MiCOM ALSTOM P341


Interconnection Protection Relay

Software Version: 36 & 71


Hardware Version: J

Technical Data Sheet


P341/EN TDS/F74

GRID
Note: The technical manual for this device gives instructions for its installation, commissioning,
and operation. However, the manual cannot cover all conceivable circumstances or
include detailed information on all topics. In the event of questions or specific problems,
do not take any action without proper authorization. Contact the appropriate Alstom Grid
technical sales office and request the necessary information.

Any agreements, commitments, and legal relationships and any obligations on the part of
Alstom Grid including settlements of warranties, result solely from the applicable
purchase contract, which is not affected by the contents of the technical manual.

This device MUST NOT be modified. If any modification is made without the express
permission of Alstom Grid, it will invalidate the warranty, and may render the product
unsafe.

The Alstom Grid logo and any alternative version thereof are trademarks and service marks of Alstom
Grid.
MiCOM is a registered trademark of Alstom Grid. All trade names or trademarks mentioned herein
whether registered or not, are the property of their owners.
This manual is provided for informational use only and is subject to change without notice.
© 2010, Alstom Grid. All rights reserved.
) .

&'(

! "# ! #
$ $ ! %" #
! ! $ ! #
! !
$ !

!
" #$ # " %

# #& "
" ! " ' # %

# #
% &
" "& # %( & "
# ' " %

)*+ # ", -
#& " " " , - %
/

12 3
' " "
, " "
" ,
( "
) *
+ +
(
&
+ ! " "# "
" $ "% "&
, 12 3 4 %
-
+% "
, +

. ) *
+

0
' $ % &

!
#

( $ %

"

$ %
#
!"#
# &

#
+ ) * '

! " # $

% &
( $

#
#

& # $ #
$ ' " $

#
'
( !
" 30
# ) * $
* $ # #

$
+*, +(! +(((
" ! $
+*, # #
#
$
# # " 30
#
$#

$ #
# -. /
00-)01- 1- / 2-)33-
%
1 ( $
$ 4 )
#

# #

3
5 " (+ ( *

$ % & " ' */,


-. "
' " ' " !
# !

!
# ! )
! ! "

" " !
" # ! $% $
+ + 5 $& $
. " +
2- */, !
" !
! 12 "! !"
- *0

' () * ! 3
() & + , &
"
! *0
"#
- -. *" / , )
' 3 */, "
" ! ! " 0 1 2 !
" ! !
! * ! 0 *0 '
! ! !
+ " " !" 3
" .
+ 4 !
* & ) ' &
'
! !
-. # "! " .
4

* & ) ' & &


%
'
-. 6 '
!
!
' 3"

1
" '& $ "&)

0 10 ,2 !
0 "
#$%
( &' ()% *

+
,! ,
13 4 2 +
-

1 ,2 ,! ,

&).&// -
! ,#

" !

5
6

6
"+ ! 7 8+ 8 - 7
6

9
, /* ( ,*9

( )
!! ) "*
)
! + "

, )
)
) !
-.
. "

) !
!) ' "%
) ! !
! !
-" % ,/,0
.1 ) !
! -" %
!)
! -
!
"

! ! !
! " !! )
2 ! ! ! !! " " 6
) ! ! ) 5"
) ! " 75 ! ! !8 !
! " % )
# )
$ 3 !
$+ ' $ ! !!
$ $ ! ! " )
$+ ! ' $% ! + +
$ 3 $& ' "" ) !"
$+ '
$ 234 34%

5
) $ !" ! 6

!" #$ "
* ' ( ' ! )
') 7 ; ) 9
( ' ) < $%! $ %
! ' ! '
$ 8./ %6! ) !
' ( )
! " # $% &
' ( % %
! &* ( (
( )
) '
)
'
' ')
( )
)

! &*

' (
( '
)
+ ,-./
+ '
+ " 01 21.3. 1&4
+ 56 & 1
+ " 0 31

" 0 31 ' (

" 0 31 .
. .
'
)
# ' . '
) ' ( &*
#
( ' !

( % %
7 ) '
$ 8./

((( , ,
! 9 :** 1 2 3 31 121
(((
Technical Data Isolation to ELV level.

Rear communications port (RP1)


Mechanical specifications
EIA(RS)485 signal levels, two wire
connections located on general purpose block,
Design M4 screw.
Modular platform relay, P341 in 40 TE or For screened twisted pair cable, multidrop,
60 TE case. Mounting is front of panel flush 1000 m max.
mounting, or 19“ rack mounted with rack frame For K-Bus, IEC-60870-5-103, MODBUS or
(ordering options). DNP3.0 protocol (ordering options).
Isolation to SELV (safety extra low low voltage)
Enclosure protection level.
Per IEC 60529: 1992:
IP 52 Protection (front panel) against dust and Optional rear fiber connection for
dripping water, SCADA/DCS
IP 50 Protection for rear and sides of the case, BFOC 2.5 -(ST®)-interface for glass fiber, as
against dust, per IEC 874-10.
IP 10 Protection Product safety protection for 850 nm short-haul fibers, one Tx and one Rx.
the rear due to live connections on the terminal For Courier, IEC-60870-5-103, MODBUS or
block. DNP3.0 (Ordering options).

Weight Optional second rear communications port


P341 (40 TE) :7 kg (RP2)
P341 (60 TE) :9.2 kg EIA(RS)232, 9 pin D-type female connector,
socket SK4.
Courier protocol: K-Bus, EIA(RS)232, or
Terminals EIA(RS)485 connection.
Isolation to SELV level.
AC current and voltage measuring inputs
Located on heavy duty (black) terminal block: Optional rear IRIG-B interface modulated or
Threaded M4 terminals, for ring lug de-modulated
connection.
BNC plug
CT inputs have integral safety shorting, on
Isolation to SELV level.
removal of the terminal block.
50 ohm coaxial cable.
Optional Rear Ethernet Connection for
General input/output terminals IEC 61850
For power supply, opto inputs, output contacts
and RP1 rear communications. Optional rear Ethernet connection for
Located on general purpose (grey) blocks:
IEC 61850
Threaded M4 terminals, for ring lug
connection.
10BaseT/100BaseTX communications
Case protective earth connection Interface in accordance with IEEE802.3 and
Two rear stud connections, threaded M4. IEC 61850
Must be earthed (grounded) for safety, Isolation: 1.5 kV
minimum earth wire size 2.5 mm2. Connector type: RJ45
Cable type: Screened Twisted Pair (STP)
Max. cable length: 100 m
Front port serial PC interface
EIA(RS)232 DCE, 9 pin D-type female
connector Socket SK1. 100 base FX interface
Courier protocol for interface to S1 Studio Interface in accordance with IEEE802.3 and
software. IEC 61850
Isolation to ELV (extra low voltage) level. Wavelength: 1300 nm
Maximum cable length 15 m. Fiber: multi-mode 50/125 µm or 62.5/125 µm
Connector type: BFOC 2.5 - (ST®)
Front download/monitor port
EIA(RS)232, 25 pin D-type female connector
Socket SK2.
For firmware and menu text downloads.

P341 Technical Data Sheet 9 P341 Software versions 36 & 71J


Optional rear redundant Ethernet Ratings
connection for IEC 61850
AC measuring inputs
100 base FX interface Nominal frequency: 50 and 60 Hz (settable)
Interface in accordance with IEEE802.3 and Operating range: 40 to 70 Hz
IEC 61850
Wavelength: 1300 nm AC current
Fiber: multi-mode 50/125 µm or 62.5/125 µm
Connector style: BFOC 2.5 -(ST®) Nominal current (In): 1 and 5 A dual rated.
Transmitter optical characteristics 100 base (1 A and 5 A inputs use different transformer
FX interface tap connections, check correct terminals are
wired).
Nominal burden:
Parameter Sym Min Typ Max Unit <0.04 VA at In, <40 mΩ(0-30 In) In = 1 A
Output Optical <0.01 VA at In, <8 mΩ(0-30 In) In = 5 A
Power BOL
-19 dBm Thermal withstand:
62.5/125 µm, PO -16.8 -14
-20 avg. continuous 4 In
NA = 0.275
Fiber EOL for 10 s: 30 In
Output Optical
for 1 s; 100 In
Power BOL
-22.5
Standard: linear to 64 In (non-offset AC
50/125 µm, dBm
PO
-23.5
-20.3 -14
avg. current).
NA = 0.20 Sensitive: linear to 2 In (non-offset AC
Fiber EOL
current).
Optical 10 %
Extinction
Ratio -10 dB
AC voltage
Output Optical Nominal voltage (Vn): 100 to 120 V or 380 to
Power at PO dBm
-45 480 V phase-phase.
Logic “0” (“0”) avg.
State Nominal burden per phase: < 0.02 VA at
110/√3 V or 440/√3 V
BOL - Beginning of life Thermal withstand:
EOL - End of life continuous 2 Vn
for 10 s: 2.6 Vn
Linear to 200 V (100 V/120 V), 800 V
Receiver optical characteristics 100 base (380/480 V).
FX interface

Parameter Sym Min Typ Max Unit


Power supply
Input Optical
PIN Auxiliary voltage (Vx)
Power dBm
Min. -33.5 -31
Minimum at avg. Three ordering options:
(W)
Window Edge
(i) Vx: 24 to 48 Vdc
Input Optical
PIN (ii) Vx: 48 to 110 Vdc, and 40 to 100 Vac (rms)
Power Bm
Min. -34.5 -31.8 (iii) Vx: 110 to 250 Vdc, and 100 to 240 Vac (rms)
Minimum at avg.
(C)
Eye Center
Input Optical Operating range
PIN dBm
Power
Max.
-14 -11.8
avg. (i) 19 to 65 V (dc only for this variant)
Maximum (ii) 37 to 150 V (dc), 32 to 110 V (ac)
Fiber defect connector (watchdog relay) – (iii) 87 to 300 V (dc), 80 to 265 V (ac).
redundant Ethernet board With a tolerable ac ripple of up to 12% for a dc
supply, per IEC 60255-11: 1979.
Connector (3 terminals): 2 NC contacts
Rated voltage: 250 V
Continuous current: 5A Nominal burden
Short-duration current: 30 A for 3 s Quiescent burden: 11 W or 24 VA. (Extra
Breaking capacity: 1.25 W when fitted with second rear
DC: 50 W resistive communications board).
DC: 25 W inductive (L/R = 40 ms) Additions for energized binary inputs/outputs:
AC: 1500 VA resistive (cos φ = unity) Per opto input:
AC: 1500 VA inductive (cos φ = 0.5) 0.09 W (24 to 54 V),
Subject to maxima of 5 A and 250 V 0.12 W (110/125 V),
0.19 W (220/250 V).
Per energized output relay: 0.13 W
P341 Technical Data Sheet 10 P341 Software versions 36 & 71J
Power-up time Maximum loading = all digital inputs/outputs
Time to power up < 11 s. energized
Quescent or 1/2 loading = 1/2 of all digital
Power supply interruption inputs/outputs energized
3 power supply options:
(i) Vx: 24 to 48 V dc Battery backup
(ii) Vx: 48 to 110 V dc, 40 to 100 V ac (rms) Front panel mounted
(iii) (i) Vx: 110 to 250 V dc, 100 to 240 V ac Type ½ AA, 3.6 V Lithium Thionyl Chloride
(rms) Battery (SAFT advanced battery reference
Per IEC 60255-11: 2008 LS14250)
The relay will withstand a 100% interruption in Battery life (assuming relay energized
the DC supply without de-energizing as for 90% time) >10 years
follows:
Field voltage output
(i) Vx: 24 to 48 V dc Regulated 48 Vdc
Quescent / half load Current limited at 112 mA maximum output
20 ms at 24 V Operating range 40 to 60 V
50 ms at 36 V
100 ms at 48 V
Digital (“Opto”) inputs
maximum loading:
20 ms at 24 V Universal opto inputs with programmable
50 ms at 36 V voltage thresholds (24/27, 30/34, 48/54,
100 ms at 48 V 110/125, 220/220 V). May be energized from
the 48 V field voltage, or the external battery
(ii) Vx: 48 to 110 V dc supply.
Quescent / half load Rated nominal voltage: 24 to 250 Vdc
20 ms at 36 V Operating range: 19 to 265 Vdc
50 ms at 60 V Withstand: 300 Vdc, 300 Vrms.
100 ms at 72 V Nominal pick-up and reset thresholds:
200 ms at 110 V Nominal battery 24/27: 60 - 80% DO/PU
maximum loading: (logic 0) <16.2(logic 1) >19.2
20 ms at 36 V Nominal battery 24/27: 50 - 70% DO/PU
50 ms at 60 V (logic 0) <12.0(logic 1) >16.8
100 ms at 85 V Nominal battery 30/34: 60 - 80% DO/PU
200 ms at 110 V (logic 0) <20.4(logic 1) >24.0
Nominal battery 30/34: 50 - 70% DO/PU
(iii) (i) Vx: 110 to 250 V dc (logic 0) <15.0(logic 1) >21.0
Quescent / half load Nominal battery 48/54: 60 - 80% DO/PU
50 ms at 110 V (logic 0) <32.4(logic 1) >38.4
100 ms at 160 V Nominal battery 48/54: 50 - 70% DO/PU
200 ms at 210 V (logic 0) <24.0(logic 1) >33.6
maximum loading: Nominal battery 110/125: 60 - 80% DO/PU
20 ms at 85 V (logic 0) <75.0(logic 1) >88.0
50 ms at 98 V Nominal battery 110/125: 50 - 70% DO/PU
100 ms at 135 V (logic 0) <55.0(logic 1) >77.0
200 ms at 174 V Nominal battery 220/250: 60 - 80% DO/PU
(logic 0) <150.0 (logic 1) >176.0
Per IEC 60255-11: 2008: Nominal battery 220/250: 50 - 70% DO/PU
The relay will withstand an interruption in the (logic 0) <110 (logic 1) >154
AC supply without de-energizing as follows: Recognition time:
(ii) Vx = 40 to 100 V ac <2 ms with long filter removed,
Quescent / half load <12 ms with half cycle ac immunity filter on
50 ms at 27 V for 100% voltage dip
maximum loading: Output contacts
10 ms at 27 V for 100% voltage dip
Standard contacts
(iii) Vx = 100 to 240 V ac General purpose relay outputs for signaling,
Quescent / half load tripping and alarming:
50 ms at 80 V for 100% voltage dip Continuous Carry Ratings (Not Switched):
maximum loading: Maximum continuous current: 10 A (UL: 8 A)
50 ms at 80 V for 100% voltage dip Short duration withstand carry: 30 A for 3 s
P341 Technical Data Sheet 11 P341 Software versions 36 & 71J
250 A for 30 ms 30 A for 200 ms, dc resistive, 10,000
Rated voltage: 300 V operations (subject to the above limits of
Make & Break Capacity: make / break capacity & rated voltage)
DC: 50 W resistive 10 A (*), dc inductive, 10,000 operations
DC: 62.5 W inductive (L/R = 50 ms) (subject to the above limits of make / break
AC: 2500 VA resistive (cos φ = unity) capacity & rated voltage)
AC: 2500 VA inductive (cos φ = 0.7)
*Typical for repetitive shots – 2 minutes idle for
Make, Carry: thermal dissipation
30 A for 3 secs, dc resistive, 10,000
operations (subject to the above limits of No of shots in 1
Voltage Current L/R
make / break capacity and rated voltage) sec
Make, Carry & Break: 65 V 10 A 40 ms 5
30 A for 200 ms, ac resistive, 2,000
150 V 10 A 40 ms 4
operations (subject to the above limits of
make / break capacity & rated voltage) 250 V 10 A 40 ms 2
4 A for 1.5 secs, dc resistive, 10,000 250 V 10 A 20 ms 4
operations (subject to the above limits of
make / break capacity & rated voltage) MOV protection: Max Voltage 330 V dc
0.5 A for 1 sec, dc inductive, 10,000 Durability:
operations (subject to the above limits of Loaded contact: 10 000 operations
make / break capacity & rated voltage) minimum,
Unloaded contact: 100 000 operations
10 A for 1.5 secs, ac resistive / inductive, minimum.
10,000 operations (subject to the above Operate Time:
limits of make / break capacity & rated voltage) Less than 0.2 ms
Reset Time:
Durability: Less than 8 ms
Loaded contact: 10 000 operations
minimum,
Unloaded contact: 100 000 operations Watchdog contacts
minimum. Non-programmable contacts for relay
healthy/relay fail indication:
Operate Time Breaking capacity:
Less than 5 ms DC: 30 W resistive
DC: 15 W inductive (L/R = 40 ms)
Reset Time AC: 375 VA inductive (cos φ = 0.7)
Less than 5 ms
IRIG-B interface (Modulated)
High break contacts External clock synchronization per IRIG
standard 200-98, format B12x
Continuous Carry Ratings (Not Switched):
Maximum continuous current: 10 A Input impedance 6 kΩ at 1000 Hz
Short duration withstand carry: 30 A for 3 s Modulation ratio: 3:1 to 6:1
250 A for 30 ms Input signal, peak-peak: 200 mV to 20 V
Rated voltage: 300 V
IRIG-B 00X interface (Demodulated)
Make & Break Capacity: External clock synchronization per IRIG
DC: 7500 W resistive standard 200-98, format B00X.
DC: 2500 W inductive (L/R = 50 ms) Input signal TTL level
Input impedance at dc 10 kΩ
Make, Carry:
30 A for 3 secs, dc resistive, 10,000 Environmental conditions
operations (subject to the above limits of
make / break capacity & rated voltage)
Ambient temperature range
Make, Carry & Break: Per IEC 60255-6: 1988:
30 A for 3 secs, dc resistive, 5,000 Operating temperature range:
operations (subject to the above limits of -25°C to +55°C (or -13°F to +131°F)
make / break capacity & rated voltage) Storage and transit:
-25°C to +70°C (or -13°F to +158°F)

P341 Technical Data Sheet 12 P341 Software versions 36 & 71J


Tested as per (ii) Per ANSI/IEEE C37.90-1989 (reaffirmed
IEC 60068-2-1: 2007 1994):
-25°C storage (96 hours) 1.5 kV rms AC for 1 minute, across open
-40°C operation (96 hours) contacts of normally open output relays.
IEC 60068-2-2: 2007 1 kV rms AC for 1 minute, across open
+85°C storage (96 hours) watchdog contacts.
+85°C operation (96 hours) 1 kV rms AC for 1 minute, across open
contacts of changeover output relays.
Ambient humidity range
Per IEC 60068-2-3: 1969: Impulse voltage withstand test
56 days at 93% relative humidity and +40 °C Per IEC 60255-27: 2005
Per IEC 60068-2-30: 1980 Front time: 1.2 µs, Time to half-value: 50 µs,
Damp heat cyclic, six (12 + 12) hour cycles, Peak value: 5 kV, 0.5 J
93% RH, +25 to +55 °C Between all independent circuits.
Between all independent circuits and
Corrosive environments protective (earth) conductor terminal.
Between the terminals of independent circuits.
(For relays with harsh environment coating EIA(RS)232 & EIA(RS)485 ports and normally
of PCBs) open contacts of output relays excepted.
Per IEC 60068-2-60: 1995, Part 2, Test Ke,
Method (class) 3 Electromagnetic compatibility (EMC)
Industrial corrosive environment/poor
environmental control, mixed gas flow test. 1 MHz burst high frequency disturbance
21 days at 75% relative humidity and +25oC test
exposure to elevated concentrations of H2S Per IEC 60255-22-1: 1988, Class III,
(100 ppb), NO2 (200 ppb), Cl2 (20 ppb). Common-mode test voltage: 2.5 kV,
Differential test voltage: 1.0 kV,
Per IEC 60068-2-52 Salt mist (7 days) Test duration: 2 s, Source impedance: 200 Ω
Per IEC 60068-2-43 for H2S (21 days), 15 ppm (EIA(RS)232 ports excepted).
Per IEC 60068-2-42 for SO2 (21 days), 25 ppm
100 kHz damped oscillatory test
Type tests Per EN61000-4-18: 2007: Level 3
Common mode test voltage: 2.5 kV
Insulation Differential mode test voltage: 1 kV
Per IEC 60255-27: 2005
Insulation resistance > 100 MΩ at 500 Vdc Immunity to electrostatic discharge
(Using only electronic/brushless insulation Per IEC 60255-22-2: 1996, Class 4,
tester). 15 kV discharge in air to user interface,
display, communication port and exposed
Creepage distances and clearances metalwork.
6 kV point contact discharge to any part of the
IEC 60255-27: 2005 front of the product.
Pollution degree 3,
Overvoltage category III,
Impulse test voltage 5 kV. Electrical fast transient or burst
requirements
High voltage (dielectric) withstand Per IEC 60255-22-4: 2002 and
EN61000-4-4:2004. Test severity Class III and
(i) Per IEC 60255-27: 2005, 2 kV rms IV:
AC, 1 minute:
Amplitude: 2 kV, burst frequency 5 kHz
Between all independent circuits. (Class III),
Between independent circuits and protective Amplitude: 4 kV, burst frequency 2.5 kHz
(earth) conductor terminal.
(Class IV).
1 kV rms AC for 1 minute, across open Applied directly to auxiliary supply, and applied
watchdog contacts. to all other inputs. (EIA(RS)232 ports
1 kV rms AC for 1 minute, across open
excepted).
contacts of changeover output relays. Amplitude: 4 kV, burst frequency 5 kHz
1 kV rms AC for 1 minute for all D-type (Class IV) applied directly to auxiliary.
EIA(RS)232/EIA(RS)485 ports between the
communications port terminals and protective
(earth) conductor terminal.

P341 Technical Data Sheet 13 P341 Software versions 36 & 71J


Surge withstand capability Conducted emissions
Per IEEE/ANSI C37.90.1: 2002: Per EN 55022: 1998 Class A:
4 kV fast transient and 2.5 kV oscillatory 0.15 - 0.5 MHz, 79 dBμV (quasi peak)
applied directly across each output contact, 66 dBμV (average)
optically isolated input, and power supply 0.5 - 30 MHz, 73 dBμV (quasi peak) 60 dBμV
circuit. (average).
4 kV fast transient and 2.5 kV oscillatory
applied common mode to communications,
IRIG-B. Radiated emissions
Per EN 55022: 1998 Class A:
30 - 230 MHz, 40 d BμV/m at 10 m
Surge immunity test measurement distance
(EIA(RS)232 ports excepted). 230 - 1 GHz, 47 dBμV/m at 10 m
Per IEC 61000-4-5: 2005 Level 4, measurement distance.
Time to half-value: 1.2 / 50 µs,
Amplitude: 4 kV between all groups and
protective (earth) conductor terminal. EU directives
Amplitude: 2 kV between terminals of each
group. EMC compliance
Per 2004/108/EC:
Immunity to radiated electromagnetic Compliance to the European Commission
energy Directive on EMC is demonstrated using a
Per IEC 60255-22-3: 2000, Class III: Technical File. Product Specific Standards
Test field strength, frequency band 80 to 1000 were used to establish conformity:
MHz: EN50263: 2000
10 V/m,
Test using AM: 1 kHz / 80%, Product safety
Spot tests at 80, 160, 450, 900 MHz Per 2006/95/EC:
Per IEEE/ANSI C37.90.2: 2004: Compliance to the European Commission
80 MHz to 1000 MHz, 1 kHz 80% AM and AM Low Voltage Directive. (LVD) is
pulsed modulated. demonstrated using a Technical File.
Field strength of 35 V/m. A product specific standard was used to
establish conformity.
Radiated immunity from digital EN 60255-27: 2005
communications
Per EN61000-4-3: 2002, Level 4:
Test field strength, frequency band 800 to
960 MHz, and 1.4 to 2.0 GHz:
30 V/m,
Test using AM: 1 kHz/80%. R&TTE compliance
Radiated Immunity from Digital Radio Radio and Telecommunications Terminal
Telephones Equipment (R & TTE) directive 99/5/EC.
Per IEC 61000-4-3: 2002: Compliance demonstrated by compliance to
10 V/m, 900 MHz and 1.89 GHz. both the EMC directive and the Low voltage
directive, down to zero volts.
Immunity to conducted disturbances Applicable to rear communications ports.
induced by radio frequency fields
Per IEC 61000-4-6: 1996, Level 3, ATEX compliance
Disturbing test voltage: 10 V. ATEX Potentially Explosive Atmospheres
directive 94/9/EC, for equipment.
Power frequency magnetic field immunity The equipment is compliant with Article 1(2) of
European directive 94/9/EC.
Per IEC 61000-4-8: 1994, Level 5,
It is approved for operation outside an ATEX
100 A/m applied continuously,
hazardous area. It is however approved for
1000 A/m applied for 3 s.
connection to Increased Safety, “Ex e”, motors
Per IEC 61000-4-9: 1993, Level 5,
with rated ATEX protection, Equipment
1000 A/m applied in all planes.
Category 2, to ensure their safe operation in
Per IEC 61000-4-10: 1993, Level 5,
gas Zones 1 and 2 hazardous areas.
100 A/m applied in all planes at 100 kHz/
1 MHz with a burst duration of 2 s. CAUTION - Equipment with this marking is not
itself suitable for operation within a potentially
explosive atmosphere.
P341 Technical Data Sheet 14 P341 Software versions 36 & 71J
Compliance demonstrated by Notified Body
certificates of compliance.

II (2) G

Mechanical robustness

Vibration test
Per IEC 60255-21-1: 1996:
Response Class 2
Endurance Class 2

Shock and bump


Per IEC 60255-21-2: 1996:
Shock response Class 2
Shock withstand Class 1
Bump Class 1
Seismic test
Per IEC 60255-21-3: 1995:
Class 2

P341 third party compliances

Underwriters laboratory (UL)

File Number: E202519


Original Issue Date: 05-10-2002
(Complies with Canadian and US
requirements).

Energy Networks Association (ENA)

Certificate Number: 104 Issue 2


Assessment Date: 16-04-2004

P341 Technical Data Sheet 15 P341 Software versions 36 & 71J


Protection functions Characteristic US: IEEE
C37.112…1996
* Under reference conditions
Reverse/low forward/overpower
Negative phase sequence
Accuracy overcurrent
Pick-up: Setting ±10%
Reverse/Over Power Drop-off: Accuracy
0.95 of setting ±10% I2>Pick-up: Setting ±5%
Low forward power Drop-off: I2> Drop-off: 0.95 x Setting ±5%
1.05 of setting ±10% Vpol Pick-up: Setting ±5%
Angle variation Pick-up: Vpol Drop-off: 0.95 x Setting ±5%
Expected pick-up angle ±2 degree DT operation: ±2% or 60 ms whichever is
Angle variation Drop-off: greater
Expected drop-off angle ±2.5 degree Disengagement time: <35 ms
Operating time: ±2% or 50 ms whichever is Directional accuracy (RCA ±90°):
greater ±2° hysteresis <1%
Repeatability: <5% Repeatability (operating times): <10 ms
Disengagement time: <50 ms
tRESET: ±5%
Instantaneous operating time: <50 ms
Thermal overload

Accuracy
Sensitive/low forward/overpower
Setting accuracy: ±5%
Reset: 95% of thermal setting ±5%
Accuracy Thermal alarm Pick-up:
Pick-up: Setting ±10% Calculated trip time ±5%
Reverse/Over power Drop-off: Thermal overload Pick-up:
0.9 of setting ±10% Calculated trip time ±5%
Low forward power Drop-off: Cooling time accuracy: ±6% of theoretical
1.1 of Setting ±10% Repeatability: <2.5%
Angle variation Pick-up:
Expected pick-up angle ±2 degree
Angle variation Drop-off:
Directional/non-directional earth
Expected drop-off angle ±2.5% degree fault
Operating time: ±2% or 50 ms whichever is
greater Earth fault accuracy
Repeatability: <5% Pick-up: Setting ±5%
Disengagement time: <50 ms Drop-off: >0.85 x Setting ±5%
tRESET: ±5% IDMT trip level elements: 1.05 x Setting ±5%
Instantaneous operating time: <50 ms IDMT characteristic shape: ±5% or 40 ms
whichever is greater*
Directional/non-directional IEEE reset: ±5% or 40 ms whichever is greater
overcurrent DT operation: ±2% or 50 ms whichever is
greater
Accuracy DT reset: ±5%
Repeatability: 5%
Pick-up: Setting ±5%
Drop-off: 0.95 x Setting ±5%
SEF accuracy
Minimum trip level (IDMT): 1.05 x Setting ±5%
IDMT characteristic shape: ±5% or 40 ms Pick-up: Setting ±5%
whichever is greater* Drop-off: 0.95 x Setting ±5%
IEEE reset: ±5% or 50 ms whichever is greater IDMT trip level elements: 1.05 x Setting ±5%
DT operation: ±2% or 50 ms whichever is IDMT characteristic shape: ±5% or 40 ms
greater whichever is greater*
DT Reset: ±5% IEEE reset: ±7.5% or 60 ms whichever is
Directional accuracy (RCA ±90°): greater
±2° hysteresis 2° DT operation: ±2% or 50 ms whichever is
Characteristic UK: IEC 6025-3…1998 greater
DT reset: ±5%
Repeatability: 5%
P341 Technical Data Sheet 16 P341 Software versions 36 & 71J
Wattmetric SEF accuracy Rate of change of frequency ‘df/dt’
P = 0 W Pick-up: ISEF> ±5%
P > 0 W Pick-up: P> ±5% Accuracy
P = 0 W Drop-off: (0.95 x ISEF>) ±5% Fixed Window
P > 0 W Drop-off: 0.9 x P> ±5% Pick-up: Setting ±0.05 Hz/s or ±3% whichever
Boundary accuracy: ±5% with 1° hysteresis is greater
Repeatability: 5% Repeatability: <5%

Zero sequence polarizing quantities Rolling Window


accuracy Pick-up: Setting ±0.01 Hz/s or ±3% whichever
Operating boundary Pick-up: ±2° of RCA ±90° is greater
Hysteresis: <3° Repeatability: <5%
Freq Low, Freq High
Vnpol Pick-up: Setting ±10%
Pick-up: Setting ±2% or ±0.08 Hz whichever is
Vnpol Drop-off: 0.9 x Setting or 0.7 V
greater
(whichever is greater) ±10% DT operation

Negative sequence polarizing quantities Fixed Window:


accuracy Setting ±2% or ±(40+20*X*Y)ms
Operating boundary Pick-up: ±2° of RCA ±90° Repeatability: <5%
Hysteresis: <3°
V2pol Pick-up: Setting ±10% Rolling Window
V2pol Drop-off: 0.9 x Setting or 0.7 V Setting ±2% or ±(60+20*X+5*Y)ms
(whichever is greater) ±10% Note: X = average cycles, Y = Iterations
I2pol Pick-up: Setting ±10% Repeatability: <20%
I2pol Drop-off: 0.9 x Setting ±10%
df/dt
Restricted earth fault
Accuracy
Accuracy Pick-up: Setting ±0.5 Hz/s
Pick-up: Setting formula ±5% Operating time: ±2% or 160 ms whichever is
Drop-off: 0.80 (or better) of calculated greater
differential current Lower/Upper dead band operating time: ±2%
High impedance Pick-up: Setting ±5% or 160 ms whichever is greater
High impedance operating time: <30 ms Operation over dead band: ±2% or 170 ms
whichever is greater
Repeatability: <5%
Transient overreach and overshoot

Accuracy
Voltage vector shift
Additional tolerance X/R ratios:
Accuracy
±5% over the X/R ratio of 1…90
Overshoot of overcurrent elements: <40 ms Pick-up: Setting ±0.5°
Disengagement time: <60 ms (65 ms SEF) Trip pulse time: 500 ms ±2%

Neutral displacement/residual Reconnect delay


overvoltage
Accuracy
Accuracy Operating time: ±2% or 50 ms whichever is
DT/IDMT Pick-up: Setting ±5% greater
Drop-off: 0.95 x Setting ±5%
IDMT characteristic shape: ±5% or 55 ms Undervoltage
whichever is greater
DT operation: ±2% or 55 ms whichever is Accuracy
greater Instantaneous operation <55 ms DT Pick-up: Setting ±5%
Reset: <35 ms IDMT Pick-up: 0.95 x Setting ±5%
Repeatability: <1%
Drop-off: 1.05 x Setting ±5%

P341 Technical Data Sheet 17 P341 Software versions 36 & 71J


IDMT characteristic shape: ±2% or 50 ms CB fail
whichever is greater
DT operation: ±2% or 50 ms whichever is Timer accuracy
greater
Timers: ±2% or 40 ms whichever is greater
Reset: <7 ms
Reset time: <30 ms
Repeatability: <1%

Undercurrent accuracy
Overvoltage
Pick-up: ±10%
Operating time: < 12 ms (Typical <10 ms)
Accuracy Reset: < 15 ms (Typical < 10 ms)
DT Pick-up: Setting ±5%
IDMT Pick-up: Setting ±5% Supervisory functions
Drop-off: 0.98 x Setting ±5%
IDMT characteristic shape: ±2% or 50 ms
whichever is greater Voltage transformer supervision
DT operation: ±2% or 50 ms whichever is
greater Accuracy
Reset: <75 ms Fast block operation: <25 ms
Fast block reset: <30 ms
NPS overvoltage Time delay: Setting ±2% or 20 ms whichever is
greater
Accuracy
Pick-up: Setting ±5% Current transformer supervision
Drop-off: 0.95 x Setting ±5%
Repeatability (operating threshold): <1% Accuracy
DT operation: ±2% or 65 ms whichever is IN > Pick-up: Setting ±5%
greater VN < Pick-up: Setting ±5%
Instantaneous operation: <60 ms IN > Drop-off: 0.9 x Setting ±5%
Instantaneous operation: VN < Drop-off: (1.05 x Setting) ±5% or 1 V
(accelerated): <45 ms whichever is greater
Disengagement time: <35 ms CTS block operation: < 1 cycle
Repeatability (operating times): <10 ms CTS reset: < 35 ms

Underfrequency System checks


Accuracy Voltage monitors
Pick-up: Setting ±0.01 Hz
Drop-off: (Setting +0.025 HZ) ±0.01 Hz Accuracy
DT operation: ±2% or 50 ms whichever is
greater* Gen/Bus Voltage Monitors
* The operating will also include a time for Over/Live/Diff voltage:
the relay to frequency track 20 Hz/ second). Pick-up: setting ±3% or 0.1 V whichever is
greater
Overfrequency Drop-off: (0.98 x Setting) ±3%or 0.1 V
whichever is greater
Accuracy Repeatability: <1%
Pick-up: Setting ±0.01 Hz
Drop-off: (Setting -0.025 Hz) ±0.01 Hz Bus Under/Dead voltage:
DT operation: ±2% or 50 ms whichever is Pick-up: Setting ±3% or 0.1 V whichever is
greater * greater
* The operating will also include a time for Drop-off: (1.02 x Setting) ±3%or 0.1 V
the relay to frequency track 20 Hz/ second). whichever is greater
Repeatability: <1%

Generator underfrequency
Pick-up: Setting ±0.01 Hz
Drop-off: (Setting +0.1 Hz) ±0.01 Hz
Repeatability: <1%
P341 Technical Data Sheet 18 P341 Software versions 36 & 71J
Generator overfrequency System Split
Pick-up: Setting ±0.01 Hz
Accuracy
Drop-off: (Setting -0.1 Hz) ±0.01 Hz
Repeatability: <1% SS Phase Angle:
Pick-up: (Setting+2°) ±1°
Check Synch Drop-off: (Setting+1°) ±1°
Repeatability: <1%
Accuracy SS Undervoltage:
CS1 Pick-up: Setting ±3%
Drop-off: 1.02 x Setting
CS1 Phase Angle: Repeatability: <1%
Pick-up: (Setting-2°) ±1° SS Timer:
Drop-off: (Setting-1°) ±1°
Timers: setting ±1% or 40 ms whichever is
Repeatability: <1%
greater
CS1 Slip Freq: Reset time: <30 ms
Pick-up: Setting ±0.01 Hz Repeatability: <10 ms
Drop-off: (0.95 x Setting) ±0.01 Hz Plant supervision
Repeatability: <1%
CS1 Slip Timer: CB state monitoring control and
Timers: setting ±1% or 40 ms whichever is condition monitoring
greater
Reset time: < 30 ms Accuracy
Repeatability: <10ms Timers: ±2% or 20 ms whichever is greater
Broken current accuracy: ±5%
CS2
CS2 Phase Angle: Dynamic rating
Pick-up: (Setting-2°) ±1°
Drop-off: (Setting-1°) ±1° Accuracy
Repeatability: <1% DLR I> Pick-up: Setting ±2%
DLR I> Drop-off: (0.7 to 0.99) x Setting ±2%
CS2 Slip Freq: DT operation: ±2% or 2 s whichever is greater
Pick-up: Setting ±0.01 Hz Instantaneous operation: <2 s
Drop-off: (0.95 x Setting) ±0.01 Hz Disengagement time: <1 s
Repeatability: <1% Repeatability (operating times): <2 s
Repeatability (PU and DO): <3%
CS2 Slip Timer:
Timer: setting ±1% or 40 ms whichever is Programmable scheme logic
greater
Reset time: < 30 ms Accuracy
Repeatability: <1% Output conditioner timer: Setting ±2% or 50 ms
whichever is greater
CS2 Advanced CB Compensation Phase Dwell conditioner timer: Setting ±2% or 50 ms
Angle: whichever is greater
Pick-up: 0°±1° Pulse conditioner timer: Setting ±2% or 50 ms
Drop-off: 2°±1° whichever is greater
Repeatability: <1%
Measurements and recording
CS2 CB Closing Timer facilities
Timer: <30 ms
Repeatability: <10 ms

P341 Technical Data Sheet 19 P341 Software versions 36 & 71J


Measurements Other specifications
CLI load resistance 0-1 mA: < 4 kΩ
Accuracy CLI load resistance 0-1 mA/0-20 mA/4 20 mA:
Current: 0.05…3 In: ±1% of reading <300 Ω
Voltage: 0.05…2 Vn: ±5% of reading Isolation between common input channels:
zero
Power (W): 0.2…2 Vn, 0.05…3 In: ±5% of
Isolation between input channels and case
reading at unity power factor
earth/other circuits: 2 kV rms for 1 minute
Reactive Power (VArs): 0.2…2 Vn, 0.05…3 In:
CLO compliance voltage 0-1 mA/0 10 mA:
±5% of reading at zero power factor
10 V
Apparent Power (VA): 0.2…2 Vn, 0.05…3 In:
CLO compliance voltage 0-20 mA/4 20 mA:
±5% of reading 8.8 V
Energy (Wh): 0.2…2 Vn, 0.2…3 In: ±5% of Isolation between common output channels:
reading at zero power factor zero
Energy (Varh): 0.2…2 Vn, 0.2…3 In: ±5% of Isolation between output channels and case
reading at zero power factor earth/other circuits: 2 kV rms for 1 minute
Phase accuracy: 0°…360: ±5%
Frequency: 40…70 Hz: ±0.025 Hz
Disturbance records
IRIG-B and real time clock Accuracy
Magnitude and relative phases: ±5% of applied
Performance quantities
Year 2000: Compliant Duration: ±2%
Real time accuracy: < ±1 second / day Trigger Position: ±2% (minimum 100 ms)
Record length: 50 records each 1.5 s duration
Features (75 s total memory) with 8 analogue
Real time 24 hour clock settable in hours, channels and 32 digital channels
minutes and seconds (Courier, MODBUS, DNP 3.0, IEC 61850), 8
Calendar settable from January 1994 to records each 3 s (50 Hz) or 2.5 s (60 Hz)
December 2092 duration (IEC 60870-5-103).
Clock and calendar maintained via battery
after loss of auxiliary supply Event, fault & maintenance records
Internal clock synchronization using IRIG-B
Interface for IRIG-B signal is BNC Maximum 512 events in a cyclic memory
Maximum 5 fault records
Current loop input and outputs Maximum 10 maintenance records

Accuracy
Accuracy
Event time stamp resolution 1 ms
Current loop input accuracy: ±1% of full scale
CLI drop-off threshold Under: setting ±1% of
full scale
CLI drop-off threshold Over: setting ±1% of full
scale
CLI sampling interval: 50 ms
CLI instantaneous operating time: < 250 ms
CLI DT operating time: ±2% setting or 200 ms
whichever is the greater
CLO conversion interval: 5 ms
CLO latency: < 1.07 s or <70 ms depending on
CLO output parameter’s internal refresh rate
- (1 s or 0.5 cycle)
Current loop output accuracy: ±0.5% of full
scale
Repeatability: <5%
CLI - Current Loop Input
CLO - Current Loop Output

P341 Technical Data Sheet 20 P341 Software versions 36 & 71J


IEC 61850 Ethernet data

100 Base FX Interface


Transmitter optical characteristics
(TA = 0°C to 70°C, VCC = 4.75 V to 5.25 V)

Parameter Sym Min. Typ. Max. Unit


Output Optical
Power BOL -19 dBm
62.5/125 µm, PO -16.8 -14
-20 avg.
NA = 0.275
Fiber EOL
Output Optical
Power BOL -22.5 dBm
50/125 µm, PO -20.3 -14
-23.5 avg.
NA = 0.20
Fiber EOL
Optical 10 %
Extinction
Ratio -10 dB

Output Optical PO
dBm
Power at Logic -45
(“0”) avg.
“0” State
BOL - Beginning of life
EOL - End of life

Receiver optical characteristics


(TA = 0°C to 70°C, VCC = 4.75 V to 5.25 V)

Parameter Sym Min. Typ. Max. Unit


Input Optical
PIN
Power dBm
Min. -33.5 –31
Minimum at avg.
(W)
Window Edge
Input Optical
PIN
Power Bm
Min. -34.5 -31.8
Minimum at avg.
(C)
Eye Center
Input Optical
PIN dBm
Power -14 -11.8
Max. avg.
Maximum

Note: The 10BaseFL connection will no


longer be supported as IEC 61850
does not specify this interface

P341 Technical Data Sheet 21 P341 Software versions 36 & 71J


Settings, measurements and
DST End Month: Jan/Feb/Mar/Apr
records list /May/Jun/Jul/Aug/
Sept/Oct/Nov/Dec
Settings list DST End Mins: 0 min…1425 min
RP1 Time Zone: UTC/Local
RP2 Time Zone: UTC/Local
Global settings (system data) Tunnel Time Zone: UTC/Local
Language: English/French/German/Spanish
Frequency: 50/60 Hz
Configuration
Setting Group:
Circuit breaker control Select via Menu
(CB control): Select via PSL
CB Control by: Active Settings: Group 1/2/3/4
Disabled Setting Group 1: Disabled/Enabled
Local Setting Group 2: Disabled/Enabled
Remote Setting Group 3: Disabled/Enabled
Local+Remote Setting Group 4: Disabled/Enabled
Opto System Config: Invisible/Visible
Opto+local Power: Disabled/Enabled
Opto+Remote Overcurrent: Disabled/Enabled
Opto+Rem+local Thermal Overload: Disabled/Enabled
Close Pulse Time: 0.10...10.00 s Earth Fault: Disabled/Enabled
Trip Pulse Time: 0.10…5.00 s SEF/REF/Spower: Disabled or SEF/REF
Man Close t max: 0.01…9999.00 s or Sensitive Power
Man Close Delay: 0.01…600.00 s Residual O/V NVD: Disabled/Enabled
CB Healthy Time: 0.01…9999.00 s df/dt: Disabled/Enabled
Check Sync. Time: 0.01...9999.00 s V Vector Shift: Disabled/Enabled
Reset Lockout by: User Interface/CB Close Reconnect Delay: Disabled/Enabled
Man Close RstDly: 0.10...600.00 s Volt Protection: Disabled/Enabled
CB Status Input: Freq Protection: Disabled/Enabled
None CB Fail: Disabled/Enabled
52A Supervision: Disabled/Enabled
52B Dynamic Rating Disabled/Enabled
52A & 52B Input Labels: Invisible/Visible
Output Labels: Invisible/Visible
Date and time CT & VT Ratios: Invisible/Visible
IRIG-B Sync: Disabled/Enabled Event Recorder: Invisible/Visible
Battery Alarm: Disabled/Enabled Disturb Recorder: Invisible/Visible
LocalTime Enable: Disabled/Fixed/Flexible Measure’t Setup: Invisible/Visible
LocalTime Offset: -720 min…720 min Comms Settings: Invisible/Visible
DST Enable: Disabled/Enabled Commission Tests: Invisible/Visible
DST Offset: 30 min…60 min Setting Values: Primary/Secondary
DST Start: First/Second/Third/ Control Inputs: Invisible/Visible
Fourth/Last CLIO Inputs: Disabled/Enabled
DST Start Day: Sun/Mon/Tues/Wed/ CLIO Outputs: Disabled/Enabled
Thurs/Fri/Sat System Checks Disabled/Enabled
DST Start Month: Jan/Feb/Mar/Apr/ Ctrl I/P Config: Invisible/Visible
May/Jun/ Jul/Aug/ Ctrl I/P Labels: Invisible/Visible
Sept/Oct/Nov/Dec Direct Access: Disabled/Enabled
DST Start Mins: 0 min…1425 min IEC GOOSE Invisible/Visible
DST End: First/Second/ RP1 Read Only Disabled/Enabled
Third/Fourth/Last RP2 Read Only Disabled/Enabled
DST End Day: Sun/Mon/Tues/Wed/ NIC Read Only Disabled/Enabled
Thurs/Fri/Sat LCD Contrast: 0…31

P341 Technical Data Sheet 22 P341 Software versions 36 & 71J


CT and VT ratios Power
Main VT Primary: 100...1000000 V Date and Time
Main VT Sec'y: 80...140 Description
(100/120 V) 320…560 V (380/480 V) Plant Reference
C/S VT Primary: 100 V…1 MV Frequency
C/S VT Secondary: 80…140 V Local Values: Primary/Secondary
VN VT Primary (P342/3): 100…1000000 V Remote Values: Primary/Secondary
VN VT Secondary (P342/3): 80…140 V Measurement Ref: VA/VB/VC/IA/IB/IC
(100/120 V) 320…560 V (380/480 V) Measurement Mode: 0/1/2/3
PH CT Polarity: Standard, Inverted Fix Dem Period: 1…99 mins
Phase CT Primary: 1 A…50 kA Roll Sub Period: 1…99 mins
Phase CT Sec'y Sec'y : 1 A/5 A Num Sub Periods: 1…15
Remote2 Values: Primary/Secondary
ISen CT Polarity: Standard/Inverted
ISen CT Primary: 1 A…60 KA Communications
ISen CT Sec’y: 1 A/5 A RP1 Address: (Courier or IEC 870-5-103):
0…255
Sequence of event recorder (record RP1 Address: (DNP3.0):
control) 0…65534
Alarm Event: Disabled/Enabled RP1 Address: (MODBUS):
Relay O/P Event: Disabled/Enabled 1…247
Opto Input Event: Disabled/Enabled RP1 InactivTimer: 1…30 mins
General Event: Disabled/Enabled RP1 Baud Rate: (IEC 870-5-103):
Fault Rec Event: Disabled/Enabled 9600/19200 bits/s
Maint Rec Event: Disabled/Enabled RP1 Baud Rate: (MODBUS, Courier):
Protection Event: Disabled/Enabled 9600/19200/38400 bits/s
DDB 31 - 0: (up to): RP1 Baud Rate: (DNP3.0):
DDB 2047 - 2016: 1200/2400/4800/9600/19200/ 38400 bits/s
Binary function link strings, selecting which RP1 Parity: Odd/Even/None
DDB signals will be stored as events, and (MODBUS, DNP3.0)
which will be filtered out. RP1 Meas Period: 1…60 s
(IEC 870-5-103)
RP1 PhysicalLink:
Oscillography Copper (EIA(RS)485/K bus) or Fiber Optic
(disturbance recorder) RP1 Time Sync: Disabled/Enabled
Duration: 0.10…10.50 s MODBUS IEC Timer: Standard/Reverse
Trigger Position: 0.0…100.0% RP1 CS103Blocking:
Trigger Mode: Single/Extended Disabled
Analog Channel 1: (up to): Monitor Blocking
Analog Channel 8: Command Blocking
Disturbance channels selected from: RP1 Port Config: (Courier):
IA/IB/IC/VA/VB/VC/VN/ISensitive/Frequency K Bus
V Checksync EIA485 (RS485)
Digital Input 1: (up to): RP1 Comms Mode: (Courier):
Digital Input 32: IEC 60870 FT1.2
Selected binary channel assignment from IEC 60870 10-Bit No parity
any DDB status point within the relay (opto Note: If RP1 Port Config is K Bus the baud
input, output contact, alarms, starts, trips, rate is fixed at 64 kbits/s
controls, logic…).
Input 1 Trigger: No Trigger/Trigger/LH (Low to Optional Ethernet port
High)/Trigger H/L (High to Low) NIC Tunl Timeout: 1...30 mins
(up to): NIC Link Report: Alarm, Event, None
Input 32 Trigger: No Trigger/Trigger NIC Link Timeout: 0.1...60 s
L/H/Trigger H/L

Optional additional second rear


Measured operating data
communication (rear Port2 (RP2))
(measure’t setup) RP2 Port Config:
Default Display: EIA(RS)232
Access Level EIA(RS)485
3Ph + N Current K-Bus
3Ph Voltage
P341 Technical Data Sheet 23 P341 Software versions 36 & 71J
RP2 Comms Mode: Custom
IEC 60870 FT1.2 Opto Input 1:
IEC 60870 10-Bit No parity (up to):
RP2 Address: 0…255 Opto Input #. (# = max. opto no. fitted):
RP2 InactivTimer: 1…30 mins Custom options allow independent
RP2 Baud Rate: thresholds to be set per opto, from the same
9600/19200/38400 bits/s range as above.
Note: If RP2 Port Config is K Bus the baud Opto Filter Control:
rate is fixed at 64 kbits/s Binary function link string, selecting which
optos will have an extra 1/2 cycle noise filter,
Commission tests and which will not.
Monitor Bit 1: Characteristics:
(up to): Standard 60% - 80%
Monitor Bit 8: 50% - 70%
Binary function link strings, selecting which
DDB signals have their status visible in the Control inputs into PSL
Commissioning menu, for test purposes (Ctrl. I/P config.)
Test Mode: Hotkey Enabled:
Disabled Binary function link string, selecting which of
Test Mode the control inputs will be driven from
Blocked Contacts Hotkeys.
Test Pattern: Control Input 1: Latched/Pulsed
Configuration of which output contacts are to (up to):
be energized when the contact test is Control Input 32: Latched/Pulsed
applied Ctrl Command 1:
(up to):
Circuit breaker condition monitoring Ctrl Command 32:
(CB monitor setup) ON/OFF
Broken I^: 1.0…2.0 SET/RESET
I^ Maintenance: Alarm IN/OUT
Disabled/Enabled ENABLED/DISABLED
I^ Maintenance: 1…25000
I^ Lockout: Alarm IED configurator
Disabled/Enabled Switch Conf. Bank: No Action/Switch Banks
I^ Lockout: 1…25000 Restore MCL: No Action, Restore MCL
No. CB Ops Maint: Alarm
Disabled/Enabled IEC 61850 GOOSE
No. CB Ops Maint: 1…10000 GoEna: Disabled/Enabled
No. CB Ops Lock: Alarm Test Mode: Disabled/Pass Through/Forced
Disabled/Enabled VOP Test Pattern: 0x00000000...
No. CB Ops Lock: 1…10000 0xFFFFFFFF
CB Time Maint: Alarm Ignore Test Flag: No/Yes
Disabled/Enabled
CB Time Maint: 0.005…0.500 s
CB Time Lockout: Alarm Control input user labels
Disabled/Enabled (Ctrl. I/P labels)
CB Time Lockout: 0.005…0.500 s Control Input 1:
Fault Freq Lock: Alarm (up to):
Disabled/Enabled Control Input 32:
Fault Freq Count: 1…9999 User defined text string to describe the
Fault Freq Time: 0…9999 s function of the particular control input

Opto coupled binary inputs Settings in multiple groups


(opto config) Note: All settings here onwards apply for
Global Nominal V: setting groups # = 1 to 4.
24 - 27 V
30 - 34 V
48 - 54 V
110 - 125 V
220 - 250 V

P341 Technical Data Sheet 24 P341 Software versions 36 & 71J


Protection functions Phase overcurrent (overcurrent)
Phase O/C: Sub Heading
I>1 Function:
System config. Disabled
Phase Sequence: Standard ABC/Reverse DT
ACB IEC S Inverse
VT Reversal: No Swap/A-B Swapped/B-C IEC V Inverse
Swapped/C-A Swapped IEC E Inverse
CT Reversal: No Swap/A-B Swapped/B-C UK LT Inverse
Swapped/C-A Swapped UK Rectifier
C/S Input: A-N, B-N, C-N, A-B, B-C, C-A RI
C/S V Ratio Corr: 0.500...2.000 IEEE M Inverse
Main VT Vect Grp: 0...11 IEEE V Inverse
Main VT Location: Gen/Bus IEEE E Inverse
US Inverse
Reverse/low forward/overpower US ST Inverse
Operating mode: I>1 Direction:
Generating Non-Directional
Motoring Directional Fwd
Power 1 Function: Directional Rev
Reverse I>1 Current Set: 0.08…4.00 In
Low forward I>1 Time Delay: 0.00…100.00 s
Over I>1 TMS: 0.025…1.200
-P>1 Setting (reverse power/P<1 I>1 Time Dial: 0.01…100.00
Setting (Low forward power)/ P>1 I>1 K (RI): 0.10…10.00
Setting (Overpower): I>1 Reset Char: DT/Inverse
4…300.0 W (1 A, 100 V/120 V) I>1 tRESET: 0.00…100.00 s
16…1200.0 W (1 A, 380 V/480 V) I>2 as I>1
20…1500.0 W (5 A, 100 V/120 V) I>3 Status: Disabled/Enabled
80…6000.0 W (5 A, 380 V/480 V) I>3 Direction:
Equivalent Range in %Pn 2%…157% Non-Directional
Power 1 Time Delay: 0.00…100.0 s Directional Fwd
Power 1 DO Timer: 0.00…100.0 s Directional Rev
P1 Poledead Inh: Disabled/Enabled I>3 Current Set: 0.08…10.00 In
Power 2 as Power 1 I>3 Time Delay: 0.00…100.00 s
I>4 as I>3
Sensitive/reverse/low I> Char Angle: -95…+95o
I >Function Link:
forward/overpower Bit 0 = VTS Blocks I>1
Operating mode: Bit 1 = VTS Blocks I>2
Generating Bit 2 = VTS Blocks I>3
Motoring Bit 3 = VTS Blocks I>4
Sen Power1 Func: Bit 4, 5, 6 & 7 are not used
Reverse Binary function link string, selecting which
Low forward overcurrent elements (stages 1 to 4) will be
Over blocked if VTS detection of fuse failure
Sen -P>1 Setting (Reverse Power)/Sen <P occurs.
Setting (Low Forward Power)/Sen >P Setting
(Over Power):
0.3…100.0 W (1 A, 100/120 V)
Inverse time (IDMT) characteristic
IDMT characteristics are selectable from a
1.20…400.0 W (1 A, 380/480 V)
choice of four IEC/UK and five IEEE/US curves
1.50…500.0 W (5 A, 100/120 V)
as shown in the table below.
6.0…2000.0 W (5 A, 380/480 V)
Equivalent range in %Pn 0.5%…157%
The IEC/UK IDMT curves conform to the
Sen Power 1 Delay: 0.00…100.0 s
following formula:
Power 1 DO Timer: 0.00…100.0 s
P1 Poledead Inh: Disabled/Enabled
⎛ K ⎞
Comp angle θC: -5°…+5.0° ⎜ + L⎟
t=Tx
Sen Power2 as Sen Power 1 ⎜ (Ι/Ιs) α - 1 ⎟
⎝ ⎠

P341 Technical Data Sheet 25 P341 Software versions 36 & 71J


The IEEE/US IDMT curves conform to the TD x S
following formula: tRESET = in seconds
(1 - M2)
⎛ K ⎞ Where:
t = TD x ⎜ α
+ L⎟
⎜ (Ι/Ιs) - 1 ⎟
⎝ ⎠ TD = Time dial setting for IEEE
curves
Where: S = Constant
t = Operation time M = Ι/Ιs
K = Constant
Ι = Measured current Curve description Standard S
ΙS = Current threshold setting Moderately inverse IEEE 4.85
α = Constant Very inverse IEEE 21.6
L = ANSI/IEEE constant (zero for Extremely inverse IEEE 29.1
IEC/UK curves)
Inverse US 5.95
T = Time multiplier setting for
IEC/UK curves Short time inverse US 2.261
TD = Time dial setting for IEEE/US
curves The RI curve (electromechanical) has been
included in the first stage characteristic setting
IDMT characteristics options for Phase Overcurrent and Earth Fault
protections. The curve is represented by the
following equation:
IDMT curve Stand. K α L
Standard 1
IEC 0.14 0.02 0 ⎛ ⎞
inverse
⎜ ⎟ in seconds
Very inverse IEC 13.5 1 0 ⎜
⎝ (
t = K x 0.339 - 0.236/
M ) ⎟

Extremely
IEC 80 2 0
inverse
Long time
With K adjustable from 0.1 to 10 in steps of
UK 120 1 0 0.05
inverse
Rectifier UK 45900 5.6 0
M = Ι/Ιs
Moderately
IEEE 0.0515 0.02 0.114
inverse
Very inverse IEEE 19.61 2 0.491
Extremely
IEEE 28.2 2 0.1217
inverse
Inverse US-C08 5.95 2 0.18
Short time
US-C02 0.16758 0.02 0.11858
inverse

The IEC extremely inverse curve becomes


definite time at currents greater than 20 x
setting. The IEC standard, very and long time
inverse curves become definite time at
currents greater than 30 x setting.

For all IEC/UK curves, the reset characteristic


is definite time only.

For all IEEE/US curves, the reset characteristic


can be selected as either inverse curve or
definite time.

The inverse reset characteristics are


dependent upon the selected IEEE/US IDMT
curve as shown in the table below.
All inverse reset curves conform to the
following formula:

P341 Technical Data Sheet 26 P341 Software versions 36 & 71J


IEC Curves Amercian Curves

1000 100

100

10
Operating Time (s)

10

Operating Time (s)


Curve 4

Curve 1 1
Curve 5

1 Curve 6

Curve 9
Curve 2

Curve 7
Curve 3
Curve 8
0.1
0.1 1.0 10.0 100.0
1.0 10.0 100.0
Current (Multiples of Is)
Current (Multiples of Is)

Curve 1 Standard inverse Curve 5 IEEE moderately inverse


Curve 2 Very inverse Curve 6 IEEE very inverse
Curve 3 Extremely inverse Curve 7 IEEE extremely inverse
Curve 4 UK long time inverse Curve 8 US inverse
P2136ENa Curve 9 US short time inverse
P2137ENa

NPS overcurrent
Ι2>1 Status: Disabled/Enabled
Ι2>1 Direction:
Non-Directional
Directional Fwd
Directional Rev
Ι2> Current Set: 0.08…4.0 Ιn
Ι2> Time Delay: 0.00…100.00 s
Ι2>2/3/4 as for Ι2>1
Ι2> VTS Block:
Bit 0 = VTS Blocks Ι2>1
Bit 1 = VTS Blocks Ι2>2
Bit 2 = VTS Blocks Ι2>3
Bit 3 = VTS Blocks Ι2>4
Bits 4, 5, 6 & 7 are not used
Binary function link string, selecting which
NPS overcurrent elements (stages 1 to 4)
will be blocked if VTS detection of fuse
failure occurs.
Ι2> V2pol Set:
0.5…25.0 (100 V 120 V)
2…100 V (380/480 V)
Ι2> Char Angle: -95°…+95°

P341 Technical Data Sheet 27 P341 Software versions 36 & 71J


Thermal overload IN1>1 K(RI): 0.10….10.00
Thermal: Disabled/Enabled IN1>1 IDG Time: 1.00...2.00
Thermal I>: 0.50…2.50 In IN1>1 Reset Char.: DT/Inverse
Thermal Alarm: 20..100% IN1>1 tRESET: 0.00…100.00 s
T-heating: 1…200 minutes IN1>2 as IN>1
T-cooling: 1…200 minutes IN1>3 Status:
M Factor: 0…10 Disabled
Enabled
The thermal time characteristic is given by: IN1>3 Directional:
Non-Directional
t = τ loge (Ιeq2 - ΙP2)/(Ιeq2 - (Thermal Ι>)2) Directional Fwd
t = τ. loge ((K2-A2)/(K2-1)) Directional Rev
IN1>3 Current Set: 0.08…32.00 In
Where: IN1>3 Time Delay: 0.00…200.00 s
K = Ιeq/Thermal Ι> IN1>4 as IN>3
IN1> Blocking:
A = ΙP/Thermal Ι>
Binary function link string, selecting which
t =Time to trip, following application of the
ground overcurrent elements (stages 1 to 4)
overload current, Ι
will be blocked if VTS detection of fuse
τ =Heating time constant of the failure occurs.
protected plant
IN1> Char Angle: -95… +95°
Ιeq = Equivalent current IN1> Polarization:
Thermal Ι> = Relay setting current Zero Sequence
ΙP = Steady state pre-load Neg. Sequence
current before IN1> VNpol Set:
application of the 0.5…80.0 V (100/110 V)
overload 2…320 V (380/480 V)
Ιeq = √(Ι12 + MΙ22) IN1> V2pol Set:
Ι1 = Positive sequence 0.5…25.0 V (100/110 V)
current 2…100 V (380/480 V)
Ι2 = Negative sequence IN1> I2pol Set: 0.08…1.00 In
current
M = A user settable The IDG curve is commonly used for time
constant proportional delayed earth fault protection in the Swedish
to the thermal market. This curve is available in stage 1 of
capacity of the the Earth Fault protection.
machine
The IDG curve is represented by the following
Earth fault equation:
IN1>1 Function: ⎛ Ι ⎞
Disabled t = 5.8 - 1.35 loge ⎜ ⎟ in seconds
⎝ ΙN > Setting ⎠
DT
Where:
IEC S Inverse
IEC V Inverse
Ι = Measured current
IEC E Inverse
UK LT Inverse ΙN>Setting = An adjustable setting
RI which defines the start
IEEE M Inverse point of the
IEEE V Inverse characteristic
IEEE E Inverse
US Inverse Although the start point of the characteristic is
US ST Inverse defined by the “ΙN>” setting, the actual relay
IDG current threshold is a different setting called
IN1>1 Directional “IDG Ιs”. The “IDG Ιs” setting is set as a
Non-Directional multiple of “ΙN>”.
Directional Fwd
Directional Rev An additional setting “IDG Time” is also used
IN1>1 Current Set: 0.08…4.00 In to set the minimum operating time at high
IN1>1 IDG Is: 1.0…4.0 In levels of fault current.
IN1>1 Time Delay: 0.00…200.00 s
IN1>1 TMS: 0.025…1.200
IN1>1 Time Dial: 0.01…100.00
P341 Technical Data Sheet 28 P341 Software versions 36 & 71J
10 failure occurs.
9
ISEF> Char. Angle: -95...+95°
IDG Is Setting Range
8
ISEF> VNpol Set:
Operating time (seconds)

7
0.5...80.0 V (100/120 V)
6

5
2...320 V (380/480 V)
4
WATTMETRIC SEF:
3
PN> Setting: 0....20 In W (100/120 V)
2
IDG Time Setting Range
PN> Setting: 0 ....80 In W (380/480 V)
1

0
1 10 100
Restricted earth fault
I/IN>
P2242ENa (high impedance)
IDG Characteristic IREF> Is: 0.05.1.00 In

SEF/REF Prot’n Residual O/V NVD


SEF/REF Options: VN>1 Status: Disabled/Enabled
SEF VN>1 Input: Derived
SEF Cos (PHI) VN> 1 Function:
SEF Sin (PHI) Disabled
Wattmetric DT
Hi Z REF IDMT
ISEF>1 Function: VN> 1 Voltage Set:
Disabled 1…80 V (100/120 V)
DT 4…320 V (380/480 V)
IEC S Inverse VN> 1 Time Delay: 0.00…100.00 s
IEC V Inverse VN>1 TMS: 0.5…100.0
IEC E Inverse VN> 1 tRESET: 0.00…100.00
UK LT Inverse VN>2 as VN>1
RI VN>3/4 as VN>1 except
IEEE M Inverse VN>3/4 Input: VN1
IEEE V Inverse
IEEE E Inverse DF/DT
US Inverse Operating Mode: Fixed Window/Rolling
US ST Inverse Window
IDG df/dt Avg Cycles: 2…12
ISEF>1 Directional: df/dt Iterations: 1…4
Non-Directional df/dt>1 Status: Disabled/Enabled
Directional Fwd df/dt>1 Setting: 0.10…10.00 Hz
Directional Rev. df/dt>1 Dir'n: Negative/Positive/Both
ISEF>1 Current Set: 0.005...0.10 In df/dt>1 Time: 0.00…100.00 s
ISEF>1 IDG Is: 1.0...4.0 In df/dt>1 f L/H: Disabled/Enabled
ISEF>1 Time Delay: 0.00...200.00 s df/dt>1 f Low: 45.00…65.00 Hz
ISEF>1 TMS: 0.025...1.200 df/dt>1 f High: 45.00…65.00 Hz
ISEF>1 Time Dial: 0.01...100.0 df/dt>2/3/4 Status: Disabled/Enabled
ISEF>1 IDG Time: 1.00...2.00 df/dt>2/3/4 Setting: 0.10…10.00 Hz
ISEF>1 Reset Char: DT/Inverse df/dt>2/3/4 Dir'n: Negative/Positive/Both
ISEF>1 tRESET: 0.00...100.00 s df/dt>2/3/4 Time: 0.00…100.00 s
ISEF>2 as ISEF>2
ISEF>3 Status:
Disabled V vector shift
Enabled V Shift Status: Disabled/Enabled
ISEF>3 Directional: V Shift Angle: 2…30°
Non-Directional
Directional Fwd
Directional Rev
Reconnect delay
Reconnect Status: Disabled/Enabled
ISEF>3 Current Set: 0.005...0.80 In
Reconnect Delay: 0…300.0 s
ISEF>3 Time Delay: 0.00...200.00 s
Reconnect tPULSE: 0…10.0 s
ISEF>4 as ISEF>3
ISEF> Blocking:
Binary function link string, selecting which
ground overcurrent elements (stages 1 to 4)
will be blocked if VTS detection of fuse
P341 Technical Data Sheet 29 P341 Software versions 36 & 71J
Voltage protection V>2 Voltage Set:
60…185 V (100/120 V)
240…740 V (380/480 V)
Undervoltage V>2 Time Delay: 0.00…100.00 s
V< Measur’t Mode:
Phase-Phase The inverse characteristic is given by the
Phase-Neutral following formula:
V< Operate Mode: K
Any Phase t =
Three Phase (M - 1)
V< 1 Function: Where:
Disabled K = Time multiplier setting
DT t = Operating time in seconds
IDMT M = Applied input voltage/relay setting
V<1 Voltage Set: voltage
10…120 V (100/120 V)
40…480 V (380/480 V)
V<1 Time Delay: 0.00…100.00 s NPS overvoltage
V<1 TMS: 0.05…100.0 V2>1 status: Enabled/Disabled
V<1 Poledead Inh: Disabled/Enabled V2>1 Voltage Set:
V<2 Function: 1…150 V (100/120 V)
Disabled 4…600 V (380/480 V)
DT V2>1 Time Delay: 0.00…100.00 s
V<2 Status: Disabled/Enabled
V<2 Voltage Set: Frequency protection
10…120 V (100/120 V)
40…480 V (380/480 V)
V<2 Time Delay: 0.00…100.00 s Underfrequency
V<2 Poledead Inh: Disabled/Enabled F<1 Status: Disabled/Enabled
F<1 Setting: 45.00…65.00 Hz
The inverse characteristic is given by the F<1 Time Delay: 0.1…100.0 s
following formula: F<2/3/4 as F<1
F< Function Link:
K Bit 0 - Enable Block F<1 during poledead
t = Bit 1 - Enable Block F<2 during poledead
(1 - M) Bit 2 - Enable Block F<3 during poledead
Bit 3 - Enable Block F<4 during poledead
Where:
Overfrequency
K = Time multiplier setting F>1 Status: Disabled/Enabled
t = Operating time in seconds F>1 Setting: 45.00…68.00 Hz
M = Applied input voltage/relay setting F>1 Time Delay: 0.1…100.0 s
voltage F>2 as F>1

Overvoltage CB fail
V> Measur’t Mode: CB Fail 1 Status: Disabled/Enabled
Phase-Phase CB Fail 1 Timer: 0.00…10.00 s
Phase-Neutral CB Fail 2 Status: Disabled/Enabled
V> Operate Mode: CB Fail 2 Timer: 0.00…10.00 s
Any Phase CBF Non I Reset: I< Only, CB Open & I<, Prot
Three Phase Reset & I<
V> 1 Function: CBF Ext Reset: I< Only, CB Open & I <, Prot
Disabled Reset & I<
DT I< Current Set: 0.02…3.200 In
IDMT IN< Current Set: 0.02…3.200 In
V>1 Voltage Set: ISEF< Current: 0.0010…0.8000 In
60…185 V (100/120 V) Remove I> Start: Disabled/Enabled
240…740 V (380/480 V) Remove IN< Start: Disabled/Enabled
V>1 Time Delay: 0.00…100.00 s
V>1 TMS: 0.05…100.0
V>2 Status: Disabled/Enabled

P341 Technical Data Sheet 30 P341 Software versions 36 & 71J


Supervisory functions Check sync
CS1 Status: Disabled/Enabled
Voltage transformer supervison CS1 Phase Angle: 5…90o
VTS Status: Blocking/Indication CS1 Slip Control:
VTS Reset Mode: Manual/Auto None
VTS Time Delay: 1.0…10.0 s Timer
VTS I> Inhibit: 0.08 In…32.0 In Frequency
VTS I2> Inhibit: 0.05 In…0.50 In Both
Negative phase sequence voltage (V2): CS1 Slip Freq.: 0.01…1.00 Hz
10 V (100/120 V) CS1 Slip Timer: 0.00…99.00 s
40 V (380/480 V) CS2 Status: Disabled/Enabled
Phase overvoltage: CS1 Slip Control:
Pick-up 30 V, None
Drop-off 10 V (100/120 V) Timer
Pick-up 120 V, Frequency
Drop-off 40 V (380/480 V) Timer + Freq
Superimposed Current: 0.1 In Freq + CB Comp
CS2 Slip Freq.: 0.01…1.00 Hz
CS2 Slip Timer: 0.00…99.00 s
Current transformer supervision
CTS 1 Status: Disabled/Enabled
CTS 1 VN Input: Measured/Derived
System split
CTS 1 VN< Inhibit: SS Status: Disabled/Enabled
0.5…22 V (100/120 V) SS Phase Angle: 90…175o
2…88 V (380/480 V) SS Under V Block: Disabled/Enabled
CTS 1 IN> Set: 0.08…4 In SS Undervoltage:
10.0…132.0 V (100/110 V)
40…528 V (380/440 V)
System checks SS Timer: 0.00…99.00 s
voltage monitors CB Close Time: 0.000…0.500 s
Live/Dead Voltage:
1.0…132.0 V (100/110 V) Plant supervision
22…528 V (380/440 V)
Gen Undervoltage:
1.0…132.0 V (100/110 V) CB state monitoring control and
22…528 V (380/440 V) condition monitoring
Gen Overvoltage: Broken I^: 1…2.0
1.0…185.0 V (100/110 V) I^ Maintenance:
22…740 V (380/440 V) Alarm disabled
CS Undervoltage: Alarm enabled
10.0…132.0 V (100/110 V) I^ Maintenance: 1 In^…25000 In^
22…528 V (380/440 V) I^ Lockout:
CS Overvoltage: Alarm disabled
60.0…185.0 V (100/110 V) Alarm enabled
240…740 V (380/440 V) I^ Lockout: 1…25000
CS Diff Voltage: No CB Ops. Maint:
1.0…132.0 V (100/110 V) Alarm disabled
4…528 V (380/440 V) Alarm enabled
CS Voltage Block: No CB Ops: Maint: 1…10000
None No CB Ops Lock:
Undervoltage Alarm disabled
Overvoltage Alarm enabled
Differential No CB Ops Lock: 1…10000
UV & O V CB Time Maint:
UV & Diff V Alarm disabled
OV & Diff V Alarm enabled
UV, OV & Diff V CB Time Maint: 0.005…0.500 s
Gen Underfreq: 45.00...65.00 Hz CB Time Lockout:
Gen Overfreq: 45.00...65.00 Hz Alarm disabled
Alarm enabled
CB Time Lockout: 0.005…0.500 s

P341 Technical Data Sheet 31 P341 Software versions 36 & 71J


Fault Freq Lock: WV I< Alarm: Disabled/Enabled
Alarm disabled WV I< Alarm Set: 0…4 mA
Alarm enabled Wind Direction: Disabled, CLI1, CLI2, CLI3,
Fault Freq Count: 1…9999 CLI4
Fault Freq Time: 0…9999 s Default Wind Dir: 0.0…360.0°
Wind Dir Corr: -180.0…180.0°
Dynamic rating Wind Dir Min: 0.0…360.0°
Dyn Line Rating: Disabled/CIGRE Std 207/ Wind Dir Max: 0.0…360.0°
IEEE Std 738 Wind Dirl AvgSet: Disabled/Enabled
DLR LINE SETTING Wind Dir Avg Dly: 60…3600 s
Conductor Type: Gopher, Weasel, Ferret, WD Input Type : 0-1 mA, 0-10 mA, 0-20 mA,
Rabbit, Horse, Dog, Wolf, Dingo, Lynx, 4-20 mA
Caracal, Panther, Jaguar, Zebra, Fox, Mink, WD I/P Minimum: 0.0…360.0°
Skunk, Beaver, Raccoon, Otter, Cat, Hare, WD I/P Maximum: 0.0…360.0°
Hyena, Leopard, Tiger, Coyote, Lion, Bear, WD I< Alarm: Disabled/Enabled
Batang, Goat, Antelope, Sheep, Bison, Deer, WD I< Alarm Set: 0…4 mA
Camel, Elk, Moose, Custom Solar Radiation: Disabled, CLI1, CLI2, CLI3,
NonFerrous Layer: 1…3 CLI4
DC Resist per km: 0.001…2.0000 Ω Default Solar R: 0…3000 W
Overall Diameter: 0.001…0.10000 m Solar Rad Corr: -1000...1000 W
Outer Layer Diam: 0.001…0.0100 m Solar Rad Min: 0…3000 W
TotalArea(mm sq): 10.00…1000.00 mm2 Solar Rad Max: 0…3000 W
TempCoefR x0.001: 1.00…10.00 K Solar Rad AvgSet: Disabled/Enabled
mc: 1.0…5000.0 J/(m⋅K) Solar Rad Avg Dly: 60…3600 s
Solar Absopt: 0.23…0.95 SR Input Type : 0-1 mA, 0-10 mA, 0-20 mA,
Line Emissivity: 0.23...0.95 4-20 mA
Line Elevation: -1000...6000 m SR I/P Minimum: 0…3000 W
Line Azimuth Min: 0.0…360.0° SR I/P Maximum: 0…3000 W
Line Azimuth Max: 0.0…360.0° SR I< Alarm: Disabled/Enabled
T Conductor Max: 0.0 …300.0°C SR I< Alarm Set: 0…4 ma
Ampacity Min: 0.100…4.000 In DLR PROT
Ampacity Max: 0.100…4.000 In DLR I>1 Trip: Disabled/Enabled
Drop-off Ratio: 70.0...99.0% DLT I>1 Set: 20.0%...200.0%
Line Direction: 0.0…360.0° DLR I>1 Delay: 0…30000 s
DLR CHANNEL SET DLR I>2/3/4/5/6 as DLR I>1
Ambient Temp: Disabled, CLI1, CLI2, CLI3,
CLI4 Input labels
Default Ambient T: -100.0 …100.0°C Opto Input 1…32: Input L1…Input L32
Ambient T Corr: -50.0 …50.0°C
Ambient T Min: -100.0 …100.0°C Output labels
Ambient T Max: -100.0 …100.0°C Relay 1…32: Output R1…Output R32
Ambient T AvgSet: Disabled/Enabled
Ambient T Avg Dly: 60…3600 s
Amb T Input Type : 0-1 mA, 0-10 mA, Current loop input
0-20 mA, 4-20 mA CLIO1 Input 1: Disabled/Enabled
Amb T I/P Min: -100.0…100.0°C CLI1 Input Type:
0 - 1 mA
Amb T I/P Max: -100.0 …100.0°C
0 - 10 mA
Amb T I< Alarm: Disabled/Enabled
0 - 20 mA
Amb T I< Alm Set: 0…4 mA
4 - 20 mA
Wind Velocity: Disabled, CLI1, CLI2, CLI3,
CLI1 Input Label: 16 characters (CLIO input 1)
CLI4
CLI1 Minimum: -9999…+9999
Default Wind Vel: 0.00…60.00 m/s
CLI1 Maximum: -9999…+9999
Wind Vel Corr: 0...150%
CLI1 Alarm: Disabled/Enabled
Wind Vel Min: 0.00…60.00 m/s
CLI1 Alarm Fn: Over/Under
Wind Vel Max: 0.00…60.00 m/s
CLI1 Alarm Set: CLI1 min…CLI1 max
Wind Vel AvgSet: Disabled/Enabled
CLI1 Alarm Delay: 0.0…100.0 s
Wind Vel Avg Dly: 60…3600 s
CLI1 Trip: Disabled/Enabled
WV Input Type : 0-1 mA, 0-10 mA, 0-20 mA,
CLI1 Trip Fn: Over/Under
4-20 mA
CLI1 Trip Set: CLI1 min…CLI1 max
WV I/P Minimum: 0.00…60.00 m/s
CLI1 Trip Delay: 0.0…100.0 s
WV I/P Maximum: 0.00…60.00 m/s
P341 Technical Data Sheet 32 P341 Software versions 36 & 71J
CLI1 I< Alarm (4…20 mA input only): 3 Phase Vars*: -6000 Var…6000 Var
Disabled/Enabled 3 Phase VA*: 0…6000 VA
CLI1 I< Alm Set (4…20 mA input only): 3Ph Power Factor*: -1…1
0.0…4.0 mA Single Phase Active Power:
CLI2/3/4 as CLI1 A Phase Watts*:
B Phase Watts*:
Current loop output C Phase Watts*:
CLO1 Output 1: Disabled/Enabled -2000 W…2000 W
CLO1 Output Type: Single Phase Reactive Power:
0 - 1 mA A Phase Vars*:
0 - 10 mA B Phase Vars*:
0 - 20 mA C Phase Vars*
4 - 20 mA -2000 Var…2000 Var
CLO1 Set Values: Primary/Secondary Single Phase Apparent Power:
CLO1 Parameter: As shown below* A Phase VA*:
CLO1 Min: Range, step size and unit B Phase VA*:
corresponds to the selected parameter C Phase VA*
CLO1 Max: Same as CLO1 Min 0…2000 VA
CLO2/3/4 as CLO1 Single Phase Power Factor:
Current Loop Output Parameters Aph Power Factor*
Current Magnitude: BPh Power Factor*
IA Magnitude CPh Power Factor*
IB Magnitude -1…1
IC Magnitude 3 Phase Current Demands:
IN Derived Mag: 0.00…16.0 A IA Fixed/Roll/Peak Demand*
I Sen Mag: 0.00… 2.0 A IB Fixed/Roll/Peak Demand*
Phase Sequence Components: IC Fixed/Roll/Peak Demand*
I1 Magnitude 0.00…16.0 A
I2 Magnitude 3ph Active Power Demands:
I0 Magnitude: 3Ph W Fix/Roll/Peak Demand*
0.00…16.0 A -6000W…6000W
Phase Currents: 3ph Reactive Power Demands:
IA RMS* 3Ph Vars Fix/Roll/Peak Dem*
IB RMS* -6000 Var…6000 Var
IC RMS* Thermal Overload: 0.00…200.0%
0.00…16.0 A CL Input 1-4: -9999…9999.0
P-P Voltage Magnitude: DLR Ampacity: 0.00…4.0 A
VAB Magnitude Maximum ac current: 0.00…16.0 A
VBC Magnitude df/dt: -10.00…10.00 Hz/s
VCA Magnitude Check Synch Voltages: 0.0…200.0 V
0.0…200.0 V Slip Frequency: 0.00…70.00 Hz
P-N Voltage Magnitude: Note 1: Measurements marked with an
VAN Magnitude asterisk, the internal refresh rate is
VBN Magnitude nominally 1 s, others are 0.5 power
VCN Magnitude system cycles or less.
0.0…200.0 V
Neutral Voltage Magnitude: Note 2: The polarity of Watts, Var and power
VN1 Measured Mag factor is affected by the measurements
VN Derived Mag Mode setting.
0.0…200.0 V
Phase Sequence Voltage Components: Note 3: These settings are for nominal 1 A and
V1 Magnitude* 100/120 V versions only. For other
V2 Magnitude versions they need to be multiplied
V0 Magnitude accordingly.
0.0…200.0 V
RMS Phase Voltages:
VAN RMS*
VBN RMS*
VCN RMS*
0.0…200.0 V
Frequency: 0.00…70.0 Hz
3 Phase Watts*: -6000 W…6000 W
P341 Technical Data Sheet 33 P341 Software versions 36 & 71J
Measurements list 3 Phase VArs
3 Phase VA
NPS Power S2
Measurements 1 3Ph Power Factor
Iϕ Magnitude ϕPh Power Factor
Iϕ Phase Angle Independent power factor measurements for
Per phase (ϕ = A/A-1, B/B-1, C/C-1) current all three phases (ϕ = A, B, C).
measurements 3Ph WHours Fwd
IN Derived Mag 3Ph WHours Rev
IN Derived Angle 3Ph VArHours Fwd
ISen Mag 3Ph VArHours Rev
ISen Angle 3Ph W Fix Demand
I1 Magnitude 3Ph VArs Fix Dem
I2 Magnitude Iϕ Fixed Demand
I0 Magnitude Maximum demand currents measured on a
Iϕ RMS per phase basis (ϕ = A, B, C).
Per phase (ϕ = A, B, C) RMS current 3Ph W Roll Dem
measurements 3Ph VArs Roll Dem
IN -2 Derived Iϕ Roll Demand
Vϕ-ϕ Magnitude Maximum demand currents measured on a
Vϕ-ϕ Phase Angle per phase basis (ϕ = A, B, C).
Vϕ Magnitude 3Ph W Peak Dem
Vϕ Phase Angle 3Ph VAr Peak Dem
All phase-phase and phase-neutral voltages Iϕ Peak Demand
(ϕ = A, B, C). Maximum demand currents measured on a
VN Measured Mag per phase basis (ϕ = A, B, C).
VN Measured Ang Reset Demand: No/Yes
VN Derived Mag
V1 Magnitude
V2 Magnitude Measurements 3
V0 Magnitude IREF Diff
Vϕ RMS A Ph Sen Watts
A Ph Sen VArs
All phase-neutral voltages (ϕ = A, B, C).
A Phase Power Angle
Thermal Overload
Frequency
Reset Thermal O/L: No/Yes
I1 Magnitude
CLIO Input 1/2/3/4
I1 Angle
df/dt
I2 Magnitude
I2 Angle
I0 Magnitude Measurements 4
I0 Angle Max Iac
V1 Magnitude DLR Ambient Temp
V1 Angle Wind Velocity
V2 Magnitude Wind Direction
V2 Angle Solar Radiation
V0 Magnitude Effct wind angle
V0 Angle Pc
C/S Voltage Mag Pc, natural
C/S Voltage Ang Pc1, forced
Gen-Bus Volt Pc2, forced
Gen-Bus Angle DLR Ampacity
Slip Frequency DLR CurrentRatio
C/S Frequency Dyn Conduct Temp
Steady Conduct T
Measurements 2 Time Constant
ϕ Phase Watts
ϕ Phase VArs
ϕ Phase VA
All phase segregated power measurements,
real, reactive and apparent (ϕ = A, B, C).
3 Phase Watts
P341 Technical Data Sheet 34 P341 Software versions 36 & 71J
Circuit breaker monitoring statistics
CB Operations
Total Iϕ Broken
Cumulative breaker interruption duty
on a per phase basis (ϕ = A, B, C)
CB Operate Time
Reset CB Data: No/Yes.

P341 Technical Data Sheet 35 P341 Software versions 36 & 71J


CASE DIMENSIONS

P1647ENd

P341 case dimensions (40TE case)

P341 case dimensions (60TE case)

P341 Technical Data Sheet 36 P341 Software versions 36 & 71J


P341 Technical Data Sheet
REAR
PORT 1:
17
-
EIA485/
KBUS 18
PORT +
16
SCN

IRIG-B INPUT
NOTE: FOR TERMINAL BLOCK CONNECTION (OPTIONAL)

Comms. options Px40 platform


REFER TO RELEVANT EXTERNAL CONNECTION DIAGRAM.
(ALWAYS ON PSU BLOCK) IRIG-B INPUT SERIAL PORT IRIG-B INPUT
(OPTIONAL)
SK4 EIA232 EIA485
1 1 N.C. N.C.
2 2 RXD N.C.
RJ45
3 3 TXD N.C.
1 TX+ 1
4 4 DTR# TXRXA FAULT
2 TX- SK7 2
5 5 -0V -0V STATUS RELAY
3 RX+ 3
6 6 N.C. N.C.
4 10 BASE-T/
SK2 SK6 7
5 100 BASE-TX 7 RTS TXRXB
DATA READY 1 TX
FIBRE OPTIC 8 8 CTS N.C.
DATA COMMUNICATION 6 RX-
10 9 9 N.C. N.C.
ACKNOWLEDGE (OPTIONAL) 7
EXTERNAL CONNECTION DIAGRAMS

OR OR OR RX1
RX
EXTERNAL 8 100 BASE-FX
RESET 16 SK5
TX1
DOWNLOAD 1 DCD

37
COMMAND 17 IRIG-B INPUT
FRONT 2 RXD
(OPTIONAL)
TX 3 TXD RX2
TEST/ DO-D7 2-9 10 BASE-FL
DOWNLOAD OR 4 DTR# 100 BASE-FX
11,12,15,13, 100 BASE-FX EIA232
TO-T7 RX 5 0V SERIAL PORT TX2
20,21,23,24
6 N.C.
0V 19,18,22,25 7 RTS#
8 N.C.
NOT 14
CONNECTED 9 N.C.

1 SK1
TX 2 # PERMANENTLY ACTIVE
RX 3
FRONT 4 IRIG-B BOARD SINGLE PORT ETHERNET BOARD REAR COMMS BOARD DUAL PORT REDUNDANT ETHERNET BOARD
EIA232 0V 5
SERIAL PORT 6
CTS 7
RTS 8 10Px4001
N.C. 9

P2139ENd

P341 Software versions 36 & 71J


Interconnection protection relay (40TE) for embedded generation using VEE connected VT's
(8 I/P & 7 O/P)

P341 Technical Data Sheet 38 P341 Software versions 36 & 71J


10P34101_5

P4659ENa

Interconnection protection relay (40TE) for embedded generation and sensitive power
(8 I/P & 7 O/P)
P341 Technical Data Sheet 39 P341 Software versions 36 & 71J
10P34101_7

P4592ENb

Interconnection protection relay (40TE) for embedded generation and check synchronizing
(8 I/P & 7 O/P)

P341 Technical Data Sheet 40 P341 Software versions 36 & 71J


Interconnection protection relay (40TE) for embedded generation (8 I/P & 7 O/P)

P341 Technical Data Sheet 41 P341 Software versions 36 & 71J


DIRECTION OF FORWARD CURRENT FLOW
NOTE 4 A
P2 P1 P2 P1
A
S2 S1
B
C C B MiCOM P341 (PART) F11
PHASE ROTATION WATCHDOG
S2 S1 F12 CONTACT
F13

P341 Technical Data Sheet


WATCHDOG
MiCOM P341 (PART) F14 CONTACT
A B C C1 5A E1
D1
- E2 RELAY 1
IA OPTO 1 COMMS
D2 NOTE 3 E3
C2 +
N RELAY 2
D3 E4
NOTE 2 C3 1A -
D4 OPTO 2 E5
dn n C4 5A + RELAY 3
E6
D5
IB - E7
D6 OPTO 3
a b c C5 + E8 RELAY 4
da 1A D7 F17 E9
C6 - -
D8 OPTO 4 SEE DRAWING E10
C7 5A + EIA485/
KBUS 10Px4001. E11 RELAY 5
IC D9 F18
- PORT + E12
C8 D10 OPTO 5
+ F16 E13
1A SCN E14
C9 D11 RELAY 6
-
OPTO 6 E15
D12
C13 5A + E16
IN D13 E17
- RELAY 7
SENSITIVE OPTO 7
D14 E18
C14 +
1A D15
C15 - F1 *
OPTO 8 AC OR DC -
D16 B3
+ Vx AUX SUPPLY F2 -
D17 +
VA RELAY 8
C19 COMMON B4
D18 CONNECTION F7 +
+
B7 -
+ F8

42
48V DC FIELD RELAY 9
VOLTAGE OUT - F9 B8
+ HIGH BREAK
VB C20 F10
- B11 - CONTACTS
NOTE 5
RELAY 10
B12
+
B15 -
VC C21 CASE RELAY 11
EARTH B16
+

VN C22
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
C23
NOTES 1.
V NEUTRAL 2. C.T. CONNECTIONS ARE SHOWN 1A CONNECTED AND ARE TYPICAL ONLY.

C24 (a) C.T. SHORTING LINKS 3. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

4. DIRECTION OF FORWARD CURRENT FLOW FOR OPERATION


(b) PIN TERMINAL (P.C.B. TYPE) OF DIRECTIONAL O/C + EF + SEF PROTECTION.

5. TO OBTAIN HIGH BREAK DUTY, CONTACTS MUST BE


CONNECTED WITH THE CORRECT POLARITY.

Interconnection Protection Relay (40TE) for Embedded Generation (8 I/P & 11 O/P (4HB))

P341 Software versions 36 & 71J


Dynamic line rating protection relay (40TE) (8 I/P & 7 O/P & CLIO)

P341 Technical Data Sheet 43 P341 Software versions 36 & 71J


P2236ENa

Interconnection protection relay (40TE) for embedded generation (8 I/P & 15 O/P)

P341 Technical Data Sheet 44 P341 Software versions 36 & 71J


P2235ENa

Interconnection protection relay (40TE) for embedded generation (16 I/P & 7 O/P)

P341 Technical Data Sheet 45 P341 Software versions 36 & 71J


Interconnection protection relay (40TE) for embedded generation (12 I/P & 11 O/P)

P341 Technical Data Sheet 46 P341 Software versions 36 & 71J


10P34101_4

P4581ENa

Dynamic line protection relay (60TE) (16 I/P & 16 O/P & CLIO)

P341 Technical Data Sheet 47 P341 Software versions 36 & 71J


10P34106_1

P4579ENb

Interconnection protection relay (60TE) for embedded generation (24 I/P& 16 O/P)
P341 Technical Data Sheet 48 P341 Software versions 36 & 71J
P10P34107_1

P4580ENa

Interconnection protection relay (60TE) for embedded generation (16 I/P & 24 O/P)

P341 Technical Data Sheet 49 P341 Software versions 36 & 71J


10P34111_1

P4582ENa

Interconnection protection relay (60TE) for embedded generation (16 I/P & 20 O/P (4HB))

P341 Technical Data Sheet 50 P341 Software versions 36 & 71J


10P34112_1

P4583ENa

Interconnection protection relay (60TE) (16 I/P & 12 O/P (4HB) & CLIO)

P341 Technical Data Sheet 51 P341 Software versions 36 & 71J


GN0292_1

P4586ENa

Assembly P341 interconnection and DLR protection relay (40TE) (8 I/P & 7 O/P with optional
I/P & O/P)

P341 Technical Data Sheet 52 P341 Software versions 36 & 71J


GN0293_1

P4656ENa

Assembly P341 interconnection and DLR protection relay (40TE) (8 I/P & 7 O/P with optional
CLIO)

P341 Technical Data Sheet 53 P341 Software versions 36 & 71J


GN0294_1

P4655ENa

Assembly P341 interconnection and DLR protection relay (60TE) (16 I/P & 16 O/P with
optional I/P & O/P)

P341 Technical Data Sheet 54 P341 Software versions 36 & 71J


GN0295_1

P4654ENa

Assembly P341 interconnection and DLR protection relay (60TE) (16 I/P & 16 O/P with
optional HB O/P)

P341 Technical Data Sheet 55 P341 Software versions 36 & 71J


GN0295_1

P4653ENa

Assembly P341 interconnection and DLR protection relay (60TE) (16 I/P & 16 O/P with
optional CLIO)

P341 Technical Data Sheet 56 P341 Software versions 36 & 71J


Ordering options
Information required with order

P341 Interconnection Protection Relay P341


Vx Aux rating
24-48 Vdc 1
48-110 Vdc, 40-100 Vac 2
110-250 Vdc, 100-240 Vac 3
I/n/Vn rating
In=1 A/5 A, Vn=100/120 V (40 TE case) 1
In=1 A/5 A Vn=380/480 V (40 TE case) 2
In=1 A/5 A, Vn=100/120 V, with Check
3
Sync VT Input (60 TE case only)
In=1 A/5 A, Vn=380/480 V, with Check
4
Sync VT Input (60 TE case only)
Hardware options
Nothing 1
IRIG-B only (Modulated) 2
Fiber Optic Rear Comms Port 3
IRIG-B (Modulated) & Fiber Optic Rear Comms Port 4
Ethernet (100 Mbps)** 6
2nd Rear Comms. Board* 7
IRIG-B* (Modulated) plus 2nd Rear Comms Board 8
Ethernet (100 Mbps) + IRIG-B (Modulated)** A
Ethernet (100 Mbps) + IRIG-B (Unmodulated) ** B
IRIG-B (Unmodulated) ** C
Redundant Ethernet Self-Healing Ring, 2 multi-mode
G
fiber ports + (IRIG-B Modulated*)
Redundant Ethernet Self-Healing Ring, 2 multi-mode
H
fiber ports + IRIG-B* (Unmodulated*)
Redundant Ethernet RSTP, 2 multi-mode fiber ports
J
+ IRIG-B* (Modulated*)
Redundant Ethernet RSTP, 2 multi-mode fiber ports
K
+ IRIG-B* (Unmodulated*)
Redundant Ethernet Dual Homing Star, 2 multi-mode
L
fiber ports + IRIG-B* (Modulated*)
Redundant Ethernet Dual Homing Star, 2 multi-mode
M
fiber ports + IRIG-B* (Unmodulated*)
Product specific
Size 40TE Case, No Option (8 Optos + 7 Relays) A
Size 40TE Case, 8 Optos + 7 Relays + CLIO * B
Size 40TE Case, 16 Optos + 7 Relays* C
Size 40TE Case, 8 Optos + 15 Relays* D
Size 40TE Case, 12 Optos + 11 Relays* E
Size 60TE Case, 16 Optos + 16 Relays** F
Size 60TE Case, 16 Optos + 16 Relays + CLIO ** G
Size 60TE Case, 24 Optos + 16 Relays** H
Size 60TE Case, 16 Optos + 24 Relays** J
Size 40TE Case, 8 Optos + 11 Relays (4 High Break) K
Size 60TE Case, 16 Optos + 20 Relays (4 High
L
Break)
Size 60TE Case, 16 Optos + 12 Relays (4 High M

P341 Technical Data Sheet 57 P341 Software versions 36 & 71J


P341 Interconnection Protection Relay P341
Break) + CLIO**
Note: HB = High Break
Protocol options
K-Bus 1
MODBUS 2
IEC 60870-5-103 (VDEW) 3
DNP3.0 4
IEC 61850 + Courier via rear EIA(RS)485
6
port
Mounting
Panel Mounting
M
Panel Mounting with Harsh Environment
P
Coating
Language options
Multilingual - English, French, German,
Spanish
Multilingual - English, French, German, 0
Russian 5
Chinese, English or French via HMI, with C
English or French only via
Communications port**
Software number
Latest software 36
Latest software + Dynamic Line Rating 71
Settings File
Default 0
Customer A
Design suffix
Phase 2 CPU and front panel with 2
J
hotkeys and dual characteristic optos
Improved power supply C
Universal Optos, low powered relay
B
outputs
Original release – phase 1 A

Note Design Suffix


A = Original hardware (48 V opto inputs only, lower contact rating, no I/O
expansion available)
C = Universal optos, new high capacity relays, new power supply
J = Phase 2 CPU and front panel with 2 hotkeys and dual characteristic optos
* Not available in design suffix A relays
** Not available in design suffix A,B, C

Note: For rack mounting assembled single rack frames and blanking
plates are available

P341 Technical Data Sheet 58 P341 Software versions 36 & 71J


PUBLICATION: P341/EN TDS/F74

Alstom Grid Substation Automation Solutions Business www.alstom.com/grid