Electronic position transmitter

RWG 4020
RWG 5020 Ex

Technical Information
Features of the electronic position transmitter RWG

Application Areas of application Function & features


If a continuous feedback signal of the The electronic position transmitter The electronic position transmitter
valve position is required, an elec- can be employed in the following continuously monitors the valve
tronic position transmitter RWG can AUMA multi-turn and part-turn actu- travel. The valve movement is trans-
be used. The signal may be transmit- ators: mitted via a reduction gearing1)
ted to l Version RWG 4020 in actuators within the actuator to a high quality
l a remote position indicator AUMA NORM: precision potentiometer. In the elec-
l an external positioner SA 07.1 to SA 48.1 tronic board the feedback is con-
l an integral positioner (actuators SAR 07.1 to SAR 30.1 verted into an analogue current sig-
for modulating service with motor SG 05.1 to SG 12.1 nal, whose range may be set to 0 -
controls AUMA MATIC) and in AUMA MATIC: 20 mA or 4 - 20 mA.
SA 07.1 to SA 16.1 1) The reduction gearing must be selected
Two versions are available: SAMEx 07.1 to SAMEx 16.1 to suit the valve travel i.e. number of
l RWG 4020 SARMEx 07.1 to SARMEx 16.1 turns or amount of swing angle.
l RWG 5020 Ex (explosion proof) SG 05.1 to SG 12.1
A slip clutch protects the position
The electronic position transmitter l Version RWG 5020 Ex in actua- transmitter from being damaged, in
provides a continuous current signal, tors AUMA NORM: the event of the potentiometer’s max.
which corresponds to the actual SAEx 07.1 to SAEx 40.1 rotation being exceeded.
valve position. SAREx 07.1 to SAREx 16.1
SGEx 05 to SGEx 12 In multi-turn actuators for modulating
duty, the slip clutch is additionally fit-
The version RWG 4020 can be oper- ted with a spring to minimise back-
ated as a 2-wire, 3- or 4-wire system. lash.
The version RWG 5020 Ex is intrinsi-
cally safe and can be operated as a On-line setting with integrated
2-wire system in hazardous areas. measuring points
Measuring points on the electronic
board allow the connected RWG to
be adjusted without having to take it
out of circuit.

Settings
Zero and span can be adjusted inde-
pendently at the electronic board via
trimmer potentiometers, which are
easily accessible in the control unit.
Precision
potentiometer Signal
in mA

20

0
0 60 100
Valve travel in %

Electronic board

2
Technical Data

Version RWG 4020

Data 2-wire-system 3- and 4-wire-system


Output signal Ia 4 - 20 mA 0 - 20 mA
4 - 20 mA
Supply voltage UV1) 14 V DC + (I x RB) 24 V DC
max. 30 V ±15% smoothed
Current drawn max. 20 mA 24 mA
(with 20 mA output current)
(U V − 14 V)
External resistance RB max. 600 Ω
20 mA
Effect of supply voltage fluctuation 0,1% / V 0,02% / V
Effect of external resistance 0,1% / 100 Ω 0,1% / (0 - 600 Ω)
Temperature drift < 0,3% / 10 K < 0,3% / 10 K
Linearity variation ≤ 1% ≤ 1%
(electronics and potentiometer)
EMC tests in accordance with EN 50 081-2 and EN 50 082-2 tested toget-
her with motor controls AUMA MATIC and with power supply unit
PS 01 resp. in the case of AUMA NORM actuators
Ambient temperature range:
- Multi-turn actuators for open-close duty SA –40 °C to +70 °C –40 °C to +70 °C
- Multi-turn actuators for modulating duty SAR –40 °C to +60 °C –40 °C to +60 °C
- Part-turn actuators SG –40 °C to +70 °C –40 °C to +70 °C
1) Smoothed supply voltage; for actuators AUMA NORM we recommend our power supply unit PS 01.

Explosion-proof version RWG 5020 Ex

Data 2-wire-system
Output signal Ia 4 - 20 mA
Supply voltage UV 10 - 28,5 V DC
Current drawn max. 20 mA
(U V − 10 V)
External resistance RB max.
20 mA
Effect of supply voltage fluctuation 0,01% / V
Effect of external resistance 0,1% / (0 - 600) Ω
Temperature drift < 0,1% / 10 K
Linearity variation ≤ 1%
(electronics and potentiometer)
EMC tests in accordance with
EN 50 081-2 and EN 50 082-2
tested together with power
supply unit PS 01
Ambient temperature2) –20 °C to +60 °C
Explosion protection EEx ib IIC T5
Certificate of conformity PTB Nr. Ex-90.C.2017 X
2) AUMA actuators SAEx 07.1 to SAEx 40.1 and SAREx 07.1 to SAREx 16.1 are approved by PTB
for ambient temperature up to +40 °C.
Special rating of the actuators SAEx/SAREx for max. +60 °C ambient temperature is possible.

3
Installation and configuration

Installation
The electronic position transmitter
can be installed in the control unit of
AUMA actuators as an option. Sub-
sequent fitting is possible.

Electronic board

Control unit of
the actuator Precision potentiometer Precision potentiometer with
with slip clutch slip clutch and anti-back lash spring
(for modulating duty)

Configuration
Version RWG 4020 can be configured as: The explosion-proof version RWG
l 2-wire system 5020 Ex is designed as a 2-wire-sys-
l 3- and 4-wire system. tem. Inverse signal is possible.
l Inverse signal 2-wire system The RWG 5020 Ex cannot be used as
l Inverse signal 3- and 4-wire system a 3- or 4- wire system.

4
Connection and wiring

Version RWG 4020


Connection: Internal wiring: General Notes:
2-wire system 2-wire system AUMA supply
RD = red
RWG 4020 RWG 4020
5 kΩ
BK = black
YE = yellow
7 6 5

RWG-
board ● Use screened cables to the
plug / socket for
customer connections actuator
21 22 23 24
1 RD 4 BK

● For actuators AUMA NORM we


23 24 recommend the use of our stabi-
4 – 20 mA
lized power supply unit PS 01.
3-wire system 3-wire system
● For actuators with motor controls
RWG 4020 RWG 4020 AUMA MATIC an internal voltage
5 kΩ supply is available at no extra
cost.
7 6 5

RWG- Important notes:


board
plug / socket for
customer connections
for version RWG 5020 Ex
20 21 22 23 24
1 RD 2 BK 4 YE
● The power supply unit has to be
21 22 24
intrinsically safe or must be
0 – 20 mA
+24 V 0 V 4 – 20 mA installed with a safety barrier.

4-wire system 4-wire system ● Observe applicable regulations


and installation instructions for
RWG 4020 RWG 4020
5 kΩ intrinsically safe circuits.

7 6 5

RWG-
plug / socket for
board
customer connections
20 21 22 23 24
1 RD 2 BK 3 BK 4 YE

0 – 20 mA 21 22 23 24
+24 V 0 V 4 – 20 mA

Version RWG 5020 Ex


Connection: 2-wire system Internal wiring: 2-wire system
RWG 5020 Ex RWG 5020 Ex
5 kΩ

5 4 3

RWG-
terminals for
customer connections
board
23 24

safety For PTB-requirements 1 RD 2 BK


barrier refer to PTB certificate

4 – 20 mA
+U
0V 23 24
voltage supply

5
Settings and adjustment

Settings and adjustment


The electronic position transmitter is ting instructions below have to be fol- justed, if necessary.
set at the factory according to the sig- lowed. Specific safety instructions as appli-
nal range specified by the customer. After mounting the actuator to the cable for such equipment must be
For subsequent adjustments, e.g. valve or during commissioning, the observed.
with an indicator instrument, the set- setting has to be checked and read-

N M max
0(4) (20 mA)
N R2 M

R2

DSR

WSR

WDR

Measuring points
Housing Cover plate 0/4-20 mA

On-line setting
At the connected RWG 4020 it is signal on site by using the measuring - 20 mA appears directly in the
possible to perform an on-line mea- points. The current circuit does not ammeter display.
surement of the transmitter output have to be interrupted, the signal 0/4

Setting for 2-wire system 4 - 20 mA and 3-/4-wire Setting for 3- and 4-wire system 4 - 20 mA
system 0 - 20 mA
1. Move valve to end position CLOSED.
1. Move valve to end position CLOSED. 2. Remove cover plate.
2. Remove cover plate. 3. Connect ammeter to measuring points.
3. Connect ammeter for 0 - 20 mA to measuring 4. Turn potentiometer (R2) clockwise to initial posi-
points. In end position CLOSED for 3- and 4-wire tion. Turn potentiometer (R2) whilst observing a
system value is normally 0 mA, for 2-wire system decreasing output signal until stop is felt.
4 mA. 5. Turn trimmer potentiometer (N) clockwise, until
4. Turn potentiometer (R2) clockwise to initial posi- output current starts to increase.
tion. Turn potentiometer (R2) whilst observing a 6. Turn back trimmer potentiometer (N), until a resid-
decreasing output signal until stop is felt. ual current of approx. 0,1 mA is obtained.
5. Turn trimmer potentiometer (N) clockwise, until 7. Move valve to end position OPEN.
output current starts to increase. 8. Set to end value 16 mA with trimmer potentiome-
6. Turn back trimmer potentiometer (N), until a resid- ter (M).
ual current of approx. 0,1 mA (or 4,1 mA in the 9. Move valve to end position CLOSED.
case of a 2-wire system) is obtained. This ensures 10 Set trimmer potentiometer (N) to initial value
that the signal remains above the dead and live 4 mA. This results in a simultaneous shift of the
zero point. end value by 4 mA so that the range is now 4 -
7. Move valve to end position OPEN. 20 mA
8. Set to end value 20 mA with trimmer potentiome- 11. Approach both end positions anew and check set-
ter (M). ting. If necessary, readjust.
9. Approach end position CLOSED anew and check 12. Refit cover plate.
minimum value (0 mA or 4 mA). If necessary, 13. Clean sealing face, check O-Ring, apply a thin film
readjust. of non-acidic grease to sealing face.
10. Refit cover plate. 14. Fit and fasten switch compartment cover.
11. Clean sealing face, check O-Ring, apply a thin film
of non-acidic grease to sealing face.
12. Fit and fasten switch compartment cover.

6
Notes
Inverse signal Note:
Interchange the connections red (RD) and black (BK) at If the maximum value of the output current 20 mA is not
the potentiometer for inverse signal. reached, check whether reduction gearing with correct
ratio has been fitted.

PTB Certificate of Conformity for RWG 5020Ex

7
automates valves

INDUSTRA Lda. K. Y. CONTROLS Ltd.


Germany Europe P-2796 Linda A Velha ROC-Taipei, Taiwan
Tel 01 / 4 14 06 06 Tel 2733 - 3530
WERNER RIESTER AUMA Armaturenantriebe Fax 01 / 4 19 56 52 Fax 2736 - 5526
GmbH & Co. KG Gesellschaft m.b.H e-mail mop32760@mail.epac.pt e-mail kycl3530@msb.hinet.net
A-2512 Tribuswinkel
Factory Müllheim Tel 0 22 52 / 8 25 40 ERICHS ARMATUR AB DONG WOO Valve Control Co. Ltd.
P.O.Box 13 62 Fax 0 22 52 / 8 25 40-50 S-20039 Malmö ROK-Seoul, Korea
e-mail office@auma.at Tel 0 40 / 31 15 50 Tel 02 / 7 61 62 33
D-79373 Müllheim
Tel 0 76 31 / 809-0 Fax 0 40 / 94 55 15 Fax 02 / 7 61 12 78
AUMA (Switzerland) AG e-mail info@erichsarmatur.se e-mail dw7994@users.unitel.co.kr
Fax 0 76 31 / 1 32 18
e-mail riester@auma.com CH-8965 Berikon / AG
Tel 56 64 00 945 MEGA ENDÜSTRI KONTROL Sunny Valves and Intertrade Corp. Ltd.
Factory Ostfildern-Nellingen Fax 56 64 00 948 TR-06060 Ankara THA-Yannawa - Bangkok 10120
P.O.Box 11 51 e-mail RettichP.ch@auma.com Tel 312 / 478 08 13 Tel 2 40 06 56 11
D-73747 Ostfildern Fax 312 / 478 08 31 Fax 2 40 10 95
AUMA Servopohony e-mail megaltd@escortnet.com
Tel 07 11 / 3 48 03-0
Fax 07 11 / 3 48 03 34 CZ-10 200 Praha 10
e-mail riester@wof.auma.com Tel 2 / 70 41 25 Australia
Fax 2 / 70 41 25 Africa
Service-Centre Cologne AUMA France BARRON GJM Pty. Ltd.
Mathias-Brüggen-Str.164 AUMA South Africa (Pty) Ltd. AUS-Artarmon NSW 2064
F-95157 Taverny Cedex
D-50829 Köln Tel 01 / 39 32 72 72 ZA-Springs 1560 Tel 02 / 9436 1088
Tel 02 21 / 5 97 72-0 Fax 01 / 39 32 17 55 Tel 36 32 880 Fax 02 / 9439 3413
Fax 02 21 / 5 97 72-19 e-mail aumaf@club-internet.fr Fax 8 18-52 48 e-mail barron@intercoast.com.au
e-mail riester@sck.auma.com e-mail auma-sa@cis.co.za
OY AUMATOR AB
Service-Centre Magdeburg
Am Stadtberg 1 FIN-02271 Espoo 27
A.T.E.C. North- and South America
Tel 09 / 5840 22 ET-Cairo
D-39167 Niederndodeleben Fax 09 / 5840 2300 Tel 03 506 621 AUMA ACTUATORS INC.
Tel 03 9204 / 7 59 0 e-mail aumator@aumator.inet.fi Fax 03 506 621
Fax 03 9204 / 7 59 19 e-mail ATEC@INTOUCH.com USA-Pittsburgh, PA 15 205
Tel
e-mail riester@scm.auma.com AUMA ACTUATORS Ltd Fax
GB-Clevedon e-mail 4 12 / 7 87-13 40
North Office
North Somerset BS21 6QH Asia
D-29664 Walsrode Tel 012 75 / 87 11 41 ASVOTEC Termoindustrial Ltda.
Tel 0 51 67 / 5 04 AUMA (INDIA) Ltd. BR-04634 São Paulo SP
Fax 0 51 67 / 5 65 Fax 012 75 / 87 54 92
e-mail HandwerkerE@auma.com e-mail auma@auma.co.uk IND-Bangalore 560 058 Tel 0 11 / 50 90 9458
Tel 8 39 46 55 Fax 0 11 / 50 90 9425
West Office AUMA ITALIANA s.r.l. Fax 8 39 28 09 e-mail impex@asvotec.com.br
D-45549 Sprockhövel I-20020 Lainate / Milano
Tel 02 / 93 17 911 AUMA Beijing Representative Office TROY-ONTOR Inc.
Tel 0 23 39 / 92 12 0 PRC-Beijing 100029 CDN-Etobicoke, Ontario
Fax 0 23 39 / 92 12 15 Fax 02 / 93 74 387
e-mail aumait@galactica.it Tel 10 62 02 24 91 Tel 4 16 / 6 14-12 10
e-mail EpkeS@auma.com Fax 10 62 02 24 96 Fax 4 16 / 6 14-15 37
South-West Office AUMA BENELUX B.V. e-mail aumabs@ihw.com.cn
NL-2314 XT Leiden TECNICA HANSA Ltd.
D-69502 Hemsbach Tel 0 71 / 5 81 40 40 AUMA ACTUATORS RCH-Santiago de Chile 1
Tel 0 62 01 / 4 56 16 (SINGAPORE) Pte. Ltd. Tel 2 04 / 53 48
Fax 0 62 01 / 4 56 17 Fax 0 71 / 5 81 40 49
SGP Singapore 318992 Fax 2 04 / 52 31
Baden/Switzerland Office AUMA Polska SP. zo . o Tel 4 81 87 50 e-mail hansa@entelchile.net
PL-40816 Katowice Fax 4 81 82 69
D-79373 Müllheim Tel 0 32 2 50 54 12
Tel 0 76 31 / 80 91 93 AUMA Middle East Representative Office
Fax 0 76 31 / 1 32 18 Fax 0 32 2 50 54 12
e-mail riester@auma.com UAE-Abu Dhabi
GRØNBECH & SØNNER Tel 2 / 77 02 43
Württemberg Office DK-2450 København SV Fax 2 / 77 25 61
Tel 33 26 63 00 e-mail auma@emirates.net.ae
D-73747 Ostfildern Fax 33 26 63 01
Tel 07 11 / 34 803 80 PERFECT CONTROLS Ltd.
Fax 07 11 / 34 803 81 e-mail gs@groenbech-sons.dk
e-mail riester@wof.auma.com HK-Tsuen Wan,
IBEROPLAN S.A. Kowloon, Hongkong
Bavaria Office E-28027 Madrid Tel 24 93 77 26
D-93352 Rohr Tel 91 / 371 71 30 Fax 24 16 37 63
Tel 0 87 83 / 14 79 Fax 91 / 7 42 71 26
Fax 0 87 83 / 10 23 e-mail iberoplan@mad.servicom.es MORITANI & Co. Ltd.
J-Tokyo 103
East Office D. G. Bellos & Co. O.E. Tel 03 / 32 78 63 43
D-39167 Niederndodeleben GR-10438 Athens Fax 03 / 32 78 61 21
Tel 03 9204 / 7 59 80 Tel 1 / 5 22 38 48 e-mail 105725.3367@compuserve.com
Fax 03 9204 / 7 59 89 Fax 1 / 5 23 22 46
e-mail dgb@eexi.gr AL-ARFAJ Eng. Company W.L.L.
KWT-Salmiyah 22004
SIGURD SØRUM A.S. Tel 4 81 74 48
N-1301 Sandvika Fax 4 81 74 42
Tel 67 57 26 00 e-mail arfa@ncc.moc.kw
Fax 67 57 26 10
e-mail tom.grostad@sigurd-sorum.no BEHZAD Trading
Q-Doha
Tel 43 32 36
Fax 43 32 37

WERNER RIESTER GmbH & Co. KG


Armaturen- und Maschinenantriebe
P.O. Box 1362 D - 79373 Müllheim
Tel 07631/809-0 Fax 07631/13218
e-mail riester@auma.com
http://www.auma.com
DO 01.01.006GB / 1.99

S-ar putea să vă placă și