Sunteți pe pagina 1din 56

Page 1 of 56

Caterpillar Electronic Technician 2012A v1.0


Product Status Report

6/9/2013 2:59 PM

Product Status Report


Parameter Value
Engine Serial Number MJE00283
Equipment ID NOT PROGRAMMED
Comments

EMCP 3.2
Parameter Value
ECM Part Number 2275801-05
ECM Serial Number 2966B190HQ
Software Group Part Number 3041337-00
Software Group Release Date OCT2006
Software Group Description L1_4_5_Standard -- English, 2.1 Prod, 26Oct2006

Logged Diagnostic Codes [Diagnostic Clock = Unavailable hours] - EMCP 3.2


Code Description Occ. First Last
1383-11 Engine was Shut Down Hot : Other Failure Mode 1 3504 3504

Logged Event Codes [Diagnostic Clock = Unavailable hours] - EMCP 3.2


Code Description Occ. First Last
110- 0 Engine Coolant Temperature : High - most severe (3) 4 3874 3874
110-15 Engine Coolant Temperature : High - least severe (1) 27 3874 3874
110-17 Engine Coolant Temperature : Low - least severe (1) 35 783 3883
168-15 Battery Potential / Power Input #1 : High - least severe (1) 99 6 1758
190- 1 Engine Speed : Low - most severe (3) 3 3087 3507
190-17 Engine Speed : Low - least severe (1) 10 2932 3507
970-31 Engine Auxiliary Engine Shutdown Switch 38 1025 4792

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 2 of 56

2436- 1 Generator Average AC Frequency : Low - most severe (3) 4 2932 3507
2436-
Generator Average AC Frequency : Low - least severe (1) 99 2924 2933
17
Generator Average Line-Line AC RMS Voltage : Low - most severe
2440- 1 93 2925 3825
(3)
2440- Generator Average Line-Line AC RMS Voltage : Low - least severe
99 2916 2931
17 (1)
2448- 0 Generator Average AC RMS Current : High - most severe (3) 1 3507 3507
2448-
Generator Average AC RMS Current : High - least severe (1) 99 6 3272
15
2648-
Maintenance Lamp 99 505 1181
31
4007-
Generator Control not in Automatic 99 0 537
31

Active Diagnostic Codes - EMCP 3.2


Code Description
No Active Codes

Active Event Codes - EMCP 3.2


Code Description
2648-31 Maintenance Lamp
4007-31 Generator Control not in Automatic

Current Totals - EMCP 3.2


Description Value Unit
Total Operating Hours Unavailable hours
Generator Total kW Hours Export Unavailable KW-hr

Configuration - EMCP 3.2


Description Value Unit
Engine Start Fault Protection Activation Delay Time 30 sec
Crank Duration 10 sec
Crank Cycle Rest Interval 10 sec

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 3 of 56

Engine Purge Cycle Time 0 sec


Maximum Number of Crank Cycles 5
Cooldown Duration 5 min
Start Aid Activation Time 0 sec
Crank Alert Activation Time 0 sec
Crank Terminate RPM 400 rpm
Engine Fuel Type Configuration Diesel
Fuel Shutoff Solenoid Type Configuration Energized to Run
Engine Type Configuration Electronic
Engine Controller J1939 Data Link Support Configuration Proprietary J1939 Support
Engine Cooldown Speed Configuration Rated Speed
Engine Operating State Input Configuration CAN Input
Fuel Priming Feature Enable Status Disabled
Engine Forced Idle Feature Enable Status Enabled
Maximum Generator Voltage Output Bias Percentage 5 %
Generator Nominal Output Voltage 480 Volts
High Battery Voltage Warning Event Threshold 29.4 Volts
High Battery Voltage Warning Event Notification Delay
30 sec
Time
High Battery Voltage Shutdown Event Threshold 32.0 Volts
High Battery Voltage Shutdown Event Notification Delay
2 sec
Time
Low Battery Voltage Warning Event Threshold 18.0 Volts
Low Battery Voltage Warning Event Notification Delay
10 sec
Time
Low Battery Charging System Voltage Warning Event
24.5 Volts
Threshold
Low Battery Charging System Voltage Warning Event
30 sec
Notification Delay Time
Customer Password Security Level to Reset Crank/Start
3-Factory, Single Use
Counters
SCADA Data Link Baud Rate 19200 baud
SCADA Data Link Parity None
SCADA Data Link Slave Address 1
SCADA Data Link Access Password 00000000
SCADA Data Link Connection Timeout Interval 30.0 sec
RS-485 Bias Resistor Enable Status Enabled
Digital Input #1 Active State Configuration High
Digital Input #2 Active State Configuration Low

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 4 of 56

Digital Input #3 Active State Configuration Low


Digital Input #4 Active State Configuration Low
Digital Input #5 Active State Configuration Low
Digital Input #6 Active State Configuration Low
Digital Input #7 Active State Configuration Low
Digital Input #8 Active State Configuration Low
Digital Output #1 Active State Configuration Low
Digital Selector #1 Source Configuration Input #2
Digital Selector #2 Source Configuration Input #4
Digital Selector #3 Source Configuration Input #4
Digital Selector #4 Source Configuration Input #6
Digital Selector #5 Source Configuration Input #5
Digital Selector #6 Source Configuration Input #5
Digital Selector #7 Source Configuration Input #1
Digital Selector #8 Source Configuration Disabled or Not Installed
Digital Selector #9 Source Configuration Disabled or Not Installed
Digital Selector #10 Source Configuration Disabled or Not Installed
Engine Coolant Temperature Sensor Configuration Data Link
High Engine Coolant Temperature Warning Event Deg
216
Threshold F
High Engine Coolant Temperature Warning Event
2 sec
Notification Delay Time
High Engine Coolant Temperature Shutdown Event Deg
225
Threshold F
High Engine Coolant Temperature Shutdown Event
10 sec
Notification Delay Time
Low Engine Coolant Temperature Warning Event Deg
32
Threshold F
Low Engine Coolant Temperature Warning Event
30 sec
Notification Delay Time
Engine Coolant Temperature Sensor Configuration Code Map #1
Engine Oil Pressure Sensor Configuration Data Link
Low Engine Oil Pressure Warning Event Threshold 35 psi
Low Idle Low Engine Oil Pressure Warning Event
15 psi
Threshold
Low Engine Oil Pressure Warning Event Notification
0 sec
Delay Time
Low Engine Oil Pressure Shutdown Event Threshold 30 psi
Low Idle Low Engine Oil Pressure Shutdown Event
10 psi
Threshold

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 5 of 56

Low Engine Oil Pressure Shutdown Event Notification


0 sec
Delay Time
Low Engine Oil Pressure Step Speed 1200 rpm
Engine Oil Pressure Sensor Configuration Code Map #1
Flywheel Teeth 136
Engine Overspeed Setpoint 2124 rpm
Engine Underspeed Warning Event Threshold 1548 rpm
Engine Underspeed Warning Event Notification Delay
2.0 sec
Time
Engine Underspeed Shutdown Event Threshold 1476 rpm
Engine Underspeed Shutdown Event Notification Delay
2.0 sec
Time
Engine Speed Sensor Configuration Sensor
Event Input Function #1 Suspect Parameter Number Earth Fault
Event Input Function #1 Failure Mode Identifier Condition Exists
Event Input Function #1 Event Notification Delay Time 10 sec
Event Input Function #1 Active State Configuration High
Event Input Function #2 Suspect Parameter Number Custom Event
Event Input Function #2 Failure Mode Identifier Condition Exists
Event Input Function #2 Event Notification Delay Time 0 sec
Event Input Function #2 Active State Configuration High
Event Input Function #3 Suspect Parameter Number Custom Event
Event Input Function #3 Failure Mode Identifier Condition Exists
Event Input Function #3 Event Notification Delay Time 0 sec
Event Input Function #3 Active State Configuration High
Event Input Function #4 Suspect Parameter Number Battery Charger Failure
Event Input Function #4 Failure Mode Identifier Condition Exists
Event Input Function #4 Event Notification Delay Time 0 sec
Event Input Function #4 Active State Configuration High
Event Input Function #5 Suspect Parameter Number Custom Event
Event Input Function #5 Failure Mode Identifier Condition Exists
Event Input Function #5 Event Notification Delay Time 0 sec
Event Input Function #5 Active State Configuration High
Event Input Function #6 Suspect Parameter Number Custom Event
Event Input Function #6 Failure Mode Identifier Condition Exists
Event Input Function #6 Event Notification Delay Time 0 sec
Event Input Function #6 Active State Configuration High
Event Input Function #7 Suspect Parameter Number Disabled or Not Installed
Event Input Function #7 Failure Mode Identifier Disabled or Not Installed

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 6 of 56

Event Input Function #7 Event Notification Delay Time Disabled or Not Installed sec
Event Input Function #7 Active State Configuration Disabled or Not Installed
Event Input Function #8 Suspect Parameter Number Disabled or Not Installed
Event Input Function #8 Failure Mode Identifier Disabled or Not Installed
Event Input Function #8 Event Notification Delay Time Disabled or Not Installed sec
Event Input Function #8 Active State Configuration Disabled or Not Installed
Event Output Function #1 Suspect Parameter Number Engine Oil Pressure
Event Output Function #1 Trigger Condition **Disabled
Event Output Function #2 Suspect Parameter Number Disabled or Not Installed
Event Output Function #2 Trigger Condition Disabled or Not Installed
Event Output Function #3 Suspect Parameter Number Disabled or Not Installed
Event Output Function #3 Trigger Condition Disabled or Not Installed
Event Output Function #4 Suspect Parameter Number Disabled or Not Installed
Event Output Function #4 Trigger Condition Disabled or Not Installed
Event Output Function #5 Suspect Parameter Number Disabled or Not Installed
Event Output Function #5 Trigger Condition Disabled or Not Installed
Event Output Function #6 Suspect Parameter Number Disabled or Not Installed
Event Output Function #6 Trigger Condition Disabled or Not Installed
Event Output Function #7 Suspect Parameter Number Disabled or Not Installed
Event Output Function #7 Trigger Condition Disabled or Not Installed
Event Output Function #8 Suspect Parameter Number Disabled or Not Installed
Event Output Function #8 Trigger Condition Disabled or Not Installed
Accessory Data Link Diagnostic Response Configuration Activate Warning Condition
Accessory Data Link Diagnostic Audible Alert Yes
Accessory Data Link Diagnostic Breaker #1 Trip No
Accessory Data Link Diagnostic Breaker #2 Trip No
Air Filter Differential Pressure Sensor Diagnostic
Activate Warning Condition
Response Configuration
Air Filter Differential Pressure Sensor Diagnostic Audible
No
Alert
Air Filter Differential Pressure Sensor Diagnostic Breaker
No
#1 Trip
Air Filter Differential Pressure Sensor Diagnostic Breaker
No
#2 Trip
Ambient Air Temperature Sensor Diagnostic Response
Activate Warning Condition
Configuration
Ambient Air Temperature Sensor Diagnostic Audible Alert No
Ambient Air Temperature Sensor Diagnostic Breaker #1
No
Trip

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 7 of 56

Ambient Air Temperature Sensor Diagnostic Breaker #2


No
Trip
Digital Output #1 Diagnostic Response Configuration Activate Warning Condition
Digital Output #1 Diagnostic Audible Alert No
Digital Output #1 Diagnostic Breaker #1 Trip No
Digital Output #1 Diagnostic Breaker #2 Trip No
Engine Coolant Level Sensor Diagnostic Response
Activate Warning Condition
Configuration
Engine Coolant Level Sensor Diagnostic Audible Alert No
Engine Coolant Level Sensor Diagnostic Breaker #1 Trip No
Engine Coolant Level Sensor Diagnostic Breaker #2 Trip No
Engine Coolant Temperature Sensor Diagnostic
Activate Warning Condition
Response Configuration
Engine Coolant Temperature Sensor Diagnostic Audible
No
Alert
Engine Coolant Temperature Sensor Diagnostic Breaker
No
#1 Trip
Engine Coolant Temperature Sensor Diagnostic Breaker
No
#2 Trip
Engine Oil Level Sensor Diagnostic Response
Activate Warning Condition
Configuration
Engine Oil Level Sensor Diagnostic Audible Alert No
Engine Oil Level Sensor Diagnostic Breaker #1 Trip No
Engine Oil Level Sensor Diagnostic Breaker #2 Trip No
Engine Oil Pressure Sensor Diagnostic Response
Activate Warning Condition
Configuration
Engine Oil Pressure Sensor Diagnostic Audible Alert No
Engine Oil Pressure Sensor Diagnostic Breaker #1 Trip No
Engine Oil Pressure Sensor Diagnostic Breaker #2 Trip No
Engine Oil Temperature Sensor Diagnostic Response
Activate Warning Condition
Configuration
Engine Oil Temperature Sensor Diagnostic Audible Alert No
Engine Oil Temperature Sensor Diagnostic Breaker #1
No
Trip
Engine Oil Temperature Sensor Diagnostic Breaker #2
No
Trip
Activate Hard Shutdown
Engine Speed Sensor Diagnostic Response Configuration
Condition
Engine Speed Sensor Diagnostic Audible Alert Yes
Engine Speed Sensor Diagnostic Breaker #1 Trip No

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 8 of 56

Engine Speed Sensor Diagnostic Breaker #2 Trip No


Exhaust Temperature Sensor Diagnostic Response
Activate Warning Condition
Configuration
Exhaust Temperature Sensor Diagnostic Audible Alert No
Exhaust Temperature Sensor Diagnostic Breaker #1 Trip No
Exhaust Temperature Sensor Diagnostic Breaker #2 Trip No
Right Exhaust Temperature Sensor Diagnostic Response
Activate Warning Condition
Configuration
Right Exhaust Temperature Sensor Diagnostic Audible
No
Alert
Right Exhaust Temperature Sensor Diagnostic Breaker
No
#1 Trip
Right Exhaust Temperature Sensor Diagnostic Breaker
No
#2 Trip
Left Exhaust Temperature Sensor Diagnostic Response
Activate Warning Condition
Configuration
Left Exhaust Temperature Sensor Diagnostic Audible
No
Alert
Left Exhaust Temperature Sensor Diagnostic Breaker #1
No
Trip
Left Exhaust Temperature Sensor Diagnostic Breaker #2
No
Trip
Fire Extinguisher Pressure Sensor Diagnostic Response
Activate Warning Condition
Configuration
Fire Extinguisher Pressure Sensor Audible Alert No
Fire Extinguisher Pressure Sensor Breaker #1 Trip No
Fire Extinguisher Pressure Sensor Breaker #2 Trip No
Fuel Filter Differential Pressure Sensor Diagnostic
Activate Warning Condition
Response Configuration
Fuel Filter Differential Pressure Sensor Diagnostic
No
Audible Alert
Fuel Filter Differential Pressure Sensor Diagnostic
No
Breaker #1 Trip
Fuel Filter Differential Pressure Sensor Diagnostic
No
Breaker #2 Trip
Fuel Level Sensor Diagnostic Response Configuration Activate Warning Condition
Fuel Level Sensor Diagnostic Audible Alert No
Fuel Level Sensor Diagnostic Breaker #1 Trip No
Fuel Level Sensor Diagnostic Breaker #2 Trip No
External Tank Fuel Level Sensor Diagnostic Response
Activate Warning Condition
Configuration

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 9 of 56

External Tank Fuel Level Sensor Diagnostic Audible Alert No


External Tank Fuel Level Sensor Diagnostic Breaker #1
No
Trip
External Tank Fuel Level Sensor Diagnostic Breaker #2
No
Trip
Generator Bearing #1 Temperature Sensor Diagnostic
Activate Warning Condition
Response Configuration
Generator Bearing #1 Temperature Sensor Diagnostic
No
Audible Alert
Generator Bearing #1 Temperature Sensor Diagnostic
No
Breaker #1 Trip
Generator Bearing #1 Temperature Sensor Diagnostic
No
Breaker #2 Trip
Generator Output Sensing System Diagnostic Response
Activate Warning Condition
Configuration
Generator Output Sensing System Diagnostic Audible
Yes
Alert
Generator Output Sensing System Diagnostic Breaker #1
No
Trip
Generator Output Sensing System Diagnostic Breaker #2
No
Trip
Engine Oil Filter Differential Pressure Sensor Diagnostic
Activate Warning Condition
Response Config
Engine Oil Filter Differential Pressure Sensor Diagnostic
No
Audible Alert
Engine Oil Filter Differential Pressure Sensor Diagnostic
No
Breaker #1 Trip
Engine Oil Filter Differential Pressure Sensor Diagnostic
No
Breaker #2 Trip
Primary Data Link Diagnostic Response Configuration Activate Warning Condition
Primary Data Link Diagnostic Audible Alert No
Primary Data Link Diagnostic Breaker #1 Trip No
Primary Data Link Diagnostic Breaker #2 Trip No
SCADA Data Link Diagnostic Response Configuration Activate Warning Condition
SCADA Data Link Diagnostic Audible Alert No
SCADA Data Link Diagnostic Breaker #1 Trip No
SCADA Data Link Diagnostic Breaker #2 Trip No
SCADA Data Link Diagnostic Fault Protection Timer No
Starting Air Pressure Sensor Diagnostic Response
Activate Warning Condition
Configuration
Starting Air Pressure Sensor Diagnostic Audible Alert No

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 10 of 56

Starting Air Pressure Sensor Diagnostic Breaker #1 Trip No


Starting Air Pressure Sensor Diagnostic Breaker #2 Trip No
Battery Charger Failure Diagnostic Response
Activate Warning Condition
Configuration
Battery Charger Failure Diagnostic Audible Alert Yes
Engine Controller Not Responding Diagnostic Response
Activate Warning Condition
Configuration
Engine Controller Not Responding Diagnostic Audible
No
Alert
Engine Controller Not Responding Diagnostic Breaker #1
No
Trip
Engine Controller Not Responding Diagnostic Breaker #2
No
Trip
Hard Shutdown & Active
Air Damper Closed Event Response Configuration
Only Condition
Air Damper Closed Event Audible Alert Yes
High Air Filter Differential Pressure Warning Event
Activate Warning Condition
Response Configuration
High Air Filter Differential Pressure Warning Event
Yes
Audible Alert
High Air Filter Differential Pressure Warning Event
No
Breaker #1 Trip
High Air Filter Differential Pressure Warning Event
No
Breaker #2 Trip
High Air Filter Differential Pressure Shutdown Event Activate Hard Shutdown
Response Configuration Condition
High Air Filter Differential Pressure Shutdown Event
Yes
Audible Alert
High Air Filter Differential Pressure Shutdown Event
No
Breaker #1 Trip
High Air Filter Differential Pressure Shutdown Event
No
Breaker #2 Trip
Low Air Filter Differential Pressure Warning Event
Activate Warning Condition
Response Configuration
Low Air Filter Differential Pressure Warning Event
Yes
Audible Alert
Low Air Filter Differential Pressure Warning Event
No
Breaker #1 Trip
Low Air Filter Differential Pressure Warning Event
No
Breaker #2 Trip
Yes
Low Air Filter Differential Pressure Warning Event Fault

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 11 of 56

Protection Timer
Low Air Filter Differential Pressure Shutdown Event Activate Hard Shutdown
Response Configuration Condition
Low Air Filter Differential Pressure Shutdown Event
Yes
Audible Alert
Low Air Filter Differential Pressure Shutdown Event
No
Breaker #1 Trip
Low Air Filter Differential Pressure Shutdown Event
No
Breaker #2 Trip
Low Air Filter Differential Pressure Shutdown Event Fault
Yes
Protection Timer
Activate Hard Shutdown
Emergency Stop Activated Event Response Configuration
Condition
Emergency Stop Activated Event Audible Alert Yes
Emergency Stop Activated Event Breaker #1 Trip No
Emergency Stop Activated Event Breaker #2 Trip No
High Engine Coolant Level Warning Event Response
Activate Warning Condition
Configuration
High Engine Coolant Level Warning Event Audible Alert Yes
High Engine Coolant Level Warning Event Breaker #1
No
Trip
High Engine Coolant Level Warning Event Breaker #2
No
Trip
High Engine Coolant Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Engine Coolant Level Shutdown Event Audible Alert Yes
High Engine Coolant Level Shutdown Event Breaker #1
No
Trip
High Engine Coolant Level Shutdown Event Breaker #2
No
Trip
Low Engine Coolant Level Warning Event Response
Activate Warning Condition
Configuration
Low Engine Coolant Level Warning Event Audible Alert Yes
Low Engine Coolant Level Warning Event Breaker #1
No
Trip
Low Engine Coolant Level Warning Event Breaker #2
No
Trip
Low Engine Coolant Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Engine Coolant Level Shutdown Event Audible Alert Yes

Low Engine Coolant Level Shutdown Event Breaker #1 No

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 12 of 56

Trip
Low Engine Coolant Level Shutdown Event Breaker #2
No
Trip
High Engine Coolant Temperature Warning Event
Activate Warning Condition
Response Configuration
High Engine Coolant Temperature Warning Event
Yes
Audible Alert
High Engine Coolant Temperature Warning Event
No
Breaker #1 Trip
High Engine Coolant Temperature Warning Event
No
Breaker #2 Trip
High Engine Coolant Temperature Warning Event Fault
Yes
Protection Timer
High Engine Coolant Temperature Shutdown Event Activate Hard Shutdown
Response Configuration Condition
High Engine Coolant Temperature Shutdown Event
Yes
Audible Alert
High Engine Coolant Temperature Shutdown Event
No
Breaker #1 Trip
High Engine Coolant Temperature Shutdown Event
No
Breaker #2 Trip
High Engine Coolant Temperature Shutdown Event Fault
Yes
Protection Timer
Low Engine Coolant Temperature Warning Event
Activate Warning Condition
Response Configuration
Low Engine Coolant Temperature Warning Event Audible
Yes
Alert
Low Engine Coolant Temperature Warning Event Breaker
No
#1 Trip
Low Engine Coolant Temperature Warning Event Breaker
No
#2 Trip
Low Engine Coolant Temperature Warning Event Fault
No
Protection Timer
Engine Failure To Start Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Engine Failure To Start Shutdown Event Audible Alert Yes
Engine Failure To Start Shutdown Event Breaker #1 Trip No
Engine Failure To Start Shutdown Event Breaker #2 Trip No
High Engine Oil Level Warning Event Response
Activate Warning Condition
Configuration
High Engine Oil Level Warning Event Audible Alert Yes

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 13 of 56

High Engine Oil Level Warning Event Breaker #1 Trip No


High Engine Oil Level Warning Event Breaker #2 Trip No
High Engine Oil Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Engine Oil Level Shutdown Event Audible Alert Yes
High Engine Oil Level Shutdown Event Breaker #1 Trip No
High Engine Oil Level Shutdown Event Breaker #2 Trip No
Low Engine Oil Level Warning Event Response
Activate Warning Condition
Configuration
Low Engine Oil Level Warning Event Audible Alert Yes
Low Engine Oil Level Warning Event Breaker #1 Trip No
Low Engine Oil Level Warning Event Breaker #2 Trip No
Low Engine Oil Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Engine Oil Level Shutdown Event Audible Alert Yes
Low Engine Oil Level Shutdown Event Breaker #1 Trip No
Low Engine Oil Level Shutdown Event Breaker #2 Trip No
Low Engine Oil Pressure Warning Event Response
Activate Warning Condition
Configuration
Low Engine Oil Pressure Warning Event Audible Alert Yes
Low Engine Oil Pressure Warning Event Breaker #1 Trip No
Low Engine Oil Pressure Warning Event Breaker #2 Trip No
Low Engine Oil Pressure Warning Event Fault Protection
Yes
Timer
Low Engine Oil Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Engine Oil Pressure Shutdown Event Audible Alert Yes
Low Engine Oil Pressure Shutdown Event Breaker #1
No
Trip
Low Engine Oil Pressure Shutdown Event Breaker #2
No
Trip
Low Engine Oil Pressure Shutdown Event Fault
Yes
Protection Timer
High Engine Oil Temperature Warning Event Response
Activate Warning Condition
Configuration
High Engine Oil Temperature Warning Event Audible
Yes
Alert
High Engine Oil Temperature Warning Event Breaker #1
No
Trip
High Engine Oil Temperature Warning Event Breaker #2
No
Trip

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 14 of 56

High Engine Oil Temperature Warning Event Fault


No
Protection Timer
High Engine Oil Temperature Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Engine Oil Temperature Shutdown Event Audible
Yes
Alert
High Engine Oil Temperature Shutdown Event Breaker
No
#1 Trip
High Engine Oil Temperature Shutdown Event Breaker
No
#2 Trip
High Engine Oil Temperature Shutdown Event Fault
No
Protection Timer
Low Engine Oil Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Engine Oil Temperature Warning Event Audible
Yes
Alert
Low Engine Oil Temperature Warning Event Breaker #1
No
Trip
Low Engine Oil Temperature Warning Event Breaker #2
No
Trip
Low Engine Oil Temperature Warning Event Fault
Yes
Protection Timer
Low Engine Oil Temperature Shutdown Event Response
Disable Condition
Configuration
Low Engine Oil Temperature Shutdown Event Audible
No
Alert
Low Engine Oil Temperature Shutdown Event Breaker
No
#1 Trip
Low Engine Oil Temperature Shutdown Event Breaker
No
#2 Trip
Low Engine Oil Temperature Shutdown Event Fault
No
Protection Timer
Unexpected Engine Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Unexpected Engine Shutdown Event Audible Alert Yes
Unexpected Engine Shutdown Event Breaker #1 Trip No
Unexpected Engine Shutdown Event Breaker #2 Trip No
Engine Overspeed Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Engine Overspeed Shutdown Event Audible Alert Yes
Engine Overspeed Shutdown Event Breaker #1 Trip No

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 15 of 56

Engine Overspeed Shutdown Event Breaker #2 Trip No


Engine Underspeed Warning Event Response
Disable Condition
Configuration
Engine Underspeed Warning Event Audible Alert Yes
Engine Underspeed Warning Event Breaker #1 Trip No
Engine Underspeed Warning Event Breaker #2 Trip No
Engine Underspeed Warning Event Fault Protection
Yes
Timer
Engine Underspeed Shutdown Event Response
Disable Condition
Configuration
Engine Underspeed Shutdown Event Audible Alert Yes
Engine Underspeed Shutdown Event Breaker #1 Trip No
Engine Underspeed Shutdown Event Breaker #2 Trip No
Engine Underspeed Shutdown Event Fault Protection
Yes
Timer
High Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
High Exhaust Temperature Warning Event Audible Alert Yes
High Exhaust Temperature Warning Event Breaker #1
No
Trip
High Exhaust Temperature Warning Event Breaker #2
No
Trip
High Exhaust Temperature Warning Event Fault
No
Protection Timer
High Exhaust Temperature Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Exhaust Temperature Shutdown Event Audible Alert Yes
High Exhaust Temperature Shutdown Event Breaker #1
No
Trip
High Exhaust Temperature Shutdown Event Breaker #2
No
Trip
High Exhaust Temperature Shutdown Event Fault
No
Protection Timer
Low Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Exhaust Temperature Warning Event Audible Alert Yes
Low Exhaust Temperature Warning Event Breaker #1
No
Trip
Low Exhaust Temperature Warning Event Breaker #2
No
Trip

Low Exhaust Temperature Warning Event Fault

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 16 of 56

Protection Timer Yes


Low Exhaust Temperature Shutdown Event Response
Disable Condition
Configuration
Low Exhaust Temperature Shutdown Event Audible Alert No
Low Exhaust Temperature Shutdown Event Breaker #1
No
Trip
Low Exhaust Temperature Shutdown Event Breaker #2
No
Trip
Low Exhaust Temperature Shutdown Event Fault
Yes
Protection Timer
High Right Exhaust Temperature Warning Event
Activate Warning Condition
Response Configuration
High Right Exhaust Temperature Warning Event Audible
Yes
Alert
High Right Exhaust Temperature Warning Event Breaker
No
#1 Trip
High Right Exhaust Temperature Warning Event Breaker
No
#2 Trip
High Right Exhaust Temperature Warning Event Fault
No
Protection Timer
High Right Exhaust Temperature Shutdown Event Activate Hard Shutdown
Response Configuration Condition
High Right Exhaust Temperature Shutdown Event
Yes
Audible Alert
High Right Exhaust Temperature Shutdown Event
No
Breaker #1 Trip
High Right Exhaust Temperature Shutdown Event
No
Breaker #2 Trip
High Right Exhaust Temperature Shutdown Event Fault
No
Protection Timer
Low Right Exhaust Temperature Warning Event
Activate Warning Condition
Response Configuration
Low Right Exhaust Temperature Warning Event Audible
Yes
Alert
Low Right Exhaust Temperature Warning Event Breaker
No
#1 Trip
Low Right Exhaust Temperature Warning Event Breaker
No
#2 Trip
Low Right Exhaust Temperature Warning Event Fault
Yes
Protection Timer
Low Right Exhaust Temperature Shutdown Event
Disable Condition
Response Configuration

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 17 of 56

Low Right Exhaust Temperature Shutdown Event


No
Audible Alert
Low Right Exhaust Temperature Shutdown Event
No
Breaker #1 Trip
Low Right Exhaust Temperature Shutdown Event
No
Breaker #2 Trip
Low Right Exhaust Temperature Shutdown Event Fault
No
Protection Timer
High Left Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
High Left Exhaust Temperature Warning Event Audible
Yes
Alert
High Left Exhaust Temperature Warning Event Breaker
No
#1 Trip
High Left Exhaust Temperature Warning Event Breaker
No
#2 Trip
High Left Exhaust Temperature Warning Event Fault
No
Protection Timer
High Left Exhaust Temperature Shutdown Event Activate Hard Shutdown
Response Configuration Condition
High Left Exhaust Temperature Shutdown Event Audible
Yes
Alert
High Left Exhaust Temperature Shutdown Event Breaker
No
#1 Trip
High Left Exhaust Temperature Shutdown Event Breaker
No
#2 Trip
High Left Exhaust Temperature Shutdown Event Fault
No
Protection Timer
Low Left Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Left Exhaust Temperature Warning Event Audible
Yes
Alert
Low Left Exhaust Temperature Warning Event Breaker
No
#1 Trip
Low Left Exhaust Temperature Warning Event Breaker
No
#2 Trip
Low Left Exhaust Temperature Warning Event Fault
Yes
Protection Timer
Low Left Exhaust Temperature Shutdown Event
Disable Condition
Response Configuration
Low Left Exhaust Temperature Shutdown Event Audible
No
Alert

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 18 of 56

Low Left Exhaust Temperature Shutdown Event Breaker


No
#1 Trip
Low Left Exhaust Temperature Shutdown Event Breaker
No
#2 Trip
Low Left Exhaust Temperature Shutdown Event Fault
No
Protection Timer
High Fuel Filter Differential Pressure Warning Event
Activate Warning Condition
Response Configuration
High Fuel Filter Differential Pressure Warning Event
Yes
Audible Alert
High Fuel Filter Differential Pressure Warning Event
No
Breaker #1 Trip
High Fuel Filter Differential Pressure Warning Event
No
Breaker #2 Trip
High Fuel Filter Differential Pressure Shutdown Event Activate Hard Shutdown
Response Config Condition
High Fuel Filter Differential Pressure Shutdown Event
Yes
Audible Alert
High Fuel Filter Differential Pressure Shutdown Event
No
Breaker #1 Trip
High Fuel Filter Differential Pressure Shutdown Event
No
Breaker #2 Trip
Low Fuel Filter Differential Pressure Warning Event
Activate Warning Condition
Response Configuration
Low Fuel Filter Differential Pressure Warning Event
Yes
Audible Alert
Low Fuel Filter Differential Pressure Warning Event
No
Breaker #1 Trip
Low Fuel Filter Differential Pressure Warning Event
No
Breaker #2 Trip
Low Fuel Filter Differential Pressure Warning Event Fault
Yes
Protection Timer
Low Fuel Filter Differential Pressure Shutdown Event Activate Hard Shutdown
Response Configuration Condition
Low Fuel Filter Differential Pressure Shutdown Event
Yes
Audible Alert
Low Fuel Filter Differential Pressure Shutdown Event
No
Breaker #1 Trip
Low Fuel Filter Differential Pressure Shutdown Event
No
Breaker #2 Trip
Low Fuel Filter Differential Pressure Shutdown Event
Yes
Fault Protection Timer

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 19 of 56

High Fuel Level Warning Event Response Configuration


Activate Warning Condition
High Fuel Level Warning Event Audible Alert Yes
High Fuel Level Warning Event Breaker #1 TripNo
High Fuel Level Warning Event Breaker #2 TripNo
Activate Hard Shutdown
High Fuel Level Shutdown Event Response Configuration
Condition
High Fuel Level Shutdown Event Audible Alert Yes
High Fuel Level Shutdown Event Breaker #1 Trip No
High Fuel Level Shutdown Event Breaker #2 Trip No
Low Fuel Level Warning Event Response Configuration Activate Warning Condition
Low Fuel Level Warning Event Audible Alert Yes
Low Fuel Level Warning Event Breaker #1 Trip No
Low Fuel Level Warning Event Breaker #2 Trip No
Activate Hard Shutdown
Low Fuel Level Shutdown Event Response Configuration
Condition
Low Fuel Level Shutdown Event Audible Alert Yes
Low Fuel Level Shutdown Event Breaker #1 Trip No
Low Fuel Level Shutdown Event Breaker #2 Trip No
External Tank High Fuel Level Warning Event Response
Activate Warning Condition
Configuration
External Tank High Fuel Level Warning Event Audible
Yes
Alert
External Tank High Fuel Level Warning Event Breaker #1
No
Trip
External Tank High Fuel Level Warning Event Breaker #2
No
Trip
External Tank High Fuel Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
External Tank High Fuel Level Shutdown Event Audible
Yes
Alert
External Tank High Fuel Level Shutdown Event Breaker
No
#1 Trip
External Tank High Fuel Level Shutdown Event Breaker
No
#2 Trip
External Tank Low Fuel Level Warning Event Response
Activate Warning Condition
Configuration
External Tank Low Fuel Level Warning Event Audible
Yes
Alert
External Tank Low Fuel Level Warning Event Breaker #1
No
Trip
External Tank Low Fuel Level Warning Event Breaker #2

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 20 of 56

Trip No
External Tank Low Fuel Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
External Tank Low Fuel Level Shutdown Event Audible
Yes
Alert
External Tank Low Fuel Level Shutdown Event Breaker
No
#1 Trip
External Tank Low Fuel Level Shutdown Event Breaker
No
#2 Trip
Fuel Leak Event Response Configuration Activate Warning Condition
Fuel Leak Event Audible Alert Yes
Fuel Leak Event Breaker #1 Trip No
Fuel Leak Event Breaker #2 Trip No
High Engine Oil Filter Differential Pressure Warning
Activate Warning Condition
Event Response Config
High Engine Oil Filter Differential Pressure Warning
Yes
Event Audible Alert
High Engine Oil Filter Differential Pressure Warning
No
Event Breaker #1 Trip
High Engine Oil Filter Differential Pressure Warning
No
Event Breaker #2 Trip
High Engine Oil Filter Differential Pressure Shutdown Activate Hard Shutdown
Event Response Config Condition
High Engine Oil Filter Differential Pressure Shutdown
Yes
Event Audible Alert
High Engine Oil Filter Differential Pressure Shutdown
No
Event Breaker #1 Trip
High Engine Oil Filter Differential Pressure Shutdown
No
Event Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Warning Event
Activate Warning Condition
Response Config
Low Engine Oil Filter Differential Pressure Warning Event
Yes
Audible Alert
Low Engine Oil Filter Differential Pressure Warning Event
No
Breaker #1 Trip
Low Engine Oil Filter Differential Pressure Warning Event
No
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Warning Fault
Yes
Protection Timer
Low Engine Oil Filter Differential Pressure Shutdown Activate Hard Shutdown
Event Response Config Condition

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 21 of 56

Low Engine Oil Filter Differential Pressure Shutdown


Yes
Event Audible Alert
Low Engine Oil Filter Differential Pressure Shutdown
No
Event Breaker #1 Trip
Low Engine Oil Filter Differential Pressure Shutdown
No
Event Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Shutdown
Yes
Fault Protection Timer
Service Maintenance Interval Warning Event Response
Activate Warning Condition
Configuration
Service Maintenance Interval Warning Event Audible
No
Alert
High Starting Air Pressure Warning Event Response
Activate Warning Condition
Configuration
High Starting Air Pressure Warning Event Audible Alert Yes
High Starting Air Pressure Warning Event Breaker #1
No
Trip
High Starting Air Pressure Warning Event Breaker #2
No
Trip
High Starting Air Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Starting Air Pressure Shutdown Event Audible Alert Yes
High Starting Air Pressure Shutdown Event Breaker #1
No
Trip
High Starting Air Pressure Shutdown Event Breaker #2
No
Trip
Low Starting Air Pressure Warning Event Response
Activate Warning Condition
Configuration
Low Starting Air Pressure Warning Event Audible Alert Yes
Low Starting Air Pressure Warning Event Breaker #1
No
Trip
Low Starting Air Pressure Warning Event Breaker #2
No
Trip
Low Starting Air Pressure Warning Event Fault Protection
Yes
Timer
Low Starting Air Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Starting Air Pressure Shutdown Event Audible Alert Yes
Low Starting Air Pressure Shutdown Event Breaker #1
No
Trip
Low Starting Air Pressure Shutdown Event Breaker #2
No
Trip

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 22 of 56

Low Starting Air Pressure Shutdown Event Fault


Yes
Protection Timer
High Gas Pressure Warning Event Response
Activate Warning Condition
Configuration
High Gas Pressure Warning Event Audible Alert Yes
High Gas Pressure Warning Event Breaker #1 Trip No
High Gas Pressure Warning Event Breaker #2 Trip No
High Gas Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Gas Pressure Shutdown Event Audible Alert Yes
High Gas Pressure Shutdown Event Breaker #1 Trip No
High Gas Pressure Shutdown Event Breaker #2 Trip No
Low Gas Pressure Warning Event Response
Activate Warning Condition
Configuration
Low Gas Pressure Warning Event Audible Alert Yes
Low Gas Pressure Warning Event Breaker #1 Trip No
Low Gas Pressure Warning Event Breaker #2 Trip No
Low Gas Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Gas Pressure Shutdown Event Audible Alert Yes
Low Gas Pressure Shutdown Event Breaker #1 Trip No
Low Gas Pressure Shutdown Event Breaker #2 Trip No
Engine Intake Manifold Charge Combustion Event Activate Hard Shutdown
Response Configuration Condition
Engine Intake Manifold Charge Combustion Event
Yes
Audible Alert
Engine Intake Manifold Charge Combustion Event Loss
No
of Utility
Engine Intake Manifold Charge Combustion Event
No
Breaker #1 Trip
Engine Intake Manifold Charge Combustion Event
No
Breaker #2 Trip
Engine Intake Manifold Charge Combustion Event Fault
No
Protection Timer
High Generator Bearing #1 Temperature Warning Event
Activate Warning Condition
Response Configuration
High Generator Bearing #1 Temperature Warning Event
Yes
Audible Alert
High Generator Bearing #1 Temperature Warning Event
No
Breaker #1 Trip
High Generator Bearing #1 Temperature Warning Event

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 23 of 56

Breaker #2 Trip No
High Generator Bearing #1 Temperature Warning Event
No
Fault Protection Timer
High Generator Bearing #1 Temperature Shutdown Activate Hard Shutdown
Event Response Configuration Condition
High Generator Bearing #1 Temperature Shutdown
Yes
Event Audible Alert
High Generator Bearing #1 Temperature Shutdown
No
Event Breaker #1 Trip
High Generator Bearing #1 Temperature Shutdown
No
Event Breaker #2 Trip
High Generator Bearing #1 Temperature Shutdown
No
Event Fault Protection Timer
Low Generator Bearing #1 Temperature Warning Event
Activate Warning Condition
Response Configuration
Low Generator Bearing #1 Temperature Warning Event
Yes
Audible Alert
Low Generator Bearing #1 Temperature Warning Event
No
Breaker #1 Trip
Low Generator Bearing #1 Temperature Warning Event
No
Breaker #2 Trip
Low Generator Bearing #1 Temperature Warning Event
Yes
Fault Protection Timer
Low Generator Bearing #1 Temperature Shutdown
Disable Condition
Event Response Configuration
Low Generator Bearing #1 Temperature Shutdown
No
Event Audible Alert
Low Generator Bearing #1 Temperature Shutdown
No
Event Breaker #1 Trip
Low Generator Bearing #1 Temperature Shutdown
No
Event Breaker #2 Trip
Low Generator Bearing #1 Temperature Shutdown
No
Event Fault Protection Timer
Generator Overcurrent Warning Event Response
Activate Warning Condition
Configuration
Generator Overcurrent Warning Event Audible Alert Yes
Generator Overcurrent Warning Event Breaker #1 Trip No
Generator Overcurrent Warning Event Breaker #2 Trip No
Generator Overcurrent Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Generator Overcurrent Shutdown Event Audible Alert Yes

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 24 of 56

Generator Overcurrent Shutdown Event Breaker #1 Trip No


Generator Overcurrent Shutdown Event Breaker #2 Trip No
Generator Over Frequency Warning Event Response
Activate Warning Condition
Configuration
Generator Over Frequency Warning Event Audible Alert Yes
Generator Over Frequency Warning Event Breaker #1
No
Trip
Generator Over Frequency Warning Event Breaker #2
No
Trip
Generator Over Frequency Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Generator Over Frequency Shutdown Event Audible Alert Yes
Generator Over Frequency Shutdown Event Breaker #1
No
Trip
Generator Over Frequency Shutdown Event Breaker #2
No
Trip
Generator Under Frequency Warning Event Response
Disable Condition
Configuration
Generator Under Frequency Warning Event Audible Alert Yes
Generator Under Frequency Warning Event Breaker #1
No
Trip
Generator Under Frequency Warning Event Breaker #2
No
Trip
Generator Under Frequency Warning Event Fault
Yes
Protection Timer
Generator Under Frequency Shutdown Event Response
Disable Condition
Configuration
Generator Under Frequency Shutdown Event Audible
Yes
Alert
Generator Under Frequency Shutdown Event Breaker #1
No
Trip
Generator Under Frequency Shutdown Event Breaker #2
No
Trip
Generator Under Frequency Shutdown Event Fault
Yes
Protection Timer
Generator Reverse Power Warning Event Response
Activate Warning Condition
Configuration
Generator Reverse Power Warning Event Audible Alert Yes
Generator Reverse Power Warning Event Breaker #1
No
Trip
No
Generator Reverse Power Warning Event Breaker #2

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 25 of 56

Trip
Generator Reverse Power Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Generator Reverse Power Shutdown Event Audible Alert Yes
Generator Reverse Power Shutdown Event Breaker #1
No
Trip
Generator Reverse Power Shutdown Event Breaker #2
No
Trip
Generator Over Voltage Warning Event Response
Activate Warning Condition
Configuration
Generator Over Voltage Warning Event Audible Alert Yes
Generator Over Voltage Warning Event Breaker #1 Trip No
Generator Over Voltage Warning Event Breaker #2 Trip No
Generator Over Voltage Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Generator Over Voltage Shutdown Event Audible Alert Yes
Generator Over Voltage Shutdown Event Breaker #1
No
Trip
Generator Over Voltage Shutdown Event Breaker #2
No
Trip
Generator Under Voltage Warning Event Response
Disable Condition
Configuration
Generator Under Voltage Warning Event Audible Alert Yes
Generator Under Voltage Warning Event Breaker #1 Trip No
Generator Under Voltage Warning Event Breaker #2 Trip No
Generator Under Voltage Warning Event Fault Protection
Yes
Timer
Generator Under Voltage Shutdown Event Response
Disable Condition
Configuration
Generator Under Voltage Shutdown Event Audible Alert Yes
Generator Under Voltage Shutdown Event Breaker #1
No
Trip
Generator Under Voltage Shutdown Event Breaker #2
No
Trip
Generator Under Voltage Shutdown Event Fault
Yes
Protection Timer
Activate Hard Shutdown
Earth Fault Event Response Configuration
Condition
Earth Fault Event Audible Alert Yes
Earth Fault Event Breaker #1 Trip No
Earth Fault Event Breaker #2 Trip No

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 26 of 56

Generator Winding #1 High Temperature Warning Event


Activate Warning Condition
Response Configuration
Generator Winding #1 High Temperature Warning Event
Yes
Audible Alert
Generator Winding #1 High Temperature Warning Event
No
Breaker #1 Trip
Generator Winding #1 High Temperature Warning Event
No
Breaker #2 Trip
Generator Winding #1 High Temperature Warning Event
No
Fault Protection Timer
Generator Winding #2 High Temperature Warning Event
Activate Warning Condition
Response Configuration
Generator Winding #2 High Temperature Warning Event
Yes
Audible Alert
Generator Winding #2 High Temperature Warning Event
No
Breaker #1 Trip
Generator Winding #2 High Temperature Warning Event
No
Breaker #2 Trip
Generator Winding #2 High Temperature Warning Event
No
Fault Protection Timer
Generator Winding #3 High Temperature Warning Event
Activate Warning Condition
Response Configuration
Generator Winding #3 High Temperature Warning Event
Yes
Audible Alert
Generator Winding #3 High Temperature Warning Event
No
Breaker #1 Trip
Generator Winding #3 High Temperature Warning Event
No
Breaker #2 Trip
Generator Winding #3 High Temperature Warning Event
No
Fault Protection Timer
Generator Winding #1 High Temperature Shutdown Activate Hard Shutdown
Event Response Configuration Condition
Generator Winding #1 High Temperature Shutdown
Yes
Event Audible Alert
Generator Winding #1 High Temperature Shutdown
No
Event Breaker #1 Trip
Generator Winding #1 High Temperature Shutdown
No
Event Breaker #2 Trip
Generator Winding #1 High Temperature Shutdown
No
Event Fault Protection Timer
Generator Winding #2 High Temperature Shutdown
Data Invalid
Event Response Configuration

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 27 of 56

Generator Winding #2 High Temperature Shutdown


Yes
Event Audible Alert
Generator Winding #2 High Temperature Shutdown
No
Event Breaker #1 Trip
Generator Winding #2 High Temperature Shutdown
No
Event Breaker #2 Trip
Generator Winding #2 High Temperature Shutdown
No
Event Fault Protection Timer
Generator Winding #3 High Temperature Shutdown Activate Hard Shutdown
Event Response Configuration Condition
Generator Winding #3 High Temperature Shutdown
Yes
Event Audible Alert
Generator Winding #3 High Temperature Shutdown
No
Event Breaker #1 Trip
Generator Winding #3 High Temperature Shutdown
No
Event Breaker #2 Trip
Generator Winding #3 High Temperature Shutdown
No
Event Fault Protection Timer
High Ambient Air Temperature Warning Event Response
Activate Warning Condition
Configuration
High Ambient Air Temperature Warning Event Audible
Yes
Alert
High Ambient Air Temperature Warning Event Breaker
No
#1 Trip
High Ambient Air Temperature Warning Event Breaker
No
#2 Trip
High Ambient Air Temperature Warning Event Fault
No
Protection Timer
High Ambient Air Temperature Shutdown Event Activate Hard Shutdown
Response Configuration Condition
High Ambient Air Temperature Shutdown Event Audible
Yes
Alert
High Ambient Air Temperature Shutdown Event Breaker
No
#1 Trip
High Ambient Air Temperature Shutdown Event Breaker
No
#2 Trip
High Ambient Air Temperature Shutdown Event Fault
No
Protection Timer
Low Ambient Air Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Ambient Air Temperature Warning Event Audible
Yes
Alert

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 28 of 56

Low Ambient Air Temperature Warning Event Breaker


No
#1 Trip
Low Ambient Air Temperature Warning Event Breaker
No
#2 Trip
Low Ambient Air Temperature Shutdown Event
Disable Condition
Response Configuration
Low Ambient Air Temperature Shutdown Event Audible
No
Alert
Low Ambient Air Temperature Shutdown Event Breaker
No
#1 Trip
Low Ambient Air Temperature Shutdown Event Breaker
No
#2 Trip
Automatic Transfer Switch In Normal Position Event
Active Only Condition
Response Configuration
Automatic Transfer Switch In Normal Position Event
No
Audible Alert
Automatic Transfer Switch In Emergency Position Event
Active Only Condition
Response Config
Automatic Transfer Switch In Emergency Position Event
No
Audible Alert
High Battery Voltage Warning Event Response
Activate Warning Condition
Configuration
High Battery Voltage Warning Event Audible Alert Yes
High Battery Voltage Warning Event Breaker #1 Trip No
High Battery Voltage Warning Event Breaker #2 Trip No
High Battery Voltage Shutdown Event Response Activate Soft Shutdown
Configuration Condition
High Battery Voltage Shutdown Event Audible Alert Yes
High Battery Voltage Shutdown Event Breaker #1 Trip No
High Battery Voltage Shutdown Event Breaker #2 Trip No
Low Battery Voltage Warning Event Response
Activate Warning Condition
Configuration
Low Battery Voltage Warning Event Audible Alert Yes
Low Battery Voltage Warning Event Breaker #1 Trip No
Low Battery Voltage Warning Event Breaker #2 Trip No
Low Battery Voltage Warning Event Fault Protection
No
Timer
Low Battery Charging System Voltage Warning Event
Disable Condition
Response Configuration
Low Battery Charging System Voltage Warning Event
No
Audible Alert

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 29 of 56

Low Battery Charging System Voltage Warning Event


No
Breaker #1 Trip
Low Battery Charging System Voltage Warning Event
No
Breaker #2 Trip
Low Battery Charging System Voltage Warning Event
No
Fault Protection Timer
Generator Breaker Failure To Open Event Response
Activate Warning Condition
Configuration
Generator Breaker Failure To Open Event Audible Alert Yes
Generator Breaker Failure To Open Event Breaker #1
No
Trip
Generator Breaker Failure To Open Event Breaker #2
No
Trip
Generator Breaker Failure To Close Event Response Activate Hard Shutdown
Configuration Condition
Generator Breaker Failure To Close Event Audible Alert Yes
Generator Breaker Failure To Close Event Breaker #1
No
Trip
Generator Breaker Failure To Close Event Breaker #2
No
Trip
Generator Breaker Open Event Response Configuration Active Only Condition
Generator Breaker Open Event Audible Alert No
Generator Breaker Closed Event Response Configuration Active Only Condition
Generator Breaker Closed Event Audible Alert No
Utility Breaker Failure To Open Event Response Activate Hard Shutdown
Configuration Condition
Utility Breaker Failure To Open Event Audible Alert Yes
Utility Breaker Failure To Open Event Breaker #1 Trip No
Utility Breaker Failure To Open Event Breaker #2 Trip No
Utility Breaker Failure To Close Event Response
Activate Warning Condition
Configuration
Utility Breaker Failure To Close Event Audible Alert Yes
Utility Breaker Failure To Close Event Breaker #1 Trip No
Utility Breaker Failure To Close Event Breaker #2 Trip No
Utility Breaker Open Event Response Configuration Active Only Condition
Utility Breaker Open Event Audible Alert No
Utility Breaker Closed Event Response Configuration Active Only Condition
Utility Breaker Closed Event Audible Alert No
Emergency Shutdown Override Mode Active Warning
Activate Warning Condition
Event Response Config

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 30 of 56

Emergency Shutdown Override Mode Active Warning


No
Event Audible Alert
Engine In Cooldown Event Response Configuration Active Only Condition
Engine In Cooldown Event Audible Alert No
Engine Speed-Generator Output Freq Mismatch Warning
Activate Warning Condition
Event Response Config
Engine Speed-Generator Output Freq Mismatch Warning
Yes
Event Audible Alert
Engine Speed-Generator Output Freq Mismatch Warning
No
Event Breaker #1 Trip
Engine Speed-Generator Output Freq Mismatch Warning
No
Event Breaker #2 Trip
High Fire Extinguisher Pressure Warning Event Response
Activate Warning Condition
Configuration
High Fire Extinguisher Pressure Warning Event Audible
Yes
Alert
High Fire Extinguisher Pressure Warning Event Breaker
No
#1 Trip
High Fire Extinguisher Pressure Warning Event Breaker
No
#2 Trip
High Fire Extinguisher Pressure Shutdown Event Activate Hard Shutdown
Response Configuration Condition
High Fire Extinguisher Pressure Shutdown Event Audible
Yes
Alert
High Fire Extinguisher Pressure Shutdown Event Breaker
No
#1 Trip
High Fire Extinguisher Pressure Shutdown Event Breaker
No
#2 Trip
Low Fire Extinguisher Pressure Warning Event Response
Activate Warning Condition
Configuration
Low Fire Extinguisher Pressure Warning Event Audible
Yes
Alert
Low Fire Extinguisher Pressure Warning Event Breaker
No
#1 Trip
Low Fire Extinguisher Pressure Warning Event Breaker
No
#2 Trip
Low Fire Extinguisher Pressure Warning Event Fault
No
Protection Timer
Low Fire Extinguisher Pressure Shutdown Event Activate Hard Shutdown
Response Configuration Condition
Low Fire Extinguisher Pressure Shutdown Event Audible
Yes
Alert

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 31 of 56

Low Fire Extinguisher Pressure Shutdown Event Breaker


No
#1 Trip
Low Fire Extinguisher Pressure Shutdown Event Breaker
No
#2 Trip
Low Fire Extinguisher Pressure Shutdown Event Fault
No
Protection Timer
Generator Control Not in Automatic Warning Event
Activate Warning Condition
Response Configuration
Generator Control Not in Automatic Warning Event
Yes
Audible Alert
Generator Breaker Locked Out Warning Event Response Warning & Active Only
Configuration Condition
Generator Breaker Locked Out Warning Event Audible
Yes
Alert
Generator Breaker Locked Out Warning Event Breaker
No
#1 Trip
Generator Breaker Locked Out Warning Event Breaker
No
#2 Trip
Utility Breaker Locked Out Warning Event Response
Disable Condition
Configuration
Utility Breaker Locked Out Warning Event Audible Alert No
Utility Breaker Locked Out Warning Event Loss of Utility No
Utility Breaker Locked Out Warning Event Breaker #1
No
Trip
Utility Breaker Locked Out Warning Event Breaker #2
No
Trip
Warning & Active Only
Loss of Utility Event Response Configuration
Condition
Loss of Utility Event Audible Alert Yes
Utility to Generator Transfer Failure Warning Event
Activate Warning Condition
Response Configuration
Utility to Generator Transfer Failure Warning Event
Yes
Audible Alert
Utility to Generator Transfer Failure Warning Event
No
Breaker #1 Trip
Utility to Generator Transfer Failure Warning Event
No
Breaker #2 Trip
Utility to Generator Transfer Failure Shutdown Event
Data Invalid
Response Configuration
Utility to Generator Transfer Failure Shutdown Event
Yes
Audible Alert
Utility to Generator Transfer Failure Shutdown Event

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 32 of 56

Breaker #1 Trip Yes


Utility to Generator Transfer Failure Shutdown Event
No
Breaker #2 Trip
Generator to Utility Transfer Failure Warning Event
Activate Warning Condition
Response Configuration
Generator to Utility Transfer Failure Warning Event
Yes
Audible Alert
Generator to Utility Transfer Failure Warning Event
No
Breaker #1 Trip
Generator to Utility Transfer Failure Warning Event
No
Breaker #2 Trip
Activate Hard Shutdown
Earth Leakage Event Response Configuration
Condition
Earth Leakage Event Audible Alert Yes
Earth Leakage Event Breaker #1 Trip No
Earth Leakage Event Breaker #2 Trip No
Utility Breaker System Fault Event Response
Disabled or Not Installed
Configuration
Utility Breaker System Fault Event Audible Alert Disabled or Not Installed
Utility Breaker System Fault Event Breaker #1 Trip Disabled or Not Installed
Utility Breaker System Fault Event Breaker #2 Trip Disabled or Not Installed
Custom Event #1 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #1 High Warning Event Audible Alert Yes
Custom Event #1 High Warning Event Breaker #1 Trip No
Custom Event #1 High Warning Event Breaker #2 Trip No
Custom Event #1 High Warning Event Fault Protection
No
Timer
Custom Event #1 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #1 High Shutdown Event Audible Alert Yes
Custom Event #1 High Shutdown Event Breaker #1 Trip No
Custom Event #1 High Shutdown Event Breaker #2 Trip No
Custom Event #1 High Shutdown Event Fault Protection
No
Timer
Custom Event #1 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #1 Low Warning Event Audible Alert Yes
Custom Event #1 Low Warning Event Breaker #1 Trip No
Custom Event #1 Low Warning Event Breaker #2 Trip No

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 33 of 56

Custom Event #1 Low Warning Event Fault Protection


No
Timer
Custom Event #1 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #1 Low Shutdown Event Audible Alert Yes
Custom Event #1 Low Shutdown Event Breaker #1 Trip No
Custom Event #1 Low Shutdown Event Breaker #2 Trip No
Custom Event #1 Low Shutdown Event Fault Protection
No
Timer
Custom Event #1 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #1 Condition Exists Event Audible Alert No
Custom Event #1 Condition Exists Event Loss of Utility No
Custom Event #1 Condition Exists Event Breaker #1 Trip No
Custom Event #1 Condition Exists Event Breaker #2 Trip No
Custom Event #1 Condition Exists Event Fault Protection
No
Timer
Custom Event #2 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #2 High Warning Event Audible Alert Yes
Custom Event #2 High Warning Event Breaker #1 Trip No
Custom Event #2 High Warning Event Breaker #2 Trip No
Custom Event #2 High Warning Event Fault Protection
No
Timer
Custom Event #2 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #2 High Shutdown Audible Alert Yes
Custom Event #2 High Shutdown Breaker #1 Trip No
Custom Event #2 High Shutdown Breaker #2 Trip No
Custom Event #2 High Shutdown Fault Protection Timer No
Custom Event #2 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #2 Low Warning Audible Alert Yes
Custom Event #2 Low Warning Breaker #1 Trip No
Custom Event #2 Low Warning Breaker #2 Trip No
Custom Event #2 Low Warning Fault Protection Timer
No
Custom Event #2 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #2 Low Shutdown Event Audible Alert Yes
Custom Event #2 Low Shutdown Event Breaker #1 Trip No

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 34 of 56

Custom Event #2 Low Shutdown Event Breaker #2 Trip No


Custom Event #2 Low Shutdown Event Fault Protection
No
Timer
Custom Event #2 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #2 Condition Exists Event Audible Alert No
Custom Event #2 Condition Exists Event Loss of Utility No
Custom Event #2 Condition Exists Event Breaker #1 Trip No
Custom Event #2 Condition Exists Event Breaker #2 Trip No
Custom Event #2 Condition Exists Event Fault Protection
No
Timer
Custom Event #3 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #3 High Warning Event Audible Alert Yes
Custom Event #3 High Warning Event Breaker #1 Trip No
Custom Event #3 High Warning Event Breaker #2 Trip No
Custom Event #3 High Warning Event Fault Protection
No
Timer
Custom Event #3 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #3 High Shutdown Event Audible Alert Yes
Custom Event #3 High Shutdown Event Breaker #1 Trip No
Custom Event #3 High Shutdown Event Breaker #2 Trip No
Custom Event #3 High Shutdown Event Fault Protection
No
Timer
Custom Event #3 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #3 Low Warning Event Audible Alert Yes
Custom Event #3 Low Warning Event Breaker #1 Trip No
Custom Event #3 Low Warning Event Breaker #2 Trip No
Custom Event #3 Low Warning Event Fault Protection
No
Timer
Custom Event #3 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #3 Low Shutdown Event Audible Alert Yes
Custom Event #3 Low Shutdown Event Breaker #1 Trip No
Custom Event #3 Low Shutdown Event Breaker #2 Trip No
Custom Event #3 Low Shutdown Event Fault Protection
No
Timer
Active Only Condition
Custom Event #3 Condition Exists Event Response

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 35 of 56

Configuration
Custom Event #3 Condition Exists Event Audible Alert No
Custom Event #3 Condition Exists Event Loss of Utility No
Custom Event #3 Condition Exists Event Breaker #1 Trip No
Custom Event #3 Condition Exists Event Breaker #2 Trip No
Custom Event #3 Condition Exists Event Fault Protection
No
Timer
Custom Event #4 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #4 High Warning Event Audible Alert Yes
Custom Event #4 High Warning Event Breaker #1 Trip No
Custom Event #4 High Warning Event Breaker #2 Trip No
Custom Event #4 High Warning Event Fault Protection
No
Timer
Custom Event #4 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #4 High Shutdown Event Audible Alert Yes
Custom Event #4 High Shutdown Event Breaker #1 Trip No
Custom Event #4 High Shutdown Event Breaker #2 Trip No
Custom Event #4 High Shutdown Event Fault Protection
No
Timer
Custom Event #4 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #4 Low Warning Event Audible Alert Yes
Custom Event #4 Low Warning Event Breaker #1 Trip No
Custom Event #4 Low Warning Event Breaker #2 Trip No
Custom Event #4 Low Warning Event Fault Protection
No
Timer
Custom Event #4 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #4 Low Shutdown Event Audible Alert Yes
Custom Event #4 Low Shutdown Event Breaker #1 Trip No
Custom Event #4 Low Shutdown Event Breaker #2 Trip No
Custom Event #4 Low Shutdown Event Fault Protection
No
Timer
Custom Event #4 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #4 Condition Exists Event Audible Alert No
Custom Event #4 Condition Exists Event Loss of Utility No
Custom Event #4 Condition Exists Event Breaker #1 Trip No

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 36 of 56

Custom Event #4 Condition Exists Event Breaker #2 Trip No


Custom Event #4 Condition Exists Event Fault Protection
No
Timer
Custom Event #5 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #5 High Warning Event Audible Alert Yes
Custom Event #5 High Warning Event Breaker #1 Trip No
Custom Event #5 High Warning Event Breaker #2 Trip No
Custom Event #5 High Warning Event Fault Protection
No
Timer
Custom Event #5 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #5 High Shutdown Event Audible Alert Yes
Custom Event #5 High Shutdown Event Breaker #1 Trip No
Custom Event #5 High Shutdown Event Breaker #2 Trip No
Custom Event #5 High Shutdown Event Fault Protection
No
Timer
Custom Event #5 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #5 Low Warning Event Audible Alert Yes
Custom Event #5 Low Warning Event Breaker #1 Trip No
Custom Event #5 Low Warning Event Breaker #2 Trip No
Custom Event #5 Low Warning Event Fault Protection
No
Timer
Custom Event #5 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #5 Low Shutdown Event Audible Alert Yes
Custom Event #5 Low Shutdown Event Breaker #1 Trip No
Custom Event #5 Low Shutdown Event Breaker #2 Trip No
Custom Event #5 Low Shutdown Event Fault Protection
No
Timer
Custom Event #5 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #5 Condition Exists Event Audible Alert No
Custom Event #5 Condition Exists Event Loss of Utility No
Custom Event #5 Condition Exists Event Breaker #1 Trip No
Custom Event #5 Condition Exists Event Breaker #2 Trip No
Custom Event #5 Condition Exists Event Fault Protection
No
Timer
Activate Warning Condition
Custom Event #6 High Warning Event Response

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 37 of 56

Configuration
Custom Event #6 High Warning Event Audible Alert Yes
Custom Event #6 High Warning Event Breaker #1 Trip No
Custom Event #6 High Warning Event Breaker #2 Trip No
Custom Event #6 High Warning Event Fault Protection
No
Timer
Custom Event #6 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #6 High Shutdown Event Audible Alert Yes
Custom Event #6 High Shutdown Event Breaker #1 Trip No
Custom Event #6 High Shutdown Event Breaker #2 Trip No
Custom Event #6 High Shutdown Event Fault Protection
No
Timer
Custom Event #6 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #6 Low Warning Event Audible Alert Yes
Custom Event #6 Low Warning Event Breaker #1 Trip No
Custom Event #6 Low Warning Event Breaker #2 Trip No
Custom Event #6 Low Warning Event Fault Protection
No
Timer
Custom Event #6 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #6 Low Shutdown Event Audible Alert Yes
Custom Event #6 Low Shutdown Event Breaker #1 Trip No
Custom Event #6 Low Shutdown Event Breaker #2 Trip No
Custom Event #6 Low Shutdown Event Fault Protection
No
Timer
Custom Event #6 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #6 Condition Exists Event Audible Alert No
Custom Event #6 Condition Exists Event Loss of Utility No
Custom Event #6 Condition Exists Event Breaker #1 Trip No
Custom Event #6 Condition Exists Event Breaker #2 Trip No
Custom Event #6 Condition Exists Event Fault Protection
No
Timer
Custom Event #7 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #7 High Warning Event Audible Alert Yes
Custom Event #7 High Warning Event Breaker #1 Trip No
Custom Event #7 High Warning Event Breaker #2 Trip No

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 38 of 56

Custom Event #7 High Warning Event Fault Protection


No
Timer
Custom Event #7 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #7 High Shutdown Event Audible Alert Yes
Custom Event #7 High Shutdown Event Breaker #1 Trip No
Custom Event #7 High Shutdown Event Breaker #2 Trip No
Custom Event #7 High Shutdown Event Fault Protection
No
Timer
Custom Event #7 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #7 Low Warning Event Audible Alert Yes
Custom Event #7 Low Warning Event Breaker #1 Trip No
Custom Event #7 Low Warning Event Breaker #2 Trip No
Custom Event #7 Low Warning Event Fault Protection
No
Timer
Custom Event #7 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #7 Low Shutdown Event Audible Alert Yes
Custom Event #7 Low Shutdown Event Breaker #1 Trip No
Custom Event #7 Low Shutdown Event Breaker #2 Trip No
Custom Event #7 Low Shutdown Event Fault Protection
No
Timer
Custom Event #7 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #7 Condition Exists Event Audible Alert No
Custom Event #7 Condition Exists Event Loss of Utility No
Custom Event #7 Condition Exists Event Breaker #1 Trip No
Custom Event #7 Condition Exists Event Breaker #2 Trip No
Custom Event #7 Condition Exists Event Fault Protection
No
Timer
Custom Event #8 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #8 High Warning Event Audible Alert Yes
Custom Event #8 High Warning Event Breaker #1 Trip No
Custom Event #8 High Warning Event Breaker #2 Trip No
Custom Event #8 High Warning Event Fault Protection
No
Timer
Custom Event #8 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 39 of 56

Custom Event #8 High Shutdown Event Audible Alert Yes


Custom Event #8 High Shutdown Event Breaker #1 Trip No
Custom Event #8 High Shutdown Event Breaker #2 Trip No
Custom Event #8 High Shutdown Event Fault Protection
No
Timer
Custom Event #8 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #8 Low Warning Event Audible Alert Yes
Custom Event #8 Low Warning Event Breaker #1 Trip No
Custom Event #8 Low Warning Event Breaker #2 Trip No
Custom Event #8 Low Warning Event Fault Protection
No
Timer
Custom Event #8 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #8 Low Shutdown Event Audible Alert Yes
Custom Event #8 Low Shutdown Event Breaker #1 Trip No
Custom Event #8 Low Shutdown Event Breaker #2 Trip No
Custom Event #8 Low Shutdown Event Fault Protection
No
Timer
Custom Event #8 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #8 Condition Exists Event Audible Alert No
Custom Event #8 Condition Exists Event Loss of Utility No
Custom Event #8 Condition Exists Event Breaker #1 Trip No
Custom Event #8 Condition Exists Event Breaker #2 Trip No
Custom Event #8 Condition Exists Event Fault Protection
No
Timer
Event Warning Condition Response Auto Reset Enable
Enabled
Status
Event Audible Alert Response Auto Reset Enable Status Enabled
Event Loss Of Utility Response Auto Reset Enable Status Enabled
Event Breaker #1 Trip Response Auto Reset Enable
Enabled
Status
Event Breaker #2 Trip Response Auto Reset Enable
Enabled
Status
Generator Connection Configuration Wye (or Star) Connection
Generator Potential Transformer Primary Winding Rating 1 Volts
Generator Potential Transformer Secondary Winding
1 Volts
Rating
Generator Current Transformer Primary Winding Rating 1500 Amps

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 40 of 56

Generator Current Transformer Secondary Winding


5 Amps
Rating
Number of Generator Poles 4 Poles
Generator Rated Frequency 60 Hz
Generator Rated Voltage 480 Volts
Generator Rated Power 800 kW
Generator Rated Apparent Power 1035 kVA
Customer Password Security Level to Reset Generator
3-Factory, Single Use
Energy Meters
Generator Breaker Closing Pulse Active Time Disabled or Not Installed sec
Generator Breaker Closing Pulse Rest Interval Disabled or Not Installed sec
Generator Breaker Maximum Closing Time Disabled or Not Installed sec
Generator Breaker Maximum Opening Time Disabled or Not Installed sec
Generator Breaker Lockout Configuration Disabled or Not Installed
Generator Breaker Type Configuration Disabled or Not Installed
Automatic Generator Breaker Control Source
Disabled or Not Installed
Configuration
Generator Definite Time Overcurrent Warning Event
110 %
Percentage Threshold
Generator Inverse Time Overcurrent Shutdown Event
0.27 sec
Time Multiplier
Generator Definite Time Overcurrent Shutdown Event
125 %
Percentage Threshold
Generator Definite Time Overcurrent Shutdown Event
10.0 sec
Notification Delay Time
Generator Over Frequency Warning Event Percentage
105.0 %
Threshold
Generator Over Frequency Warning Event Notification
10 sec
Delay Time
Generator Over Frequency Shutdown Event Percentage
110.0 %
Threshold
Generator Over Frequency Shutdown Event Notification
10 sec
Delay Time
Generator Under Frequency Warning Event Percentage
95.0 %
Threshold
Generator Under Frequency Warning Event Notification
10 sec
Delay Time
Generator Under Frequency Shutdown Event Percentage
90.0 %
Threshold
Generator Under Frequency Shutdown Event Notification
15 sec
Delay Time

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 41 of 56

Generator Over Voltage Warning Event Percentage


110 %
Threshold
Generator Over Voltage Warning Event Notification
10 sec
Delay Time
Generator Over Voltage Shutdown Event Percentage
110 %
Threshold
Generator Over Voltage Shutdown Event Notification
10 sec
Delay Time
Generator Under Voltage Warning Event Percentage
95 %
Threshold
Generator Under Voltage Warning Event Notification
10 sec
Delay Time
Generator Under Voltage Shutdown Event Percentage
90 %
Threshold
Generator Under Voltage Shutdown Event Notification
15 sec
Delay Time
Maximum Engine Speed Bias 400 rpm
Generator Nominal Output Frequency 60.0 Hz
Programmable Cycle Timer #1 Activation Day - Sunday Deactivate
Programmable Cycle Timer #1 Activation Day - Monday Deactivate
Programmable Cycle Timer #1 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #1 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #1 Activation Day - Thursday Deactivate
Programmable Cycle Timer #1 Activation Day - Friday Deactivate
Programmable Cycle Timer #1 Activation Day - Saturday Deactivate
Programmable Cycle Timer #1 Activation Start Time 0 min
Programmable Cycle Timer #1 Active Time 1 min
Programmable Cycle Timer #1 Output #1 Activation
Inactive
Configuration
Programmable Cycle Timer #1 Output #2 Activation
Inactive
Configuration
Programmable Cycle Timer #2 Activation Day - Sunday Deactivate
Programmable Cycle Timer #2 Activation Day - Monday Deactivate
Programmable Cycle Timer #2 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #2 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #2 Activation Day - Thursday Deactivate
Programmable Cycle Timer #2 Activation Day - Friday Deactivate
Programmable Cycle Timer #2 Activation Day - Saturday Deactivate

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 42 of 56

Programmable Cycle Timer #2 Activation Start Time 0 min


Programmable Cycle Timer #2 Active Time 1 min
Programmable Cycle Timer #2 Output #1 Activation
Inactive
Configuration
Programmable Cycle Timer #2 Output #2 Activation
Inactive
Configuration
Programmable Cycle Timer #3 Activation Day - Sunday Deactivate
Programmable Cycle Timer #3 Activation Day - Monday Deactivate
Programmable Cycle Timer #3 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #3 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #3 Activation Day - Thursday Deactivate
Programmable Cycle Timer #3 Activation Day - Friday Deactivate
Programmable Cycle Timer #3 Activation Day - Saturday Deactivate
Programmable Cycle Timer #3 Activation Start Time 0 min
Programmable Cycle Timer #3 Active Time 1 min
Programmable Cycle Timer #3 Output #1 Activation
Inactive
Configuration
Programmable Cycle Timer #3 Output #2 Activation
Inactive
Configuration
Programmable Cycle Timer #4 Activation Day - Sunday Deactivate
Programmable Cycle Timer #4 Activation Day - Monday Deactivate
Programmable Cycle Timer #4 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #4 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #4 Activation Day - Thursday Deactivate
Programmable Cycle Timer #4 Activation Day - Friday Deactivate
Programmable Cycle Timer #4 Activation Day - Saturday Deactivate
Programmable Cycle Timer #4 Activation Start Time 0 min
Programmable Cycle Timer #4 Active Time 1 min
Programmable Cycle Timer #4 Output #1 Activation
Inactive
Configuration
Programmable Cycle Timer #4 Output #2 Activation
Inactive
Configuration
Programmable Cycle Timer #5 Activation Day - Sunday Deactivate
Programmable Cycle Timer #5 Activation Day - Monday Deactivate
Programmable Cycle Timer #5 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #5 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #5 Activation Day - Thursday Deactivate

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 43 of 56

Programmable Cycle Timer #5 Activation Day - Friday Deactivate


Programmable Cycle Timer #5 Activation Day - Saturday Deactivate
Programmable Cycle Timer #5 Activation Start Time 0 min
Programmable Cycle Timer #5 Active Time 1 min
Programmable Cycle Timer #5 Output #1 Activation
Inactive
Configuration
Programmable Cycle Timer #5 Output #2 Activation
Inactive
Configuration
Programmable Cycle Timer #6 Activation Day - Sunday Deactivate
Programmable Cycle Timer #6 Activation Day - Monday Deactivate
Programmable Cycle Timer #6 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #6 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #6 Activation Day - Thursday Deactivate
Programmable Cycle Timer #6 Activation Day - Friday Deactivate
Programmable Cycle Timer #6 Activation Day - Saturday Deactivate
Programmable Cycle Timer #6 Activation Start Time 0 min
Programmable Cycle Timer #6 Active Time 1 min
Programmable Cycle Timer #6 Output #1 Activation
Inactive
Configuration
Programmable Cycle Timer #6 Output #2 Activation
Inactive
Configuration
Programmable Cycle Timer #7 Activation Day - Sunday Deactivate
Programmable Cycle Timer #7 Activation Day - Monday Deactivate
Programmable Cycle Timer #7 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #7 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #7 Activation Day - Thursday Deactivate
Programmable Cycle Timer #7 Activation Day - Friday Deactivate
Programmable Cycle Timer #7 Activation Day - Saturday Deactivate
Programmable Cycle Timer #7 Activation Start Time 0 min
Programmable Cycle Timer #7 Active Time 1 min
Programmable Cycle Timer #7 Output #1 Activation
Inactive
Configuration
Programmable Cycle Timer #7 Output #2 Activation
Inactive
Configuration
Programmable Cycle Timer #8 Activation Day of Week Unavailable
Programmable Cycle Timer #8 Activation Start Time Unavailable min
Programmable Cycle Timer #8 Active Time Unavailable min
Programmable Cycle Timer #8 Output #1 Activation

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 44 of 56

Configuration Unavailable
Programmable Cycle Timer #8 Output #2 Activation
Unavailable
Configuration
Programmable Cycle Timer #9 Activation Day of Week Unavailable
Programmable Cycle Timer #9 Activation Start Time Unavailable min
Programmable Cycle Timer #9 Active Time Unavailable min
Programmable Cycle Timer #9 Output #1 Activation
Unavailable
Configuration
Programmable Cycle Timer #9 Output #2 Activation
Unavailable
Configuration
Programmable Cycle Timer #10 Activation Day of Week Unavailable
Programmable Cycle Timer #10 Activation Start Time Unavailable min
Programmable Cycle Timer #10 Active Time Unavailable min
Programmable Cycle Timer #10 Output #1 Activation
Unavailable
Configuration
Programmable Cycle Timer #10 Output #2 Activation
Unavailable
Configuration
Programmable Cycle Timer #11 Activation Day of Week Unavailable
Programmable Cycle Timer #11 Activation Start Time Unavailable min
Programmable Cycle Timer #11 Active Time Unavailable min
Programmable Cycle Timer #11 Output #1 Activation
Unavailable
Configuration
Programmable Cycle Timer #11 Output #2 Activation
Unavailable
Configuration
Programmable Cycle Timer #12 Activation Day of Week Unavailable
Programmable Cycle Timer #12 Activation Start Time Unavailable min
Programmable Cycle Timer #12 Active Time Unavailable min
Programmable Cycle Timer #12 Output #1 Activation
Unavailable
Configuration
Programmable Cycle Timer #12 Output #2 Activation
Unavailable
Configuration
Programmable Cycle Timer #13 Activation Day of Week Unavailable
Programmable Cycle Timer #13 Activation Start Time Unavailable min
Programmable Cycle Timer #13 Active Time Unavailable min
Programmable Cycle Timer #13 Output #1 Activation
Unavailable
Configuration
Programmable Cycle Timer #13 Output #2 Activation
Unavailable
Configuration
Programmable Cycle Timer #14 Activation Day of Week Unavailable
Programmable Cycle Timer #14 Activation Start Time Unavailable min

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 45 of 56

Programmable Cycle Timer #14 Active Time Unavailable min


Programmable Cycle Timer #14 Output #1 Activation
Unavailable
Configuration
Programmable Cycle Timer #14 Output #2 Activation
Unavailable
Configuration
Electronic Control Module Reduced Power Mode Enable
Disabled
Status
Electronic Control Module Reduced Power Mode Delay
30 min
Time
Relay Output #1 Active State Configuration High
Relay Output #2 Active State Configuration High
Relay Output #3 Active State Configuration High
Relay Output #4 Active State Configuration High
Relay Output #5 Active State Configuration High
Relay Output #6 Active State Configuration High
Relay Output #7 Active State Configuration High
Relay Output #8 Active State Configuration High
Maintenance Level 1 Cycle Interval Hours 500 hours
Maintenance Level 1 Cycle Interval Days 180
Customer Password Security Level to Reset Service
0-No Security
Maintenance Interval
Spare Analog Input Enable Status Disabled
Spare Analog Input Type Configuration Pressure
Spare Analog Input Suspect Parameter Number Engine Oil Temperature
Spare Analog Input High Warning Event Percentage
99 %
Threshold
Spare Analog Input High Temperature Warning Event Deg
230
Threshold F
Spare Analog Input High Pressure Warning Event
131 psi
Threshold
Spare Analog Input High Warning Event Notification
2 sec
Delay Time
Spare Analog Input High Shutdown Event Percentage
100 %
Threshold
Spare Analog Input High Temperature Shutdown Event Deg
239
Threshold F
Spare Analog Input High Pressure Shutdown Event
146 psi
Threshold
Spare Analog Input High Shutdown Event Notification
10 sec
Delay Time
Spare Analog Input Low Warning Event Percentage

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 46 of 56

Threshold 10 %
Spare Analog Input Low Temperature Warning Event Deg
68
Threshold F
Spare Analog Input Low Pressure Warning Event
15 psi
Threshold
Spare Analog Input Low Warning Event Notification
15 sec
Delay Time
Spare Analog Input Low Shutdown Event Percentage
5 %
Threshold
Spare Analog Input Low Temperature Shutdown Event Deg
32
Threshold F
Spare Analog Input Low Pressure Shutdown Event
11 psi
Threshold
Spare Analog Input Low Shutdown Event Notification
30 sec
Delay Time
Spare Analog Input Sensor Configuration Code Map #1
Programmable Trip Point Function #1 Trigger Condition Trip Above Threshold
Programmable Trip Point Function #1 Percentage
90 %
Threshold
Programmable Trip Point Function #1 Hysteresis
5 %
Percentage
Programmable Trip Point Function #1 Trip Activation
10 sec
Delay Time
Programmable Trip Point Function #1 Trip Deactivation
1 sec
Delay Time
Programmable Trip Point Function #2 Trigger Condition Disabled or Not Installed
Programmable Trip Point Function #2 Percentage
-1 %
Threshold
Programmable Trip Point Function #2 Hysteresis
Disabled or Not Installed %
Percentage
Programmable Trip Point Function #2 Trip Activation
Disabled or Not Installed sec
Delay Time
Programmable Trip Point Function #2 Trip Deactivation
Disabled or Not Installed sec
Delay Time
Programmable Trip Point Function #3 Trigger Condition Disabled or Not Installed
Programmable Trip Point Function #3 Percentage
-1 %
Threshold
Programmable Trip Point Function #3 Hysteresis
Disabled or Not Installed %
Percentage
Programmable Trip Point Function #3 Trip Activation
Disabled or Not Installed sec
Delay Time

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 47 of 56

Programmable Trip Point Function #3 Trip Deactivation


Disabled or Not Installed sec
Delay Time
Programmable Trip Point Function #4 Trigger Condition Disabled or Not Installed
Programmable Trip Point Function #4 Percentage
-1 %
Threshold
Programmable Trip Point Function #4 Hysteresis
Disabled or Not Installed %
Percentage
Programmable Trip Point Function #4 Trip Activation
Disabled or Not Installed sec
Delay Time
Programmable Trip Point Function #4 Trip Deactivation
Disabled or Not Installed sec
Delay Time
Generator/Utility Automatic Transfer Enable Status Disabled or Not Installed
Loss of Utility Event Notification Delay Time Disabled or Not Installed sec
Utility to Generator Transfer Delay Time Disabled or Not Installed sec
Generator to Utility Transfer Delay Time Disabled or Not Installed min
Generator to Utility Fast Transfer Delay Time Disabled or Not Installed sec
Utility to Generator Transfer Failure Warning Event
Disabled or Not Installed sec
Threshold
Utility to Generator Transfer Failure Shutdown Event
Disabled or Not Installed sec
Threshold
Generator to Utility Transfer Failure Warning Event
Disabled or Not Installed sec
Threshold
Generator/Utility Automatic Transfer Unpowered Load
Disabled or Not Installed sec
Time
Generator Ready to Load Threshold Percentage Disabled or Not Installed %
Generator Ready to Load Delay Time Disabled or Not Installed sec
Generator to Utility Transfer Mode Disabled or Not Installed
Utility Breaker Closing Pulse Active Time Disabled or Not Installed sec
Utility Breaker Closing Pulse Rest Interval Disabled or Not Installed sec
Utility Breaker Maximum Closing Time Disabled or Not Installed sec
Utility Breaker Maximum Opening Time Disabled or Not Installed sec
Utility Breaker Lockout Configuration Disabled or Not Installed
Engine Serial Number Not Programmed
Display Pressure Units Configuration psi
Display Temperature Units Configuration Degrees Farenheit
Display Volume Units Configuration liters

C27 Genset (MJE00283)


Parameter Value

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 48 of 56

Equipment ID NOT PROGRAMMED


Engine Serial Number MJE00283
ECM Serial Number 33566469JV
Software Group Part Number 3459194-00
Software Group Release Date MAY09
Software Group Description C27 MEUI ACERT A4

Logged Diagnostic Codes [Diagnostic Clock = 4788.7388 hours] - C27 Genset


(MJE00283)
Code Description Occ. First Last
247- 9 SAE J1939 Data Link : Abnormal Update Rate 24 4713 4788
274- 3 Atmospheric Pressure Sensor : Voltage Above Normal 127 3871 4788
168- 1 Electrical System Voltage : Low 37 3953 4786

Logged Event Codes [Diagnostic Clock = 4788.7388 hours] - C27 Genset


(MJE00283)
Code Description Occ. First Last
E390 (1) Fuel Filter Restriction 6 4768 4788

Active Diagnostic Codes - C27 Genset (MJE00283)


Code Description
274- 3 Atmospheric Pressure Sensor : Voltage Above Normal

Active Event Codes - C27 Genset (MJE00283)


Code Description
No Active Events

Current Totals - C27 Genset (MJE00283)


Description Value Unit
Total Fuel 86389 gal
Total Time 4788 hours
Engine Starts 795

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 49 of 56

Average Fuel Rate Based Percent Engine Load Factor 31 %

Configuration - C27 Genset (MJE00283)


Description Value Unit
Equipment ID NOT PROGRAMMED
Engine Serial Number MJE00283
ECM Serial Number 33566469JV
Software Group Part Number 3459194-00
Software Group Release Date MAY09
Software Group Description C27 MEUI ACERT A4
Rating Number 4
Rated Frequency 60 Hz
Rated Engine Speed 1800 rpm
Rated Real Genset Power 800 kW
Unavailable
Rated Apparent Genset Power
Parameter
Rating Configuration Low Emissions
Test Spec 0K74900K7925
Engine Acceleration Rate 350 rpm/s
Low Idle Speed 1200 rpm
Engine Speed Droop 3.0 %
Engine State Control Input Configuration CAN Input
Remote Throttle Control Min Speed 125 rpm
Remote Throttle Control Max Speed 125 rpm
Cooldown Speed 1800 rpm
Cooldown Duration 5 min
Engine Pre-Lube Duration 0 sec
Crank Duration 30 sec
Maximum Number of Crank Cycles 5
Crank Terminate RPM 400 rpm
Droop Mode Selection Isochronous
Ether Control Disabled
Desired Speed Input Configuration CAN Input
Secondary Desired Speed Input Configuration CAN Input
Coolant Level Sensor Installed
Droop/Isochronous Switch Enable Disabled
Emergency Shutdown Override Switch Installation Status Not Installed

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 50 of 56

Emergency Shutdown Override Input Configuration Switch to Ground


Remote Emergency Stop (E-Stop) Switch Input Type
Normally Open
Configuration
Air Intake Shutoff Detection Installation Status Not Installed
Engine Oil Temperature Sensor Installation Status Installed
Governor Gain Factor #1 10000
Governor Minimum Stability Factor #1 600
Governor Maximum Stability Factor #1 3600
FLS 37
FTS -27
Total Tattletale 10

Lifetime: Time vs Engine Coolant Temperature - C27 Genset (MJE00283)


Engine Coolant Temperature( Deg F ) hours %
<122 55.70 1.17
122-130 12.90 0.27
131-139 14.05 0.29
140-148 16.10 0.34
149-157 17.25 0.36
158-166 19.50 0.41
167-175 1222.85 25.58
176-184 3422.00 71.58
185-193 0.05 0.00
194-202 0.05 0.00
203-211 0.15 0.00
212-220 0.20 0.00
221-229 0.00 0.00
230-238 0.00 0.00
239-247 0.00 0.00
>248 0.00 0.00

Lifetime: Time vs Inlet Air Temperature - C27 Genset (MJE00283)


Inlet Air Temperature( Deg F ) hours %
<104 4.85 97.98
104-112 0.00 0.00
113-121 0.10 2.02

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 51 of 56

122-130 0.00 0.00


131-139 0.00 0.00
140-148 0.00 0.00
149-157 0.00 0.00
158-166 0.00 0.00
167-175 0.00 0.00
176-184 0.00 0.00
185-193 0.00 0.00
194-202 0.00 0.00
203-211 0.00 0.00
>212 0.00 0.00

Lifetime: Time vs Boost Pressure - C27 Genset (MJE00283)


Boost Pressure( psi ) hours %
<12 0.60 12.77
12-12 1.90 40.43
13-14 1.75 37.23
15-15 0.45 9.57
16-16 0.00 0.00
17-18 0.00 0.00
19-19 0.00 0.00
20-21 0.00 0.00
22-22 0.00 0.00
23-24 0.00 0.00
25-25 0.00 0.00
26-27 0.00 0.00
28-28 0.00 0.00
>29 0.00 0.00

Lifetime: Total Occurrences vs Engine Speed - C27 Genset (MJE00283)


Engine Speed( rpm ) %
<2500 0.00 0.00
2500-2599 0.00 0.00
2600-2699 0.00 0.00
2700-2799 0.00 0.00
2800-2899 0.00 0.00

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 52 of 56

2900-2999 0.00 0.00


3000-3099 0.00 0.00
3100-3199 0.00 0.00
3200-3299 0.00 0.00
>3300 0.00 0.00

Lifetime: Time vs Engine Speed And Engine Load Factor - C27 Genset (MJE00283)
1100- 1300- 1500- 1700- 1900- 2100-
rpm <1100 >2300 Total
1299 1499 1699 1899 2099 2299
%
<50 0.04 0.06 0.01 0.00 98.81 0.00 0.00 0.00 98.92
50-
0.00 0.00 0.00 0.00 0.92 0.00 0.00 0.00 0.92
60
60-
0.00 0.00 0.00 0.00 0.02 0.00 0.00 0.00 0.02
70
70-
0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
80
80-
0.00 0.00 0.00 0.00 0.02 0.00 0.00 0.00 0.02
90
>90 0.00 0.00 0.00 0.04 0.07 0.00 0.00 0.00 0.11
Total 0.04 0.06 0.01 0.04 99.85 0.00 0.00 0.00 100.00

Injector Trim Calibration - C27 Genset (MJE00283)


Injector Serial Number File Version
Injector1 000000005A5119357998 0
Injector2 000000005A51193574BB 0
Injector3 000000005A51193570A7 0
Injector4 000000005A51193567A7 0
Injector5 000000005A5119359849 0
Injector6 000000005A5119362863 0
Injector7 000000005A511936136D 0
Injector8 000000005A5119359764 0
Injector9 000000005A51193564AE 0
Injector10 000000005A5119361771 0
Injector11 000000005A51193561B5 0
Injector12 000000005A51193548A0 0

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 53 of 56

Monitoring System - C27 Genset (MJE00283)


Description State Trip Point Delay Time
Engine Overspeed
Least Severe (1) Always On 2200 rpm 0 sec
Most Severe (3) Always On 2300 rpm 0 sec
High Engine Coolant Temperature
Least Severe (1) Always On 221 Deg F 10 sec
Moderate Severity (2) Off 232 Deg F 10 sec
Most Severe (3) On 225 Deg F 10 sec
High Engine Inlet Air Temperature
Least Severe (1) Always On 167.0 Deg F 8 sec
Moderate Severity (2) Off 174.2 Deg F 8 sec
High Engine Oil Temperature
Least Severe (1) On 230 Deg F 15 sec
Moderate Severity (2) Off 239 Deg F 15 sec
Most Severe (3) Off 239 Deg F 15 sec
High Fuel Filter Pressure Restriction
Least Severe (1) On None 30 sec
Moderate Severity (2) Off None 28800 sec
Most Severe (3) Off None 28800 sec
High Fuel Pressure
Least Severe (1) On 127.6 psi 8 sec
Moderate Severity (2) Off 132.0 psi 10 sec
Most Severe (3) Off 133.4 psi 12 sec
High Fuel Temperature
Least Severe (1) Always On 194.0 Deg F 30 sec
Moderate Severity (2) Off 195.8 Deg F 10 sec
Most Severe (3) Off 197.6 Deg F 10 sec
Low Coolant Level
Least Severe (1) On None 10 sec
Moderate Severity (2) Off None 10 sec
Most Severe (3) Off None 10 sec
Low Engine Oil Pressure
Least Severe (1) Always On None 8 sec
Most Severe (3) Always On None 4 sec
Low Fuel Pressure
Least Severe (1) On 63 psi 10 sec

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 54 of 56

Moderate Severity (2) Off 62 psi 10 sec


Most Severe (3) Off 60 psi 10 sec

Digital Voltage Regulator


Parameter Value
ECM Part Number 235-5725
ECM Serial Number 35366118GD
Software Group Part Number 2790916-00
Software Group Release Date Aug2005
Software Group Description Regulator Software

Logged Diagnostic Codes [Diagnostic Clock = Unavailable hours] - Digital Voltage


Regulator
Code Description Occ. First Last
No Logged Diagnostic Codes

Logged Event Codes [Diagnostic Clock = Unavailable hours] - Digital Voltage


Regulator
Code Description Occ. First Last
No Logged Events

Active Diagnostic Codes - Digital Voltage Regulator


Code Description
No Active Codes

Active Event Codes - Digital Voltage Regulator


Code Description
No Active Events

Configuration - Digital Voltage Regulator


Description Value Unit

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 55 of 56

Voltage Regulator Power Input Frequency Configuration 240 Hz


Potential Transformer Primary Winding Rating 120 Volts
Potential Transformer Secondary Winding Rating 120 Volts
Current Transformer Primary Winding Rating 1500 Amps
Current Transformer Secondary Winding Rating 5 Amps
Generator Connection Configuration Three Phase
Generator Rated Frequency 60 Hz
Generator Rated Voltage 480 Volts
Generator Rated Current 1245 Amps
Voltage Regulator Loss of Sensing Shutdown Event Notification
2.0 sec
Delay Time
Generator Rotating Diode Monitor Shutdown Event Current
2.0 Amps
Threshold
Generator Reverse VAr Shutdown Event Percentage Threshold 40 %
Generator Reverse VAr Shutdown Event Notification Delay
0.5 sec
Time
Generator Reverse VAr Shutdown Event Response Activate Warning
Configuration Condition
Generator Over Voltage Shutdown Event Percentage Threshold 135 %
Generator Over Voltage Shutdown Event Notification Delay
2 sec
Time
Generator Over Voltage Shutdown Event Response Activate Warning
Configuration Condition
Generator Under Voltage Shutdown Event Percentage
60 %
Threshold
Generator Under Voltage Shutdown Event Notification Delay
30 sec
Time
Generator Under Voltage Shutdown Event Response Activate Warning
Configuration Condition
Voltage Regulator Over Excitation Shutdown Event Threshold 12.0 Amps
Voltage Regulator Over Excitation Shutdown Event Notification
10.0 sec
Delay Time
Voltage Regulator Over Excitation Shutdown Event Notification
Definite Time
Delay Type
Voltage Regulator Fault Reset Switch Diagnostic Response Activate Warning
Configuration Condition
Generator Nominal Output Voltage 480 Volts
Voltage Regulator Corner (Knee) Frequency 59.8 Hz
Voltage Regulator Deviation From Corner (Knee) Frequency 5.0 Hz
Voltage Regulator Volts/Hz Slope 1 2.0

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013


Page 56 of 56

Voltage Regulator Volts/Hz Slope 2 2.0


Voltage Regulator Minimum Voltage Setpoint Percentage 50.0 %
Voltage Regulator Minimum Frequency Threshold 33.0 Hz
Voltage Regulator Maximum Droop Percentage 0.0 %
Voltage Regulator Voltage (IR) Compensation Percentage 0.0 %
Voltage Regulator Starting Time 5.0 sec
Voltage Regulator Starting Voltage Percent 10.0 %
Voltage Regulator Noise Filter Time Constant 0.00 sec
Voltage Regulation Proportional Gain Percentage 20.00 %
Voltage Regulation Integral Gain Percentage 60.00 %
Voltage Regulation Derivative Gain Percentage 3.00 %
Voltage Regulator Gain Setting Selection Number 7
Voltage Regulator Gain Setting Type Configuration User Defined
Voltage Regulator Loop Gain Percentage 5.00 %
Maximum Generator Voltage Output Bias Percentage Setpoint 15 %
Generator Nominal Output Power Factor 1.00
Voltage Regulator Nominal Reactive Power Percentage 0.0 %
Generator Power Factor Controller Loop Gain Percentage 0.30 %
Generator Power Factor Controller Integral Gain Percentage 0.50 %
Voltage Regulator Load Compensation Type Configuration Off
Voltage Regulator Power Factor/VAr Controller Mode Selection Reactive Power
Voltage Regulator Desired Power Factor Configuration Lagging
Generator VAr Controller Loop Gain Percentage 0.25 %
Generator VAr Controller Integral Gain Percentage 0.50 %

file://C:\Documents and Settings\All Users\Application Data\Caterpillar\Electronic Technici... 6/9/2013