Documente Academic
Documente Profesional
Documente Cultură
6/9/2013 2:59 PM
EMCP 3.2
Parameter Value
ECM Part Number 2275801-05
ECM Serial Number 2966B190HQ
Software Group Part Number 3041337-00
Software Group Release Date OCT2006
Software Group Description L1_4_5_Standard -- English, 2.1 Prod, 26Oct2006
2436- 1 Generator Average AC Frequency : Low - most severe (3) 4 2932 3507
2436-
Generator Average AC Frequency : Low - least severe (1) 99 2924 2933
17
Generator Average Line-Line AC RMS Voltage : Low - most severe
2440- 1 93 2925 3825
(3)
2440- Generator Average Line-Line AC RMS Voltage : Low - least severe
99 2916 2931
17 (1)
2448- 0 Generator Average AC RMS Current : High - most severe (3) 1 3507 3507
2448-
Generator Average AC RMS Current : High - least severe (1) 99 6 3272
15
2648-
Maintenance Lamp 99 505 1181
31
4007-
Generator Control not in Automatic 99 0 537
31
Event Input Function #7 Event Notification Delay Time Disabled or Not Installed sec
Event Input Function #7 Active State Configuration Disabled or Not Installed
Event Input Function #8 Suspect Parameter Number Disabled or Not Installed
Event Input Function #8 Failure Mode Identifier Disabled or Not Installed
Event Input Function #8 Event Notification Delay Time Disabled or Not Installed sec
Event Input Function #8 Active State Configuration Disabled or Not Installed
Event Output Function #1 Suspect Parameter Number Engine Oil Pressure
Event Output Function #1 Trigger Condition **Disabled
Event Output Function #2 Suspect Parameter Number Disabled or Not Installed
Event Output Function #2 Trigger Condition Disabled or Not Installed
Event Output Function #3 Suspect Parameter Number Disabled or Not Installed
Event Output Function #3 Trigger Condition Disabled or Not Installed
Event Output Function #4 Suspect Parameter Number Disabled or Not Installed
Event Output Function #4 Trigger Condition Disabled or Not Installed
Event Output Function #5 Suspect Parameter Number Disabled or Not Installed
Event Output Function #5 Trigger Condition Disabled or Not Installed
Event Output Function #6 Suspect Parameter Number Disabled or Not Installed
Event Output Function #6 Trigger Condition Disabled or Not Installed
Event Output Function #7 Suspect Parameter Number Disabled or Not Installed
Event Output Function #7 Trigger Condition Disabled or Not Installed
Event Output Function #8 Suspect Parameter Number Disabled or Not Installed
Event Output Function #8 Trigger Condition Disabled or Not Installed
Accessory Data Link Diagnostic Response Configuration Activate Warning Condition
Accessory Data Link Diagnostic Audible Alert Yes
Accessory Data Link Diagnostic Breaker #1 Trip No
Accessory Data Link Diagnostic Breaker #2 Trip No
Air Filter Differential Pressure Sensor Diagnostic
Activate Warning Condition
Response Configuration
Air Filter Differential Pressure Sensor Diagnostic Audible
No
Alert
Air Filter Differential Pressure Sensor Diagnostic Breaker
No
#1 Trip
Air Filter Differential Pressure Sensor Diagnostic Breaker
No
#2 Trip
Ambient Air Temperature Sensor Diagnostic Response
Activate Warning Condition
Configuration
Ambient Air Temperature Sensor Diagnostic Audible Alert No
Ambient Air Temperature Sensor Diagnostic Breaker #1
No
Trip
Protection Timer
Low Air Filter Differential Pressure Shutdown Event Activate Hard Shutdown
Response Configuration Condition
Low Air Filter Differential Pressure Shutdown Event
Yes
Audible Alert
Low Air Filter Differential Pressure Shutdown Event
No
Breaker #1 Trip
Low Air Filter Differential Pressure Shutdown Event
No
Breaker #2 Trip
Low Air Filter Differential Pressure Shutdown Event Fault
Yes
Protection Timer
Activate Hard Shutdown
Emergency Stop Activated Event Response Configuration
Condition
Emergency Stop Activated Event Audible Alert Yes
Emergency Stop Activated Event Breaker #1 Trip No
Emergency Stop Activated Event Breaker #2 Trip No
High Engine Coolant Level Warning Event Response
Activate Warning Condition
Configuration
High Engine Coolant Level Warning Event Audible Alert Yes
High Engine Coolant Level Warning Event Breaker #1
No
Trip
High Engine Coolant Level Warning Event Breaker #2
No
Trip
High Engine Coolant Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Engine Coolant Level Shutdown Event Audible Alert Yes
High Engine Coolant Level Shutdown Event Breaker #1
No
Trip
High Engine Coolant Level Shutdown Event Breaker #2
No
Trip
Low Engine Coolant Level Warning Event Response
Activate Warning Condition
Configuration
Low Engine Coolant Level Warning Event Audible Alert Yes
Low Engine Coolant Level Warning Event Breaker #1
No
Trip
Low Engine Coolant Level Warning Event Breaker #2
No
Trip
Low Engine Coolant Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Engine Coolant Level Shutdown Event Audible Alert Yes
Trip
Low Engine Coolant Level Shutdown Event Breaker #2
No
Trip
High Engine Coolant Temperature Warning Event
Activate Warning Condition
Response Configuration
High Engine Coolant Temperature Warning Event
Yes
Audible Alert
High Engine Coolant Temperature Warning Event
No
Breaker #1 Trip
High Engine Coolant Temperature Warning Event
No
Breaker #2 Trip
High Engine Coolant Temperature Warning Event Fault
Yes
Protection Timer
High Engine Coolant Temperature Shutdown Event Activate Hard Shutdown
Response Configuration Condition
High Engine Coolant Temperature Shutdown Event
Yes
Audible Alert
High Engine Coolant Temperature Shutdown Event
No
Breaker #1 Trip
High Engine Coolant Temperature Shutdown Event
No
Breaker #2 Trip
High Engine Coolant Temperature Shutdown Event Fault
Yes
Protection Timer
Low Engine Coolant Temperature Warning Event
Activate Warning Condition
Response Configuration
Low Engine Coolant Temperature Warning Event Audible
Yes
Alert
Low Engine Coolant Temperature Warning Event Breaker
No
#1 Trip
Low Engine Coolant Temperature Warning Event Breaker
No
#2 Trip
Low Engine Coolant Temperature Warning Event Fault
No
Protection Timer
Engine Failure To Start Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Engine Failure To Start Shutdown Event Audible Alert Yes
Engine Failure To Start Shutdown Event Breaker #1 Trip No
Engine Failure To Start Shutdown Event Breaker #2 Trip No
High Engine Oil Level Warning Event Response
Activate Warning Condition
Configuration
High Engine Oil Level Warning Event Audible Alert Yes
Trip No
External Tank Low Fuel Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
External Tank Low Fuel Level Shutdown Event Audible
Yes
Alert
External Tank Low Fuel Level Shutdown Event Breaker
No
#1 Trip
External Tank Low Fuel Level Shutdown Event Breaker
No
#2 Trip
Fuel Leak Event Response Configuration Activate Warning Condition
Fuel Leak Event Audible Alert Yes
Fuel Leak Event Breaker #1 Trip No
Fuel Leak Event Breaker #2 Trip No
High Engine Oil Filter Differential Pressure Warning
Activate Warning Condition
Event Response Config
High Engine Oil Filter Differential Pressure Warning
Yes
Event Audible Alert
High Engine Oil Filter Differential Pressure Warning
No
Event Breaker #1 Trip
High Engine Oil Filter Differential Pressure Warning
No
Event Breaker #2 Trip
High Engine Oil Filter Differential Pressure Shutdown Activate Hard Shutdown
Event Response Config Condition
High Engine Oil Filter Differential Pressure Shutdown
Yes
Event Audible Alert
High Engine Oil Filter Differential Pressure Shutdown
No
Event Breaker #1 Trip
High Engine Oil Filter Differential Pressure Shutdown
No
Event Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Warning Event
Activate Warning Condition
Response Config
Low Engine Oil Filter Differential Pressure Warning Event
Yes
Audible Alert
Low Engine Oil Filter Differential Pressure Warning Event
No
Breaker #1 Trip
Low Engine Oil Filter Differential Pressure Warning Event
No
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Warning Fault
Yes
Protection Timer
Low Engine Oil Filter Differential Pressure Shutdown Activate Hard Shutdown
Event Response Config Condition
Breaker #2 Trip No
High Generator Bearing #1 Temperature Warning Event
No
Fault Protection Timer
High Generator Bearing #1 Temperature Shutdown Activate Hard Shutdown
Event Response Configuration Condition
High Generator Bearing #1 Temperature Shutdown
Yes
Event Audible Alert
High Generator Bearing #1 Temperature Shutdown
No
Event Breaker #1 Trip
High Generator Bearing #1 Temperature Shutdown
No
Event Breaker #2 Trip
High Generator Bearing #1 Temperature Shutdown
No
Event Fault Protection Timer
Low Generator Bearing #1 Temperature Warning Event
Activate Warning Condition
Response Configuration
Low Generator Bearing #1 Temperature Warning Event
Yes
Audible Alert
Low Generator Bearing #1 Temperature Warning Event
No
Breaker #1 Trip
Low Generator Bearing #1 Temperature Warning Event
No
Breaker #2 Trip
Low Generator Bearing #1 Temperature Warning Event
Yes
Fault Protection Timer
Low Generator Bearing #1 Temperature Shutdown
Disable Condition
Event Response Configuration
Low Generator Bearing #1 Temperature Shutdown
No
Event Audible Alert
Low Generator Bearing #1 Temperature Shutdown
No
Event Breaker #1 Trip
Low Generator Bearing #1 Temperature Shutdown
No
Event Breaker #2 Trip
Low Generator Bearing #1 Temperature Shutdown
No
Event Fault Protection Timer
Generator Overcurrent Warning Event Response
Activate Warning Condition
Configuration
Generator Overcurrent Warning Event Audible Alert Yes
Generator Overcurrent Warning Event Breaker #1 Trip No
Generator Overcurrent Warning Event Breaker #2 Trip No
Generator Overcurrent Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Generator Overcurrent Shutdown Event Audible Alert Yes
Trip
Generator Reverse Power Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Generator Reverse Power Shutdown Event Audible Alert Yes
Generator Reverse Power Shutdown Event Breaker #1
No
Trip
Generator Reverse Power Shutdown Event Breaker #2
No
Trip
Generator Over Voltage Warning Event Response
Activate Warning Condition
Configuration
Generator Over Voltage Warning Event Audible Alert Yes
Generator Over Voltage Warning Event Breaker #1 Trip No
Generator Over Voltage Warning Event Breaker #2 Trip No
Generator Over Voltage Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Generator Over Voltage Shutdown Event Audible Alert Yes
Generator Over Voltage Shutdown Event Breaker #1
No
Trip
Generator Over Voltage Shutdown Event Breaker #2
No
Trip
Generator Under Voltage Warning Event Response
Disable Condition
Configuration
Generator Under Voltage Warning Event Audible Alert Yes
Generator Under Voltage Warning Event Breaker #1 Trip No
Generator Under Voltage Warning Event Breaker #2 Trip No
Generator Under Voltage Warning Event Fault Protection
Yes
Timer
Generator Under Voltage Shutdown Event Response
Disable Condition
Configuration
Generator Under Voltage Shutdown Event Audible Alert Yes
Generator Under Voltage Shutdown Event Breaker #1
No
Trip
Generator Under Voltage Shutdown Event Breaker #2
No
Trip
Generator Under Voltage Shutdown Event Fault
Yes
Protection Timer
Activate Hard Shutdown
Earth Fault Event Response Configuration
Condition
Earth Fault Event Audible Alert Yes
Earth Fault Event Breaker #1 Trip No
Earth Fault Event Breaker #2 Trip No
Configuration
Custom Event #3 Condition Exists Event Audible Alert No
Custom Event #3 Condition Exists Event Loss of Utility No
Custom Event #3 Condition Exists Event Breaker #1 Trip No
Custom Event #3 Condition Exists Event Breaker #2 Trip No
Custom Event #3 Condition Exists Event Fault Protection
No
Timer
Custom Event #4 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #4 High Warning Event Audible Alert Yes
Custom Event #4 High Warning Event Breaker #1 Trip No
Custom Event #4 High Warning Event Breaker #2 Trip No
Custom Event #4 High Warning Event Fault Protection
No
Timer
Custom Event #4 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #4 High Shutdown Event Audible Alert Yes
Custom Event #4 High Shutdown Event Breaker #1 Trip No
Custom Event #4 High Shutdown Event Breaker #2 Trip No
Custom Event #4 High Shutdown Event Fault Protection
No
Timer
Custom Event #4 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #4 Low Warning Event Audible Alert Yes
Custom Event #4 Low Warning Event Breaker #1 Trip No
Custom Event #4 Low Warning Event Breaker #2 Trip No
Custom Event #4 Low Warning Event Fault Protection
No
Timer
Custom Event #4 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #4 Low Shutdown Event Audible Alert Yes
Custom Event #4 Low Shutdown Event Breaker #1 Trip No
Custom Event #4 Low Shutdown Event Breaker #2 Trip No
Custom Event #4 Low Shutdown Event Fault Protection
No
Timer
Custom Event #4 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #4 Condition Exists Event Audible Alert No
Custom Event #4 Condition Exists Event Loss of Utility No
Custom Event #4 Condition Exists Event Breaker #1 Trip No
Configuration
Custom Event #6 High Warning Event Audible Alert Yes
Custom Event #6 High Warning Event Breaker #1 Trip No
Custom Event #6 High Warning Event Breaker #2 Trip No
Custom Event #6 High Warning Event Fault Protection
No
Timer
Custom Event #6 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #6 High Shutdown Event Audible Alert Yes
Custom Event #6 High Shutdown Event Breaker #1 Trip No
Custom Event #6 High Shutdown Event Breaker #2 Trip No
Custom Event #6 High Shutdown Event Fault Protection
No
Timer
Custom Event #6 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #6 Low Warning Event Audible Alert Yes
Custom Event #6 Low Warning Event Breaker #1 Trip No
Custom Event #6 Low Warning Event Breaker #2 Trip No
Custom Event #6 Low Warning Event Fault Protection
No
Timer
Custom Event #6 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #6 Low Shutdown Event Audible Alert Yes
Custom Event #6 Low Shutdown Event Breaker #1 Trip No
Custom Event #6 Low Shutdown Event Breaker #2 Trip No
Custom Event #6 Low Shutdown Event Fault Protection
No
Timer
Custom Event #6 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #6 Condition Exists Event Audible Alert No
Custom Event #6 Condition Exists Event Loss of Utility No
Custom Event #6 Condition Exists Event Breaker #1 Trip No
Custom Event #6 Condition Exists Event Breaker #2 Trip No
Custom Event #6 Condition Exists Event Fault Protection
No
Timer
Custom Event #7 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #7 High Warning Event Audible Alert Yes
Custom Event #7 High Warning Event Breaker #1 Trip No
Custom Event #7 High Warning Event Breaker #2 Trip No
Configuration Unavailable
Programmable Cycle Timer #8 Output #2 Activation
Unavailable
Configuration
Programmable Cycle Timer #9 Activation Day of Week Unavailable
Programmable Cycle Timer #9 Activation Start Time Unavailable min
Programmable Cycle Timer #9 Active Time Unavailable min
Programmable Cycle Timer #9 Output #1 Activation
Unavailable
Configuration
Programmable Cycle Timer #9 Output #2 Activation
Unavailable
Configuration
Programmable Cycle Timer #10 Activation Day of Week Unavailable
Programmable Cycle Timer #10 Activation Start Time Unavailable min
Programmable Cycle Timer #10 Active Time Unavailable min
Programmable Cycle Timer #10 Output #1 Activation
Unavailable
Configuration
Programmable Cycle Timer #10 Output #2 Activation
Unavailable
Configuration
Programmable Cycle Timer #11 Activation Day of Week Unavailable
Programmable Cycle Timer #11 Activation Start Time Unavailable min
Programmable Cycle Timer #11 Active Time Unavailable min
Programmable Cycle Timer #11 Output #1 Activation
Unavailable
Configuration
Programmable Cycle Timer #11 Output #2 Activation
Unavailable
Configuration
Programmable Cycle Timer #12 Activation Day of Week Unavailable
Programmable Cycle Timer #12 Activation Start Time Unavailable min
Programmable Cycle Timer #12 Active Time Unavailable min
Programmable Cycle Timer #12 Output #1 Activation
Unavailable
Configuration
Programmable Cycle Timer #12 Output #2 Activation
Unavailable
Configuration
Programmable Cycle Timer #13 Activation Day of Week Unavailable
Programmable Cycle Timer #13 Activation Start Time Unavailable min
Programmable Cycle Timer #13 Active Time Unavailable min
Programmable Cycle Timer #13 Output #1 Activation
Unavailable
Configuration
Programmable Cycle Timer #13 Output #2 Activation
Unavailable
Configuration
Programmable Cycle Timer #14 Activation Day of Week Unavailable
Programmable Cycle Timer #14 Activation Start Time Unavailable min
Threshold 10 %
Spare Analog Input Low Temperature Warning Event Deg
68
Threshold F
Spare Analog Input Low Pressure Warning Event
15 psi
Threshold
Spare Analog Input Low Warning Event Notification
15 sec
Delay Time
Spare Analog Input Low Shutdown Event Percentage
5 %
Threshold
Spare Analog Input Low Temperature Shutdown Event Deg
32
Threshold F
Spare Analog Input Low Pressure Shutdown Event
11 psi
Threshold
Spare Analog Input Low Shutdown Event Notification
30 sec
Delay Time
Spare Analog Input Sensor Configuration Code Map #1
Programmable Trip Point Function #1 Trigger Condition Trip Above Threshold
Programmable Trip Point Function #1 Percentage
90 %
Threshold
Programmable Trip Point Function #1 Hysteresis
5 %
Percentage
Programmable Trip Point Function #1 Trip Activation
10 sec
Delay Time
Programmable Trip Point Function #1 Trip Deactivation
1 sec
Delay Time
Programmable Trip Point Function #2 Trigger Condition Disabled or Not Installed
Programmable Trip Point Function #2 Percentage
-1 %
Threshold
Programmable Trip Point Function #2 Hysteresis
Disabled or Not Installed %
Percentage
Programmable Trip Point Function #2 Trip Activation
Disabled or Not Installed sec
Delay Time
Programmable Trip Point Function #2 Trip Deactivation
Disabled or Not Installed sec
Delay Time
Programmable Trip Point Function #3 Trigger Condition Disabled or Not Installed
Programmable Trip Point Function #3 Percentage
-1 %
Threshold
Programmable Trip Point Function #3 Hysteresis
Disabled or Not Installed %
Percentage
Programmable Trip Point Function #3 Trip Activation
Disabled or Not Installed sec
Delay Time
Lifetime: Time vs Engine Speed And Engine Load Factor - C27 Genset (MJE00283)
1100- 1300- 1500- 1700- 1900- 2100-
rpm <1100 >2300 Total
1299 1499 1699 1899 2099 2299
%
<50 0.04 0.06 0.01 0.00 98.81 0.00 0.00 0.00 98.92
50-
0.00 0.00 0.00 0.00 0.92 0.00 0.00 0.00 0.92
60
60-
0.00 0.00 0.00 0.00 0.02 0.00 0.00 0.00 0.02
70
70-
0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
80
80-
0.00 0.00 0.00 0.00 0.02 0.00 0.00 0.00 0.02
90
>90 0.00 0.00 0.00 0.04 0.07 0.00 0.00 0.00 0.11
Total 0.04 0.06 0.01 0.04 99.85 0.00 0.00 0.00 100.00