Sunteți pe pagina 1din 1

PROTECTIONS

MD BFP PROTECTIONS
S. No. DESCRIPTIONS NORMAL ALARM TRIP REMARKS
1 Lub oil pressure (kg/cm2) 2-3 1.2 < 0.8
2 ΔT for feed water suc/disch > 10⁰C > 15⁰C
3 Deaerator level (mmwc) -1730
4 Working oil temp ⁰C 60 - 100 110⁰C > 130⁰C
5 CI sealing quench pr. low (ΔP) < 1.7 kg/cm2 < 1.2 kg/cm2 For 10 sec
6 Working oil pressure (kg/cm2) 3.5 - 4.5 < 2.2 kg/cm2
7 Suction valve not open TRIP
8 Motor protection acted TRIP

TD BFP PROTECTIONS
S. No. DESCRIPTIONS NORMAL ALARM TRIP REMARKS
1 Lub oil pressure (kg/cm2) 2.5 1.6 < 1.0
2 Gov. oil pressure (kg/cm2) > 7.0 6.5 < 4.5
3 Live steam pressure (kg/cm2) < 7.46 12 > 12.5
4 Exhaust steam pressure (kg/cm2) -0.9 -0.6 -0.3
5 Exhaust steam temp (⁰C) 50 110 120
6 Axial shift (mm) < 0.5 0.5 + / - 0.7
7 Eccentricity (μ) < 75 μ 75 μ 85 (90) μ modified
8 Bearing vibrations (μ) < 50 60 70 μ /100 μ modified
9 Thrust / Journal brg. Temp (⁰C) < 85 100 > 110
10 CI sealing quench ΔP (kg/cm2) < 1.7 < 1.2 kg/cm2 for 10 sec
11 ΔT for feed water suc/disch 5 7 > 15.0 ⁰C
12 Remote manual trip PB operated TRIP
13 Suction valve not open TRIP
14 Trip lever on Gov. rack operated TRIP
15 Emergency PB on local panel TRIP
16 Trip lever on thrust brg operated TRIP
17 Turbine overspeed - 6200 rpm 6150 6200 rpm TRIP Mech
18 Turbine overspeed - 6250 rpm 6150 6250 rpm TRIP Electrical
19 Dearator level low -1730 mmwc
20 Diffe. expansion (rotor - casing) +3, -2.5 mm +3.5, -4 mm
21 GB shaft vibrations (I/P) 50 μ 75 μ
22 GB shaft vibrations (O/P) 50 μ 100 μ
23 Turbine R J brg. Shaft vibr. (F/R) 50 μ 100 μ

My docu/ bfp protections.xlsx