Revision 1.0 Digit 3 Digit 2 Digit 1 Digit 0

0 0 F 1
Define the action to be taken while executing 0000 0000 1111 0001
this step.
1 Run Forward
2 Use Accel/Decel 1 HOW TO USE THIS WORKSHEET
3 Logic Output State = Off
Lines 1-6 contain drop down list boxes. Click the
When the logic conditions specified in digit 1 are green highlighted line to the right of the line number.
met, how should the drive respond? A drop down arrow will appear. Click the arrow to
show the list box. Choose the desired selection from
4 Jump to Step 0 the list. The parameter value (code) to set in the
parameter will be displayed above.

What are the logic conditions that are required to


perform the action defined in digit 2?
5 Ignore this logic and action programmed in digit 2

What are the logic conditions that are required to


transition to the next step?
6 Step when [Stp Logic Time x] expires
Digit 3

Accel/Decel Commanded
Setting Parameters Used Step Logic Output State Direction code
14 0 1 Off Run Forward 14 0
24 1 1 Off Run Reverse 15 6
34 2 1 Off No Output 17 3
17 3 1 On FWD 18 9
27 4 1 On REV 24 1
37 5 Use Accel/Decel 1 Logic Output State = On No Output 25 7
15 6 Use Accel/Decel 2 Logic Output State = Off FWD 27 4
25 7 2 Off REV 28 A
35 8 2 Off No Output 34 2
18 9 2 On FWD 35 8
28 A 2 On REV 37 5
38 b 2 On No Output 38 b

10 fwd
0 rev
1=1,2=2 0=off,1=on 0 no output
14 1 3 10 sum
0
0000
Digit 2 Digit 1

Setting Logic Setting Logic


0000 0 Jump to Step 0 1 0 0000 0 Skip Step - jump immediately
0110 1 Jump to Step 1 0 1 0001 1 Step when [Stp Logic Time x] expires
0011 2 Jump to Step 2 0 2 0010 2 Step if Logic In1 is on
1001 3 Jump to Step 3 0 3 0011 3 Step if Logic In2 is on
0001 4 Jump to Step 4 0 4 0100 4 Step if Logic In1 is off
0111 5 Jump to Step 5 0 5 0101 5 Step if Logic In2 is off
0100 6 Jump to Step 6 0 6 0110 6 Step if either Logic In1 or Logic In2 is on
1010 7 Jump to Step 7 0 7 0111 7 Step if both Logic In1 and Logic In2 is on
0010 8 End-Normal Stop 0 8 1000 8 Step if neither Logic In1 or Logic In2 is on
1000 9 End-Coast Stop 0 9 1001 9 Step if Logic In1 is on and Logic In2 is off
0101 A End and Fault F2 0 A 1010 A Step if Logic In2 is on and Logic In1 is off
1011 b Step after [Stp Logic Time x] and Logic In1 is on
0 C Step after [Stp Logic Time x] and Logic In2 is on
0000 d Step after [Stp Logic Time x] and Logic In1 is off
E Step after [Stp Logic Time x] and Logic In2 is off
F Ignore this logic and action programmed in digit 2

F
1111
Digit 0

Setting Logic
0 0 0000 SKIP 0 Skip Step - jump immediately 0 0 0000
0 1 0001 TIMED 1 Step when [Stp Logic Time x] expires 1 1 0001
0 2 0010 1 2 Step if Logic In1 is on 0 2 0010
0 3 0011 1 3 Step if Logic In2 is on 0 3 0011
0 4 0100 0 4 Step if Logic In1 is off 0 4 0100
0 5 0101 0 5 Step if Logic In2 is off 0 5 0101
0 6 0110 OR 6 Step if either Logic In1 or Logic In2 is on 0 6 0110
0 7 0111 AND 7 Step if both Logic In1 and Logic In2 is on 0 7 0111
0 8 1000 NOR 8 Step if neither Logic In1 or Logic In2 is on 0 8 1000
0 9 1001 XOR 9 Step if Logic In1 is on and Logic In2 is off 0 9 1001
0 A 1010 XOR A Step if Logic In2 is on and Logic In1 is off 0 A 1010
0 b 1011 TIMED AND b Step after [Stp Logic Time x] and Logic In1 is on 0 b 1011
0 C 1100 TIMED AND C Step after [Stp Logic Time x] and Logic In2 is on 0 C 1100
0 d 1101 TIMED OR d Step after [Stp Logic Time x] and Logic In1 is off 0 d 1101
0 E 1110 TIMED OR E Step after [Stp Logic Time x] and Logic In2 is off 0 E 1110
1 F 1111 IGNORE F Ignore this logic - follow logic in Digit 1 0 F 1111