THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO.

NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
NOTES:

19. SELECTOR CAN BE PART OF MULTI-FUNCTION RELAY, 1. CONTROL POWER FOR THE 0.48kV CIRCUIT BREAKERS
TO 13.8kV SWITCHGEAR TO 13.8kV SWITCHGEAR
K84-242-SG-301 BUS 1 K84-242-SG-301 BUS 2 IF AVAILABLE. SHALL BE 125V DC.
SEE DWG. No. SEE DWG. No.
RA-460461 SH.001 RA-460461 SH.001 20. CIRCUIT BREAKERS SHALL BE EQUIPPED WITH 2. THE 480V SWITCHGEAR AUTOMATIC TRANSFER
INTEGRAL, DIRECT ACTING, ADJUSTABLE SOLID-STATE SCHEME AND POWER SYSTEM AND EQUIPMENT
(SST) SYSTEMS, IN ACCORDANCE WITH 16-SAMMS-502. PROTECTION SHALL BE IN ACCORDANCE WITH
SAES-P-114 AND 16-SAMSS-502. THE ATS SCHEME
SHALL SOUND AN ALARM WHEN PRE SELECTED
BREAKER DOES NOT OPEN AFTER SPECIFIED TIME
DURING PARALLELING. THE CONTROL VOLTAGE
SHALL BE 125V DC. EACH DC CONTROL VOLTAGE
BUS SHALL HAVE AN UNDERVOLTAGE RELAY THAT

PC PC-1836 CC CC-1027 CC CC-1031 PC PC-1866 SHALL INITIATE AN ALARM.

3. THE CONTACTS FROM RELAYS INDICATED SHALL BE


PC-1850 PC-1880
CONNECTED TO A TERMINATION POINT WITHIN ONE
OF THE LV COMPARTMENTS. LOSS OF CONTINUITY
AT THE TERMINATION POINT WILL ALARM AT THE
ANNUNCIATOR SCREEN, IN ACCORDANCE WITH
K84-242-XFR(T)-303 K84-242-XFR(T)-304
13.8/0.48kV ALARM ALARM 13.8/0.48kV 15-SAMSS-502.
26 26
2.5/3.125MVA 2.5/3.125MVA
Z=5.75%%% Z=5.75%%% 4. EACH PML METER SHALL BE CONNECTED TO
ALARM ALARM SUBSTATION ETHERNET HUB VIA CAT5 CABLE
49 49

BY MEANS OF "STAR TOPOLOGY". POWER SUPPLY


ALARM/TRIP ALARM/TRIP TO EACH PML METER SHALL BE 125V DC.
63 63

5. ALL MULTI-FUNCTION RELAY SHALL BE MICROPROCESSOR


ALARM/TRIP ALARM/TRIP
71 71 TYPE IN ACCORDANCE WITH 16- SAMSS-513, SAES-P-114
AND SHALL BE AS PER IEC 61850
3200/5 ALARM ALARM 63 3200/5
63 FOR OSAS IMPLEMENTATION.
PRD PRD

6. 27 FUNCTION IN MULTI-FUNCTION RELAY


63 ALARM ALARM 63
PVG PVG SHALL PREVENT TRANSFER TO ALTERNATE SOURCE
IF ALTERNATE VOLTAGE IS NOT WITHIN SPECIFIED
27 ALARM ALARM 27
AC AC TOLERANCE.

DENOTES CABLE NUMBER.


PC-XXXX
7. PC
CC-XXXX

8. ALL LOCKOUT RELAYS SHALL BE SUPERVISED BY


CC CC-1030 PC PC-1836 CC CC-1028 CC-1032 CC PC-1866 PC CC CC-1034 A RELAY (74) AS PER 16-SAMMS-502, OMITTED FROM
CC-1029 CC-1033 THIS DRAWING FOR CLARITY.
PC-1850 PC-1880
CABLE BUS CABLE BUS 9. FAULT RATING AS PER ANSI C37.06 (1987).
3200A 3200A

10. THE SELECTED PROTECTIVE SYSTEMS SHALL BE


REVIEWED & VERIFIED BY S.A. PDD.
13.8kV UPSTREAM SWGR.

13.8kV UPSTREAM SWGR.


0.48kV SWITCHGEAR 11. SWITCHGEAR RATING, TRANSFORMER IMPEDANCE
K84-242-SG-002 VALUES AND CT TYPES, RATIOS AND CLASSES
ARE TO BE VERIFIED DURING DETAILED DESIGN.
ETHERNET ETHERNET
SWITCH SWITCH 12. MULTI-FUNCTION RELAY SHALL HAVE A VOLTAGE

13.8kV UPSTREAM SWGR.

13.8kV UPSTREAM SWGR.


INPUT FROM A DEDICATED FUSE.
TRIP TO

TRIP TO
13. DENOTES EQUIPMENT MOUNTED ON TRANSFORMER.
50 50
51
51NT G G
51
51NT 14. TRANSFORMER MECHANICAL ALARMS SHALL BE
TS TS ANNUNCIATED THROUGH MULTI-FUNCTION RELAY.
86 74 R R 86 74 AN INDEPENDENT LOCKOUT RELAY (86T) SHALL BE

TRIP FROM

TRIP FROM
PROVIDED FOR THE TRANSFORMER MECHANICAL TRIPS,
3200/5A TS ETHERNET TS 3200/5A
3 25 27-1A 25 27-1A 3
EG. 63, 73.
SWITCH G

15. FAN FAILURE ALARM SHALL BE INCLUDED FOR


METER 27-1B
R
METER 27-1B TRANSFORMER FORCED COOLING FANS.
NOTE 2
TYPICAL 50
16. LOW OIL LEVEL TRIP/ALARM (71) SHALL BE PROVIDED

CLOSE/OPEN
51N
FOR ALL SELECTORS 51 WHERE THIS FUNCTION IS NOT PROVIDED BY
CLOSE/OPEN

CLOSE/OPEN
BUCHHOLZ (63) DEVICE.
43 43
86 74
43 1/T/2 R/L 43
J001 R/L R/L J002 17. AS PER PARA 5.1.3 OF 16-SAMSS-513, IF THE DESIGN
480/120V 480/120V
2 43 52 2 OF THE RELAY CASE DOES NOT INHERENTLY PROVIDE
25 ATS
A/M CS
52 TRANSFER SIGNAL (27(62)-1A) TRANSFER SIGNAL (27(62)-1A) 52
A TEST CAPABILITY, EXTERNAL TEST SWITCHES OR A
CS
BLOCK TRANSFER (86+27-1B+51NB) BLOCK TRANSFER (86+27-1B+51NB) CS TEST-PLUG-AND-SOCKET ARRANGEMENT SHALL BE
METER
BLOCK TRANSFER BLOCK TRANSFER PROVIDED. THE TEST CAPABILITY SHALL PROVIDE THE
MEANS TO ISOLATE THE RELAY FROM THE INPUTS
OPEN

OPEN
WHILE SAFELY SHORTING THE CT CONNECTIONS AND
TS TS TS
ALLOWING CONNECTIONS OF SECONDARY INJECTION
K84-242-CB-011 K84-242-CB-012
3200A 3200A
TEST EQUIPMENT.
N.C N.C
18. THE STATUS OF MOC AND TOC CONTACTS SHALL BE

OPEN
CONNECTED TO THE CORRESPONDING RELAYS.
LT LT
SST

SST
ST ST ETHERNET
ETHERNET
SWITCH GF GF SWITCH REFERENCE DRAWINGS
NOTE 1 TITLE DRAWING NO.
TYPICAL
FOR ALL CB SINGLE LINE DIAGRAM LEGEND & SYMBOL RA-280960-003

SUBSTATION 242 OVERALL ONE LINE DIAGRAM RA-460460-001


CONTROLLER CONTROLLER
13.8kV PROT. & METERING K84-242-SG-301 RA-460461-001
ONE LINE DIAGRAM 0.48kV MCC K84-242-MCC-003 RA-859103-001~006

LT ONE LINE DIAGRAM 0.48kV MCC K84-242-MCC-004 RA-859104-001~006


480V, 3{, 60Hz, 3200A, 85kA, SYM. BUS-1 3 480V, 3{, 60Hz, 3200A, 85kA, SYM. BUS-2
ST ONE LINE DIAGRAM 0.48kV MCC K84-219-MCC-006 RA-859106-001, 002
3200/5A GF
K84-242-CB-013 ONE LINE DIAGRAM 0.48kV MCC K84-242-MCC-009 RA-859109-001
3200A
SST
N.O 125V DC UPS ONE LINE DIAGRAM K84-242-BC-001/2 RA-460469-001
CLOSE/OPEN

CLOSE/OPEN

CLOSE/OPEN

CLOSE/OPEN

CLOSE/OPEN

CLOSE/OPEN

CLOSE/OPEN

CLOSE/OPEN

CLOSE/OPEN
52 52 52 52 52 52 52 52 52
K84-242-CB-014 K84-242-CB-015 K84-242-CB-016 K84-242-CB-017 K84-242-CB-018 K84-242-CB-019 K84-242-CB-010
CS CS CS CS CS CS CS CS CS
1600A 800A 1600A 800A 1600A 800A 1600A

G G G G J003 J004 G G G G G

LT LT LT 480/120V 480/120V LT LT LT LT
SST

SST

SST

SST

SST

SST

SST
2 2
ST ST ST ST ST ST ST
R R R R R R R R R
GF GF GF GF GF GF GF

REVISION VALIDATION

THIS REVISION NO. 01 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

10-00455-0002-402

DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER


(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

JHY KYS AAB MAB


05/20/12 05/20/12 05/20/12 05/20/12

REV.NO. DATE REVISION DESCRIPTION

01 05/20/12 AS-BUILT

JOB ORDER/EWO NO.


THIS REVISION IS NOT TO BE USED FOR
10-00455-0002 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY


DRAWING TYPE

ELECTRICAL ONE LINE DIAGRAM E1L


SPACE SPARE TO TO TO TO SPARE SPARE SPACE
K84-242-MCC-003 K84-242-MCC-009 K84-242-MCC-004 K84-219-MCC-006
SEE DWG. No. SEE DWG. No. SEE DWG. No. SEE DWG. No.
0.48KV PROT.&METER.K84-242-SG-002
RA-859103 SH.001 RA-859109 SH.001 RA-859104 SH.001 RA-859106 SH.001
SULFUR RECOVERY PLANT

KHURSANIYAH SAUDI ARABIA


PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

K84 P RA-460466 001 01


Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-05


BA-414707 001 00 P 01S329 190 TO 480V DISTR. PANEL-B (MOV-07)
TO MOV-07 NOTES:
TO MOV-11 TO 480V DISTR. PANEL-B (MOV-11)
REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO. JOB ORDER/EWO NO. 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO.NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
TO MOV-06 TO 480V DISTR. PANEL-B (MOV-06) OTHERWISE NOTED.
TO MOV-14 TO 480V DISTR. PANEL-B (MOV-14)
2. FOR GROUNDING SYSTEM INSTALLATION, REFER
TO SAES-P-111.

3. REFER TO SAUDI ARAMCO STANDARD DRAWING NO.


DD-950022 SHT. 008 AND 011 FOR GROUND
CONNECTION DETAIL.

800 300 800 300 4. OUTDOOR SWITCHRACK SHALL BE IN ACCORDANCE WITH


735 736 737 739 740 741 742 743 SAUDI ARAMCO ENGINEERING STANDARD SAES-P-114
AND SAES-P-116 AND MATERIAL SYSTEM
701 702 703 704 710 716 (TYP. 4) 23000 SPECIFICATION 16-SAMSS-512.

701 702 703 704 710 716 500 3000 2500 5. LAYING OF DIRECT BURIED CABLES SHALL BE DONE
701 702 703
734 735 736 737 739 IN ACCORDANCE WITH STANDARD DRAWINGS AB-036326,
704 710 716 AB-036273 AND AD-036874.
480V DISTRIBUTION PANEL "A" 480V DISTRIBUTION PANEL "B"
EXISTING 6. ALL DIMENSIONS AND LOCATION SHALL BE FIELD
SPARE SPARE SPARE SPARE SPARE 190-GM-18

DIKE
SPARE 190-GM-17 SPARE
MOV-03 MOV-02 MOV-11 MOV-06 728 729 730 731 732 (TYP.2) LIGHTING POLE VERIFIED AND CHECKED PRIOR TO CONSTRUCTION OR
SEWAGE SEWAGE
FABRICATION.
PUMP PUMP NEW SWITCHRACK
SPARE SPARE MOV-07 MOV-14 7. DISCONNECTED POWER CABLE FOR MOV-2, MOV-3,
190-SR-001
SEE DETAIL MOV-6, MOV-7, MOV-11 & MOV-14 AND RELOCATED TO
SPARE SPARE SPARE SPARE NEW 480V DISTRIBUTION PANEL NO. A AND B.
ON THIS DRAWING
8. EXISTING COMBINATION BREAKER AND STARTER PANEL
DIRECT BURIED
FOR MOV-2, MOV-3, MOV-6, MOV-7, MOV-11 & MOV-14

33000
760 712 729
709 729 730 731 732 761 CABLE
ARE TO BE DISCONNECTED AND REMOVED FROM
730 731 732 705 PC-1793 SWITCHRACK "A" & "B", PUMP STATION APS-4.
712 734 735 736 737 (TYP.4)
761 9. CONDUIT STUB-OUT FOR TWO SPARES COMBINATION
STARTER AND BREAKER SHALL BE CAPPED.
7200

EXISTING
SWITCHRACK 10. DUCT BANKS SHALL HAVE 20% SPARE HOLES
NOTE-8
706 711 718 AS PER SAES-P-104 PARA. 10.4.8.
DETAIL-1 BELOW 11. INSTALLATION OF CABLE MARKER SHALL BE DONE IN
755 ACCORDANCE WITH STANDARD DRAWING AB-036273.
718 755

LEGEND
TO MOV-03 TO MOV-014 TRANSFORMER
706 711 714 721 722 TO MOV-011 (EXISTING)
TO GROUND GRID 17000
TO GROUND GRID TO GROUND GRID TO TO MOV-007 NEW INSTALLATION
TO MOV-02 TO NEAREST GROUND GRID MOV-006 TO GROUND GRID
TO GROUND GRID
EXISTING INSTALLATION
FROM SUB. #52 FROM SUB. #52
710 745 752 710 745 752
MCC-1, 3F-AL MCC-1, 3R-BL
PC-1791 PC-1792 CABLE MARKER
DWG. NO. XA-F94642 DWG. NO. XA-F94642
SHT. 001 SHT. 002

480V DISTRIBUTION PANELS-A/B INSTALLATION DETAIL CONDUIT INSTALLATION DETAIL FOR


AT SWITCHRACK "A" ABQAIQ PUMP STATION APS-4 MOV-06, 07, 11 AND 14 AT SWITCHRACK "B" PUMP STATION APS-4 BOOSTER PUMP STATION-A PLAN
SCALE NTS SCALE NTS SCALE NTS
400 150 150 400 400 150 150 400

404 411 404 411


400

400
419 419
REFERENCE DRAWINGS
DRAWING CONTROL BD-414702
ONE LINE DIAG. 480V DISTR. PANELS A/B, APS #4BA-414705
CABLE AND CONDUIT SCHEDULE DD-902813
746 756 757 746 756 757
840

840
ELECTRICAL DETAILS BOOSTER PUMP STA "A" AA-026218
14000 3000 3000 8000 ELECTRICAL DETAILS BOOSTER PUMP STA "B" AA-026219

NEW SWITCHRACK
734 735 736 737 739 734 735 736 737 739 190-SR-002

8000
SEE DETAIL

DIKE
ON THIS DRAWING DIKE
480V DISTRIBUTION PANEL NO.2A 480V DISTRIBUTION PANEL NO.2B
701 702 703 704 716 754 701 702 703 704 716 754
MOV-46 MOV-47 MOV-50 MOV-51
800

800
(TYP.5) (TYP.5) EXISTING
411 411 LIGHTING POLE
MOV-48 MOV-49 MOV-52 MOV-53
709 729 730 731 732 761 709 729 730 731 732 761
TYP. 2 TYP. 2 DIRECT BURIED
SPARE MOV-67 SPARE MOV-101 CABLE

34000
PC-1794
404 750 404 750
408 408
728 728
412 729 730 731 732 754 800 412 729 730 731 732 754 800
1200

1200
TYP. 2 TYP. 2
EXISTING
SEE NOTE- 2 & 3 SEE NOTE- 2 & 3 SWITCHRACK
409 410 409 410
706 711 714 721 722 755 706 711 714 721 722 755 CONDUIT
TYP. 2 TYP. 2
STUB-UP
SCALE: NONE
FFL FFL

REVISION CERTIFICATION EDSD


VERIFICATION
00
401 407 414 415 416 417 418 401 407 414 415 416 417 418 THIS INDICATES THAT REV. NO.
OF THIS DRAWING IS COVERED, FOR ALL
8000 APPROVAL/CERTIFICATION REQUIREMENTS,
CONTROL NUMBER

(TYP.2) (TYP.2) BY DRAWING COMPLETION CERTIFICATE (DCC) BY:


NO.: 01S329-01
NEW JUNCTION . DATE:
TO NEAREST GROUNDING GRID TO GROUNDING GRID
BOX
TO EXISTING PULLBOX/ TO JB-190-218-7 TO EXISTING LIGHT TO EXISTING PULLBOX/ TO JB-190-218-7 TO EXISTING LIGHT TRANSFORMER
JUNCTION BOX @ 600 600 JUNCTION BOX @ 600 600
(MOV-67) CIRCUIT @ SWRK-A (MOV-67) CIRCUIT @ SWRK-A (EXISTING)
SWITCHRACK-A SWITCHRACK-A
2000 2000
TO JB-190-218-1 TO JB-190-218-7 TO JB-190-218-1 TO JB-190-218-7
(MOV-46) (MOV-47) (MOV-46) (MOV-47)
TO JB-190-218-1 TO JB-190-218-7 TO JB-190-218-1 TO JB-190-218-7
(MOV-48) 480V DISTRIBUTION PANEL-2A INSTALLATION DETAIL (MOV-49) (MOV-48) 480V DISTRIBUTION PANEL-2B INSTALLATION DETAIL (MOV-49)
REV.
AT SWITCHRACK 190-SR-001 BOOSTER PUMP STATION-A AT SWITCHRACK 190-SR-002 BOOSTER PUMP STATION-B BOOSTER PUMP STATION-B PLAN NO.
DATE JO/EWO DESCRIPTION ENGG. CERT. PMT OPRNS.

SCALE NTS SCALE NTS DESIGN REVIEW FOR


SCALE NTS THIS REVISION IS NOT TO BE USED FOR CONSTRUCTION
UNTIL CERTIFIED AND DATED. CERTIFICATION KEY DRAWINGS
I BEAM
708 DESIGN CERTIFICATION
DRAWN BY RGP/ACG/ADP CHECKED BY M.T. MUFTI
DATE STARTED JUNE 11, 2002 DATE COMPLETED JULY 2003
GRADE LEVEL 707 GRADE LEVEL 708 WARNING TAPE DISCIPLINE ENGINEER M.B. DIMAYUGA

PROJECT ENGINEER R.N. DIONISIO

CERTIFIED BY: E.N. MAPANAO, PROJECT MANAGER


550

THIS DRAWING IS NOT TO BE


USED FOR CONSTRUCTION (NAME)
728 UNTIL CERTIFIED AND DATED. SIGNATURE DATE JULY 2003

729 730 731 732 BACKFILL SOIL


1000

1000

SAUDI ARABIAN OIL COMPANY


150

DRY SAND COVER BACKFILL SOIL


300

REVIEW FOR KEY DRAWINGS REQUIRED NOT REQUIRED x


MINIMUM DRY 726 CONSTRUCTION AGENCY
SPARE
SAND COVER CONCRETE ENCASEMENT OPERATIONS
150

OTHER
DRY SAND CUSHION
MINIMUM DRY SPARE
SAND CUSHION NO.: WING DETAIL
COMPLETION CERT
150

DRAWING TYPE

729 730 731 732 28 758 MISCELLANEOUS ELECTRICAL EDT


PC-1791 PC-1792 PC-1791 PC-1792
300 600 480V, SWITCHRACK A ANDCOMPLETION
NO.: WING B C
(MINIMUM) (MINIMUM) NO.: WING
PUMP STA-4 TANK COMPLETION C
FARM-2
NO.: WING COMPLETION CERTIFICATE
ABQAIQ (DCC)
SAUDI ARABIA
DETAIL-1 SECTION A-A ROAD CROSSING JOB ORDER/EWO NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

NTS SCALE NTS SCALE NTS


01S329 190 P BA-414707 001 00
Saudi Aramco 2615 ENG. (03/99)

VECTOR CADD-3A
BA-414707 001 00 P 01S329 190 TO 480V DISTR. PANEL-B (MOV-07)
TO MOV-07 NOTES:
TO MOV-11 TO 480V DISTR. PANEL-B (MOV-11)
REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO. JOB ORDER/EWO NO. 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO.NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
TO MOV-06 TO 480V DISTR. PANEL-B (MOV-06) OTHERWISE NOTED.
TO MOV-14 TO 480V DISTR. PANEL-B (MOV-14)
2. FOR GROUNDING SYSTEM INSTALLATION, REFER
TO SAES-P-111.

3. REFER TO SAUDI ARAMCO STANDARD DRAWING NO.


DD-950022 SHT. 008 AND 011 FOR GROUND
CONNECTION DETAIL.

800 300 800 300 4. OUTDOOR SWITCHRACK SHALL BE IN ACCORDANCE WITH


735 736 737 739 740 741 742 743 SAUDI ARAMCO ENGINEERING STANDARD SAES-P-114
AND SAES-P-116 AND MATERIAL SYSTEM
701 702 703 704 710 716 (TYP. 4) 23000 SPECIFICATION 16-SAMSS-512.

701 702 703 704 710 716 500 3000 2500 5. LAYING OF DIRECT BURIED CABLES SHALL BE DONE
701 702 703
734 735 736 737 739 IN ACCORDANCE WITH STANDARD DRAWINGS AB-036326,
704 710 716 AB-036273 AND AD-036874.
480V DISTRIBUTION PANEL "A" 480V DISTRIBUTION PANEL "B"
EXISTING 6. ALL DIMENSIONS AND LOCATION SHALL BE FIELD
SPARE SPARE SPARE SPARE SPARE 190-GM-18

DIKE
SPARE 190-GM-17 SPARE
MOV-03 MOV-02 MOV-11 MOV-06 728 729 730 731 732 (TYP.2) LIGHTING POLE VERIFIED AND CHECKED PRIOR TO CONSTRUCTION OR
SEWAGE SEWAGE
FABRICATION.
PUMP PUMP NEW SWITCHRACK
SPARE SPARE MOV-07 MOV-14 7. DISCONNECTED POWER CABLE FOR MOV-2, MOV-3,
190-SR-001
SEE DETAIL MOV-6, MOV-7, MOV-11 & MOV-14 AND RELOCATED TO
SPARE SPARE SPARE SPARE NEW 480V DISTRIBUTION PANEL NO. A AND B.
ON THIS DRAWING
8. EXISTING COMBINATION BREAKER AND STARTER PANEL
DIRECT BURIED
FOR MOV-2, MOV-3, MOV-6, MOV-7, MOV-11 & MOV-14

33000
760 712 729
709 729 730 731 732 761 CABLE
ARE TO BE DISCONNECTED AND REMOVED FROM
730 731 732 705 PC-1793 SWITCHRACK "A" & "B", PUMP STATION APS-4.
712 734 735 736 737 (TYP.4)
761 9. CONDUIT STUB-OUT FOR TWO SPARES COMBINATION
STARTER AND BREAKER SHALL BE CAPPED.
7200

EXISTING
SWITCHRACK 10. DUCT BANKS SHALL HAVE 20% SPARE HOLES
NOTE-8
706 711 718 AS PER SAES-P-104 PARA. 10.4.8.
DETAIL-1 BELOW 11. INSTALLATION OF CABLE MARKER SHALL BE DONE IN
755 ACCORDANCE WITH STANDARD DRAWING AB-036273.
718 755

LEGEND
TO MOV-03 TO MOV-014 TRANSFORMER
706 711 714 721 722 TO MOV-011 (EXISTING)
TO GROUND GRID 17000
TO GROUND GRID TO GROUND GRID TO TO MOV-007 NEW INSTALLATION
TO MOV-02 TO NEAREST GROUND GRID MOV-006 TO GROUND GRID
TO GROUND GRID
EXISTING INSTALLATION
FROM SUB. #52 FROM SUB. #52
710 745 752 710 745 752
MCC-1, 3F-AL MCC-1, 3R-BL
PC-1791 PC-1792 CABLE MARKER
DWG. NO. XA-F94642 DWG. NO. XA-F94642
SHT. 001 SHT. 002

480V DISTRIBUTION PANELS-A/B INSTALLATION DETAIL CONDUIT INSTALLATION DETAIL FOR


AT SWITCHRACK "A" ABQAIQ PUMP STATION APS-4 MOV-06, 07, 11 AND 14 AT SWITCHRACK "B" PUMP STATION APS-4 BOOSTER PUMP STATION-A PLAN
SCALE NTS SCALE NTS SCALE NTS
400 150 150 400 400 150 150 400

404 411 404 411


400

400
419 419
REFERENCE DRAWINGS
DRAWING CONTROL BD-414702
ONE LINE DIAG. 480V DISTR. PANELS A/B, APS #4BA-414705
CABLE AND CONDUIT SCHEDULE DD-902813
746 756 757 746 756 757
840

840
ELECTRICAL DETAILS BOOSTER PUMP STA "A" AA-026218
14000 3000 3000 8000 ELECTRICAL DETAILS BOOSTER PUMP STA "B" AA-026219

NEW SWITCHRACK
734 735 736 737 739 734 735 736 737 739 190-SR-002

8000
SEE DETAIL

DIKE
ON THIS DRAWING DIKE
480V DISTRIBUTION PANEL NO.2A 480V DISTRIBUTION PANEL NO.2B
701 702 703 704 716 754 701 702 703 704 716 754
MOV-46 MOV-47 MOV-50 MOV-51
800

800
(TYP.5) (TYP.5) EXISTING
411 411 LIGHTING POLE
MOV-48 MOV-49 MOV-52 MOV-53
709 729 730 731 732 761 709 729 730 731 732 761
TYP. 2 TYP. 2 DIRECT BURIED
SPARE MOV-67 SPARE MOV-101 CABLE

34000
PC-1794
404 750 404 750
408 408
728 728
412 729 730 731 732 754 800 412 729 730 731 732 754 800
1200

1200
TYP. 2 TYP. 2
EXISTING
SEE NOTE- 2 & 3 SEE NOTE- 2 & 3 SWITCHRACK
409 410 409 410
706 711 714 721 722 755 706 711 714 721 722 755 CONDUIT
TYP. 2 TYP. 2
STUB-UP
SCALE: NONE
FFL FFL

REVISION CERTIFICATION EDSD


VERIFICATION
00
401 407 414 415 416 417 418 401 407 414 415 416 417 418 THIS INDICATES THAT REV. NO.
OF THIS DRAWING IS COVERED, FOR ALL
8000 APPROVAL/CERTIFICATION REQUIREMENTS,
CONTROL NUMBER

(TYP.2) (TYP.2) BY DRAWING COMPLETION CERTIFICATE (DCC) BY:


NO.: 01S329-01
NEW JUNCTION . DATE:
TO NEAREST GROUNDING GRID TO GROUNDING GRID
BOX
TO EXISTING PULLBOX/ TO JB-190-218-7 TO EXISTING LIGHT TO EXISTING PULLBOX/ TO JB-190-218-7 TO EXISTING LIGHT TRANSFORMER
JUNCTION BOX @ 600 600 JUNCTION BOX @ 600 600
(MOV-67) CIRCUIT @ SWRK-A (MOV-67) CIRCUIT @ SWRK-A (EXISTING)
SWITCHRACK-A SWITCHRACK-A
2000 2000
TO JB-190-218-1 TO JB-190-218-7 TO JB-190-218-1 TO JB-190-218-7
(MOV-46) (MOV-47) (MOV-46) (MOV-47)
TO JB-190-218-1 TO JB-190-218-7 TO JB-190-218-1 TO JB-190-218-7
(MOV-48) 480V DISTRIBUTION PANEL-2A INSTALLATION DETAIL (MOV-49) (MOV-48) 480V DISTRIBUTION PANEL-2B INSTALLATION DETAIL (MOV-49)
REV.
AT SWITCHRACK 190-SR-001 BOOSTER PUMP STATION-A AT SWITCHRACK 190-SR-002 BOOSTER PUMP STATION-B BOOSTER PUMP STATION-B PLAN NO.
DATE JO/EWO DESCRIPTION ENGG. CERT. PMT OPRNS.

SCALE NTS SCALE NTS DESIGN REVIEW FOR


SCALE NTS THIS REVISION IS NOT TO BE USED FOR CONSTRUCTION
UNTIL CERTIFIED AND DATED. CERTIFICATION KEY DRAWINGS
I BEAM
708 DESIGN CERTIFICATION
DRAWN BY RGP/ACG/ADP CHECKED BY M.T. MUFTI
DATE STARTED JUNE 11, 2002 DATE COMPLETED JULY 2003
GRADE LEVEL 707 GRADE LEVEL 708 WARNING TAPE DISCIPLINE ENGINEER M.B. DIMAYUGA

PROJECT ENGINEER R.N. DIONISIO

CERTIFIED BY: E.N. MAPANAO, PROJECT MANAGER


550

THIS DRAWING IS NOT TO BE


USED FOR CONSTRUCTION (NAME)
728 UNTIL CERTIFIED AND DATED. SIGNATURE DATE JULY 2003

729 730 731 732 BACKFILL SOIL


1000

1000

SAUDI ARABIAN OIL COMPANY


150

DRY SAND COVER BACKFILL SOIL


300

REVIEW FOR KEY DRAWINGS REQUIRED NOT REQUIRED x


MINIMUM DRY 726 CONSTRUCTION AGENCY
SPARE
SAND COVER CONCRETE ENCASEMENT OPERATIONS
150

OTHER
DRY SAND CUSHION
MINIMUM DRY SPARE
SAND CUSHION NO.: WING DETAIL
COMPLETION CERT
150

DRAWING TYPE

729 730 731 732 28 758 MISCELLANEOUS ELECTRICAL EDT


PC-1791 PC-1792 PC-1791 PC-1792
300 600 480V, SWITCHRACK A ANDCOMPLETION
NO.: WING B C
(MINIMUM) (MINIMUM) NO.: WING
PUMP STA-4 TANK COMPLETION C
FARM-2
NO.: WING COMPLETION CERTIFICATE
ABQAIQ (DCC)
SAUDI ARABIA
DETAIL-1 SECTION A-A ROAD CROSSING JOB ORDER/EWO NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

NTS SCALE NTS SCALE NTS


01S329 190 P BA-414707 001 00
Saudi Aramco 2615 ENG. (03/99)

VECTOR CADD-3A
001 02 DA-899574 P 111 59043
NOTES:
REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO. JOB ORDER/EWO NO.

1. MCP TRIP SETTING D.

2. MCP TRIP SETTING B.

3. MCP TRIP SETTING C.

01B
REVISION NOTES: (EWO-04S168)

1. INCOMING FEEDER TO SWITCHRACK 111-SWRK-700


01B CHANGED

2. EXISTING FEEDER TO MCC 111-P-700 IS


800AF STG BUILDING STATION
DISCONNECTED AND USED TO FEED SWITCHRACK
SERVICE BUS1, BREAKER #2B
600AT 11-SWRK-700

SEE REV. NOTE 2

6-1/C #500 MCM THWN

LEGEND:

MCP
SWITCHRACK 3P
50AT

NON-REVERSING COMBINATION
111-SWRK-700 STARTER WITH MOTOR CIRCUIT
600AF MAIN BREAKER
3P PROTECTOR (MCP)
600AT 2

PC-4541
PC
4539 3POLE, CIRCUIT BREAKER
3P

PC-4540 PC-4542
JB-1 JB-2 JB-3 JB-4 XVS VIBRATION SWITCH

PUSH BUTTON
PB
SS START/STOP

PC PC PC PC PC PC PC PC PC PC PC PC PC PC PC PC PC
4543 4544 4545 4546 4547 4548 4549 4550 4551 4552 4553 4554 4555 4556 4557 4558 4559 SPLICE BOX

100AF JB JUNCTION BOX


MCP MCP MCP MCP MCP MCP MCP MCP MCP MCP MCP MCP MCP MCP MCP 3P
40AT
3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 100AF 3P 3P 3P 3P
50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT PC-4536
3P
NOTE-2 NOTE-1 NOTE-1 NOTE-1 NOTE-1 NOTE-1 NOTE-1 NOTE-3 NOTE-3 NOTE-1 NOTE-1 60AT
MANUAL TRANSFER SWITCH-A

30KVA, TRANSF.
480V-208Y/120
MTS-A

PC-4538
PC 100AF
3P
4563 100AT
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
PC-4560
REFERENCE DRAWINGS
LIGHTING PANEL
120/208V, 3PH DRAWING TITLE INDEX DRAWING No
24 CKTS.
DRAWING CONTROL A DD-899572
ONE LINE DIAGRAM-480V SWITCHGEAR P NA-500546

PC
ONE LINE DIAGRAM-480V-MCC-111-P-700 SH 1&2 P DA-116158
MTS-B COMBINATION LINE 4561 ELEMENTARY DIAGRAM P DA-116156
STARTER SWITCHRACK INSTALLATION DETAILS P DA-899575
(TYPICAL)
MTS-A 01B ELEM. & INTERCONN. DIAG. MCC 111-P-700 P NA-587187
DRAWING CONTROL (EWO.04S168) BD-228447
ONE LINE DIAGRAM STATION SERVICE 480V BUS#1 NA-980027

SWITCHRACK LIGHTING
C C C C C C C C C C C C C
628 611 614 615 618 619 622 630 632 626 623 635 638
4x1/C#4 & 5x1/C

4x1/C#4 & 5x1/C

4x1/C#4 & 5x1/C

4x1/C#4 & 5x1/C

4x1/C#4 & 5x1/C

4x1/C#4 & 5x1/C

4x1/C#4 & 5x1/C

4x1/C#4 & 5x1/C

4x1/C#4 & 5x1/C

4x1/C#4 & 5x1/C

4x1/C#4 & 5x1/C

3x1/C#2 THWN-1 1/2 "C

4x1/C#2 THWN-1 1/2 "C


#12 THWN-1 1/2 "C

#12 THWN-1 1/2 "C

#12 THWN-1 1/2 "C

#12 THWN-1 1/2 "C

#12 THWN-1 1/2 "C

#12 THWN-1 1/2 "C

#12 THWN-1 1/2 "C

#12 THWN-1 1/2 "C

#12 THWN-1 1/2 "C

#12 THWN-1 1/2 "C

#12 THWN-1 1/2 "C


S P A R E

PC-7797
PC-7741

JB JB JB JB JB JB JB JB JB JB JB

XVS XVS XVS XVS XVS XVS XVS

REVISION CERTIFICATION EDSD


VERIFICATION
THIS INDICATES THAT REV. NO. 02
100AF
OF THIS DRAWING IS COVERED, FOR ALL
CONTROL NUMBER
30AT APPROVAL/CERTIFICATION REQUIREMENTS,
BY DRAWING COMPLETION CERTIFICATE (DCC) BY:
NO.: 532220-0709-11
. DATE:
PB PB PB PB PB PB PB PB PB PB PB

SS SS SS SS SS SS SS SS SS SS SS
AS-BUILT BY DATE

TO NEW PANEL PP-1 IN SUB#30


15 25 25 25 25 25 25 20 20 25 25

(DWG. BA-228450,SHEET 001)


PANEL D

TO NEW MCC-1 IN SUB #30


02 07/09 HAS 532220 REVISED AS BUILT AMZ MSQ MSQ
45KVA, 3PH.
480-120/208V

AIR & WATER PLANT

SEE DWG. NA-587187


01B OCT’04 04S168 REVISED AS SHOWN JI ARN

CHEMICAL BUILDING
APOE
FACILITIES BLDG.

01 01-97 SAL REVISED AS BUILT SYD AMH ASB


TRANSFER PUMP
DRINKING WATER

CHEMICAL FEED
NORTH BOILER
111-EM-727A1

111-EM-705B1

111-EM-705D1

111-EM-705F1
111-EM-705A2

111-EM-705C2

111-EM-705E2

111-EM-705G2

REV. DATE BY JO/EWO DESCRIPTION CHKD. CERT. APPD.


COOLING FAN

COOLING FAN

COOLING FAN

COOLING FAN

COOLING FAN

COOLING FAN

COOLING FAN

COOLING FAN
WATER PUMP

WATER PUMP
111-GM-706B

111-GM-700B

111-GM-700D
CONDENSATE

CONDENSATE

NO.

SAUDI ARABIAN OIL COMPANY

DRAWN BY ZATE / bfa CHECKED BY SCALE: NONE

DATE STARTED 25AUG92 DATE COMPLETED FEB’93


01B

OPR’G. DEPT. ENG. DEPT.

APP’D. FOR CONST.


01B
THIS DRAWING IS NOT TO BE USED FOR CERTIFIED
CONSTRUCTION OR FOR ORDERING ENG’G. MANAGER
BY G.K.BAHL DATE
MATERIAL UNTIL CERTIFIED AND DATED

ONE LINE DIAGRAM


480V SWITCHRACK 111-SWRK-700
POWER PLANT STEAM & ELECTRIC
ABQAIQ SAUDI ARABIA
JOB ORDER/EWO NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

59043 111 P DA-899574 001 02


Saudi Aramco 2615 ENG. (3/99)

VECTOR CADD-2A
001 01 P DA-899575 59043 111 NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHER-
REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO. JOB ORDER/EWO NO.

59 94 100 89 105 68 WISE NOTED.


5709 2. FOR SWITCHRACK STRUCTURAL SUPPORT AND ROOF/
PHOTO ELEC. SW. SHED DETAILS SEE STRUCTURAL DWG # DA-899578.
1903 1903 1903
88 102 115 99 3. DIMENSIONS GIVEN ARE APPROXIMATE.EACH DIMENSION
PHOTO ELEC. SW.
LIGHTING FIXTURE WILL DEPEND ON ACTUAL EQUIPMENT TO BE USED.
67 96 99 88 93 101 69 99 115 102 88
114 116 11 21 15 (TYP. FOR 2) 4. GROUND CONNECTIONS TO BE INSTALLED AS PER
54 55 103 104 107 STD. DWG. # AD-036383 SH.9.
95 63 61 2EA 2EA 2EA

90 106 61 63 101

4EA 4EA 4EA 6EA 4EA JUNCTION BOX JUNCTION BOX

13 17 23 108 109 92 112 128 128 128


95 61 63 69 106 90 101
775

JB #1 JB #2 (TYP. FOR 2)

59 60
33 12 16 22 129
89 100 105 68
4EA 4EA 4EA 100 89 105 68 68 105 89 100
275

57 56 56 57
12 16 22 130 33 62
68 105 89 100 57 56
4EA 4EA 4EA
COMBINATION STARTER COMBINATION STARTER
14 18 24 131
62 SIZE 2 SIZE 2
2873

MTS-B
MTS-A
762

4EA 4EA 4EA


COMBINATION STARTER 123 123
940

HOA LIGHTING PNL-1 SIZE 2


11 15 21 113 123 16 12 22 LIGHTING PANEL
2EA 2EA 2EA 4EA 4EA 4EA 131
(TYP. FOR 7)
49 43 43
100 72 44 94
100 44 94 57
(TYP. FOR 14) (TYP. FOR 7)
70 89 105 59
433

70 89 105 56 54 89 100 94 94 100 89

32 49 105 44 70 70 44 105
100 72 44 94 97 71 90 53 95
(TYP. FOR 2)
54 56 57 57 56 54
70 89 105 59 60 FROM REAR OF 63 45 101
500

SWITCHRACK
(TYP. FOR 2)

FIN. GRADE 1 20 25 29
150

47 50 51 94
76
(TYP. FOR 2) 76
TO EXISTING
GROUND GRID RED COLOR
CONCRETE (2500 PSI)
62 62 (TYP.)
SPARE CONDUITS 70 132 72 77 71 73
72 70 132
44 70 132 91 2EA 2EA 132 72 70 70 72 132
FRONT ELEVATION 2EA
2EA 2EA 2EA REFERENCE DRAWINGS
SIDE ELEVATION
DRAWING TITLE INDEX DRAWING NO
5709 DRAWING CONTROL LOG A DD-899572
ONE LINE DIAGRAM P DA-899574
1903 1903 1903
SHED & SWITCHRACK STRUCTURE SUPPORT M/Q DA-899578
67 99 88 107 93 54 55 103 INTERCONNECTION DIAGRAM P DA-899579
61 63 69 95 101
BLOCK DIAGRAM P DA-899580
59 94 100 89 105 68 LIST OF MATERIAL P DE-899581

LIGHTING FIXTURE

21 15 11 116 114

2EA 2EA 2EA


(TYP. FOR 2)

4EA 4EA 4EA 6EA 4EA

13 17 23 108 109

775
JB #3 JB #4 90 106 61 63 101
92 128 112

(TYP. FOR 2)
4EA 4EA 4EA
12 16 22
56 57
(TYP. FOR 3)

275
89 100 105 68
42 14 18 24
(TYP. FOR 10) 4EA 4EA 4EA

COMBINATION STARTER CKT CKT CKT


SIZE 2 BREAKER BREAKER BREAKER

2873
762
123 12 16 22
DIST. TRANSF. 126
4EA 4EA 4EA
(TYP. FOR 8) 52 68 89 100 105 52A AS-BUILT BY DATE
43

49 58
43 56 57 68 89 100 105
44 56 54 57 (TYP. FOR 14)
125
561

62
124
70 105 94 100 89 APOE

32 49 01 01-97 SAL REVISED AS BUILT SYD AMH ASB

2EA REV. DATE BY JO/EWO DESCRIPTION CHKD. CERT. APPD.


1 20 25 29 NO.

49 32 SAUDI ARABIAN OIL COMPANY


47 50 51 94
500

2EA
TO FRONT OF (TYP. FOR 2) (TYP. FOR 2)
DRAWN BY ZATE / bfa CHECKED BY SCALE: NONE

SWITCHRACK
DATE STARTED 16NOV1992 DATE COMPLETED FEB’93
(TYP. FOR 2) FIN. GRADE
150

OPR’G. DEPT. ENG. DEPT.

70 91 132 44 APP’D. FOR CONST.

THIS DRAWING IS NOT TO BE USED FOR CERTIFIED


2EA CONSTRUCTION OR FOR ORDERING ENG’G. MANAGER
MATERIAL UNTIL CERTIFIED AND DATED BY G.K.BAHL DATE
SPARE CONDUITS
INSTALLATION DETAILS
62
SWITCHRACK 111-SWRK-700
70 132 72 ABQAIQ POWER PLANT
2EA REAR ELEVATION ABQAIQ SAUDI ARABIA
JOB ORDER/EWO NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

59043 111 P DA-899575 001 01


Saudi Aramco 2615 ENG. (3/91)

VECTOR CADD-02
BA-422481 001 01 P 106 31660 NOTES:
REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO. JOB ORDER/EWO NO.

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO.NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
1. OUTDOOR SWITCHRACK SHALL BE IN ACCORDANCE
WITH SAUDI ARAMCO ENGINEERING STANDARD
SAES-P-114 & SAES-P-116 AND MATERIALS SYSTEM
SPECIFICATION 16-SAMSS-512.
450 3300 450 NAMEPLATE SCHEDULE
2. CIRCUIT BREAKERS AND/OR COMBINATION STARTERS
LABEL NO. FIRST LINE SECOND LINE THIRD LINE FOURTH LINE
SHALL BE IN NEMA 4X ENCLOSURES LOCATED IN
1 106-SR-001 480 V, 400A 60 Hz, 3 PH, 3 WIRE 25 KA RMS SYS NON HAZARDOUS AREAS.
2 MAIN INCOMER CIRCUIT BREAKER 90 AT/100 AF 3. DIRECT BURIED CABLES AND CONDUITS SHALL BE
INSTALLED IN ACCORDANCE WITH SAUDI ARAMCO
3 SPARE BREAKER 20 AT/100 AF
STANDARD DRAWING AD-036874.
4 LIGHTING 100W, 120V HPS
1100

4. ALL CONDUIT & FITTINGS SHALL BE HOT DIPPED


5 SPARE BREAKER 20 AT/100 AF GALVANIZED STEEL PVC COATED UNLESS OTHERWISE
6 LIGHTING CONTACTOR PANEL NO. 2 480 V NOTED.

7 106-LP-002 LIGHTING PANEL 480 V, 3 PH, 3 W, 100 A25 KAIC 5. STUB-UPS ARE TO BE 90 DEGREES LONG RADIUS
BENDS FITTED BELOW GRADE WITH BUSHING END AND
8 SPARE BREAKER 20 AT/100 AF
ARE TO BE FINISH A MINIMUN OF 6" ABOVE FINISH
CEILING 9 106-PP-001 POWER PANEL 208/120 V, 3 PH, 4 W 10 KAIC FLOOR LEVEL.
EAVES LINE 10 LIGHTING CONTACTOR PANEL NO. 1 120 VAC 6. ALL UNUSED CONDUIT RUNS INSTALLED FOR FUTURE
USE SHALL BE PLUGGED TO PREVENT INGRESS OF
11 106-XFR-001 BREAKER 20 AT/100 AF
SAND OR OTHER FOREIGN MATTER.
12 D87-MOV-104 BREAKER 20 AT/100 AF
1100

7. FOR SWITCHRACK 106-SR-001 METERING AND


13 106-MOV-2448 BREAKER 20 AT/100 AF PROTECTION THREE LINE DIAGRAM SEE VENDOR
14 106-XFR-001 5 KVA, 480 V DELTA 208/120 V, 3 PH, 4 W DRY TYPE XFR DRAWING NO. HOLD.

15 120 VAC RECEPTACLE OUTLET


16 CRADLE MOTOR BREAKER 20 AT/100 AF
17 106-GM-0314 CONTROLLER NEMA SIZE 2/70AT/100AF
18 LIGHTING CONTACTOR BREAKER 35AT/100AF

SWITCHRACK CONDUIT STUB-UP


SCALE 1:20 | SYMMENTRY
1000 3300 1000 1420 1420

4 4
583

TYP FOR 4

93 107 115 116A 119 MATERIAL LIST


ITEM NO. SAMS STOCK NO. ISSUE UNIT QTY DESCRIPTION

10 10-883-742 EA 4 WASHER: PLAIN, ROUND, BRASS, 1/2 " BOLT

3400
15 11-268-095 EA 2 LAG SCREW: SQ HEAD, 1/4 " DIAx1 1/2 " LONG
3400

786

VM
3 18 17 6 7 18 11-805-514 EA 2 ANCHOR: SCREW, MASONRY, 1/2 "x25.4 MM LONG
AM
28 14-188-844 LB 4 LOCKWASHER: PHOSPHER BRONZE, 1/2 " BOLT
29 14-198-126 EA 2 CONNECTOR: TERMINAL, COPPER, 1/2 " HOLE SIZE
TYP FOR 4
2 31 14-218-184 EA 4 NUT: HEXAGONAL, SILICON BRONZE, 1/2 " BOLT REFERENCE DRAWINGS
736

8 16 34 53 63 76 85C
32 14-256-445 EA 4 SCREW: CAP, SILICON BRONZE 1/2 " DIAx1 1/2 " LONG DRAWING CONTROL JO-31660 BD-421940
94 108 122 127 128 33 14-266-376 EA 6 SLEEVE: HEAT SHRINK, 17 THRU 48 MM ONE LINE DIAGRAM BA-422404
34 14-266-380 EA 14 SLEEVE: HEAT SHRINK, 40 THRU 128 EQUIPMENT ARRANGEMENT BA-422478
34 53 64A
53 14-872-276 PK 2 COMPOUND: SEALING, PUTTY 5 LB/BG ELECTRICAL AREA CLASSIFICATION BA-421970
500

34 53 63 76 85C 122
77A 85A 122A 58 15-195-390 MT 20 WIRE: BUILDING, 450-750V, TYPE NYA, 1C, 25 MM POWER, CONTROL & LIGHTING LAYOUT BA-422434
62 15-287-612 EA 6 BUSHING: CONDUIT, INSULATED GROUNDING, 1" CABLE & CONDUIT SCHEDULE DD-873390 SH 199-200
63 15-287-616 EA 12 BUSHING: CONDUIT, INSULATED GROUNDING, 1 1/2 " POWER PANEL LOAD SCHEDULE 106-PP-001 BC-422452
175

64A 15-287-620 EA 2 BUSHING: CONDUIT, INSULATED GROUNDING, 2" LIGHTING PANEL LOAD SCHEDULE 106-LP-002 BC-422450
69 15-311-992 JT 1 CONDUIT: PVC, EXTRA STRENGTH, 1 1/2 " DIAx20’ LG DC POWER PANEL LOAD SCHEDULE 106-PP-002 BC-422453
34 53 75 15-314-914 PC 3 CONDUIT: GALVANIZED, RIGID STEEL, 1" PVC COATED MATERIAL TAKE-OFF T/O-422481
76 15-314-916 PC 5 CONDUIT: GALVANIZED, RIGID STEEL, 1 1/2 " PVC COATED
TO GROUND 64A 85A
GRID (TYP) 77A 15-314-918 PC 1 CONDUIT: GALVANIZED, RIGID STEEL, 2" PVC COATED
85A 15-368-113 EA 2 ELBOW: PVC COATED, RIGID CONDUIT, 2", 24" RADIUS
TYP FOR 3
85B CONTRACTOR SUPPLY EA 4 ELBOW: PVC COATED, RIGID STEEL, 1", 24" RADIUS
34 53 63 76 85C 33 53 62 75 121 85B 33 53 62
SECTION
FRONT VIEW 85C CONTRACTOR SUPPLY EA 12 ELBOW: PVC COATED, RIGID STEEL, 1 1/2 ", 24" RADIUS GRAPHIC SCALE
SCALE 1:20
OR 93 15-444-136 EA 8 NIPPLE: RIGID STEEL CONDUIT, 1"
SCALE 1:20 0 0.5 1 1.5 2
34 53 63 94 15-444-147 EA 14 NIPPLE: PVC COATED, RIGID STEEL CONDUIT 1 1/2 "

1000 3300 1000 100 15-510-825 EA 2 CLAMP: RIGID CONDUIT, MALLEABLE IRON, 1 1/2 " 1:20 METERS
OR
107 15-537-334 EA 4 UNION: PVC COATED, RIGID CONDUIT, STEEL, 1" SCALE: 1:20
34 53 64
108 15-537-340 EA 7 UNION: PVC COATED, RIGID CONDUIT STEEL, 1 1/2 "
REVISION CERTIFICATION EDSD
115 15-602-080 EA 6 BODY: CONDUIT, TYPE LB, 1" VERIFICATION
THIS INDICATES THAT REV. NO. 01
1
116A 15-613-562 EA 6 COVER: CONDUIT BODY FORM 7 SERIES, 1" OF THIS DRAWING IS COVERED, FOR ALL
DCC
CONTROL NUMBER
APPROVAL/CERTIFICATION REQUIREMENTS,

119 15-657-670 EA 6 GASKET: CONDUIT BODY, FLAT SOLID, 1" BY DRAWING COMPLETION CERTIFICATE (DCC) BY: MSm
NO.: 724200-JO-2001-31660-001
1 PPLE: PVC COATED, RGS,
. DATE: 2" FOR ITEM 85C - 0
06/04/2003
121 15-670-864 EA 4 HUB: CONDUIT, FERALLOY, PVC COATED 1"
4 4 122 15-670-871 EA 8 HUB: CONDUIT, FERALLOY, PVC COATED 38 MM
122A 15-670-105 EA 1 HUB: CONDUIT 2" DIA, PVC COATED
583

127 15-745-003 CN 4 SEALING COMPOUND: POWDER, 1 LB CAN, CH# CHICO A4


TYP FOR 2
128 15-746-463 EA 7 SEALING FITTING: PVC COATED, 1 1/2 " NPT
01 02/05/2003 JO-31660 REVISED AS-BUILT EGS AAA AMJ MJM
93 107 115 116A 119 129 15-750-007 EA 4 SEALING FITTING: 1" NPT, PVC COATED
152 CONTRACTOR SUPPLY EA 1 SWITCHRACK: OUTDOOR EQUIPMENT ASSEMBLY 00 09/26/2001 JO-31660 ISSUED FOR CONSTRUCTION EGS AAA AMJ MJM

EA 4 COUPLING: PVC COATED, RGS, 2" FOR ITEM 85A


3400

REV. DATE JO/EWO DESCRIPTION ENGG. CERT. PMT OPRNS.


786

TYP FOR 2 NO.


9 10 11 12 13 EA 6 COUPLING: PVC COATED, RGS, 1" FOR ITEM 85B
THIS REVISION IS NOT TO BE USED FOR CONSTRUCTION DESIGN REVIEW FOR
34 53 63 76 85C EA 24 COUPLING: PVC COATED, RGS, 1 1/2 " FOR ITEM 85C UNTIL CERTIFIED AND DATED. CERTIFICATION KEY DRAWINGS

DESIGN CERTIFICATION
94 108 122 127 128 EA 1 UNION: PVC COATED, RGS, 2"
DRAWN BY PAL/JCC CHECKED BY EGS/JSS
EA 1 NIPPLE: PVC COATED, RGS, 2" DATE STARTED 05/13/2001 DATE COMPLETED 09/26/2001
736

X
15 DISCIPLINE ENGINEER E.G. SANCHEZ
14 5 TYP FOR 2 PROJECT ENGINEER A.A. ABOUSALEH

10 28 29 31 32 58 THIS DRAWING IS NOT TO BE CERTIFIED BY: A.A. ABOUSALEH


USED FOR CONSTRUCTION (NAME)
TYP FOR 2 UNTIL CERTIFIED AND DATED. SIGNATURE DATE 12/08/2001
TYP FOR 2
500

33 53 62 75 85B SAUDI ARABIAN OIL COMPANY


15 18 53 69 100
REVIEW FOR KEY DRAWINGS REQUIRED NOT REQUIRED x
93 107 121 127 129 CONSTRUCTION AGENCY
OPERATIONS
175

OTHER

DRAWING TYPE

ELECTRICAL LAYOUT AND DETAILS EDT


SWITCHRACK 106-SR-001
SPHEROIDS FOR UTH-ABQ.(UA) P/LINES
ABQAIQ SAUDI ARABIA
REAR VIEW JOB ORDER/EWO NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

SCALE 1:20
31660 106 P BA-422481 001 01
Saudi Aramco 2615 ENG. (03/99)

VECTOR CADD-3A
2EA
1- FOR MATERIAL TAKE-OFF SEE DWG. DA-604718
3EA 295 060 059 063 064
314 317 2- FOR ASBESTOS CONNECTION DETAIL SEE ARAMCO
119 123 321 326 161 033 034 165
216 019 032 034 020 STD. DWG. AA-036243 DETAIL 3.
318 319
127 131 ASBESTOS PROOFING 004 193 224 060 064
2EA
ASBESTOS PROOFING
(TYP. 12 PLACES)
(TYP. 12 PLACES) 4EA 2EA 2EA 5EA

26EA

286 (TYP. 2 PLACES)


686 686 686
686
450
2EA
86 76 494 493 492 34
3EA
1002

235 059 031

1002
324 (2EA)
33 65 61 41
254
034 002

286
314 317 318 319
(TYP. 3 PLACES)
4EA
50

(TYP. 4 PLACES)

122 118 126 130


180
180

(TYP. 6 PLACES)
(TYP.) (TYP.)

328
LP-2

690
DP-2B DP-2C DP-2A
806

495

325

3EA
126 130 188 263 299

6EA 088
1829

327
292 060 064 032 034
003 293
002 (TYP.
222 088 288 289 290 291 292
3 PLACES) 003 3 153 57
088 288 289 126 130 188 263 299
(TYP. 4 PLACES)
(TYPICAL)
183 184 203 207
290 291 292 263
(TYP.)
278 075 063 051 041
(TYP. 3 PLACES) (TYP. 2 PLACES)

152

TYP.
GROUND WELL #1 2EA
034 530

(TYP. 3 PLACES)
2
1/C 35 mm GREEN GROUND WELL #2
TO GRDG. GRID
REFERENCE DRAWINGS

TYP.
2

914
1/C 35 mm GREEN
TO GRDG. GRID
DESCRIPTION DWG. NO.

2 297 298 DWG. CONTROL SH. KD-403655


297 298 1/C 35 mm GREEN 032 034 064 076

2 TO SWITCHRACK #2
1/C 35 mm GREEN (TYP.) DB-604723
ONE LINE DIAG. DP-2A, 2B & 2C
TO SWITCHRACK #2 2 174 281 329 2 SH-1,2&3
263 1/C-35 mm GREEN 1/C-35 mm GREEN
(TYPICAL) TO GROUND WELL #2 TO GROUND WELL #1
281 032 034 329 SITE POWER, LTG. & INSTR. PLAN DA-604718
183 184 203 207

ELEVATION SWITCH RACK #2 DC-604724


PANEL BOARD SCHEDULES, 2A, 2B & 2C
064 174 076 (TYP. 2 PLACES) SH-2,2&3
2EA

(TYP. 2 PLACES) LTG. PNL. BOARD SCHEDULE LP-2 DC-604725

038 293 228 261

294 296 297 296

ELEVATION SWITCH RACK #1 (TYP. 2 PLACES)


1727 1727

1067 660 660 1067

| SEE NOTE#2
431 ASBESTOS
RIDGE CAP
478 479 480

477
ASBESTOS CORP.
SHT. " THK. 476

300
05 X 6.7
300
628

C4 X 5.4
450
PURLINS

059
TYP.
6

-C-235

457
484 180
TYP. TYP.
6
( TYP. 4 PLACES)
477

060

LC-203 12 EA
SWITCH RACK #2
157

SP-246 SP-247 LC-204 CONTROL CONDUIT


356

086 060

TYP. 2 EA 086 016

308 787 POWER CONDUIT


117 117
(TYP. 3 PLACES)

FEILD TO VERIFY
SP-208 SP-209 SP-239 SP-237
610

168 117 250 117 117 478 385 117 308 117 538 310 117 117 872 140

FROM LEFT TO RIGHT


356

003 032 034 057 060


PC-190
174 NONE
PC-191
SWITCH RACK #1 064 095 099 216 281
| PC-192
PC-190 PC-190 PC-190
PC-193
152

3EA 2EA
183 184 203 207 263
PC-194 (TIPICAL 2 PLACES) 03

PC-195
PC-196 532220-1014-001
1372 1524 1372
PC-197 GRADE
762

4267 PC-198
PC-199 MTF AHZ APD AHZ
10/13/14 10/13/14 10/13/14 10/13/14
333
PC-200
PC-201 2 03 10/13/14 REDRAWN FOR CLARITY
(TYP. 2 PLACES) 1/C-35 mm (GREEN)
PC-202 WIRE TO GROUND GRID
1320 532220

DETAIL #2
TUBS UP PLAN SWITCH RACK #1&2 ELECTRICAL PLAN/LAYOUT/DETAIL EDT
SIDE VIEW SWITCH RACK #1&2 MOV CONNECTION GROUNDING DETAILS SH-2
DETAIL #1 GAS GATHG.FROM DEETHANISING

ABQAIQ

R57 P DA-604720 001 03

RESTRICTED VECTOR
001 01 BA-270251 M22 P 31521 NOTES:
REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO. JOB ORDER/EWO NO.
1. THIS SWITCHRACK TO BE INSTALLED IN MANIFOLD

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO.NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
AREA INSIDE THE SECURITY FENCE AS SHOWN IN
DWG NO BA-270258.

2. FOR SWITCHRACK LAYOUT, REFER TO DWG. NO.


BA-270252.

FEEDER FROM 480V M22-MCC-001 3. SWITCHRACK SHALL BE IN ACCORDANCE WITH


IN OPERATIONS SUPPORT BLDG. S. ARAMCO SPEC. 16-SAMSS-512.
(SEE DWG. NO. BA-270250)

M22-MOV-1354

M22-MOV-1337
M22-MOV-1353

M22-MOV-1352

M22-MOV-1350

M22-MOV-1347
M22-MOV-1348

M22-MOV-1339
M22-MOV-1383

M22-MOV-1338
M22-MOV-1377

M22-MOV-1378

M22-MOV-1380

M22-MOV-1382

M22-MOV-1355

M22-MOV-1342

M22-MOV-1335
M22-MOV-1336
M22-MOV-1341
M22-MOV-1381

M22-MOV-1340
DB-1383

C -1342

C -1293
C -1344

C -1345

C -1347

C -1283
C -1290

C -1289

C -1275

C -1295

C -1294

C -1292
C -1287

C -1285
C -1346

C -1288

C -1276

C -1296
C -1286
C -1341

C -1291
SPARE

SPARE

SPARE

SPARE
SWITCHRACK
MAIN
100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 250AF
INCOMER
20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 200AT BREAKER

LEGEND

CIRCUIT BREAKER

3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P DB-XXXX DIRECT BURIED CABLE TAG NUMBERS

3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 2P 3P 3P C -XXXX CABLE/CONDUIT TAG NUMBER

MOV WITH INTEGRAL STARTER

SWITCHRACK, HOA HAND-OFF-AUTOMATIC SELECTOR SWITCH


M22-P-001
480V, 3-{, 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF C CONTACTOR COIL
4-WIRE, 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 20AT 60AT 60AT 20AT

60Hz, 600A, PC PHOTO CELL


25kA Sym.
SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
C CONTACTOR

BSER
BLACKOUT SWITCH-ELECTRICAL
C -1335

C -1337

C -1339

C -1343
C -1338

C -1340
C -1336

C -1277

C -1297

C -1279

C -1274
C -1284

C -1280

C -1282

C -1278
C -1281
ROOM (OPERATIONS SUPPORT BUILDING)
M22-MOV-1373
M22-MOV-1372

M22-MOV-1374

M22-MOV-1375

M22-MOV-1379

M22-MOV-1345

M22-MOV-1349

M22-MOV-1344
M22-MOV-1376

M22-MOV-1346
M22-MOV-1343

M22-MOV-1356
M22-MOV-1371

M22-MOV-1351

M22-P-004
M22-P-005
REFERENCE DRAWINGS
DRY TYPE DISTRIBUTION
DRAWING CONTROL JO-31521 BD-269901
TRANSFORMER
480-240/120V, 1-{, 25kVA ONE LINE DIAGRAM 480V SWGR. M22-SG-001 BA-270250
CABLE AND CONDUIT SCHEDULE DD-873373
ELECTRICAL PLAN-MANIFOLD BA-270258
MISC. ELECTRICAL DETAILS-SWRK. LAYOUT BA-270252
PANEL SCHEDULE-SECURITY AREA LIGHTING BA-270253

COMBINATION
LIGHTING PC
CONTACTOR

C
SCALE: NTS

C HOA

(
BSER

LIGHTING PANEL RECEPTACLE PANEL ICAL ONE LINEICAL


DIAGRAM
ONE LINE DIAGRAM ( (
01 NOV99 31521 AS-BUILT PK RJP AMZ
240/120V, 1-{ 240/120V, 1-{
REV. DATE JO/EWO DESCRIPTION ENGG. CERT. PMT OPRNS.
NO.
THIS REVISION IS NOT TO BE USED FOR CONSTRUCTION DESIGN REVIEW FOR
UNTIL CERTIFIED AND DATED. CERTIFICATION KEY DRAWINGS

DESIGN CERTIFICATION
REFER DWG. BA-270253 REFER DWG. BA-270253 DRAWN BY BECHTEL(RCS) CHECKED BY C. GUPTA
SHT. 003 SHT. 003 DATE STARTED 30 JULY 1997 DATE COMPLETED 14 DEC. 1997
DISCIPLINE ENGINEER A. MATHUR/Y.B. SANKAR

PROJECT ENGINEER A. E. BEYER

THIS DRAWING IS NOT TO BE CERTIFIED BY: A. E. BEYER


USED FOR CONSTRUCTION (NAME)
UNTIL CERTIFIED AND DATED. SIGNATURE DATE JAN 1998

SAUDI ARABIAN OIL COMPANY


REVIEW FOR KEY DRAWINGS REQUIRED NOT REQUIRED
CONSTRUCTION AGENCY R.C. MUNTER

OPERATIONS C.G. ROWLETTE

OTHER

DRAWING TYPE

ELECTRICAL ONE LINE DIAGRAM E1L


480V SWITCHRACK M22-P-001
KHUFF GAS MANIFOLD IN PLOT AREA
UTHMANIYAH SAUDI ARABIA
JOB ORDER/EWO NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

31521 M22 P BA-270251 001 01


Saudi Aramco 2615 ENG. (07/93)

VECTOR CADD-03
01 1OF 2 BA-327269 P 51035 M24 NOTES:
REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO. JOB ORDER/EWO NO. 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO.NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
OTHERWISE NOTED.
2. SWITCHRACK VENDOR SHALL PROVIDE OUTDOOR
SWITCHRACK ASSEMBLY AS SHOWN ON THIS DRAWING
WITH ALL REQUIRED COMPONENTS AND INTER-
CONNECTING CONDUITS/ CONDUIT FITTINGS, PREWIRED
AND TESTED IN ACCORDANCE WITH 16-SAMSS-512.
3. THE SWITCHRACK VENDOR SHALL PROVIDE
ADDITIONAL STEEL BARS TO SUPPORT FIELD
CONDUITS RUN.
4. SWITCHRACK VENDOR SHALL PROVIDE STRUCTURAL
DRAWINGS TO SAUDI ARAMCO FOR APPROVAL BEFORE
FABRICATION.
5. ALL GROUNDING INSTALLATIONS SHALL BE IN
ACCORDANCE WITH SAES-P-111.
6. ALL OPENINGS OF ENCLOSURES NOT USED SHALL
BE PLUGGED.
7. CABLES & CONDUITS SHALL BE INSTALLED IN
ACCORDANCE WITH SAES-P-104.
8. BREATHER DRAIN FITTINGS SHALL BE PROVIDED AS
REQUIRED ON ALL ENCLOSURES.

1F
1" RGS
SWITCH RACK BUSBAR
29 MAIN INCOMING ENCLOSURE
METERING

1 1/2 " RGS 1 1/2 " RGS 1 1/2 " RGS 2" RGS 1" RGS 1" RGS 1" RGS CONDUIT HUB (TYP.)

BATTERY WSD CHOKE


2" RGS CHARGER PUMPS VALVE MAIN 7F AIR BLOWER METHANOL
3F
CIRCUIT CIRCUIT CIRCUIT CIRCUIT DJB-009 STARTER INJECTION
30KVA
BREAKER BREAKER BREAKER BREAKER JUNCTION PANEL CIRCUIT
TRANSFORMER
BOX BREAKER
CB-05 CB-04 CB-03 CB-01 SCP-02 CB-02

WEATHER PROOF
RECEPTACLE
1" RGS

3 7 10 13 16 TO SCP-01A/01B

REFERENCE DRAWINGS
FLAT BAR WELDED TO
UNISTRUT STRUCTURAL STEEL WITH
CHANNEL DRAWING CONTROL BD-327106
2-HOLE LUG AND BOLTS (TYP.)
ELECTRICAL ONE LINE DIAGRAM BA-327268
16 13 3 1
4
GROUNDING LAYOUT BA-327270
5

1 1/2 " RGS


1 1/2 " RGS
33
2 6 9 12 15 POWER AND CONTROL LAYOUT BA-327313
8
34

3" RGS

2" RGS
1" RGS

1" RGS

1" RGS

1" RGS
PLAN, SECTION AND DETAILS-
BA-327292
11 MISC. FOUNDATIONS
35

150
150

14

30 31 32
24 28
19 22 24 25 23 18 17

24 21 20
26
36 24 24
SCALE: NTS

TO GROUND GRID 37 25 25 TO GROUND GRID


REVISION CERTIFICATION EDSD
VERIFICATION
THIS INDICATES THAT REV. NO. 01
OF THIS DRAWING IS COVERED, FOR ALL
CONTROL NUMBER
APPROVAL/CERTIFICATION REQUIREMENTS,
BY DRAWING COMPLETION CERTIFICATE (DCC) BY:
NO.: 10-08276-0081-01
. DATE:

01 10/04 0081 REVISED AS-BUILT AMS AMS AMS EMO

REV. DATE JO/EWO DESCRIPTION ENGG. CERT. PMT OPRNS.


NO.

1 REAR ELEVATION THIS REVISION IS NOT TO BE USED FOR CONSTRUCTION


UNTIL CERTIFIED AND DATED.
DESIGN REVIEW FOR
CERTIFICATION KEY DRAWINGS

DESIGN CERTIFICATION
269 DRAWN BY CHECKED BY ALTAF AHMAD
SCEC
DATE STARTED MARCH 1999 DATE COMPLETED DECEMBER 1999
DISCIPLINE ENGINEER MARWAN KADDOURA

PROJECT ENGINEER SALAH SERRY ALI

THIS DRAWING IS NOT TO BE CERTIFIED BY: VASKEN MADAGHJIAN


USED FOR CONSTRUCTION (NAME)
UNTIL CERTIFIED AND DATED. SIGNATURE DATE

SAUDI ARABIAN OIL COMPANY


REVIEW FOR KEY DRAWINGS REQUIRED NOT REQUIRED
CONSTRUCTION AGENCY
OPERATIONS
OTHER

NO.: WING COMPLETION CERT DRAWING TYPE

SWITCHRACK ARRANGEMENT EDT


NO.: WING COMPLETION C
SDGM WELL-413
NO.: IN
KHUFF GAS MANIFOLD WING COMPLETION
PLOT AREA C
NO.: WING COMPLETION CERTIFICATE
SHEDGUM (DCC)
SAUDI ARABIA
JOB ORDER/EWO NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

51035 M24 P BA-327269 1OF 2 01


Saudi Aramco 2615 ENG. (03/99)

VECTOR CADD-3A
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
NOTES:
PHOTO CELL

BUS BOX

PC-1594

X55 X55 LC
MAIN
XFR PP-2 MCP1 MCP2 MCP3 CB2
BREAKER
CB1 002

120V
RECEPTACLE
OUTLET
PC-1598 PC-1599 PC-1592

PC-1621

CC-1631
PC-1627

PC-1622

CC-1632
PC-1612
FIN. GRADE

TO GROUND
TO GROUND
GRID

TO X55-GM-0258A

TO X55-GM-0258B
TO X55-LCP-0556

TO X55-LCP-0556

TO X55-LCP-0556
GRID

TO X55-ATS-001
AT ATS ROOM
REFERENCE DRAWINGS
DRAWING CONTROL J.O. 10-00084-0001 VD-338752
ELECTRICAL ONE LINE DIAGRAM VA-401593
ELECTRICAL ONE LINE DIAGRAM VA-445279

ELECTRICAL ONE LINE DIAGRAM VA-445280

POWER AND GROUNDING LAYOUT VA-445283


2 D E T A I L CABLE LAYOUT VA-445284
VA-445285
NTS CABLE LAYOUT VA-445285
SH 001
SWITCHRACK X55-SR-0002
CABLE AND CONDUIT SCHEDULE VD-338812

PHOTO CELL

BUS BOX BUS BOX

PC-1593

X55 X55 LC
MAIN
XFR PP-1 MCP1 MCP2 MCP3 MCP4 MCP5 MCP6 MCP7 MCP8 MCP9 CB2
BREAKER
CB1 001

120V
RECEPTACLE
OUTLET
PC-1628 PC-1629

PC-1591 X55-CJB-013
PC-1661

PC-1620

CC-1640
PC-1626

CC-1636

CC-1639
PC-1623
PC-1624
PC-1625

PC-1662
PC-1663

CC-1633

CC-1634

CC-1635

CC-1637

CC-1638
PC-1616
PC-1611

PC-1619
PC-1613

PC-1614

PC-1615

PC-1617

PC-1618
PC-1596

IC-1670
IC-1666

IC-1669
IC-1665

IC-1582
IC-1667
SCALE: NTS

REVISION VALIDATION
FIN. GRADE FIN. GRADE
THIS REVISION NO. 01 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

10-00084-0001-009

DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER


TO GROUND TO GROUND
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
TO GROUND TO GROUND
GRID GRID
TO REC. TRANSFER PUMP AREA LTG.
FLOW METER, FM/FI-0418

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE


GRID GRID
TO GENERATOR LTG.

CEE MAN EGA OAB

TO X55-CVJB-0554
TO X55-CVJB-0554
06/17/06 06/17/06 06/17/06 06/17/06
TO X55-LCP-0551

TO X55-LCP-0551

TO X55-LCP-0551
TO X55-GM-0257A

TO X55-GM-0259A
TO X55-GM-0257B

TO X55-GM-0259B
TO X55-LCP-0553
TO X55-LCP-0554
TO X55-LCP-0555

TO PNL X55-PP-3

TO X55-LCP-0553

TO X55-LCP-0553

TO X55-LCP-0554

TO X55-LCP-0554

TO X55-LCP-0555

TO X55-LCP-0555
TO X55-GM-0261
TO X55-ATS-001

TO X55-GM-0260

TO X55-GM-0263

TO X55-GM-0262

TO X55-CJB-011
REV.NO. DATE REVISION DESCRIPTION

TO X55-6-0262
TO X55-6-0263
TO X55-6-0264
01 01/29/11 AS-BUILT
AT ATS ROOM

AT ATS ROOM

JOB ORDER/EWO NO.


THIS REVISION IS NOT TO BE USED FOR
10-00084-0004 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY


DRAWING TYPE

ELECTRICAL DETAILS EDT

SWITCHRACK X55-SR-0001/0002/0003

3 D E T A I L BULK PLANT
FRONT REAR
VA-445284 NAJRAN SAUDI ARABIA
NTS
SH 001
SWITCHRACK X55-SR-0001 PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

X55 P VA-445278 001 01


Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01


THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
NOTES:

1. ALL GENERAL LOAD FEEDER BREAKERS WITH THE


TRIP RATING OF 70A OR GREATER SHALL BE
EQUIPPED WITH INTEGRAL GROUND FAULT
DETECTION TRIP UNIT.

2. REPLACE THE EXISTING SPACE WITH 20AT/100AF


BREAKER FOR ALTERNATE SUPPLY FOR NEW LIFT
STATION PUMPS.
DISTRIBUTION

FOR CONTINUATION
SEE BELOW LEFT
TRANSFORMER
X04-001-XFR(T)-401 480V SWITCHRACK X04-001-SR-001

1600A BUS, 480V, 3PH, 3W, 60HZ, 42KA SYM. MIN.


SPARE

480-120V 480-120V 480-120V 480-120V 480-120V 480-120V


1300AT
1600AF, 3P MCP MCP
150AF 150AF
2 1 2 1 2 1 2 1 2 1 2 1

300A MCP MCP MCP MCP MCP MCP


200A,3P 200A,3P 200A,3P 200A,3P 200A,3P 200A,3P
LEGEND
50GS 50GS 50GS 50GS 50GS 50GS 50GS 50GS

30A CLF
4 4 4 4 4 4 CIRCUIT BREAKER, MOLDED-CASE TYPE
C C C C C C
PC-1267

AF
BREAKER AMPERE FRAME AND TRIP RATING
AT

1 MVA SPARE SPARE


33-0.48/ CONTROL FUSE
0.277kV
300A 3{,60HZ
Z=5.75% CONTROL POWER TRANSFORMER

C MAGNETIC COIL

PC-1231

C-1291
PC-1232

C-1292
PC-1251

PC-1233
CC-1320
C-1296

CC-1311
PC-1252

PC-1253

C-1297

C-1295
CONTROL STATION

CC-1316
CS

CC-1319
CC-1317

CC-1318

CC-1315

CC-1313

CC-1314

CC-1312
THERMAL OVERLOAD RELAY
PC-1270

75 CS 75 CS 75 CS 75 CS 75 CS
MOTOR
75
(INDICATED RATING, IN HORSEPOWER)

X04-GM-0118 X04-GM-0119 X04-GM-0120 X04-GM-0116 X04-GM-0115 X04-001-AFD-001


SUPER GASOLINE SUPER GASOLINE PREMIUM GASOLINE DIESEL LOADING PREMIUM GASOLINE ADJUSTABLE CORE BALANCE CURRENT TRANSFORMER
LOADING PUMP LOADING PUMP LOADING PUMP PUMP LOADING PUMP SPEED DRIVE

50GS INSTANTANEOUS GROUND FAULT RELAY

PC-1234
CC-1293 MCP MOTOR CIRCUIT PROTECTOR

X04-IRP-020 (BY INSTRUMENTS)


LOR SS
PC-XXX POWER CABLE NUMBER

LCS CC-XXX CONTROL CABLE NUMBER

40
TO 33KV SF6 SWITCH
REFERENCE DRAWINGS
X04-001-SG-001
REFER DRAWING X04-GM-0117 DWG. CONTROL FOR J.O. (10-00069-0003) VD-284417
X04-ESDIRP-020 (BY INSTRUMENTS)
VA-289982.001 GASOLINE DWG. CONTROL FOR J.O. (10-03548-0003) VD-027637
UNLOADING PUMP CABLE AND CONDUIT SCHEDULE VD-285399

ELECTRICAL ONE LINE DIAGRAM VA-289982 SH. 001

DWG. CONTROL FOR J.O. 10-00610-0001 VD-429355


ELECTRICAL ONE LINE DIAGRAM VA-415049

120V POWER
SUPPLY
CONTINUED FROM
ABOVE RIGHT

50AT 50AT 50AT 50AT 30AT


100AF,3P 100AF,3P 100AF,3P 100AF,3P 100AF,3P
PC-1256
PC-1254

PC-1255

PC-1257

PC-1838

REVISION VALIDATION

THIS REVISION NO. 03 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

10-00610-0001-012

DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER


(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

MAR HAK AHH WAS


12/03/12 12/03/12

REV.NO. DATE REVISION DESCRIPTION

03 11/19/12 AS-BUILT

X04-001-PP-003 X04-001-PP-004 X04-001-PP-005 X04-001-PP-006


JOB ORDER/EWO NO.
480V, 3{, 3W 480V, 3{, 3W 480V, 3{, 3W 480V, 3{, 3W THIS REVISION IS NOT TO BE USED FOR
10-00610-0001 CONSTRUCTION UNTIL CERTIFIED AND DATED

POWER PANEL POWER PANEL POWER PANEL POWER PANEL ALTERNATE SUPPLY TO SAUDI ARABIAN OIL COMPANY
AT LOADING ISLAND AT UNLOADING ISLAND AT PUMP STATION-2 AT PUMP STATION-1 LOCAL CONTROL PANEL DRAWING TYPE

REFER DRAWING REFER DRAWING REFER DRAWING REFER DRAWING LIFT STATION PUMPS ELECTRICAL ONE LINE DIAGRAM E1L
VA-285386.001 VA-289987.002 VA-289987.003 VA-289987.004 X04-GM-1633A/B
SEE DWG. VA-415049 SH. 001 480V SWITCHRACK X04-001-SR-001
TABUK BULK PLANT

TABUK SAUDI ARABIA


PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

X04 P VA-289985 001 03


Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-05


THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
NOTES:

1. THE SWITCHRACK AND THE POWER DISTRIBUTION


PANELS SHALL BE MANUFACTURED IN ACCORDANCE
WITH THE APPLICABLE SAUDI ARAMCO ENGINEERING
AND MATERIAL SPECIFICATION STANDARDS.

FROM X10-MCC-002 2. CABLE DESIGNATIONS AND SIZES TO BE REFERRED


(SEE DWG. VA-453049 SH. 001) TO THE CABLE AND CONDUIT SCHEDULE, DWG
VD-007410.

3. ALL GENERAL-LOAD FEEDER BREAKERS, WITH


30kW RATING AND ABOVE, AND TRANSFORMER
FEEDER BREAKERS SHALL BE PROVIDED WITH GROUND
OVERCURRENT PROTECTION AS PER 16-SAMSS-512.
480V SWITCHRACK X10-SR-003 (JET A-1 PUMP CANOPY)
4. FOR GENERAL NOTES, LEGEND AND SYMBOLS REFER
TO DWG NO.VA-453044 AND VA-453045.
600A BUS, 480V, 3PH, 4W, 60HZ, 25KA SYM.

600AF 100AF 150AF 150AF 150AF 100AF 100AF 150AF


(NOTE 3) (NOTE 3) (NOTE 3) (NOTE 3)
400AT 70AT 110AT 110AT 110AT 7AT 30AT 90AT
LEGEND
(NOTE 3)
480-120V 480-120V 480-120V 480-120V 480-120V

2 2 2 2 2 2 2 2 2 2 CIRCUIT BREAKER, MOLDED-CASE TYPE


3
4 4 4 2
TR C C C C
AF
BREAKER AMPERE FRAME AND TRIP RATING
AT

CONTROL FUSE

PC

PC-852
CONTROL POWER TRANSFORMER

C MAGNETIC COIL

TIMER RELAY
TR
(ON-DELAY)

PC-950
PC-946
PC-949

CC-603

PC-947

CC-604

PC-948
CC-742

CC-743
PC PHOTOELECTRIC CELL

CS CONTROL STATION

N MAGNETIC CONTACTOR
55 CS 55 CS
50 kVA 3HP NON-REVERSING TYPE
(NEMA SIZE, AS INDICATED)

MAGNETIC CONTACTORS

LOCAL CONTROL PANEL


X10-RP-006
REVERSING TYPE

RECOVERED OIL PUMP


(NEAR X10-D-0005C)
JET A-1 TANK AREA

CC-1524

CPI O/W SEPARATOR


JET A-1 PRODUCT

JET A-1 PRODUCT


LOADING PUMP A

LOADING PUMP B
THERMAL OVERLOAD RELAY
LIGHTING PANEL

X10-GM-0004A

X10-GM-0004B
JUNCTION BOX

(X10-GM-0014)
X10-CJB-008
TO CONTROL
X10-LP-008

X10-CP-010
S P A R E

S P A R E
(STAND-BY)
MOTOR
3.7
(INDICATED RATING, IN KILOWATTS)

DISTRIBUTION TRANSFORMER
(RATING, AS INDICATED)

kVA GENERAL LOAD

MOLDED CASE SWITCH (MCS)

POWER PANEL X10-PP-020 (JET A-1 PUMP CANOPY)


WELDING RECEPTACLE
WR
150AF
90AT PC-948 POWER CABLE NUMBER
150A BUS, 480V, 3PH, 4W, 60HZ, 25KA SYM.
(NOTE 3)
CC-608 CONTROL CABLE NUMBER

100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF
7AT 7AT 7AT 7AT 7AT 7AT 25AT 40AT 3AT 60AT 30AT
REFERENCE DRAWINGS
(NOTE 3) (NOTE 3)
DRAWING CONTROL (J.O.NO.35081) VD-420075
SPARE
ONE LINE DIAGRAM VA-453046
OVERALL POWER DISTRIBUTION SYSTEM
ONE LINE DIAGRAM VA-453049
480V CONTROLGEAR X10-MCC-002

CABLE AND CONDUIT SCHEDULE VD-007410


PC-951

PC-956

PC-959
PC-952

PC-953

PC-954

PC-955

PC-957

X10-XFR-011
15 KVA
480-208Y/120V
PC-958

CS CS CS CS CS CS
REVISION VALIDATION

3.7 3.7 3.7 3.7 3.7 3.7 15 KVA THIS REVISION NO. 02 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
WR REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

11W006-008
(JET A-1 PUMP CANOPY)
JET A-1 TANK D-0005A

JET A-1 TANK D-0005A


JET A-1 TANK D-0005B

JET A-1 TANK D-0005C

JET A-1 TANK D-0005B

JET A-1 TANK D-0005C

DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER


WELDING RECEPTACLE

(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

RFP JAF FMS AOA


TANK FARM AREA

05/31/07 05/31/07 05/31/07 05/31/07


OUTLET, 25 kVA
(NEAR JET A-1
LOADING PUMP)
OUTLET VALVE

OUTLET VALVE

OUTLET VALVE

UTILITY PANEL

REV.NO. DATE REVISION DESCRIPTION


INLET VALVE

INLET VALVE

INLET VALVE

X10-MOV-120

02 05/11/11 AS-BUILT
X10-MOV-116
X10-MOV-119
X10-MOV-115

X10-MOV-117

X10-MOV-118

X10-WR-005
X10-PP-011

S P A R E

S P A R E
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
35081 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY


DRAWING TYPE

ELECTRICAL ONE LINE DIAGRAM E1L

480V SWITCHRACK X10-SR-003


BULK PLANT

ABHA SAUDI ARABIA


PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

X10 P VA-453055 001 02


Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-05


THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
NOTES CONT’D: NOTES:
6. MOTOR SHALL BE SUPPLIED ALONG WITH VARIABLE 8. AS PER NEW ELECTRICAL SCOPE CHANGE UNDER 1. THE SWITCHRACK AND THE POWER DISTRIBUTION
FREQUENCY DRIVE (VFD) AND ALL CONTROLS J.O. 10-00610-0001, EXISTING SPARE FEEDER WHICH PANELS SHALL BE MANUFACTURED IN ACCORDANCE
SHALL BE AS PER 17-SAMSS-502. IS PRESENTLY LEFT AS BLANK SHALL BE WITH THE APPLICABLE SAUDI ARAMCO ENGINEERING
CONSIDERED AS A SPACE FEEDER AND PROVIDED AND MATERIAL SPECIFICATION STANDARDS.
7. STARTER CONTROL WIRING SHALL BE REVISED
WITH NEW NEMA-4 STARTER IN THE EXISTING SPACE
AS PER ELE. DIAGRAM DWG. NO. VA-XXXXXX. 2. CABLE DESIGNATIONS AND SIZES TO BE REFERRED
FROM X10-MCC-001 ENCLOSURE TO FEED THE NEW DIESEL PUMP MOTOR

(SEE DWG. VA-453048 SH. 001) X10-GM-0202. TO THE CABLE AND CONDUIT SCHEDULE, DWG
VD-007410.
9. AS PER NEW ELECTRICAL SCOPE CHANGE UNDER
J.O. 10-00610-0001, EXISTING MAIN BREAKER 3. ALL GENERAL/MOTOR LOAD FEEDER BREAKERS,
800AF/600AT SHALL BE REPLACED WITH NEW WITH 30kW RATING AND ABOVE, AND TRANSFORMER
MAIN CIRCUIT BREAKER 800AF/700AT. FEEDER BREAKERS, SHALL BE PROVIDED WITH GROUND
OVERCURRENT PROTECTION AS PER 16-SAMSS-512.

480V SWITCHRACK X10-SR-001 (DIESEL PUMP CANOPY) 4. FOR GENERAL NOTES, LEGEND AND SYMBOLS REFER
TO DWG NO.VA-453044 AND VA-453045.
800A BUS, 480V, 3PH, 4W, 60HZ, 30KA SYM.
5. THIS IS A TEMPORARY FACILITY, THE MOST SUITABLE
AVAILABLE SPARE FEEDER IS USED FOR THE PUMP.

800AF 150AF 225AF 100AF 100AF 100AF 150AF 150AF 150AF 150AF 150AF LEGEND
(NOTE 3) (NOTE 3) (NOTE 3) (NOTE 3) MCP
700AT 80AT 175AT 50AT 15AT 15AT 110AT 110AT 110AT 110AT (NOTE 3) 110AT
150A
NOTE 3 (NOTE 3)
480-120V 480-120V 480-120V 480-120V 480-120V 480-120V 480-120V 480-120V
480-120V CIRCUIT BREAKER, MOLDED-CASE TYPE

2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
4 2 2 AF
3 1 1 4 4 4 4 BREAKER AMPERE FRAME AND TRIP RATING
TR TR C C C C C C 4 AT
C

(NOTE 7) CONTROL FUSE

50G
IN-COMING
CONTROL POWER TRANSFORMER
SPLACE C
BOX PC
PC-850

TIMER RELAY
TR
(ON-DELAY)

PC-2544

PC-2543
PC PHOTOELECTRIC CELL

C MAGNETIC COIL

CC-2342
PC-2301
CC-736

CC-596
CC-594

CC-735

CC-595

CC-737

CC-597

CC-738
PC-916

PC-919
PC-913

PC-912

PC-915

PC-917

PC-918
CS CONTROL STATION

10 X10-PP-014, SEE
N MAGNETIC CONTACTOR
NON-REVERSING TYPE

DWG. VA-453139
(NEMA SIZE, AS INDICATED)

55 CS 55 CS 55 CS 55 CS 100 CS
100HP 35 KVA
MAGNETIC CONTACTORS
REVERSING TYPE

THERMAL OVERLOAD RELAY

X10-RP-005

MOTOR
3.7
LOCAL CONTROL PANEL

CC-1523 (INDICATED RATING, IN KILOWATTS)


(NEAR X10-D-0001C)
DIESEL TANK AREA
X10-GM-0012/0013

DISTRIBUTION TRANSFORMER

LOADING PUMP D
DIESEL PRODUCT

DIESEL PRODUCT
DIESEL LOADING
LOADING PUMP A

LOADING PUMP C
LOADING PUMP B
DIESEL PRODUCT

DIESEL PRODUCT
DIESEL PRODUCT
LIGHTING PANEL
SUMP PUMP A/B

LOADING PUMP
(RATING, AS INDICATED)

JUNCTION BOX
NORMAL FLOW)

X10-GM-0001D
X10-GM-0001A

X10-GM-0001C
X10-GM-0001B
(MAXIMUM AND

X10-CJB-006

X10-GM-0202
X10-LP-006

PUMP AREA
OILY WATER
X10-CP-005

S P A R E

S P A R E
GENERAL LOAD

CONTROL
MOULDED CASE SWITCH (MCS)

WELDING RECEPTACLE
WR

PC-917 POWER CABLE NUMBER


POWER PANEL X10-PP-015 (DIESEL PUMP CANOPY)

CC-601 CONTROL CABLE NUMBER


:$$

VFD VARIABLE FREQUENCY DRIVE


$$SARAMCO-DCC-STAMP$$:756500-JO-1999-35081-004 :MSM:128131 :2003-09-16:V453053001V01

150AF
100AT
125A BUS, 480V, 3PH,4W, 60HZ, 25KA SYM. REFERENCE DRAWINGS
DWG. CONTROL FOR J.O. 10-00610-0001 VD-429356
CABLE AND CONDUIT SCHEDULE VD-350512

100AF CABLE ROUTING PLAN VA-453081


100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF 100AF
7AT 7AT 7AT 7AT 7AT 7AT 3AT 60AT 15AT 60AT 30AT CABLE ROUTING PLAN VA-453082 SH. 001
ELECTRICAL ONE LINE DIAGRAM, OVERALL PWR. DIST. VA-453046 SH. 001
(NOTE 3) (NOTE 3)
ELECTRICAL ONE LINE DIAGRAM, 480V SWITCHGEAR VA-453047 SH. 001
PANEL SCHEDULE VA-453139
DRAWING CONTROL (J.O.NO.35081) VD-420075
ELECTRICAL ONE LINE DIAGRAM, X10-MCC-001 VA-453048
CABLE AND CONDUIT SCHEDULE VD-007410
PC-998
PC-921
PC-920

PC-926
PC-922

PC-923

PC-924

PC-925

PC-987
S P A R E

REVISION VALIDATION

THIS REVISION NO. 03 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
CS CS CS CS CS CS CS
X10-PP-026
10-00610-0001-017

3.7 3.7 3.7 3.7 3.7 3.7 0.3 DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)
WR WR WR
ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

MAR HAK AAD MMB


10/31/12 10/31/12
DIESEL TANK D-0001A

DIESEL TANK D-0001A


DIESEL TANK D-0001B

DIESEL TANK D-0001C

DIESEL TANK D-0001B

DIESEL TANK D-0001C

REV.NO. DATE REVISION DESCRIPTION


WELDING RECEPTACLE

WELDING RECEPTACLE

WELDING RECEPTACLE
(NEAR X10-D-0001A)

(NEAR X10-D-0001C)

03 06/30/12 AS-BUILT
PRINTER BUILDING

JOB ORDER/EWO NO.


THIS REVISION IS NOT TO BE USED FOR
OUTLET, 25 kVA

OUTLET, 25 kVA

OUTLET, 25 kVA
(NEAR GASOLINE

10-00610-0001 CONSTRUCTION UNTIL CERTIFIED AND DATED


OUTLET VALVE

OUTLET VALVE

OUTLET VALVE

PUMP CANOPY)
INLET VALVE

INLET VALVE

INLET VALVE

X10-WR-003A
X10-WR-003C

X10-WR-003B
X10-MOV-122

(BY SIEMENS)
X10-MOV-101

SAUDI ARABIAN OIL COMPANY


X10-MOV-106
X10-MOV-103

X10-MOV-105

X10-MOV-102

X10-MOV-104

X10-PP-026
S P A R E

DRAWING TYPE

ELECTRICAL ONE LINE DIAGRAM E1L

480V SWITCHRACK X10-SR-001


ABHA BULK PLANT

ABHA SAUDI ARABIA


PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

X10 P VA-453053 001 03


Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-05


THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
NOTES:
1. 120V AC, 1{ POWER SUPPLY FOR (LCP) LOCAL
CONTROL PANELS IS SUPPLIED FROM PANEL
X55-PP-1.

X55-ATS-001
AUTO TRANSFER SWITCH
3 PH, 480V, 400 AMP
(LOCATED IN ATS ROOM)

FROM EXISTING X55-XFR(T)-3002


(ALTERNATE SUPPLY) (NORMAL SUPPLY) 13.8kV-480/277V TRANSFORMER
TO GENERATOR SET X55-P-001
VIA ENCLOSED CIRCUIT BREAKER
BLOCK
SEE DWG. VA-401593 SH. 001
TRANSFER
PC-1590 PC-1610

86

(3) (1)
480/120V 480/120V
50 50

CT 51 51G

400/5A
(3)
LEGEND

TRANSFORMER
RATING AS INDICATED
VS A 0-400A VS
CT
400/5A POTENTIAL TRANSFORMER
(1)
PT

V V WINDOW TYPE, ZERO SEQUENCE


CT
CURRENT TRANSFORMER

(0-600V) (0-600V)

MCP MOTOR CIRCUIT PROTECTOR


(MAGNETIC ONLY)
*
(* RATING AS INDICATED)

X55-JB-XXXX TO SWITCHRACK
X55-SR-0002, SEE
AF MOLDED CASE CIRCUIT BREAKER,
DWG. VA-445280 SH. 001
PC-1612 AT (THERMAL/MAGNETIC)

MAGNETIC CONTACTOR

THERMAL OVERLOAD
DEVICE

PC-1611
10 MOTOR RATING IN HORSEPOWER

SWITCHRACK X55-SR-0001 50
GROUND SENSOR RELAY
GS

400AF POWER CABLE


PC- *
350AT ( * - INDICATES NUMBER )

CONTROL CABLE
CC- *
( * - INDICATES NUMBER )

LCP LOCAL CONTROL PANEL

FUSE (CARTRIDGE TYPE)

400 AMP, 480V, 60Hz, 3{, 3W, 22KAIC (SYM. BUS)

A AMMETER

MCP MCP 100AF MCP MCP MCP MCP 100AF MCP MCP MCP MCP V VOLTMETER
30A 100A 60AT 15A 15A 70A 70A 45AT 15A 15A 15A 15A
1 3 1 1 3 3 1 1 1 1
PC-1628 PB PUSH BUTTON STATION
X55-XFR-001
15KVA, 3{,
PC ELECTRIC PHOTOCELL
480-208V/120V

X55-PP-1 PC-1629
LCS LOCAL CONTROL STATION
208/120V, 3{,
50
50 50 4W, 18 CIRCUITS
GS
PC
GS GS (SEE NOTE-1)

PC-1593
REFERENCE DRAWINGS
PC-1591
LIGHTING DRAWING CONTROL J.O. 10-00084-0001 VD-338752
CONTROL PANEL ELECTRICAL ONE LINE DIAGRAM, 13.8KV SWGR. VA-401593
CABLE ROUTING PLAN VA-401595

CABLE AND CONDUIT SCHEDULE VD-338812

120V RECEPTACLE OUTLET

PC-1620

PC-1650
CC-1640
CC-1636

PC-1626

PC-1656

CC-1639
CC-1635

CC-1637

CC-1638

PC-1623

PC-1624

PC-1625

PC-1662

PC-1663
PC-1616

PC-1619
PC-1615

PC-1617

PC-1618
CC-1633

CC-1634
PC-1613

PC-1614

LCS LCS
TO X55-PP-3 AT ATS ROOM
FLOW METER, FM/FI-0418

10 LCP 40 LCP 5 7.5 30 LCP 30 LCP 6 LCP 6 LCP 3 LCS


TO X55-JB-0001

REVISION VALIDATION

X55-GM-0254
PLC

PLC

X55-LCP-0551
X55-GM-0257A

X55-GM-0259A
X55-GM-0257B

X55-GM-0259B
X55-LCP-0553

X55-LCP-0554

X55-LCP-0555

PLC
X55-GM-0261
X55-GM-0260

X55-GM-0263

X55-GM-0262

THIS REVISION NO. 01 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
(STANDBY)

(STANDBY)
(NORMAL)

10-00084-0001-009
MAXIMUM

SPARE

SPARE
(DUTY)

(DUTY)
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

CEE MAN EGA OAB


06/17/06 06/17/06 06/17/06 06/17/06
CPI RECOVERED PRODUCT SEWAGE LIFT CPI SEPARATOR
SUMP PUMP MOTORS REV.NO. DATE REVISION DESCRIPTION
TRANSFER/INJECTION STATION LS-2 SLUDGE PUMPS
01 01/29/11 AS-BUILT
PUMP MOTORS
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
10-00084-0004 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY


DRAWING TYPE

ELECTRICAL ONE LINE DIAGRAM E1L

SWITCHRACK X55-SR-0001
BULK PLANT

NAJRAN SAUDI ARABIA


PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

X55 P VA-445279 001 01


Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-05


THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
NOTES:
1. SWITCHRACK SHALL BE DESIGNED, MANUFACTURED
AND TESTED IN ACCORDANCE WITH 16-SAMSS-512.

2. SWITCHRACK INSTALLATION SHALL BE DONE AS PER


SAUDI ARAMCO ENGINEERING STANDARD SAES-P-116.

3. ALL CONTROL VOLTAGE SHALL BE 120V AC, 1{,


60 Hz.

4. 120V AC, 1{ POWER SUPPLY FOR (LCP) LOCAL


CONTROL PANELS IS SUPPLIED FROM PANEL
X07-PP-3.

5. MOTOR RATING FOR SEWAGE LIFT STATION-1


REVISED TO 7.5HP.

LEGEND

TRANSFORMER
RATING AS INDICATED

MCP MOTOR CIRCUIT PROTECTOR


(MAGNETIC ONLY)
*
(* RATING AS INDICATED)

FROM LV SWITCHGEAR X07-001-SG-001


SEE DWG. VA-284650 SH.001
AF MOLDED CASE CIRCUIT BREAKER,
AT (THERMAL/MAGNETIC)

MAGNETIC CONTACTOR
PC-2082

SWITCHRACK X07-SR-0003 THERMAL OVERLOAD


DEVICE
225AF
200AT
12 MOTOR RATING IN HORSEPOWER

50
PHASE OVER CURRENT RELAY
51

POWER CABLE
PC- *
( * - INDICATES NUMBER )
CONTROL CABLE
CC- *
225AMP, 480V, 60Hz, 3{, 3W, 10KAIC (SYM. BUS) ( * - INDICATES NUMBER )

LCP LOCAL CONTROL PANEL

MCP MCP 100AF MCP MCP 100AF MCP MCP MCP


PC ELECTRIC PHOTOCELL
30A 30A 45AT 15A 15A 45AT 15A 15A 50A
2 2 1 1 PC-2036 1 1 2
X07-XFR-003 REFERENCE DRAWINGS
15KVA, 3{, DRAWING CONTROL J.O. 10-00084-0001 VD-338562
480-208V/120V
ELECTRICAL ONE LINE DIAGRAM, LSG-105 VA-140405 SH. 004
PC-2037
X07-PP-3 CABLE ROUTING PLAN VA-140400
208/120V, 3{, CABLE AND CONDUIT SCHEDULE VD-338637
4W, 18 CIRCUITS PC
(SEE NOTE-4)

LIGHTING
CONTROL PANEL

PC-2039
PC-2038

PC-2041
PC-2079
PC-2078

CC-2092

CC-2093

PC-2083

PC-2062

PC-2063
PC-2196
PC-2195

CC-2117

CC-2118
120V RECEPTACLE OUTLET

SANITARY LIFT STN-1


7.5 LCP 7.5 LCP 10 LCP 60 LCP

STORM WATER SUMP


X07-LCP-0701

X07-LCP-0709

AREA LIGHTING

AREA LIGHTING
X07-GM-0301A

X07-GM-0301B

X07-GM-0317

X07-GM-0318
(STANDBY)

(MAXIMUM)
(NORMAL)
SPARE

SPARE

SPARE

SPARE
(DUTY)

SANITARY WASTE WATER STORM WATER SUMP


LIFT STATION-1 PUMPS

REVISION VALIDATION

THIS REVISION NO. 01 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

10-00084-0001-101

DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER


(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

CEE MAN EGA OAB


06/17/06 06/17/06 06/17/06 06/17/06

REV.NO. DATE REVISION DESCRIPTION

01 12/04/10 AS-BUILT

JOB ORDER/EWO NO.


THIS REVISION IS NOT TO BE USED FOR
10-00084-0009 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY


DRAWING TYPE

ELECTRICAL ONE LINE DIAGRAM E1L

SWITCHRACK X07-SR-0003
BULK PLANT NORTH JIDDAH

JIDDAH SAUDI ARABIA


PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

X07 P VA-445184 001 01


Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-05


FOR CONTINUATION FOR CONTINUATION
SEE ABOVE RIGHT SEE ABOVE RIGHT

7AMPS, 3PH, 480V PC-1288


7AMPS, 3PH,480V

M
X05-JB-0004

&
PC-1305
X05-JB-0007

M
X05-FCV-191
X05-FCV-202 DIESEL CUSTODY

15AT
X05-MCC-0002
FROM EXISTING

VA-414724.002

CS
100AF
GASOLINE CUSTODY METERING

15AT
100AF

CS
METERING
SEE DWG. VA-608528

PC-1272
7AMPS, 3PH, 480V PC-1289

M
PC-1306 X05-JB-0004
7AMPS,3PH, 480V

M
X05-FCV-193
X05-JB-0007
DIESEL CUSTODY

15AT
X05-FCV-204
MCS

CS
100AF
METERING

15AT
480V, 3{, 3W, 60Hz, 200A, 25kA
GASOLINE CUSTODY
200A

100AF
480V, 3{, 3W, 60Hz, 200A, 25kA

CS
METERING

7AMPS, 3PH, 480V


PC-1290
7AMPS, 3PH, 480V X05-JB-0003 PC-1273

M
PC-1307
X05-MOV-716

M
7AMPS, 3PH,480V X05-JB-0005

M
480V, 3{, 3W, 60Hz, 200A, 25kA

X05-JB-0008 X05-FCV-195 DIESEL CUSTODY-

15AT
X05-FCV-206 DIESEL METER METERING

CS
100AF

15AT
15AT

CS
GASOLINE CUSTODY PROVER

100AF
100AF

CS
METERING
1.5HP
X05-JB-0006 7AMPS,3PH,480V
PC-1291
X05-GM-0121 PC-1274
7AMPS, 3PH, 480V PC-1308
X05-JB-0003

M
M
DIESEL DENSITY X05-MOV-717

M
X05-JB-0008
METER DIESEL CUSTODY-
X05-FCV-208

15AT

CS
CUSTODY METERING

100AF
METERING
15AT

GASOLINE CUSTODY
CS

15AT
100AF

CS
(FAST LOOP PUMP)

100AF
METERING

PC-1292
7AMPS, 3PH, 480V PC-1275
7AMPS, 3PH, 480V

M
PC-1309
M

X05-JB-0007
7AMPS, 3PH, 480V X05-JB-0003

M
X05-MOV-731
X05-JB-0009 X05-MOV-718

15AT
GASOLINE

CS
100AF
X05-FCV-210 DIESEL CUSTODY-
15AT

15AT
CS
100AF

CUSTODY METERING

100AF

CS
GASOLINE METER METERING

PROVER

7AMPS, 3PH, 480V


1.5HP PC-1293
X05-JB-0007 7AMPS, 3PH, 480V PC-1276

M
X05-JB-0010 PC-1310
M

X05-MOV-732 X05-JB-0003
X05-GM-0123

M
GASOLINE CUSTODY X05-MOV-719
GASOLINE DENSITY

15AT
DIESEL CUSTODY-

CS
METERING

100AF
15AT

METER
CS

15AT
100AF

METERING

CS
100AF
CUSTODY METERING
(FAST LOOP PUMP)

7AMPS, 3PH, 480V PC-1294


7AMPS, 3PH, 480V PC-1277

M
X05-JB-0007
M

X05-PP-0021
X05-MOV-733 X05-JB-0003
INSTRUMENT
GASOLINE CUSTODY X05-MOV-720
POWER PANEL
15AT

CS
100AF

DIESEL CUSTODY-
15AT

20 kVA
METERING
CS
100AF

METERING

100AF
50AT
7AMPS, 3PH, 480V PC-1295
7AMPS, 3PH, 480V PC-1278

M
X05-JB-0007

30kVA, 3{,
M

X05-JB-0003
LIGHTING X05-MOV-734

X05-XFR-T010
X05-MOV-721

480-208/120V
CONTROL PANEL GASOLINE CUSTODY
15AT

DIESEL CUSTODY-

CS
X05-LCP-0006
100AF

METERING
15AT

PC
CS

AREA LIGHTING AT METERING


100AF

METERING STATION

7AMPS, 3PH, 480V PC-1296


WELDING 7AMPS, 3PH, 480V PC-1279

M
X05-JB-0007
M

RECEPTACLE X05-JB-0004
X05-MOV-735
(X05-WR-0002 X05-MOV-722
GASOLINE CUSTODY
15AT

WR
(15kVA) DIESEL CUSTODY-
CS
100AF
15AT

METERING
CS
100AF

METERING

100AF
50AT
7AMPS, 3PH, 480V
PC-1297
X05-JB-0007 7AMPS, 3PH,480V PC-1280
M

7AMPS, 3PH, 480V PC-1315


M

X05-MOV-736 X05-JB-0004

M
X05-JB-0005
GASOLINE CUSTODY X05-MOV-723
X05-MOV-729
15AT

METERING DIESEL CUSTODY-


CS
100AF

DIESEL METER
15AT

15AT
CS
100AF

100AF
METERING

CS
PROVER SKID

7AMPS, 3PH, 480V PC-1298


7AMPS, 3PH, 480V PC-1316 PC-1281
7AMPS, 3PH,480V
M

X05-JB-0008
M

M
X05-JB-0009
X05-MOV-737 X05-JB-0004
X05-MOV-744
GASOLINE CUSTODY X05-MOV-724
15AT

GASOLINE METER
CS

15AT METERING DIESEL CUSTODY-


100AF
15AT

CS

100AF

CS
PROVER SKID
100AF

METERING

7AMPS, 3PH, 480V


PC-1299
X05-JB-0008 PC-1282
PC-2015 7AMPS, 3PH,480V
M
M

1.5
X05-MOV-738 X05-JB-0004
480V SWITCHRACK X05-SR-0002 AT METERING STATION

X05-MOV-0884
GASOLINE CUSTODY X05-MOV-725
15AT

METERING AREA
100AF

CS

METERING DIESEL CUSTODY-


15AT

CS

CS
100AF

METERING
100AF
20AT

PC-1300
7AMPS, 3PH, 480V PC-1283
M

PC-2016
7AMPS, 3PH, 480V
M

X05-JB-0008

1.5
X05-MOV-0885 X05-MOV-739 X05-JB-0004
15AT

METERING AREA GASOLINE CUSTODY X05-MOV-726


CS
100AF
15AT

CS

METERING DIESEL CUSTODY-


100AF

CS
100AF
20AT

METERING

PC-1301
X05-001-CP-001
7AMPS, 3PH, 480V PC-1284
M

DYE SENSING PC-2017 7AMPS, 3PH, 480V


M

X05-JB-0008
UNIT CONTROL X05-JB-0004
PANEL (SUPPLY X05-MOV-740
X05-MOV-727
15AT

BY VENDOR) GASOLINE CUSTODY


CS
100AF

DIESEL CUSTODY-
15AT

CS

METERING
100AF

METERING
100AF
25AT

7AMPS, 3PH, 480V PC-1302


PC-1285
M

X05-JB-0008
M

7AMPS, 3PH, 480V


SPARE X05-MOV-741
X05-JB-0005
15AT

GASOLINE CUSTODY
100AF

X05-MOV-728
CS
15AT

CS

METERING
100AF

DIESEL METER
100AF
25AT

PROVER

7AMPS, 3PH, 480V


PC-1303
PC-1286
M

X05-JB-0008
7AMPS, 3PH, 480V
M

X05-MOV-742
SPARE X05-JB-0003
GASOLINE CUSTODY
15AT

X05-FCV-187
100AF

CS

METERING
15AT

CS

DIESEL CUSTODY
100AF

METERING
100AF
25AT

7AMPS, 3PH, 480V PC-1304


PC-1287
M

X05-JB-0009 7AMPS, 3PH,480V


M

X05-MOV-743 X05-JB-0003

GASOLINE METER X05-FCV-189


15AT

CS
100AF

SPARE
15AT

PROVER DIESEL CUSTODY


CS
100AF

METERING

FOR CONTINUATION
SPARE
SEE BELOW LEFT
FOR CONTINUATION
SEE BELOW LEFT
01
REV.NO.
ENGG./DATE

RFP
PC

DUBA
CS

DATE
AF

X05
AT

PLANT NO.
3.7

05/31/07
MCS
MCP
NOTES:

15kVA

PC-XXXX
MCP

05/31/07
WR

JOB ORDER/EWO NO.

INDEX

P
THIS REVISION NO.

(DESIGN AGENCY)
01

AS-BUILT
JAF
DESIGN CERTIFICATION
MOTOR

05/31/07

10-03548-0002
CERTIFIED BY/DATE

REVISION DESCRIPTION
CABLE & CONDUIT SCHEDULE
100AF/20AT BREAKER.

MOTOR PUMP

CABLE AND CONDUIT SCHEDULE


ELECTRICAL ONE LINE DIAGRAM
ELECTRICAL ONE LINE DIAGRAM
AMPERE TRIP

CONTROL FUSE

GENERAL LOAD
AMPERE FRAME

ELECTRICAL DETAILS X05-SR-0002

FMS
CONTROL STATION

05/31/07
x REQUIRED

RESTRICTED
SPECIFICATION 16-SAMSS-512.

CABLE ROUTING PLAN-OVERALL LAYOUT


LEGEND

DRAWING NUMBER
BOXES ARE VENDOR SUPPLIED.

REVERSING STARTER

DWG. CONTROL FOR J.O. (10-03548-0002)

CONST. AGENCY/DATE
PHOTOELECTRIC CELL

WELDING RECEPTACLE

POWER CABLE NUMBER


MOLDED CASE SWITCH

REVISION VALIDATION
(RATING, AS INDICATED)

BULK PLANT
10-03548-0002-001
CABLE AND CONDUIT LAYOUT MCC BUILDING

VA-608530
REFERENCE DRAWINGS
MOTOR CIRCUIT PROTECTOR
MOTOR CIRCUIT PROTECTOR

THERMAL OVERLOAD RELAY

DISTRIBUTION TRANSFORMER

COMPONENT OF SWITCHRACK

AOA
05/31/07

ELECTRICAL ONE LINE DIAGRAM


REVIEW FOR KEY DRAWINGS
(SAUDI ARAMCO)

OPERATIONS/DATE
(INDICATED RATING, IN KILOWATTS)

SHT. NO.
ARE FED FROM POWER PANEL X05-PP-0021.

001

VECTOR
CONTROL POTENTIAL TRANSFORMER

VA-414716
1. THE SWITCHRACK IS DESIGNED, MANUFACTURED

VD-285183
VD-608122

VD-006150

VD-027637
VA-608528

480V SWITCHRACK X05-SR-0002


4. REPLACE EXISTING 100AF/25AT BREAKER WITH

SAUDI ARABIAN OIL COMPANY


BY/DATE
2. THE LIGHTING FOR METERING AND PROVER SKIDS
AND TESTED IN ACCORDANCE WITH SAUDI ARAMCO

VA-414724.002

VA-608538.005
VA-608535.006

THIS REVISION IS NOT TO BE USED FOR


REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
IS COVERED, FOR ALL APPROVAL AND CERTIFICATION

OTHER

CONSTRUCTION UNTIL CERTIFIED AND DATED

E1L

SAUDI ARABIA

01
3. ALL ELECTRICAL EQUIPMENT AFTER FIELD JUNCTION

REV. NO.
DRAWING TYPE

Saudi Aramco 2615 ENG. (05/05)

CADD-05

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
001 0 P BA-107493 D41 31300 NOTES:
REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO. JOB ORDER/EWO NO.

1. FOR REFERENCE DWG. REFER TO XA-F67732 SH. 1.


2. CONDUIT SPACING SHALL BE FIT TO CONDUIT
ENTRY HUBS OF ALL DEVICES MOUNTED ON THE
RACK. CONDUIT STUB UPS AS SHOWN ON THIS
DRAWING ARE FOR REFERENCE ONLY.

DATA SHEET FOR LOW VOLTAGE SWITCHRACKS


SWITCHRACK COMPONENT
LAMINATED PLASTIC NAMEPLATE ENGRAVINGS MOTOR DATA STARTER CKT. BKR. MODIFICATIONS
A. GENERAL REQUIREMENTS POS. REMARKS
NO. SERVICE MAG THERM HI SEL IND AUX. CONT. SPA
OUTDOOR LINE 1 LINE 2 LINE 3 HP RPM FLA SIZE TYPE PB CPT B&D TB
ENHIRONMENTAL CONDITIONS FACTOR ONLY MAG BK SW LT N.O. N.C. HTR
AREA CLASSIFICATION: CLASSI GROUPD DIVISION2 UNCLASSIFIED 1 MAIN INCOMING BREAKER 100AF/100AT
ENCLOSURE: NEMA 4 NEMA 7 OTHER NEMA 8 2 MOV-113 FEEDER BREAKER 4.4 100AF/20AT
STRUCTURE: BUS & DEVICE ENCLOSURE MAT’L. ALUM. STAINLESS
HARDWARE
3 MOV-112 FEEDER BREAKER 7.2 100AF/30AT
(ALUM. OR GALV.) (STL, GALV., ETC.)
4 MOV-114 FEEDER BREAKER 4.4 100AF/20AT
BUS BARS COPPER 5 LTG. XFMR FEEDER BREAKER 100AF/15AT
(ALUMINUM OR COPPER)
6 SPARE FEEDER BREAKER 100AF/15AT
HORIZ. AMPS. 600 22,000
BRACED GROUND BUS NEUTRAL BUS
(22,000 STD.) 7 RTU TRF. FEEDER BREAKER 100AF/15AT
MAIN: CIRCUIT BREAKER100 AMP. TRIP/100 AMP FRAME 8 XFMR. 5KVA LIGHTING
RATING
TYPE ENCLOSURE: BOLTED THREADED 9 LIGTHING PANEL
CONTROL VOLTAGE: 120V OTHER 480V 10 XFMR. 5 KVA RTU
SPACE HEATER (BUS ENCLOSURE) POWER SOURCE LT PAN VOLTS 120 PHASE 1 11 LIGTHING CONTACTOR C/W HOA
SPACE HEATER (CONTR. ENCLOSURE) PWR. SOURCE VOLTS PHASE 12 BREAKER
CP RECTIFIER FEEDER 100AF/15AT
MAXIMUM SURFACE TEMP. SPACER HEATERS ^F ^C

B. WIRING REQUIREMENTS 1-3/C 70mm2 600 VOLT, XLPE/PVC


INCOMING POWER-WIRE SIZE AND TYPE +1/C 70mm2 GND. WIRE
CONDUIT SIZE 2" LOCATION BOTTOM
OUTGOING POWER-WIRING METHOD AND TYPE
CONDUIT SIZE LOCATION
OUTGOING CONTROL AND/OR ALARM-WIRING METHOD AND TYPE
CONDUIT SIZE LOCATION
SPARE
GROUNDING-WIRING METHOD AND TYPE

(1’-7 11/16 ")


CONDUIT SIZE LOCATION
CONTROL: LOCAL REMOTE OTHER
| OF SWITCHRACK
C. RELAYING-OVERLOAD RELAYS 50.8 25.4

500
(2") (1" TYP.)
THERMAL-(STANDARD) LOCK-OUT
AMBIENT COMPENSATED HAND RESET
AUTO RESET SEE NOTE 2
TIME DELAY UNDER VOLTAGE RELAY
540 320 162 540 320 162 540 162162 320 320
GROUND FAULT RELAY ADDITIONAL RELAYS
(1’-9 17/64 ") (1’-9 17/64 ") (1’-9 17/64 ")
(1’-0 9/16 ") (1’-0 9/16 ") (6 3/8 ") (1’-0 9/16 ")
(6 3/8 ") (6 3/8 ")

SECTION B-B

CONDUIT STUB-UP PLAN


10’-0"

REFERENCE DRAWINGS

P.E.
A DRAWING CONTROL JOB ORDER NO. 31300 BE-107407
ONE LINE DIAGRAM BA-107492 SH. 2
SWITCHRACK DATA SHEET BA-107653 SH. 1
CONDUIT LAYOUT AND DETAILS BA-107494
MATERIAL TAKE-OFF LIST T/O-107494

200A NOTE: ALL MATERIALS INTERNAL TO


18" 19" 19"
TO BUS HEATER AND SWITCHRACK ASSEMBLY SHALL BE
THERMOSTAT PROVIDED BY VENDOR SEE DWG.
NO. BA-107492 SH. 1 FOR INCLUSIONS BUS BAR BOX

1 2 5 9 12 7
11’-1"

200A

6 3 4 8 11 10
BURNDY QIKLUG GROUND
120V AC LIGHT SWITCH &
11 CONNECTOR NO. QA29B
RECEPTACLE (BY VENDOR)
(TYPICAL FOR B2)

3I 9I 92K 92K 95E 58E 78E 92E 97E 36E 36C 97C 92C 78C 58C 95C 17C 92K 165C 164C 165G 163D 26F 186A 59D 38D

B B 10"
AS-BUILT

(4")
100
BY DATE
TYP

(24")
610
78C 87C 58C TYP. 2
LOCATIONS
0 AUG94 RCL 31300 ISSUED FOR CONSTRUCTION

180A REV. DATE BY JO/EWO DESCRIPTION CHKD. CERT. APPD.


NO.

SAUDI ARABIAN OIL COMPANY


A
2F DRAWN BY IBM CHECKED BY RSCa/KG SCALE: NONE
CONCRETE
1000
ENCASEMENT DATE STARTED 11-10-93 DATE COMPLETED
(3’-3 3/8 ")
FRONT VIEW OPR’G. DEPT. ENG. DEPT.

APP’D. FOR CONST.


SECTION A-A H.M. RASHID
THIS DRAWING IS NOT TO BE USED FOR CERTIFIED
CONSTRUCTION OR FOR ORDERING
MATERIAL UNTIL CERTIFIED AND DATED BY DATE

480V SWITCHRACK ELEVATION


ABQAIQ GOSP-3 MLV AREA
ABQAIQ TO BGP GAS PIPELINE
AB-BE SAUDI ARABIA
JOB ORDER/EWO NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

31300 D41 P BA-107493 001 0


Saudi Aramco 2615 ENG. (3/91)

08-18-94 VECTOR CADD-02


01 BA-284855 001 82660 R28 Q NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS.
REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO. JOB ORDER/EWO NO.

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO.NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
2. ALL COORDINATES AND ELEVATIONS ARE IN METERS.

3. ALL ELEVATIONS ARE REFERRED TO PLANT


ELEVATION 0.00 CORRESPONDING TO FINITE
LOCAL GRADE LEVEL.

4. PAINTING OF EMBEDDED PORTION OF ANCHOR


RECTIFIER FOUNDATIONS BOLTS : APCS-1C COATING SYSTEM
AS PER SAES-H-101.

6. ALL CORNERS SHALL HAVE 25 mm CHAMFER.

7. MINIMUM DISTANCE BETWEEN STEEL REINFORCEMENTS


AND METALLIC EMBEDDED PARTS = 50 mm.

8. MATERIALS:
CEMENT : ASTM C150 Type V
as per 09-SAMSS-97
VALID FOR: KM 66-104-152 CONCRETE : Class 4000 psi
3
MIN. CEMENT CONTENT = 360 Kg/m
1 1 W/C RATIO = 0.4
3
LEAN CONCRETE : MIN. CEMENT CONTENT = 250 Kg/m

STEEL : ASTM A615 Grade 50


Epoxy Coated as per ASTM A775
as per 09-SAMSS-106

STRUCTURAL STEEL : ASTM A36

BARS COVER : 50 mm

C C 9. ANCHOR BOLTS CAN BE DIRECTLY BURIED AT SITE


OMITTING POCKETS.

SECTION C-C
FORMWORK/REINFORCEMENT

LEGEND

2
1
PLAN
FORMWORK

REFERENCE DRAWINGS

SWITCHRACK FOUNDATION
KEY PLAN KEY PLAN

ITEM A KM ITEM A KM
R28-SR-0102 2100 152 R28-SR-001 3460 00
R28-SR-002 3830 56
R28-SR-003 3460 59
0 1M
R28-SR-004 3830 66 0.25 0.50 0.75

R28-SR-005 3830 104


R28-SR-006 3460 121
SCALE: 1 : 10
R28-SR-007 3460 128
REVISION CERTIFICATION EDSD
R28-SR-008 3460 138.7 THIS INDICATES THAT REV. NO.
01
VERIFICATION

02010051
OF THIS DRAWING IS COVERED, FOR ALL
CONTROL NUMBER
R28-SR-009 3460 152 APPROVAL/CERTIFICATION REQUIREMENTS,
BY DRAWING COMPLETION CERTIFICATE (DCC) BY: dum
NO.: 743600-JO-1997-82660-002
. DATE: 03/18/2002

A A
1
1 01 30-05-00 82660 AS BUILT ROCCHEGGIANI FERRONI

00 30-04-99 82660 ISSUE FOR CONSTRUCTION ROCCHEGGIANI FERRONI

REV. DATE JO/EWO DESCRIPTION ENGG. CERT. PMT OPRNS.


NO.
THIS REVISION IS NOT TO BE USED FOR CONSTRUCTION DESIGN REVIEW FOR
UNTIL CERTIFIED AND DATED. CERTIFICATION KEY DRAWINGS

DESIGN CERTIFICATION
DRAWN BY ROCCHEGGIANI CHECKED BY FERRONI

DATE STARTED 15-04-99 DATE COMPLETED 30-04-99

DISCIPLINE ENGINEER G. FERRONI

PROJECT ENGINEER O. MARIANI

THIS DRAWING IS NOT TO BE CERTIFIED BY: G. NARDINOCCHI


USED FOR CONSTRUCTION (NAME)
UNTIL CERTIFIED AND DATED. 30-04-99
SECTION A-A
SIGNATURE DATE

FORMWORK/REINFORCEMENT SAUDI ARABIAN OIL COMPANY


REVIEW FOR KEY DRAWINGS REQUIRED NOT REQUIRED
CONSTRUCTION AGENCY
2 OPERATIONS
OTHER

DRAWING TYPE

FORMWORKS AND REINFORCEMENTS FDN


PLAN C.P. & SWITCHRACK TYPICAL FOUNDATIONS
FORMWORK
UBTG-3 PIPELINE
UTHMANIYAH SAUDI ARABIA
JOB ORDER/EWO NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

82660 R28 Q BA-284855 001 01


Saudi Aramco 2615 ENG. (03/99)

VECTOR CADD-3A
05 P DA-059950 001 271 80060 3133 478
191/64B 6401 NOTES:
ROOF EDGE 1. FOR FURTHER NOTES ON THE SWITCH RACK SEE
REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO. JOB ORDER/EWO NO. JOB ORDER/EWO NO. RTU NO.

DWG. NO. DA-059946.


2. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.

3. ADDED CABLE NOS. PC-655 TO PANEL #1


PC-656 TO PANEL # 2, PC-657, PC-658, PC-659
PC-660, PC-661 & PC-675 TO PANEL #3
1 {,3WIRE, 120-240V SEE ONE LINE DIAGRAM DA-943005.
8-WAY PANEL BOARD ADDED THIS NOTE-3 AND REFERENCE DWG.
UNDER JO #37260.

2235
MOV-1230/CKT. 7 MOV-2048/CKT. 7 SPARE 05

MOV-1508/CKT. 5 MOV-2123/CKT. 5 XFMR. 480/120-240V

MOV-1763/CKT. 3 MOV-2121/CKT. 3 SPARE

SPARE MOV-2390/CKT. 1 SPARE

MOV-560/CKT. 8 MOV-1764/CKT. 8 SPARE

MOV-1226/CKT. 6 MOV-2049/CKT. 6 SPARE

MOV-1227/CKT. 4 MOV-2047/CKT. 4 TRIP CIRCUIT


SWITCHRACK LIGHTING LAYOUT PLAN
N.T.S.
130
MOV-1228/CKT. 2 MOV-2036/CKT. 2 WELDING RECEP.
130 LEGEND
1370 1525 1525 1380 2895 2905
GUAL CONDULET

CABLE TERMINATOR
130

130
CONDUIT UNION

300

300
CONDUIT SEAL
150(TYP)
CONDUIT ABOVE GRADE

CABLE DIRECT BURIED

FLEXIBLE COUPLING
1" 4"

1515

1630
PANEL PANEL PANEL
NO. 1 NO. 2 NO. 3 LIGHTING PANEL
4"
GROUNDING LINE
JB-R478-F2

2 1/2 " PEC - PHOTO-ELECTRIC CELL


1"

1" 1" CLOSE INDICATING


1" 4"
4" 1" LIGHT (RED)
OPEN INDICATING
480V MAIN LTG. BKR.
1" 1" LIGHT (GREEN)
CKT. BKR.

810

630
480- BATTERY MOV’S LOCAL CONTROL
1" CHARGER
120/208V LTG. BATTERY
LTG. RELAY PUSH BUTTON (TYP.)
SWITCHRACK X’FORMER 1" PANEL CELL/ACID 1"
OPEN/STOP/CLOSE
PLATFORM (TYP.) No.3

CONTROL STATION "A"


740

970
905
CONTROL STATION "B"

REFERENCE DRAWINGS
TITLE INDEX DRAWING NO.
GRADE GRADE
DRAWING CONTROL A BD-114971
1-1/2" TO RTU-478 AC DIST.PL.

WELDING RECEPT. FROM PANEL #3


1 1/2 "-PC-657 MOV-1430
1 1/2 "-PC-656 MOV-1432
1 1/2 "-PC-655 MOV-1429

1 1/2 "-PC-658 MOV-1431


4" TO 13.8KV/480V TRANSF.

1" TO WELDING RECEPTACLE

PC-675 CPT. ENCLOSURE


1" TO 120/230V TRANS #3

PC-661 LTG. CONTACTOR

ELEMENTARY WIRING DIAGRAM P DA-059951


1"-DB-2 LTG. 1 , 2 & 3

PC-660 C.P. RECTIFIER


1"-DB-3 LTG. 4, 5 & 6

1"-TO RECTIFIER (QA 1-50)


1" TO PEC ON POLE #7
1" DB-4 LTG-7 TO 12

2-1/2"-TO RECTIFIER (QA 1-50)


INTERCONNECTION DIAGRAM P DA-059952

4"-TO RECTIFIER (QA 1-50)


2"-PC-659 GM-0103
1"-DB-13 MOV-2049

1"-DB-19 MOV-2390
1"-DB-15 MOV-2036

1"-DB-16 MOV-2048

1"-120V RECEPTACLE
1"-DB-17 MOV-2123
1"-DB-10 MOV-1508

1"-DB-12 MOV-1764

1"-DB-18 MOV-2121
1"-DB-11 MOV-1763

GENERAL ELECTRICAL LAYOUT P XA-F29566


1"-DB-4 MOV-2047

MOV-2036

MOV-2390
MOV-2049
MOV-2047
1"-DB-9 MOV-1230
1"-DB-7 MOV-1227

1"-DB-8 MOV-1228
1"-DB-6 MOV-1226

MOV-2123

MOV-1230
MOV-2048

MOV-1228

MOV-1227
MOV-1508
MOV-1764

MOV-1763
1"-TO CIRCUIT TRIP

MOV-2121

MOV-1226
MOV-560
1"-DB-5 MOV-560

DRAWING CONTROL JO#37260 P DD-942543


TO 13.8KV/480V

ONE LINE DIAGRAM (QA-8 SCRAPER FACILITY) P DA-943005


CABLE & CONDUIT SCHEDULE SH. 4,5,&6 P DD-913145

1"-DB-30

1"-DB-33
1"-DB-32

1"-DB-34

1"-DB-23
1"-DB-27

1"-DB-24

1"-DB-20
1"-DB-25
1"-DB-22
1"-DB-28
1"-DB-29

1"-DB-26
1"-DB-31

1"-DB-21
05

610 250 210 260 310 250 555

140

170
140
167
167

110
166
133
133
134
120
120

120
120

140

120
120

120

150

120
105
105
100
120
120
95
95

05
80(TYP)
05
05
SWITCHRACK
SWITCHRACK 05 05
REAR VIEW
FRONT VIEW

1524

CT ION
R CONSTRU
ISSUED FO
1" GUAL JB
1" GUAL JB | PLATE
MOV ACTUATOR
250MM LONG, 1/2 "{ BOLTS
1"C, 1/C #10AWG 450x450x6mm THK. PL. 1050 CAST IN CONCRETE

368
1" GUAL JB 1" SEALING FITTING
1"C, 3/C #8AWG, AS-BUILT BY KWSA DATE 12-94

1069
4/C #12AWG 1"C, 3/C #8AWG,
4/C #12AWG |
1" CONDUIT

213
STRAP (TYP.) MOV ACTUATOR
1" GUAL JB 05 06/91 SC 37260 SEE NOTE-3 ZUR MAH

1"C, 3/C #8AWG, 1"C, 3/C #8AWG,


MOV ACTUATOR 4/C #12AWG 04 01-95 CTC 3133 REVISED AS-BUILT JTW JSR MAT
4/C #12AWG
MOV ACTUATOR AS-BUILT & DIGITIZED
1"C, 7/C #10AWG

130
1" FLEXIBLE COND. CONDUIT ENTRY 03 05-92 DLG 8111 INTO CADD DATABASE JTW
1350

CONCRETE BLOCK WALL COUPLING (TYP.) 100 x 50 REV. DATE BY JO/EWO DESCRIPTION CHKD. CERT. APPD.
CHANNEL SUPPORT NO.

1" SEALING FITTING 1" FLEXIBLE COND. 598 603 SAUDI ARABIAN OIL COMPANY
CABLE TERMINATOR 2"C, 7/C #10AWG
COUPLING (TYP.) 100MM { COND.
|
75

2"C, 3/C #8AWG, SLEEVES DRAWN BY SAMDAN CHECKED BY ASLAM SCALE: AS SHOWN
20 114 114
2"C, 3/C #8AWG, 4/C #12AWG GRADE 50 DATE STARTED 03-08-79 DATE COMPLETED SEP. ’96
4/C #12AWG

100
300

GRADE
450

OPR’G. DEPT. BAS 04-30-79 ENG. DEPT. MAS 04-15-79

150 150
CONCRETE GRADE APP’D. FOR CONST.

FROM SWITCHRACK

50
FROM SWITCHRACK FOUNDATION REINFORCING FABRIC:
THIS DRAWING IS NOT TO BE USED FOR CERTIFIED
CONSTRUCTION OR FOR ORDERING
FOR CONT’N. SEE FOR CONTINUATION BY DATE 04-25-79
2" CONDUIT ELBOW 100MM x 100MM-10/10 MATERIAL UNTIL CERTIFIED AND DATED ORIG. SIGNED

DWG. DA-059949 350 SQ. SEE DWG. DA059949

50 100100
ELECTRICAL LAYOUT AND DETAILS
DETAIL-1 DETAIL-2 480V SWITCHRACK
1524
CONDUIT TERMINATIONS AT CONDUIT TERMINATIONS AT
RTU NO.
PIPELINES QATIF-ABQAIQ (QA-1,2,3,4,56,7,8 & 8)
MOV’S WITH VALVE BOX
TYP. FOR 8 NTS
MOV’S WITHOUT VALVE BOX
TYP. FOR 7 NTS
DETAIL-3 478 QATIF/ABQAIQ SAUDI ARABIA
JOB ORDER/EWO NO. JOB ORDER/EWO NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.
TRANSFORMER MOUNTING PAD
191/64B
NTS
3133 80060 271 P DA-059950 001 05
Saudi Aramco 2615 ENG. (3/91)

VECTOR CADD-02