif
is realized by means of a pair of symmetrical pilot wires allowing
3 distances of up to approximately 12 km. Adaptation to the pilot-
wire resistance is effected by means of software within the unit.
Therefore, matching is not necessary.
10 85 Intertrip, remote trip The unit can be supplied in two different housings. The one for
flush mounting in a panel or cubicle has connection terminals at
86 Lockout function the rear.
Single-stage, definite-time emergency The version for panel surface mounting is supplied with terminals
11 50
overcurrent protection accessible from the front. Alternatively, the unit can be supplied
with two-tier terminals arranged above and below the unit.
12
13
14
15
7/4 Siemens SIP · Edition No. 7
Line Differential Protection / 7SD60
Protection functions
Protection functions
function is available as an option. To achieve this, 2 kHz pulses Vector group adaptation is not effected inside the unit and must,
with a defined pulse width ratio are transmitted to the remote where necessary, be brought about by means of an external
11 relay via the pilot wires. Detection of a fault in the pilot-wire link
results in blocking of the differential protection.
matching transformer scheme.
12
13
14
15
7/6 Siemens SIP · Edition No. 7
Line Differential Protection / 7SD60
Features
Features
10
11
12
13
14
15
Siemens SIP · Edition No. 7 7/7
Line Differential Protection / 7SD60
Connection diagrams
Connection diagrams
5
Fig. 7/6 Standard connection L1-L3-E,
suitable for all types of networks
9
Fig. 7/7 Protection configuration with main
10 (7SD60) and backup overcurrent
(7SJ60) protection
11
12
13
14
Fig. 7/8 Typical circuit for auxiliary voltage
15 supply
11
12
13
14
15
Siemens SIP · Edition No. 7 7/9
Line Differential Protection / 7SD60
Technical data
1 Specification
Standards IEC 60255-5 ANSI/IEEE C37.90.0
Standard
Conducted interference voltage
EN 50081- (generic standard)
150 kHz to 30 MHz
on lines, auxiliary voltage only,
Insulation tests
EN 55022, VDE 0878 Part 22,
Voltage test (routine test) CISPR 22, limit value, limit class B
15
7/10 Siemens SIP · Edition No. 7
Line Differential Protection / 7SD60
Technical data
Setting ranges
connection
Tolerances
Delay time/release delay
1 % and 10 ms respectively 6
Current threshold I1 I/IN Line: 0 to 1.5 (step 0.01)
(release by local station current) Inherent delay
Differential current I/IN Line: 0.5 to 2.5 (step 0.01) Transmission time without delay Approx. 80 ms
Delay time t
Restraint by 2nd harmonic
0 to 60 s (step 0.01 s) Lockout function
Lockout seal-in of trip command For differential protection and
7
(see Fig. 7/4) remote trip until reset
2fN /fN 10 to 80 % Lockout reset By means of binary input and/or local
Reset ratio Approx. 0.7 – drop-off ratio
Inherent delays
(IRestraint = 0)
operator panel/DIGSI
8
TRIP time for two-end supply Approx. 20 to 28 ms without Additional functions
at 4 x set value restraint by 2nd harmonic Operational measured values
Approx. 32 to 42 ms with restraint
by 2nd harmonic
Operational currents
Measurement range
I1, I2, IDiff, Irestraint
0 to 240 % IN 9
Drop-off time Approx. 35 ms Tolerance (I1) 3 % of rated value or of measured
Tolerances at preset values under value
reference conditions Fault event recording Storage of the events relating to the
Local station current threshold
Differential current
± 3 % of setpoint, min. 0.02 x IN
± 5 % of setpoint, min. 0.02 x IN Time-tagging
last 8 faults 10
Influence parameters Resolution for operational 1s
Auxiliary supply voltage ≤1% events
0.8 ≤ Vaux/VauxN ≤ x 1.15 for fault events 1 ms
Temperature in range
0 °C ≤ Θamb ≤ 40 °C
≤ 1 %/10 K Fault recording (max. 8 faults) 11
Storage time (from response Total of 5 s max., pre-trigger and
Frequency in range 0.9 ≤ f/fN ≤ 1.1 ≤4% or trip command) post-fault time settable
Pilot wires Maximum length per
Number 2
Symmetric telephone pairs are
recording Tmax
Pre-trigger time Tpre
0.30 to 5.00 s (step 0.01 s)
0.05 to 0.50 s (step 0.01 s)
12
recommended with loop resistance Post-fault time Tpost 0.05 to 0.50 s (step 0.01 s)
73 Ω/km and capacitance 60 nF/km Time resolution at 50 Hz 1 instantaneous value per 1.66 ms
Core-to-core asymmetry at 800 Hz Max. 10-3 Time resolution at 60 Hz 1 instantaneous value per 1.38 ms
Maximum loop resistance 1200 Ω Circuit-breaker test Using test circuit 13
Permissible induced longitudinal
voltages
On direct connection of the ≤ 1.2 kV, however, max. 60 % of
pilot wires
For connection via isolating
the test voltage of the pilot wires
≥ 1.2 kV, however, max. 60 % of 14
transformer the test voltage of the pilot wires
and max. 60 % of the test voltage
of the isolating transformers
15
Siemens SIP · Edition No. 7 7/11
Line Differential Protection / 7SD60
Technical data
3 Symmetrical three-phase 0.7 0.2 0.5 Further applicable standards: ANSI/IEEE C37.90.0 and C37.90.1.
This conformity is the result of a test that was performed by
Connections 4AM4930-7DB 4AM4930-6DB Siemens AG in accordance with Article 10 of the Council Directive
CT rated current IN = 1 A IN = 5 A complying with the generic standards EN 50081-2 and EN 50082-2
for the EMC Directive and standard EN 60255-6 for the “low-voltage
4 Number of turns
Primary windings A to B 5 1
Directive”.
C to D 10 2
E to F 15 3
G to H 30 6
5 I to K
K to L
30
30
6
6
L to M 60 12
Secondary windings Y to Z 1736 1736
6 Thermal rating
Continuous
A to B
C to D
4.5
4.5
20
20
current E to F 4.5 20
in Amperes G to H 4.5 20
I to K 1.2 6.5
7 K to L
L to M
1.2
1.2
6.5
6.5
Y to Z 0.2 0.2
Secondary rated Y to Z 20 mA 20 mA
13
14
15
7/12 Siemens SIP · Edition No. 7
Line Differential Protection / 7SD60
Selection and ordering data
Operating language
English – alternatively either German or Spanish can be selected 0 5
Scope of functions
Differential protection 0
Differential protection, inrush restraint
Differential protection, pilot-wire monitoring, remote trip
1
2
6
Differential protection, pilot-wire monitoring, remote trip, inrush restraint 3
10
11
12
13
14
15
Siemens SIP · Edition No. 7 7/13
Line Differential Protection / 7SD60
Selection and ordering data
1 DIGSI 4
Software for configuration and operation of Siemens protection
units running under MS Windows 2000 / XP Professional Edition
Basis
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for control
4 displays),
DIGSI 4 Remote (remote operation)
+ IEC 61850 system configurator 7XS5403-0AA00
SIGRA 4
5 Software for graphic visualization, analysis and evaluation of
fault records. Can also be used for fault records of devices of
other manufacturers (Comtrade format). Running under
MS Windows 2000 or XP Professional Edition. (generally contai-
ned in DIGSI Professional, but can be ordered additionally)
6 Authorization by serial number. On CD-ROM. 7XS5410-0AA00
Connecting cable
Cable between PC/notebook (9-pin connector)
Converter RS485↔FO
Rated auxiliary voltage DC 24 to 250 V and AC 250 V
Isolating transformer
Up to 20 kV 7XR9513
12 Up to 5 kV 7XR9515
13
14
1) Possible versions see part 13.
* RS485 bus system up to 115 kbaud
RS485 bus cable and adaptor
15 7XV5103- AA ; see part 13.
10
11
12
13
14