DATA SHEET
NF MCCB
Based on Mitsubishi MCCB Datasheet
Detailed Specifications 12485
Molded-Case Circuit Breakers
Photo
3 5 10 3 4 6 10 16 3 4 6 10 16 20 3 4 6 10 16 20 10 16 20 25 32 50 63 80
Rated current In (Amp.) 15 20 30 20 25 32 25 32 40 50 63 25 32 40 50 63 40 50 63 100 125
Rated ambient temperature (°C) 30 40 40 40 40 40
Number of poles 2 3 2 3 2 3 2 3 4 2 3 4 2 3
Rated insulation voltage Ui (V) 500 600 600 600 690 600
690V – – – – 2.5/1 –
525V – – – – – –
500V – 2.5/1 2.5/1 7.5/4 7.5/4 7.5/4
Rated AC 440V – 2.5/1 2.5/1 7.5/4 10/5 10/5
short-circuit IEC60947-2 (50/60Hz) 415V 1.5/1.5 2.5/1 2.5/1 7.5/4 10/5 10/5
breaking (Icu/Ics) 400V – 5/2 5/2 7.5/4 10/5 10/5
capacities (kA) 380V 1.5/1.5 5/2 5/2 7.5/4 10/5 10/5
230V 2.5/2 (240V) 7.5/4 7.5/4 15/8 25/13 30/15
250V – 2.5/1 ✽4 – 2.5/1 ✽4 – 7.5/4 ✽4 – 7.5/4 ✽4 – 7.5/4 ✽1
DC
300V – – – – – –
Suitability for isolation – ● ● ● ● ●
Utilization category A A A A A A
Reverse connection (terminals unmarked) – ● ● ● ● ●
Rated impulse withstand voltage Uimp (kV) 4 6 6 6 6 8
Pollution degree 2 2 2 2 2 3
without current 10,000 10,000 10,000 15,000 15,000 10,000
440V-In/2 6,000 (415V) 6,000 6,000 15,000 15,000 6,000
Number of operating cycles 440V-In 6,000 (415V) 6,000 6,000 8,000 8,000 6,000
with current
690V-In/2 – – – – – –
690V-In – – – – –- –
a ca a 45 67.5 50 75 50 75 50 75 100 50 75 100 60 90
c
Overall dimensions (mm) b 96 130 130 130 130 130
b c 52 68 68 68 68 68
ca 67 90 90 90 90 90
Mass of front-face type (kg) 0.25 0.35 0.4 0.55 0.45 0.6 0.45 0.6 0.7 0.45 0.6 0.7 0.65 0.9
Screw terminal ● ● ● ● ● ●
Front Solderless (box) terminal (SL) – – – – – ●
Fixed
Busbar terminal – – – – – –
Installation
and Rear (B) ● ● ● ● ● ●
connections Rear (PM) – ● ● ● ● ●
Plug-in
Rear/front IP20 (PM-IP) – – – – – –
IEC 35mm Mounting hook (option) – ● ● ● ● –
rail Adapter (option) ● – – – – ●
Alarm switch (AL) ● ● ● ● ● ●
Cassette-type Auxiliary switch (AX) ● ● ● ● ● ●
accessories Shunt trip (SHT) – ● ● ● ● ●
(option) ✽ 5 ● ● ● ● ●
Undervoltage trip (UVT) Non-Synchronous Closing (UVT-N) –
Synchronous Closing (UVT-S) – – – – – ●
Accessorie’s with Lead-wire terminal block (SLT) ● ● ● ● ● ●
connection with Internal terminal type (INT) – – – – – –
(option) with Flying leads ● ● ● ● ● ●
Built-in Pre-alarm (contact output) ✽ 3 (PAL) – – – – – –
accessories Overcurrent trip alarm ✽ 3 (OAL) – – – – – –
(option) Cylinder key lock Available soon – – – – – ●
(S) ● ● ● ● – ● – ●
Dustproof
Enclosure (I) – ● ● ● – ● – ●
Waterproof (W) – – ● – ● – ● – – ● – – ●
Electrical operation device (MD) – – – – – – ●
Mechanical interlock (MI) – ● ● ● ● ●
(HL) ● ● ● ● ● ●
Handle lock device Handle lock
(HL-S) – ● ● ● ● ●
Lock cover (LC) ● ● ● ● ● ●
External
accessories (V) – – ● – ● – ● – ● – ●
External Door mounting
(option) (S) – ● ● ● ● ●
operating
handle (R) – – – – – ●
Mounted on breaker
(F) – ● ● ● ● ●
Insulating Between phase (BA-F) – ● ● ● ● ●
barrier To ground (BA-G) – ● ● ● ● ●
Large (TC-L) ● ● ● ● ● ●
Small (TC-S) ● ● ● ● ● ●
Terminal
cover Transparent (TTC) ● ● ● ● ● ●
for rear connection (BTC) ● ● ● ● ● ●
for plug-in (PTC) – ● ● ● ● ●
L/R ● ● ● ● – ● – ●
G/L – ● ● ● – ● – ●
Marine approval Available soon BV – ● ● ● – ● – ●
DNV – ● ● ● – ● – ●
ABS ● ● ● ● – ● – ●
Hydraulic- Hydraulic- Hydraulic- Hydraulic- Hydraulic- Thermal-
Automatic tripping device magnetic magnetic magnetic magnetic magnetic magnetic
Trip button – Equipped Equipped Equipped Equipped Equipped
Notes ✽ 1: Use two poles in the case of three-pole or four-pole products.
In addition, wiring as shown to the right allows the three poles to be used Line Line
for up to 400V DC and the four poles to be used for up to 500V DC.
✽ 2: Use two poles in the case of three-pole or four-pole products.
In addition, wiring as shown to the right allows the three poles to be used
for up to 500V DC and the four poles to be used for up to 600V DC.
✽ 3: Both PAL and OAL is not available. Only one specified.
✽ 4: Specify if for DC use. Load Load
✽ 5: Cassette-type accessories are not suitable for NF30-CS. 3-pole 4-pole
NF125-SW
NF125-SGW
RT
NF125-SGW
RE NF125-HW
NF125-HGW
RT
NF125-HGW
RE
NF125-RGW
RT
NF125-UGW
RT
2
16 20 32 40 50 63 16–25 25–40 40–63 16–32 32–63 63–100 16 20 32 40 50 63 16–25 25–40 40–63 16–32 32–63 63–100 16–25 25–40 16–25 25–40
80 100 125 63–100 80–125 75–125 80 100 63–100 80–125 75–125 40–63 63–100 40–63 63–100
40 40 40 40 40 40 40 40
2 3 4 2 3 4 3 4 2 3 4 2 3 4 3 4 2 3 2 3 4
690 690 690 690 690 690 690 690
8/4 8/8 8/8 10/5 20/20 20/20 25/25 30/30
18/5 22/22 22/22 22/11 35/35 35/35 – –
18/9 30/30 30/30 30/15 50/50 50/50 125/125 200/200
25/13 36/36 36/36 50/25 65/65 65/65 125/125 200/200
30/15 36/36 36/36 50/25 70/70 70/70 125/125 200/200
30/15 36/36 36/36 50/25 75/75 75/75 125/125 200/200
30/15 36/36 36/36 50/25 75/75 75/75 125/125 200/200
50/25 85/85 85/85 100/50 100/100 100/100 125/125 200/200
15/8 ✽1 – – 40/20 ✽1 – – – –
– 20/20 ✽ 2 – – 40/40 ✽ 2 – – –
● ● ● ● ● ● ● ●
A A A A A A A A
● ● ● ● ● ● ● ●
8 8 8 8 8 8 8 8
3 3 3 3 3 3 3 3
25,000 50,000 50,000 25,000 50,000 50,000 50,000 50,000
20,000 40,000 40,000 20,000 40,000 40,000 40,000 40,000
10,000 30,000 30,000 10,000 30,000 30,000 30,000 30,000
1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
60 90 120 105 140 105 140 90 120 105 140 105 140 105 105 140
130 165 165 130 165 165 240 240
68 86 86 68 86 86 86 86
90 110 110 90 110 110 110 110
0.7 0.95 1.3 2.0 2.6 2.0 2.6 0.8 0.95 1.3 2.0 2.6 2.0 2.6 3.1 3.1 3.9
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
– – – – – – – –
● ● ● ● ● ● ● ●
● – – ● – – ● ● –
– ● ● – ● ● – –
– – – – – – – – – –
● – – – ● – – – – –
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● – – ● – – – –
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
– ● ● – ● ● ● ●
● ● ● ● ● ● ● ●
– – ● – – ● – –
– – ● – – ● – –
● ● ● ● ● ● ● ●
● – – – ● – – – – –
● – ● – ● – ● – ● – ● – – –
● – ● – ● – ● – ● – ● – – –
– ● ● ● – ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
– ● ● ● – ● ● ● ● ●
● – – ● ● ● – –
● ● ● ● ● ● ● ●
● ● ● ● ● ● – –
● ● ● ● ● ● ● ●
● – – ● – – – –
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● – ● ● ● – ● ● ● ● –
● – ● ● ● – ● ● ● ● –
● – ● ● ● – ● ● ● ● –
● – ● ● ● – ● ● ● ● –
● – ● ● ● – ● ● ● ● –
Thermal- Thermal- Electronic Thermal- Thermal- Thermal- Thermal-
magnetic magnetic Electronic magnetic magnetic
magnetic magnetic
Equipped Equipped Equipped Equipped Equipped Equipped Equipped Equipped
Photo
Rated current In (Amp.) 125 150 160 125–160 80–160 125 150 160 125–160 80–160
Photo
250 300 350 400 250 300 350 400 200~400 200~400 200~400
Rated current In (Amp.) adjustable adjustable adjustable
Rated ambient temperature (°C) 40 40 40 40 40
Number of poles 2 3 2 3 4 3 4 3 4 3
Rated insulation voltage Ui (V) 600 690 690 690 690
690V – 10/10(5/5) ✽1 10/10(5/5) ✽1 10/10 15/10
500V 15/8 30/30(25/25) ✽1 30/30(25/25) ✽1 50/50 70/35
Rated 440V 25/13 42/42(36/36) ✽1 42/42(36/36) ✽1 65/65 125/63
AC
short-circuit IEC60947-2 (50/60Hz) 415V 36/18 45/45(36/36) ✽1 45/45(36/36) ✽1 70/70 125/63
breaking (Icu/Ics) 400V 36/18 45/45(36/36) ✽1 45/45(36/36) ✽1 70/70 125/63
capacities (kA) 380V 40/20 50/50(42/42) ✽1 50/50(42/42) ✽1 70/70 125/63
230V 50/25 85/85(65/65) ✽1 85/85(65/65) ✽1 100/100 150/75
DC 250V 20/10 ✽4 – 40/40 ✽4 – – – –
Suitability for isolation ● ● ● ● ●
Utilization category A A B B B
Rated short-time withstand current Icw (kA) – – 5 5 5
Reverse connection (terminals unmarked) ● ● ● ● ●
Rated impulse withstand voltage Uimp (kV) 8 8 8 8 8
Pollution degree 3 3 3 3 3
a ca a 140 140 185 140 185 140 185 140
c
Overall dimensions (mm) b 257 257 257 257 257
b c 103 103 103 103 103
ca 134 155 155 155 155
Mass of front-face type (kg) 4.7 5.5 4.9 5.7 7.5 6 7.8 6 7.8 6
Screw terminal – – – – –
Front Solderless (box) terminal (SL) ● ● ● – –
Installation Fixed
Busbar terminal ● ● ● ● ●
and
connections Rear (B) ● ● ● ● ●
Rear (PM) ● ● ● ● ●
Plug-in
Rear/front IP20 (PM-IP) – – – – –
Alarm switch (AL) ● ● ● ● ●
Cassette-type Auxiliary switch (AX) ● ● ● ● ●
accessories Shunt trip (SHT) ● ● ● ● ●
(option) ● ● ● ● ●
Undervoltage trip (UVT) Non-Synchronous Closing (UVT-N)
Synchronous Closing (UVT-S) ● ● ● ● ●
Accessorie’s with Lead-wire terminal block (SLT) ● ● ● ● ●
connection with Internal terminal type (INT) – – – – –
(option) with Flying leads ● ● ● ● ●
Built-in Pre-alarm (contact output) ✽ 3 (PAL) – – ● ✽2 ● ✽2 ● ✽2
accessories Overcurrent trip alarm ✽ 3 (OAL) – – – – –
(option) Trip indicator (TI) – – ● ● ●
(S) – – – – –
Dustproof (I)
Enclosure ● ● – ● – – –
Waterproof (W) ● ● – ● – – –
Motor-
Electrical operated type (MD) ● ● ● ● ●
operation
Spring-
device
charge type
(MDS) ● ● ● ● ●
Mechanical interlock (MI) ● ● ● ● ●
(HL) ● ● ● ● ●
Handle lock device Handle lock
(HL-S) ● ● ● ● ●
External Lock cover (LC) – – – – –
accessories
(option) (V) ● ● ● ● ●
External Door mounting
(S) ● ● ● ● ●
operating
handle (R) ● ● ● ● ●
Mounted on breaker
(F) ● ● ● ● ●
Insulating Between phase (BA-F) ● ● ● ● ●
barrier To ground (BA-G) ● ● ● ● ●
Large (TC-L) ● ● ● – –
Small (TC-S) – – – – –
Terminal
cover Transparent (TTC) ● ● ● ● ●
for rear connection (BTC) ● ● ● – ● –
for plug-in (PTC) ● ● – ● – ● – ●
L/R ● ● – ● – ● – ●
G/L ● ● – ● – ● – ●
Marine approval BV ● ● – ● – ● – ●
DNV – – – ● – – – –
ABS ● ● – ● – ● – ●
Thermal- Thermal-
Automatic tripping device magnetic Electronic Electronic Electronic
magnetic
Trip button Equipped Equipped Equipped Equipped Equipped
Notes ✽ 1: In case of solderless terminal, interrupting capacity reduces: ( / ).
✽ 2: Solid state relay output is option . Please specify if other output is
necessary. (Standard type is thus SLT equipped.)
✽ 3: Both PAL and OAL is not available. Only one specified.
✽ 4: Specify if for DC use.
● ● ● ● ● ● ●
● ● ● ● ● ● ●
● ● ● ● ● ● ●
● ● ● ● ● ● ●
– – – – – – –
– ● ● ● ● ● –
● ● ● ● ● ● ●
– ● ● ● ● ● –
● ● ● ● ● ● ●
● ● ● ● ● ● ●
● ● ● ● ● ● ●
● ● ● ● ● ● ●
– – – – – – –
– ● ● ● ● ● –
● ● ● ● ● ● ●
– – – – – – –
● – ● ● – ● – ● – ● ● –
● – ● ● – ● – ● – ● ● –
● – ● ● – ● – ● – ● ● –
– – – – – ● – – – – – –
● – ● ● – ● – ● – ● ● –
Electronic Thermal- Thermal- Electronic Electronic Electronic
magnetic magnetic Electronic
Equipped Equipped Equipped Equipped Equipped Equipped Equipped
Photo
40 40 40 40 40 40 40
3 4 2 3 4 2 3 4 3 4 2
690 – 690 – 690 690 –
25/13 – 25/13 – – 25/13 –
65/33 – 65/33 – 85/42 65/33 –
85/43 – 85/43 – 125/65 85/43 –
– – – – – – –
85/43 – 85/43 – 125/65 85/43 –
– – – – – – –
125/63 – 125/63 – 170/85 125/63 –
– 40/20 ✽4 – 40/20 ✽4 – – 40/20 ✽4
– – – – – – –
B A B A B B A
20 – 20 – 20 20 –
● ● ● ● ● ● ●
8 8 8 8 8 8 8
3 3 3 3 3 3 3
210 280 210 210 280 210 240 310 210 280 210
406 406 406 406 406 406 406
140 140 140 140 144 140 140
190 190 190 190 194 190 190
23.5 30.7 22 23.5 30.7 22 37.2 46.7 34.5 41.2 32
– – – – – – –
– – – – – – –
● ● ● ● ● ● ●
● ● ● ● ● ● ●
● – ● – ● – – –
– – – – – – –
● ● ● ● ● ● ●
● ● ● ● ● ● ●
● ● ● ● ● ● ●
● ● ● ● ● ● ●
● ● ● ● ● ● ●
● ● ● ● ●(LT) ● ●
– – – – – – –
● ● ● ● ● ● ●
– – – – – – –
– – – – – – –
– – – – – – –
– – – – – – –
● – ● ● – ● – – –
● – ● ● – ● – – –
● ● ● ● ● ● ●
● ● ● ● ● ● ●
● ● ● ● ● ● ●
● ● ● ● ● ● ●
– – – – – – –
– – – – – – –
– – – – – – –
● ● ● ● ● ● ●
– – – – – – –
● ● ● ● ● ● ●
● ● ● ● – ● ●
● ● ● ● ● ● ●
● ● ● ● ● – –
– – – – – – –
– – – – – – –
– – – – – – –
– – – – – – –
● – – ● – – – – –
● – – ● – – – – –
– – – – – – – – –
– – – – – – – – –
● – – ● – – – – –
Electronic Thermal- Electronic Thermal- Electronic Electronic
magnetic magnetic magnetic
Equipped Equipped Equipped Equipped Equipped Equipped Equipped
Rated breaking
500V —
capacity (kA)
IEC60947-2 AC 415V 1.5/1.5
(Icu/Ics)
380V 1.5/1.5
240V 2.5/2
DC 250V —
Suitability for isolation —
Utilization category A
Reverse connection —
Type NF30-CS
Rated impulse withstand voltage Uimp (kV) 4
Pollution degree 2
■Operating Characteristics
3h
2h
Operating Characteristics
1h
40min Type NF30-CS
MB30-CS
20min
10min
6min
4min
2min
1min
40s
30s Max.
20s
Operating time
10s
6s
4s
2s
1s
0.6s
0.4s Min.
0.2s
0.1s
0.06s
0.04s
0.02s
0.01s
1 1.3 2 3 4 5 7 10 20 30 40 50 70 100
×100% of rated current
300
mounting mounting direction
change rate (%)
Operating time
250
200
2-pole 150
100
80
70
3-pole
-5 0 10 20 30 40 50
Front connection
76.5
84
64
54
96
ø8.5
ø5.5
ø5
6
10
23.5 47 23.5
12.5 (max.)
28
45 67.5
49 2-pole 3-pole
Bus t max. =3
Drilling plan
2-pole 3-pole 3 52
Bus drilling for
direct connection
67
Rear connection
3-pole
M4 × 0.7 taps 2-pole
or ø5 Breaker
Mtg plat t max. =3.2 Breaker
R2
20
45 (min)
25 (min)
76.5
76.5
84
5
18
38.5
58.5
23.5 23.5 20
ø14
55 47
Insulating tube Front-plate cutout
8
Breaker mtg
M6 screw 2-pole 3-pole 1mm clearance on
M4 × 0.7 screw
each side of handle
2-pole 3-pole Drilling plan
6
25.5
80.5
77.5
63
40.5
7.5
2
9.5
18.5
5
100
35
31
4
52
Installation utensil
for 35mm IEC-rail 55
2-pole 3-pole 58
70
NF32-SW NF63-CW Type name NF32-SW NF63-CW NF63-SW NF63-HW MB30-SW MB50-CW MB50-SW
0.8 1.2 1.4
3 4 6 10 3 4 6 10 3 4 6 10 10 16 20 8 10 12 0.8 1.2
NF63-SW NF63-HW Rated current In (Amp.) 16 20 25 16 20 25 32 16 20 25 32 25 32 40
2 2.5 4 5
16 25 32 1.4 2 2.5
7.1 8 10 12
32 40 50 63 40 50 63 50 63 40 45 4 5 7.1
MB30-SW MB50-CW 16 25
Number of poles 2∗1 3 2∗1 3 2∗1 3 4 2∗1 3 4 3 3 3
MB50-SW Rated insulation voltage Ui (V) 600 600 600 690 500 500 500
690V – – – 2.5/1 – – –
Type NF32-SW
■Operating Characteristics
4h 4h 4h
2h 2h 2h
AC use (IEC60947-2)
1h 1h DC use (IEC60947-2) 1h (IEC60947-2)
NF32-SW MB30-SW
30min NF63-CW NF63-SW NF63-HW 30min NF32-SW 30min MB50-CW MB50-SW
20min 20min NF63-CW NF63-SW NF63-HW 20min
14min 14min 14min
10min 10min 10min
6min 6min 6min
4min 4min 4min
Operating time
Operating time
5s 5s 5s
2s 2s 2s
Min. Min. Min.
1s 1s 1s
Rated ambient
250
Operating time
200
AL AX
150
SHT or UVT
3-pole 100
Lead wire 80
70
direction
Remark: (1) refer to page 0. –10 0 10 20 30 40 50 60
Notes: (*1) The designation depends on the number of poles. Refer to the reference page.
(*2) HLF types are used for OFF-lock, and HLN types for ON-lock.
Front connection
Insulation barrier
(removable) M5×0.8 screw Applicable M4×0.7 taps
(M6 for 63A) wire size:1.6mm-dia.to 22mm2 or 5mm dia.hole
Mounting hole
24 Breaker
50
Screw terminal
111
130
111
84
50
φ4.5
φ8.5
Trip button
φ5.5
(6.5mm-diameter for 63A)
22 25 45
25 25
Neutral pole
6
25 50 75 61
4 72 (Conductor thickness
2-pole 3-pole 4-pole t=5 max.) Drilling plan
90
Conductor drilling
for direct connection
Rear connection
2-pole 4-pole
R1
111
111
52
8
50 M4×0.7 screw
for mounting breaker 25 22.5
M6 screw φ14
27 min.
25 25 50 70
68 42 25 50 75
6
Drilling plan Front-panel cutout
Plug-in
25
54
11
Center line of
180
83.5
111
54
80
54
7
25
25 50
21 M6 screw
10 55 φ6.5
57 82 107
89 30 Conductor drilling
Details of terminal 2-pole for direct connection 2-pole 3-pole 4-pole
6mm-dia.hole or
Cutout and drilling plan or M5×0.8 taps
Rated short-circuit
AC
(50/60Hz) 440V 10/5 25/13 50/25 25/13
IEC60947-2 400V 10/5 30/15 50/25 30/15
(Icu/Ics) 230V 30/15 50/25 100/50 50/25
250V 7.5/4 – 15/8 – 40/20 – –
DC ∗1 400V – 7.5/4 – 15/8 – 40/20 –
500V – – 15/8 – 40/20 –
Suitability for isolation ● ● ● ●
Utilization category A A A A
Reverse connection (terminals unmarked) ● ● ● ●
Rated impulse withstand voltage Uimp (kV) 8 8 8 8
Pollution degree 3 3 3 3
Type NF125-CW ∗1: When wired as shown at the bottom of page 13, 3-pole models can be used for up to 400 V DC, and
4-pole models for up to 500 V DC.
■Operating Characteristics
4h 4h 4h 4h
2h 2h 2h 2h
NF125-CW 50A~100A
1h NF125-SW 40A~100A 1h NF125-SW 16A~20A 1h 1h MB100-SW 32A
NF125-HW 40A~100A NF125-HW 16A~20A NF125-CW 125A NF125-SW 32A
30min MB100-SW 40A~100A 30min MB100-SW 12.5A~25A 30min NF125-SW 125A 30min NF125-HW 32A
20min (IEC 60947-2) 20min (IEC 60947-2) 20min (IEC 60947-2) 20min (IEC 60947-2)
14min 14min 14min 14min
10min 10min 10min 10min
6min 6min 6min 6min
4min 4min 4min 4min
Max. (60A~100A) Max.
2min 2min 2min 2min
Max. (40A~50A) Max.
Operating time
Operating time
Operating time
Operating time
5s 5s 5s 5s
Min. Min. Min.
2s 2s Min. 2s 2s
1s 1s 1s 1s
×100% of Rated current ×100% of Rated current Max. total ×100% of Rated current ×100% of Rated current
breaking time
Remark: (1) Only AC characteristics are available for the model MB100-SW.
Lead wire 90
direction
80
–10 0 10 20 30 40 50 60
Remark: (1) refer to page 50. Ambient temperature (°C)
R R1SW 64 Large TC-L TCL-1SW3W (*1) Insulation barrier: (2P: 1pc, 3P: 2pcs, 4P: 3pcs)
LC LC-1SW Skeleton TTC TTC-1SW3 (*1) 66
(*4) HLF-1SW Rear BTC BTC-1SW3W (*1) Note: These are supplied with NF125-SW, NF125-HW, and
Handle lock device 76 MB100-SW models.
HL HLN-1SW Pulg-in PTC PTC-1SW3W (*1)
HL-S HLS-1SW (*1)(*4) IEC 35mm rail
DIN-1SW3 (*1) 76
mounting adapters
Electrical
operation device MDS-NF1SWE (*3) 67
Notes: (*1) The designation depends on the number of poles. Refer to the reference page.
(*2) Attach the letter "F" to the end of designation for a fixed type.
(*3) Specify the working voltage. An order should be placed at the same time as an order of circuit breaker main body.
(*4) HLF and HLS types are used for OFF-lock, and HLN types for ON-lock.
Front connection
Insulation barrier
Solderless terminal
(removable)
for wire size
C
L C
L
Mounting hole M8 screw 14~2/0AWG CU/AL
C 24 Breaker
L C
L C
L C
L
50
110-111
C
L C
L
Wire connection
112
130
84
50
Trip
button
φ8.5 30 30
30 22 30 45
61 M4X0.7 taps
8
60 60 90
Neutral or 5mm-dia. hole
68
pole
90 120 19 max. 2-pole 3-pole 4-pole
4 72
90
2-pole 3-pole 4-pole Drilling plan
(Conductor thickness
t=5 max.)
Conductor drilling
for direct connection
Rear connection
4-pole
4-pole
3-pole
Mounting base Breaker 2-pole 3-pole C
L
2-pole
102 C
L C
L C
L Breaker
Mounting plate Stud rotatable C
L C
L
t=3.2 max. 52 by 90°
110-111
C
L C
L
R1
112
1
R
52
Connection
6
C
L
112
15 allowance
16
30 30 30 28
φ18 57
86
8.5
60 30
5 M4×0.7
M8 bolt breaker
2.5 90
60 mounting screw
15 2.5
Insulation M4×0.7 taps or 1.0mm clearance on each side
68 54.5 15 tube 5mm-dia. hole of the handle frame.
6
72 104.5 2-pole 3-pole 4-pole
Front-panel cutout
Drilling plan
Plug-in
3-pole 4-pole
M5×0.8 125
Terminal block 95
Breaker (plug-in terminal block)
mounting screw 90
Mounting plate
60
30 C
L C
L C
L
Plug-in terminal block
56
11
C
L C
L
5.5 20
190
134
98
54
94
16.5 max.
12
56
30
21 30 60
φ8.5
12.5 65
M8 screw
89 30 67 97 127
Remark: 2-pole model of NF125-HW are 3-pole model with the central pole removed.
NF250-CW NF250-SW Type name NF160-SW NF160-HW NF250-CW NF250-SW NF250-HW MB225-SW
NF250-HW NF160-SW Rated current In (Amp.) 125 150 160 125 150 160
125 150 175 125 150 175
200 225 250 200 225 250
125 150 175 125 150 175
200 225 250 200 225
NF160-HW MB225-SW
Number of poles 2 3 4 2 3 4 2 3 2 3 4 2 3 4 3
Rated insulation voltage Ui (V) 690 690 600 690 690 500
690V – 5/3 – – 5/3 –
500V 15/8 30/8 10/5 15/8 30/8 –
1h
NF250-SW NF160-SW 120
30min NF250-HW NF160-HW
20min 110
14min
10min
6min 100
4min
2min 90
Max.
Operating time
1min 80
–10 0 10 20 30 40 50 60
30s
20s Ambient temperature (°C)
(rated ambient 40°C)
10s
5s
Min.
2s
1s
■Internal Accessories
0.5s 250A AC
0.2s
Max. total Operating handle
125~225A AC breaking
0.1s
250A DC time Left-side Right-side
125~225A DC mounting mounting
0.05s
AL AX
0.02s
Time-delay trip
0.01s
Instantaneous trip
SHT or UVT
1 1.3 2 3 4 5 6 7 10 15 20 30 40
Lead wire
×100% of Rated current
direction
Remark: (1) Only AC characteristics are available for the model MB225-SW.
(2) refer to page 50.
Notes: (*1) The designation depends on the number of poles. Refer to the reference page.
(*2) Specify the working voltage. An order of MB225-SW should be placed at the same time as an order of circuit breaker main body.
(*3) Attach the letter "F" to the end of designation for a fixed type.
(*4) HLF types are used for OFF-lock, and HLN types for ON-lock.
Front connection
Insulating barrier
(removable) M8 bolt
(Hex-soket) 24
30
Breaker
Mounting hole
100
Solderless terminal
for wire size
125 175A 14 95mm2
200 250A 70 125mm2
144
165
126
Wire connection
102
50
ø4.5
φ8.5
10
Trip button
100
45
φ8.5
35 35
22 35
Neutral 61 23 max.
M4×0.7 taps
pole or φ5
70 68
105
(Bus t max.=7)
4 72 3-pole 4-pole
105 140
Bus drilling for
92 Drilling plan
direct connection
3-pole 4-pole
Rear connection
4-pole
3-pole
4-pole
Mounting plate Insulating Stud can be
tube rotated 90° Breaker Breaker
t max.=3.2
3-pole
Connection
8
allowance
1
126
144
52
144
22
20
M4×0.7
breaker
mounting 32.5
ø24 35
15 6 screw
35 35 100
15 φ9 70 M4×0.7
Insulating taps
M8 bolt tube 70 or φ5 105 1mm clearance
68 71 105
on each side
of handle
72 106 3-pole 4-pole
6
Drilling plan Front-plate cutout
Plug-in
allowance
Connection
58.5
144
200
54
80
14
22
70
6
58.5
153
28
15
M6 70 105
φ7
18 Terminal block
mounting screw 20 φ9 107 142
M8 bolt
86 32
Stud attachable in this 70 3-pole 4-pole
derection only Insulating barrier Drilling plan
Remarks: 1. 2-pole models are 3-pole models with the central pole removed.
2. Only 2- and 3-pole models are available for the model of NF250-CW, and only 3-pole models are available
for the model of MB225-SW.
Number of poles 2 3 4 3 4 2 3 4 3 4 2 3 4 3 4
Rated insulation voltage Ui (V) 690 690 690 690 690 690
690V 20/20 20/20 8/8 8/8 20/20 20/20
braking capacity (kA)
Rated short-circuit
∗1: Use either 2-pole. When wired as shown at the bottom of page 13, 3-pole models can be used for up to 500 V DC, and 4-pole models for up to 600V DC.
■Operating Characteristics
4h 4h 4h 4h
Electric types
2h 2h 2h 2h
Thermal-Adjustable types Thermal-Adjustable types Thermal-Adjustable types NF125-SGW NF125-HGW
1h NF125-SGW/HGW 25-40A (Rated current In=40A) 1h NF125-SGW/HGW 63-100A (Rated current In=100A) 1h NF250-SGW/HGW 160-250A (Rated current In=250A) 1h Note)
16-25A (Rated current In=25A) 40-63A (Rated current In=63A) NF160-SGW/HGW 125-160A (Rated current In=160A) Current setting Ir Rated current In
30min 30min 30min NF125-SGW/HGW 80-125A (Rated current In=125A) 30min 16~ 32A 32A
20min 20min 20min 20min 32~ 63A 63A
14min IEC 60947-2 IEC 60947-2 14min IEC 60947-2 63~ 100A 100A
14min
10min 10min 10min 10min 75~ 125A 125A
Instantaneous trip Instantaneous trip Instantaneous trip adjustment (Adjustable)
6min 6min 6min 6min
current ratio current ratio Max. range
4min AC DC 4min AC DC 4min Position AC DC 4min LTD operating time TL
x In (%) x In (%) x In (%) x In (%) of notch x In (%) x In (%) 12-60-80-100s ± 20%
2min 1000±200 1300±260 2min 1000±200 1300±260 2min 4 400±80 520±104 2min
Max. Max. (at 200%)
6 600 780
Operating time
Operating time
Operating time
30s 30s
20s 20s 20s 20s
4h 4h
2h
Electric types
NF160-SGW NF160-HGW 2h
Electric types
NF250-SGW NF250-HGW
■Ambient Compensating Curve
1h 1h
Note) Note)
30min
Current setting Ir Rated current In Current setting Ir Rated current In
RT type RE type
80~160A 160A 30min
20min 20min 125~250A 250A
(Adjustable)
Derating of Load current (%)
(Adjustable)
10min 10min
130 130
Rated ambient
Rated ambient
Current rating (%)
6min 6min
120
4min LTD operating time TL 4min LTD operating time TL 120
12-60-80-100s ±20% 12-60-80-100s ± 20%
2min 2min
(at 200%) (at 200%) 110
1min
110
1min
100
Operating time
100
Operating time
30s 30s
20s 20s
90
10s 10s 90
Pre-alarm STD pickup current IS Pre-alarm STD pickup current IS
5s pickup current IP 80
Ir × (2-2.5-3-3.5-4 5s pickup current IP Ir × (2-2.5-3-3.5-4 –10 0 10 20 30 40 50 60
Ir × (0.70-0.75 -5-6-7-8-10)±15% Ir × (0.70-0.75 -5-6-7-8-10) ± 15%
80
2s -0.8-0.85-0.9 2s -0.8-0.85-0.9 Ambient temperature (°C)
1s
-0.95-1.0) ±10%
1s
-0.95-1.0) ± 10%
(rated ambient 40°C) 70
–10 0 10 20 30 40 50 60
0.5s Pre-alarm STD operating time TS 0.5s Pre-alarm STD operating time TS
operating time TP 0.3±0.06s operating time TP 0.3 ± 0.06s Ambient temperature (°C)
TL 0.2±0.04s
0.2s TP= ± 20% 0.2s TP = TL ± 20% 0.2 ± 0.04s
2 0.1±0.03s 2
0.05s
0.1s (at 200%)
0.06±0.02s
0.05s
0.1s (at 200%)
0.1 ± 0.03s
0.06 ± 0.02s ■Standard Attached Parts
0.02s
INST pickup current Il
In × (4~14) ±15% Max.total breaking
time
0.02s
INST pickup current Il
In × (4~14) ± 15% Max.total breaking
(Front connection)
0.01s
time
0.01s
0.6 0.7 1 1.3 2 3 4 5 6 7 10 15 20 30 40 0.6 0.7 1 1.3 2 3 4 5 6 7 10 15 20 30 40
Mounting screw : M4 × 0.7 × 73 (4pcs)
× 100% of Current setting × 100% of Current setting
Note) Instantaneous tripping current (× 100% of In)
Insulation barrier : (2P : 2pcs, 3P : 4pcs, 4P : 6pcs)
Note) Instantaneous tripping current (× 100% of In)
for ON-lock.
R R2GSW 64 Large TC-L TCL-2GSW3W (*1) (*3) Attach the letter “F ” to the
LC LC-2GSW Skeleton TTC TTC-2GSW3 (*1) 66 end of designation for a
(*2) HLF-2GSW fixed type.
Handle lock device 76 Rear BTC BTC-2GSW3W (*1)
(*4) Specify the working voltage.
HL HLN-2GSW Plug-in PTC PTC-2GSW3W (*1)
HL-S HLS-2GSW
OFF Lock with 3 Padlock HLF3-2GSW 76 Electrical MDS-NF2GSWE
Remark: (1) refer to page 50. operation device (*4)
67
Front connection
Solderless terminal
Insulating barrier for wire size
(removable) 2.5 185mm2
M8 bolt
24
10
(Hex-soket) Breaker
Mounting hole
50
6.1
144
165
112
126
50
φ4.5
Hex-socket set screw
Trip Wire connection
50
button 22
φ8.5
φ8.5 35 35
22 35
63
10
Neutral M4×0.7 taps
70 105 pole 79 or φ5
86
3-pole 4-pole
105 140 24 max.
Drilling plan
4 90
3-pole 4-pole (Bus t max.=7)
110 Bus drilling for
direct connection
Rear connection
4-pole
Insulating tube
4-pole
3-pole
Mounting plate Stud can be
rotated 90° 3-pole Breaker
t max.=3.2 Breaker
Connection
8
1
allowance
144
126
144
52
R
22
20
M4×0.7
breaker 32.5
15 φ24 35
6 mounting
screw
15 φ9 M4×0.7 100
70 Insulating 35 taps 35
M8 bolt
tube or φ5
86 71
105 70 105 1mm clearance
90 106 on each side
of handle
3-pole 4-pole
6
Drilling plan Front-panel cutout
Plug-in
54
4
allowance
Connection
66
94
M8 bolt
120
144
200
12
96
(Hex-soket)
54
103
48
110
70 105
φ7
10
48
15 107 142
M6 20
Terminal block ø9 M8bolt
3-pole 4-pole
86 30 45 mounting screw 70
Stud can be
rotated 90° Insulating barrier Drilling plan
(removable)
Remark: 2-pole models are 3-pole models with the central pole removed.
Number of poles 2 3 2 3 4 2 3 2 3 4
Rated insulation voltage Ui (V) 690 690 690 690
690V 25/25 30/30 25/25 30/30
500V 125/125 200/200 125/125 200/200
Type NF250-UGW
■Operating Characteristics
4h 4h 4h
2h 2h 2h
Thermal-Adjustable types Thermal-Adjustable types Thermal-Adjustable types
1h NF250-RGW/UGW 160-225A (Rated current In=225A) 1h NF125-RGW/UGW 63-100A (Rated current In=100A) 1h NF125-RGW/UGW 25-40A (Rated current In=40A)
125-160A (Rated current In=160A) 40-63A (Rated current In=63A) 16-25A (Rated current In=25A)
30min 30min 30min
20min 20min 20min
14min IEC 60947-2 14min IEC 60947-2 14min IEC 60947-2
10min 10min 10min
6min Instantaneous trip adjustment 6min Instantaneous trip 6min Instantaneous trip
Max. range current ratio current ratio
4min Position AC DC 4min AC DC 4min AC DC
of notch x In (%) x In (%) x In (%) x In (%) x In (%) x In (%)
2min 4 400±80 520±104 2min 1000±200 1300±260 2min 1000±200 1300±260
Max. Max.
6 600 780
Operating time
Operating time
Operating time
1min 1min 1min
8 800 1040
30s 10 1000±200 1300±260 30s 30s
20s 20s 20s
1s 1s 1s
AC
0.5s (Adjustable range) 0.5s 0.5s
DC
(Adjustable range) AC AC
Max. total Max. total Max. total
0.2s breaking
0.2s breaking
0.2s
DC breaking
time time
DC
0.1s 0.1s 0.1s time
110
100
90
80
–10 0 10 20 30 40 50 60
Front connection
Solderless terminal
Insulating barrier for wire size
M8 bolt
(removable) (Hex-soket) 2.5 185mm2 Breaker
24
26.5
10
Mounting hole
50
75
6.1
219
240
201
165
112
50
Hex-socket set screw
φ4.5
Wire connection
Trip
φ8.5
button 50 22
10
φ8.5
35 35
22 35 63
Neutral
pole 79 M4×0.7 taps
70 105 24 max. or φ5
86
3-pole 4-pole
105 140 4 90
(Bus t max.=7)
Bus drilling for Drilling plan
3-pole 4-pole 110 direct connection
Rear connection
4-pole
Insulating tube
Breaker 3-pole
Mounting plate 4-pole
Stud can be Breaker
t max.=3.2 rotated 90°
3-pole
73
11.5
108
219
201
219
8
Connection
allowance
52
R
22
20
M4×0.7
breaker 32.5
15 6 mounting ø24 35
screw
φ9 M4×0.7 100
15 M8 bolt 35 35
70 taps
Insulating
tube or φ5
86 71 70 105 1mm clearance
105 on each side
90 106 3-pole 4-pole of handle
Drilling plan Front-panel cutout
Plug-in
Connection
58.5
22 allowance
129
155
275
219
14
15
70
153
6
58.5
28
Remark: 2-pole models are 3-pole models with the central pole removed.
Rated short-circuit
500V 15/8 30/30
IEC 60947-2 AC 440V 25/13 42/42
(Icu/Ics) 400V 36/18 45/45
230V 50/25 85/85
DC 250V 20/10 – 40/40 –
Note: (1)Types of DC specifications can be produced upon request.
Type NF400-SP
■Operating Characteristics
4h
2h Operating Characteristics
1h (IEC 60947-2)
NF400-CP
30min
NF400-SP
20min
14min
10min
6min
4min
2min
1min
Operating time
Max
30s
20s
10s
5s
Min NF400-CP
2s
1s
NF400-SP
0.5s
0.2s
0.1s
Max. total breaking time
0.05s
0.02s
Time-delay trip Instantaneous trip
0.01s
100 130 200 300 400 600 1000 1500 3000
500 700 2000 4000
130
Left-side Right-side Lead wire
AL AX SHT or UVT
Current rating (%)
110
100
(*1)
90
80
0 10 20 30 40 50 60
(*1) (*1) (*1) (Reference ambient temperature 40°C)
Ambient temperature (°C)
Note: (*1) Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting.
Remark: (1) refer to page 51.
Front connection
94.5
Insulating barrier (removable)
44
28
Conductor thickness 8 4-pole
16
t=8 max. 3-pole
110
Breaker
43
Breaker
39
Mounting hole
194
102
12
257
R6
47
92
ø12.5
ø7
Trip button
25
39
ø10.5
44 M6 tap or ø7 44
Neutral pole
44 Conductor thickness t=8 max.
118
Conductor drilling for
ø14 97 direct connection
M12 bolt 56 103
51 168 5 107 1.0mm clearance on each side of the
112 185 3-pole 4-pole handle frame.
140 196 155 (NF400-SP) Drilling plan Front-panel cutout
134 (NF400-CP)
3-pole 4-pole
24 24
8
Connection M6 tap or ø7
allowance 4-M6 tap or ø7
194
225
225
225
194
265
14
25 20 20
26
83
128
24 24
M6 screw for
mounting breaker ø35
44 44 11 11
10 8 8-M4 screw
ø13
113 87 Insulation tube 87 Add these tapped holes in
M12 bolt 43.5 44
8 positions to standard boring.
130.5 130.5 87
3-pole 4-pole
Load side
Drilling plan
Plug-in
4-pole
Mounting plate
Plug-in terminal block 3-pole
Breaker
35
55
225
allowance
135
163
24 mounting screw
24
8
79
55
160
ø10
15
28
28
Drilling plan
Remark: (1) 2-pole models are 3-pole models with the central pole removed.
Type NF400-SEP
■Operating Characteristics
10h
5h
NF400-SEP
2h NF400-HEP
NF400-REP
1h Note)
LTD operating time Current setting Rated Current
30min
at 125% Ir: 200~400A In: 400A
20min
1000s(TL=150s set) (Adjustable)
14min
10min 670s(TL=100s set)
400s(TL= 60s set)
6min
80s(TL= 12s set)
4min
LTD operating time TL
2min 12-60-100-150s ±20%
(at 200%)
1min
Operating time
30s
20s
10s
Pre-alarm STD pickup current Is
5s pickup current Ip Ir x(2-2.5-3-3.5-4
Ir x(0.70-0.75 -5-6-7-8-10) ±15%
2s -0.8-0.85-0.9 ±10%
-0.95-1.0)
1s
Pre-alarm
0.5s STD operating time Ts
operating time Tp
TL ±20% 0.3 ± 0.06s
Tp= 0.2 ± 0.04s
0.2s 2
(at 200%)
0.1s 0.1 ± 0.03s
0.06 ± 0.02s
0.05s
Rated ambient
110
100
(*1)
90
80
Note: (*1) Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting.
Remark: (1) refer to page 51.
Front connection
94.5
Insulating barrier (removable)
44
28 Conductor thickness
8 4-pole
t=8 max.
16
110
Breaker 3-pole
43
Breaker
39
Mounting hole
194
102
12
257
R6
47
92
ø12.5
ø7
Trip button
25
39
ø10.5
44 M6 tap or ø7 44
Neutral pole
44 Conductor thickness t=8 max.
118
Conductor drilling for
ø14 97 direct connection
M12 bolt 56 103
51 168 5 107 1.0mm clearance on each side of
112 185 155 3-pole 4-pole the handle frame.
140 196
Drilling plan Front-panel cutout
3-pole 4-pole
24 24
8
Connection M6 tap or ø7
allowance 4-M6 tap or ø7
194
225
225
225
194
265
14
25 20 20
26
83
128
24 24
M6 screw for
mounting breaker ø35
44 44 11 11
10 8 8-M4 screw
ø13
113 87 Insulation tube 87 Add these tapped holes in
M12 bolt 43.5 44
8 positions to standard boring.
130.5 130.5 87
3-pole 4-pole
Load side
Drilling plan
Plug-in
4-pole
Plug-in terminal block Mounting plate 3-pole Breaker
35
55
225
allowance
135
163
24 mounting screw
24
8
79
55
160
ø10
15
28
28
18 Stud attachable in 44 87
this direction only
121 136 181
87
ø13 Insulating barrier
M12 bolt 130.5
3-pole 4-pole
Drilling plan
Rated short-circuit
500V 170/170
IEC 60947-2 AC 440V 200/200
(Icu/Ics) 400V 200/200
230V 200/200
DC 250V —
Type NF400-UEP
■Operating Characteristics
10h
5h
2h NF400-UEP
1h Note)
Current setting Rated Current
LTD operating time
30min Ir: 200~400A In: 400A
at 125%
20min (Adjustable)
14min 1000s(TL=150s set)
10min 670s(TL=100s set)
400s(TL= 60s set)
6min
80s(TL= 12s set)
4min
LTD operating time TL
2min 12-60-100-150s ±20%
(at 200%)
1min
Operating time
30s
20s
10s
Pre-alarm STD pickup current Is
5s pickup current Ip Ir x(2-2.5-3-3.5-4
Ir x(0.70-0.75 -5-6-7-8-10) ±15%
2s -0.8-0.85-0.9 ±10%
-0.95-1.0)
1s
Pre-alarm
0.5s STD operating time Ts
operating time Tp
TL ±20% 0.3 ± 0.06s
Tp= 0.2 ± 0.04s
0.2s 2
0.1s (at 200%) 0.1 ± 0.03s
0.06 ± 0.02s
0.05s
110
100
(*1)
90
80
(*1) (*1) (*1)
70
0 10 20 30 40 50 60
Front connection
t=8 max. 8
Breaker
43
ø7
26
Mounting hole
ø12.5
R6
47
31
297
11.5
234
257
102
92
144
ø12.5
ø7
Trip button
25
39
ø10.5
43
44 M6 tap or ø7
Conductor thickness t=8 max.
141 118
16
24 24
8
M6 screw or ø7
Connection 4-M6 tap or ø7
234
265
allowance
305
265
234
265
25 20 20
14
24 24
26
83
11 11
128
8-M4 screw
M6 screw for ø35
10 Add these tapped holes in
mounting breaker 44
ø13 44 8 positions to standard boring.
210 8
M12 bolt 87
87
87 Insulation tube
Load side
3-pole Drilling plan
Plug-in
Mounting angle
35
Mounting angle
Connection
max. 203
320
297
265
M8 terminal block
175
allowance
24 mounting screw
24
79
8
160
28
ø10
15
28 Stud attachable
18 in this direction only
44
218 ø13 87 Insulating barrier
M12 bolt 3-pole
3-pole Drilling plan
Note (1): Overall dimension of 4-pole model is same as that of 4-pole model of NF630-UEP. Refer to page 3 2 .
Rated short-circuit
500V 18/9 30/30
IEC 60947-2 AC 440V 36/18 42/42
(Icu/Ics) 400V 36/18 45/45
230V 50/25 85/85
DC 250V 20/10 – 40/40 –
Note: (1) Types of DC specifications can be produced upon request.
Type NF630-SP
■Operating Characteristics
4h
2h Operating Characteristics
(IEC 60947-2)
1h
NF630-CP
30min NF630-SP
20min
14min
500A, 600A, 630A
10min
6min Instantaneous tripping
4min current value
Adjustable range (4 steps)
2min Position Instantaneous
Max. of tripping Current
1min adjusting standard value %
handle NF630-SP
30s Lo 500±100
Operating time
20s 2 800
3 1100
10s Hi 1400±280
5s
Min.
2s
1s
0.5s
NF630-SP
Adjustable range NF630-CP
0.2s
0.1s
Max. total breaking time
0.05s
0.02s
Time-delay trip Instantaneous trip Instantaneous tripping
0.01s
100 130 200 300 400 600 1000 1500 3000
500 700 2000 4000
130
Lead wire
Left-side Right-side AL AX SHT or UVT
direction
Current rating (%)
110
100
90
(*1) (*1)
80
0 10 20 30 40 50 60
(Reference ambient temperature 40°C) Ambient temperature (°C)
(*1) (*1)
Note: (*1) Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting.
Remark: (1) refer to page 1.
Front connection
Breaker
3-pole
87
32
Breaker
Auxiliary handle
(removable) Terminal dimension
70 M6 tap or ø7 R6
for directly connecting
conductor
102
275
3-pole
15
92
32
ø8
8
ø8.5
ø14
87 8
32
51
12
172
243
44
22
Trip button
15
51 70 97
14 40
210 103 1.0mm clearance on each side of the
40 Neutral pole
140 5 107 handle frame.
280 (Conductor thickness t=8 max.)
210 ø14 Conductor drilling for
155 Front-panel cutout
M12 bolt direct connection 70
3-pole 4-pole 217
4-pole
Drilling plan
Connection
M6 tap or ø7
allowance Stud can be rotated 90°
25 Breaker Groove for reducing
Mounting plate heat by overcurrent 6-ø48
24 24
10
10
4-M6 tap or ø7
243
243
295
243
12.5
13
40
24 24
8
70
10 70
140 11 11 8-M4 screw
70 Add these tapped holes in
8 32 15 ø13 M12 bolt M6 screw for
140 ø48 70 8 positions to standard boring.
mounting breaker 210
140
113 110
3-pole 4-pole
Drilling plan
Plug-in
20
Connection allowance
155
187
243
301
13
8
112
56
32
25
15
40
70 140
23 M8 terminal block 140 ø13 ø10
mounting screw 278
M12 bolt 208
126
3-pole 4-pole
Drilling plan
Remark: (1) 2-pole models are 3-pole models with the central pole removed.
Type NF630-SEP
■Operating Characteristics
10h
5h NF630-SEP
NF630-HEP
2h NF630-REP
Note)
1h
Current setting Rated Current
LTD operating time
30min Ir: 300~630A In: 630A
at 125%
20min
1000s(TL=150s set) (Adjustable)
14min
10min 670s(TL=100s set)
400s(TL= 60s set)
6min
80s(TL= 12s set)
4min
LTD operating time TL
2min 12-60-100-150s ±20%
(at 200%)
1min
Operating time
30s
20s
10s
Pre-alarm STD pickup current Is
5s pickup current Ip Ir x(2-2.5-3-3.5-4
Ir x(0.70-0.75 -5-6-7-8-10) ±15%
2s -0.8-0.85-0.9 ±10%
-0.95-1.0)
1s
Pre-alarm
0.5s STD operating time Ts
operating time Tp
TL ±20% 0.3 ± 0.06s
0.2s Tp= 0.2 ± 0.04s
2
0.1s (at 200%) 0.1 ± 0.03s
0.06 ± 0.02s
0.05s
130
Left-side Right-side AL Lead wire
AX SHT or UVT direction PAL TI
mounting mounting 120
110
100
(*1) (*1) 90
80
(*1) (*1) 70
0 10 20 30 40 50 60
Note: (*1) Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting. Ambient temperature (°C)
Remark: (1) refer to page 51.
Note: (*1) The designation depends on the number of poles. Refer to the reference page.
Front connection
Breaker
94.5
Mounting hole Insulating barrier (removable) 24 4-pole
Conductor thickness
t=8 max. 44 3-pole
Breaker
8
110
87
32
Auxiliary handle R6
(removable)
Terminal dimension
70 M6 tap or ø7
for directly connecting
92
conductor
102
275
15 3-pole
32
ø8
N
8
ø8.5
51
ø14
87 8 172
32
12
44
22
243
Trip button
15
51 70 97
14 40
210 103 1.0mm clearance on each side of
40 Neutral pole
140 5 107 the handle frame.
280 (Conductor thickness t=8 max.)
210 ø14
155 Conductor drilling for Front-panel cutout
M12 bolt
direct connection 70
3-pole 4-pole 217
4-pole
Drilling plan
Connection
M6 tap or ø7
allowance Stud can be rotated 90°
25 Breaker Groove for reducing
Mounting plate heat by overcurrent 6-ø48
24 24
10
10
4-M6 tap or ø7
243
243
295
243
12.5
13
40
24 24
8 70
10 70
140 11 11 8-M4 screw
70 Add these tapped holes in
8 32 15 ø13 M6 screw for 140 ø48 70 8 positions to standard boring.
M12 bolt mounting breaker 210
140
113 110 3-pole 4-pole
Drilling plan
Plug-in
20
155
187
243
301
13
8
112
56
32
25
15
40
70 140
23 M8 terminal block 140 f10
ø13
mounting screw M12 bolt 208 278
126
3-pole 4-pole
Drilling plan
Type NF630-UEP
■Operating Characteristics
10h
5h
NF630-UEP
2h
Note)
1h
Current setting Rated Current
30min LTD operating time Ir: 300~630A In: 630A
20min at-125%
(Adjustable)
14min 1000s(TL=150s set)
10min 670s(TL=100s set)
400s(TL= 60s set)
6min
80s(TL= 12s set)
4min
LTD operating time TL
2min 12-60-100-150s ±20%
(at 200%)
1min
Operating time
30s
20s
10s
Pre-alarm STD pickup current Is
5s pickup current Ip Ir x(2-2.5-3-3.5-4
Ir x(0.70-0.75 -5-6-7-8-10) ±15%
2s -0.8-0.85-0.9 ±10%
-0.95-1.0)
1s
Pre-alarm
0.5s STD operating time Ts
operating time Tp
TL ±20% 0.3 ± 0.06s
0.2s Tp= 0.2 ± 0.04s
2
(at 200%)
0.1s 0.1 ± 0.03s
0.06 ± 0.02s
0.05s
130
Lead wire
Rated ambient
110
100
(*1) (*1)
90
80
(*1) (*1) 70
0 10 20 30 40 50 60
Ambient temperature (°C)
Note: (*1) Right-side mounting is standard of SHT and UVT. Specify separately for left-side
mounting.
Remark: (1) refer to page 51.
F6UPW(*1) 61 Large (TC-L) TCL-6UP3 (*1) 66 connection 4P: M6 × 35 (3pcs), M6 × 132 (2pcs)
Operating handle Insulating barrier: (3P: 2pcs, 4P: 3pcs)
S S4SP 63 Skeleton (TTC) — —
Mechanical interlock (MI) MI-6SP3 (*1) 75 Rear (BTC) BTC-6SP3 (*1) 66
Mounting screw:
Auxiliary handle (HT) HT-4SP 76 Handle HL HL-4SP Rear 3P: M6 × 40, M6 × 137 (2pcs each)
76 connection
lock device HL-S HLS-6UP 4P: M6 × 40 (3pcs), M6 × 137 (2pcs)
Electrical operation
67
device
Note: (*1) The designation depends on the number of poles. Refer to the reference page.
Front connection
110
110
ø14
ø14
87
ø7
Auxiliary handle
ø7
(removable)
48
22.5
27.5
27.5
R6
15 Terminal dimension 15
322
290
322
92
for directly connecting
275
102
275
102
112 112
conductor
ø8.5
ø7
ø7
N N
16
12
8
51
48
ø14
ø14
87
14 22
32
8 Trip 6.5
70 70 button 51 35
Trip 51 141 40 172
70 Neutral 141
15
24 24
10
10
4-M6 tap or ø7
290
342
290
290
342
290
13
40
26
12.5
24 24
8 32 15 70 20
10 70 10
70
210 110 ø13 210 83 ø13 11 11 8-M4 screw
140 ø48
M12 bolt 8 210 M12 bolt Add these tapped holes in
M6 screw for 70 8 positions to standard boring.
mounting breaker 3-pole 4-pole
140 4-pole 140
(NF400-UEP)
Plug-in
190
Plug-in terminal block Stud can be rotated 90°
190 Breaker
Mounting angle (A) Mounting angle (B)
Mounting angle
under 234
(A)
202
348
322
290
20
172
ø10
172
Connection allowance
13
8
112
capacity (kA)
IEC 60947-2 AC 440V 36/18 42/42 65/65 125/63
(Icu/Ics) 400V 36/18 45/45 70/70 125/63
230V 50/25 85/85 100/100 150/75
DC 250V — — — —
Type NF800-SEP
■Operating Characteristics
10h
Operating Characteristics
5h (IEC 60947-2)
NF800-CEP
2h NF800-SEP
NF800-HEP
1h NF800-REP
Note)
LTD operating time Current setting
30min Rated Current
20min at 125% Ir: 400~800A In: 800A
14min 1000s(TL=150s set) (Adjustable)
10min 670s(TL=100s set)
400s(TL= 60s set)
6min
80s(TL= 12s set)
4min
LTD operating time TL
2min 12-60-100-150s ±20%
(at 200%)
1min
Operating time
30s
20s
10s
Pre-alarm STD pickup current Is
5s pickup current Ip Ir x(2-2.5-3-3.5-4
Ir x(0.70-0.75 -5-6-7-8-10) ±15%
2s -0.8-0.85-0.9 ±10%
-0.95-1.0)
1s
Pre-alarm
0.5s STD operating time Ts
operating time Tp
TL ±20% 0.3 ± 0.06s
0.2s Tp= 0.2 ± 0.04s
2
0.1s (at 200%) 0.1 ± 0.03s
0.06 ± 0.02s
0.05s
Operating handle
130
Left-side Right-side AL Lead wire
PAL TI
temperature
120
ambient
110
The rated current does not
100 depend on temperature.
However, if ambient
(*1) (*1) 90 temperature exceeds 40°C,
reduce the continuous
80
working current as left
(*1) (*1) 70 curve.
0 10 20 30 40 50 60
Ambient temperature (°C)
Note: (*1) Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting.
Remark: (1) refer to page 51.
Front connection
94.5
Mounting hole Insulating barrier (removable) Conductor thickness 26
t=12 max. 46
4-pole
8 3-pole
110
Breaker
87
32
Breake
Auxiliary handle
(removable)
Terminal dimension for R6
directly connecting
243
102
275
conductor
15
92
32
ø8
N
8
ø8.5
ø14
8
87
14
32
12
70 M6 tap 70 51
46
22 or ø7 172
Trip button
15
51 70 97
40
40 210 103
Neutral pole 1.0mm clearance on each
140
5 107 (Conductor thickness t=10 max.) 3-pole 4-pole side of the handle frame.
210 280
ø14 Conductor drilling for direct connection
M12 bolt 155
Drilling plan Front-panel cutout
3-pole 4-pole 217
24 24
10
10
4-M6 tap or ø7
243
295
243
243
12.5
13
40
24 24
10
8 70
8 32 15 70
140 11 11 8-M4 screw
70 Add these tapped holes in
113 110 ø13 M6 screw for 140 ø48 70 8 positions to standard boring.
M12 bolt mounting breaker 210
140
3-pole 4-pole
Drilling plan
Plug-in
20
155
187
243
301
13
10
112
56
32
25
15
40 70 140
23 M8 terminal block mounting screw ø10
140 ø13 208 278
126
M12 bolt
3-pole 4-pole
Drilling plan
Type NF800-SDP
■Operating Characteristics
4h
2h
NF800-SDP
1h
30min 700A,800A
DC
20min
14min
10min
6min
Inst. trip adjustment
4min range (4 steps)
Lo 2600±520
2 3900±780
30s 3 5200±1040
20s Hi 6500±1300
10s
Min.
5s
2s
Adjustment
range
1s 700A
0.5s
Adjustment
0.2s range
800A
0.1s
Max. total
interrupting time
0.05s
0.02s
Time-delay trip Inst trip
0.01s
1 1.3 2 3 4 5 6 7 10 15 20 30 40
130
Left-side Right-side AL Lead wire
AX SHT or UVT direction PAL TI
mounting mounting
Current rating (%)
120
110
(*1) (*1) 80
Rated ambient 40°C 0 10 20 30 40 50 60
Note: (*1) Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting. Ambient temperature (°C)
Remark: (1) refer to page 51.
Note: (*1) The designation depends on the number of poles. Refer to the reference page.
94.5
Mounting hole Insulating barrier (removable) Conductor thickness 26
46 4-pole
t=12 max.
3-pole
8
110
Breaker
87
32
Auxiliary handle
(removable) Terminal dimension for R6
70 M6 tap or ø7
directly connecting
conductor
102
275
92
3-pole
15 ø8.5
12
N
ø8
8
22
ø14
8
32
87
14 51
32
40 172
243
46
15
Trip button 51 70 97
1.0mm clearance on each
40 210 103 (Conductor thickness t=10 max.)
Neutral pole side of the handle frame.
140
5 107
210 280 Conductor drilling for direct connection Front-panel cutout
ø14
M12 bolt 155 70
3-pole 4-pole 217
4-pole
Drilling plan
M6 tap or ø7
Connection allowance Stud can be rotated 90°
25 Breaker Groove for reducing heat
Mounting plate by overcurrent 6-ø48
24 24
10
10
4-M6 tap or ø7
243
295
243
243
12.5
13
40
24 24
10 8
70
70
8 32 15 140 11 11 8-M4 screw
70 Add these tapped holes in
ø13 M6 screw for 140 ø48 70 8 positions to standard boring.
113 110 M12 bolt mounting breaker 210
140
3-pole Drilling plan 4-pole
Plug-in
20
155
187
243
301
13
8
112
56
32
25
15
40
70 140
23 M8 terminal block mounting screw ø10
140 ø13 208 278
M12 bolt
126
3-pole 4-pole
Drilling plan
Remarks: (1) Standard specification of NF800-SDP is 2-pole model. 3-pole and 4-pole models are available for DC special voltage.
(2) 2-pole models are 3-pole models with the central pole removed.
Type NF800-UEP
■Operating Characteristics
10h
5h
NF800-UEP
2h
Note)
1h
Current setting Rated Current
LTD operating time
30min Ir: 400~800A In: 800A
at-125%
20min (Adjustable)
14min 1000s(TL=150s set)
10min 670s(TL=100s set)
400s(TL= 60s set)
6min
80s(TL= 12s set)
4min
LTD operating time TL
2min 12-60-100-150s ±20%
(at 200%)
1min
Operating time
30s
20s
10s
Pre-alarm STD pickup current Is
5s pickup current Ip Ir x(2-2.5-3-3.5-4
Ir x(0.70-0.75 -5-6-7-8-10) ±15%
2s -0.8-0.85-0.9 ±10%
-0.95-1.0)
1s
Pre-alarm
0.5s STD operating time Ts
operating time Tp
TL ±20% 0.3 ± 0.06s
Tp= 0.2 ± 0.04s
0.2s 2
(at 200%)
0.1s 0.1 ± 0.03s
0.06 ± 0.02s
0.05s
130
Rated ambient
110
100
(*1) (*1) 90
80
(*1) (*1) 70
0 10 20 30 40 50 60
Ambient temperature (°C)
Note: (*1) Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting.
Remark: (1) refer to page 51.
F6UPW(*1) 61 Large (TC-L) TCL-6UP3 (*1) 66 Insulating barrier: (3P: 2pcs, 4P: 3pcs)
Operating handle S S4SP 63 Skeleton (TTC) — —
Rear Mounting screw: 3P: M6 × 40, M6 × 137 (2pcs each)
V — — Rear (BTC) BTC-6SP3 (*1) 66
connection 4P: M6 × 40 (3pcs), M6 × 137 (2pcs)
Mechanical interlock (MI) MI-6SP3 (*1) 75 Handle HL HL-4SP
76
Auxiliary handle (HT) HT-4SP 76 lock device HL-S HLS-6UP
Electrical operation
device 67
Note: (*1) The designation depends on the number of poles. Refer to the reference page.
44 (ON side)
Insulating barrier (removable) 123.5 (OFF side)
Mounting hole 143
Conductor thickness 64 4-pole
t=12 max.
110
8 3-pole
87
Auxiliary handle Breaker
ø14
ø7
(removable)
27.5
70
Terminal dimension for
22.5
M6 screw or ø7
15 directly connecting R6
3-pole
322 conductor
275
102
112
ø8.5 70
92
12
ø7
N
8
ø14 8 22
87
14
32
143 40 51
Trip button 51 194 172
290
70
15
40 200
(Conductor thickness t=10 max.)
210 Neutral pole 5 204 1.0mm clearance on each
140
side of the handle frame.
210 280 252 Conductor drilling for
ø14
M12 bolt 314 direct connection Front-panel cutout
3-pole 4-pole
70
4-pole
Drilling plan
M6 tap or ø7
Standard direction of stud is horizontal
Connection on power side, and vertical on load side. Breaker Groove for reducing
Mounting plate allowance Otherwise, specify the direction. heat by overcurrent 6-ø48
5
25
24 24
10
10
4-M6 tap or ø7
290
290
290
342
12.5
13
40
24 24
11 11 8-M4 screw
8 32 15 70
70 Add these tapped holes in
10 10 70
70 8 positions to standard boring.
ø13 M6 screw for 140 ø48
210 110 140 140
M12 bolt mounting breaker 210
3-pole 4-pole
Drilling plan
Type NF1000-SS
■Operating Characteristics
3h 3h
2h Type 2h Type
NF1000-SS NF1250-SS
1h 1h
Rated current 500,600, Rated current 600, 700,
40min 40min
700,800,900,1000A adjustable 800, 1000, 1200A, 1250
30min 30min
Short-time pickup 20min adjustable
20min
current adjustable Short-time pickup
10min 500% ± 50% 10min current adjustable
750% ± 75% 500% ± 50%
6min 6min
1000% ± 100% 750% ± 75%
4min inst, pickup current 4min
1000% ± 100%
+4kA
20KA inst, pickup current
2min -2kA Fixed 2min
Maximum AC Maximum +4kA
1min 1min 20KA Fixed
AC -2kA
40s 40s
Operating time
Operating time
30s 30s
20s 20s
Minimum
10s 10s Minimum
6s 6s
Short-time pickup current Short-time pickup current
4s 4s
ajustment range ajustment range
2s 2s
1s 1s
0.6s 0.6s
0.4s 0.4s
For 600A rated
For 500A 0.2s current
0.2s
rated current
0.1s 0.1s
130
Rated ambient
110
100
90
80
70
Remark: (*1) refer to page 51. 0 10 20 30 40 50 60
Ambient temperature (°C)
Front connection
Conductor thickness 15 40
Insulating barrier (removable)
t=8 × 2pcs max.
Bolt M12 × 50
110 Mounting Breaker
hole
Auxiliary handle
(removable)
346
406
375
ø9.5
13
15 32 8
ø17.5
80
18.5
Neutral pole 70 M8 tap or ø10 70
15 44
43 70 133.5
17 3-pole 4-pole
140 210 140
ø13 M12 bolt 210 280 190
280 Drilling plan
3-pole 4-pole
Rear connection
4-pole
Mounting plate
3-pole Breaker
M8 screw for mounting breaker Breaker
35.5
Stud can be rotated 90°
86
R11.5
109
269
97
18 Connection
273
39.5
81.5
allowance
ø13
22
Conductor thickness
13
86
45
Plug-in
Mounting plate
Plug-in terminal block Breaker
M10 terminal block mounting screw
100.5
25.5
269
13
28.5
225
30
15 32 8
104
136
12
Connection
allowance ø12
ø13
Conductor thickness 43
Insulating 70 140
t=6 × 2pcs max. 140
barrier 204 274
68
Bolt M12 × 45
208 134 3-pole 4-pole
Drilling plan
Draw-out
Specify in case of
mounting vertically.
105
269
514
464
464
15 32 8
97
232
257
232
13
ø13
257
12
Remark: (1) Draw-out is available only for 3-pole models of NF1000-SS and NF1250-SS.
Rated short-
circuit breaking
capacity (kA)
IEC 60947-2 40/20 40/20
DC 250V
(Icu/Ics)
Time constant
not larger than
10msec
Type NF1000-SSD
1h 1h
Type Type
40min 40min
NF1000-SSD NF1250-SSD
1000A 1250A
20min 20min
DC DC
Maximum
10min 10min
Maximum
6min 6min
4min 4min
2min 2min
1min 1min
40s 40s
Inst. trip adjustment range
30s 30s Minimum
Operating time
Operating time
(4 steps)
20s Inst. trip adjustment range 20s
Minimum
(4 steps) Control Inst. trip
10s 10s setting current(A)
Control Inst. trip
6s setting current(A) 6s L0 2800 ± 700
4s L0 2800 ± 700 4s 2 4200 ± 700
2 4200 ± 700 3 5600 ± 700
2s 2s
3 5600 ± 700 Hi 7000 ± 700
1s Hi 7000 ± 700 1s
0.6s 0.6s
0.4s 0.4s
0.2s 0.2s
0.1s 0.1s
0.06s Max. total 0.06s Max. total
interrupting time interrupting time
0.0.4s 0.0.4s
Time 0.02s Time
0.02s
delay trip Inst. trip delay trip Inst. trip
0.01s 0.01s
1 1.25 2 3 4 5 7 10 20 30 40 50 70 1 1.25 2 3 4 5 7 10 20 30 40 50 70
90
80
5 10 20 30 40 50 60
Remark: (1) refer to page 1. Ambient temperature (°C)
Front connection Outside dimensions are same as those of NF1000-SS and NF1250-SS.
Insulating barrier
(removable) Conductor thickness 15 40
t=8 × 2pcs max.
Mounting hole
Bolt M12 × 50 Breaker
110
Auxiliary handle
(removable)
406
375
346
ø9.5
13
15 32 8
ø17.5
80
18.5 70 70
15 44 M8 screw or ø10
43 70 133.5
140 210 17 140
ø13 M12 bolt 3-pole 4-pole
210 280 190
280
3-pole 4-pole Drilling plan
Rear connection Outside dimensions are different from those of NF1000-SS and NF1250-SS.
R11.5
375
233
97
Connection allowance
22 ø13
13
86
Conductor thickness
45
18 12 70 70
80
140 230 300
8 32 15 Insulation cover
(removable) M8 screw or ø10
140 97 1.0mm clearance on each side
3-pole 4-pole of the handle frame.
Plug-in Outside dimensions are different from those of NF1000-SS and NF1250-SS.
Mounting plate
Plug-in terminal block M10 terminal block mounting screw Breaker
Stud can be rotated 90˚
248
318
375
48
12
13
30
104
8
32
Connection allowance
15
Drilling plan
Remarks: (1) Standard specifications of NF1000-SSD and NF1250-SSD are 2-pole models. 3-pole and 4-pole models are for DC special voltage.
(2) 2-pole models are 3-pole models with the central pole removed.
Type NF1250-UR
■Operating Characteristics
3h
2h Type
NF1250-UR
1h
40min Rated current 600,700,800,1000,
30min 1200,1250A adjustable
20min Short-time pickupcurrent adjustable
500% ± 50%
10min
750% ± 75%
6min 1000% ± 100%
4min inst. pickup current adjustable
+4kA
20kA
2min Maximum -2kA Fixed
1min
40s
Operating time
30s
20s
10s
6s Minimum
4s Short-time pickup current
adjustment range
2s
1s
0.6s
0.4s For 600A rated current
0.1s
0.06s
0.0.4s
Unlatching time
0.02s Maximum total interrupting time
0.01s
1 1.25 2 3 4 5 7 10 20 30 40 60
130
Rated ambient
Operating handle
Left-side Right-side AL Lead wire 120
AX SHT or UVT direction
mounting mounting 110
100
90
80
70
0 10 20 30 40 50 60
Remark: (1) refer to page 51. Ambient temperature (°C)
Front connection
Conductor thickness
t=8 × 2pcs max. 15
Insulating barrier
Insulating barrier 44
43
ø13 M12 bolt Bolt M12 × 50
Terminal block
106
346
375
Neutral pole
22.5
ø9.5
13
ø17.5
80 80
Auxiliary handle 70 70
8
3-pole 4-pole
15
43 70 51
210 15
140
ø13 M12 bolt Center line of breaker 137.5 Drilling plan
240 310
17 144
3-pole 4-pole 194
284
Rear connection
R1
86
1.5
109
269
81.5
88
97
273
39.5
18 Connection
allowance
Auxiliary handle 22
45
13
120
t=6 × 2pcs max.
15 12
70 M8 tap or ø10 70
81 ø13 140 Bolt M12 × 45 260 330 80
22.5 8 Insulation cover
137.5 32 (removable) 3-pole 4-pole 1.0mm clearance on each side
of the handle frame.
17 144 185
194
Drilling plan
284 Front-panel cutout
Plug-in
ø9.5
Auxiliary handle
(removable)
269
105
22.5
100.5
269
25.5
28.5
225
13
30
32 8
104
12
136
Connection allowance
ø12
15
Type NF1600-SS
■Operating Characteristics
3h
2h Type
NF1600-SS
1h
Rated current 800, 1000,
40min
1200, 1400, 1500, 1600A
30min
adjustable
20min
Short-time pickup
10min current adjustable
300% ± 30%
6min
450% ± 45%
4min
600% ± 60%
Maximum
inst, pickup current
2min
+4kA
20kA Fixed
-2kA
1min
AC
40s
30s
Operating time
6s
4s
2s
1s
0.6s
0.4s
For 800A rated current
0.2s
0.1s
0.06s
Unlatching time
0.04s
For 1600A rated current
0.02s
Max. total interrupting time
0.01s
1 2 3 4 5 7 10 20 30 40 60
Rated ambient
110
100
Only SHT can be mounted on
right-side of NF1600-PAL. 90
80
Remark: (1) refer to page 51.
70
0 10 20 30 40 50 60
Ambient temperature (°C)
Front connection
Breaker
(185.5)
406
97
346
375
ø17.5
ø9.5
N
115
130
80
M8 tap or ø10
20 49.5 70 70
203 133.5 1.0mm clearance on each side
101.5
Neutral pole 3-pole 4-pole of the handle frame.
263 304.5 17 140
364.5 190
Drilling plan Front-panel cutout
280
3-pole 4-pole
Rear connection
Connection 15 38 15
allowance
38
60
106 106
18
318
212
160 min.
20
20
269
100 max.
109
109
273
273
15 Connection
81.5
allowance
18
38
M8 tap or ø10
60
36
70 70
54
15
140
38 38 ø11 70 3-pole 4-pole
ø11
125 15 BM10 × 50 bolt 210 140 125 M10 × 50 bolt
3-pole 140 200 4-pole Drilling plan
Draw-out
R163
Rail for draw-out
Connecting position
(removable)
Auxiliary circuit
550
430
terminal
395
430
273
158
38 19
217
217
168
25
150
38
ø14
212 Mounting hole ø14 412 Connecting position 101 20 416
203
416 502 Connecting position ø11 Insulating barrier
Handle for plug-in
466 802 M10 bolt (removable)
and draw-out
917 Connecting position Drilling plan
490
938 Draw-out position
Type NF1600-SSD
■Operating Characteristics
4h
Type
2h NF1600-SSD
for MAG-ONLY
1h
1600A
30min DC
20min
Max. allowable time of Overcurrent
14min
10min
6min
4min
2min
1min
30s
Operating time
20s
Inst. trip adjustment
10s range (4 steps)
2s Lo 3200±800
2 4800±800
1s 3 6400±800
Hi 8000±800
0.5s
0.2s
0.02s
Inst.trip
0.01s
100 135 200 300 400 500 600 700 1000 1500 2000 3000 4000
■Internal Accessories
Operating handle
Left-side Right-side AL Lead wire
AX SHT or UVT direction
mounting mounting
Bolt M10 × 65
(185.5)
(185.5)
3-pole Breaker
Auxiliary handle Breaker
(removable)
R11.5
406
346
375
97
ø17.5
ø9.5
115
130
M8 tap or ø10
20 49.5 70 70 80
101.5 133.5
203
304.5 1.0mm clearance on each side
263 17 140
364.5 3-pole 4-pole of the handle frame.
190
280
3-pole 4-pole Drilling plan Front-panel cutout
Connection allowance 15 38 15
38
60
106 106
18
318
212
109
Connection allowance
375
233
233
15
36
60
38
140 ø11 70 70
38 15 M10 × 50 bolt
38 M8 tap or ø10
Stud can be rotated 90˚ 15
Stud is in horizontal direction.
125 140 125
Stud can not be rotated 90˚
140 200 3-pole 4-pole
Drilling plan
3-pole 4-pole
Remarks: (1) Standard specification of NF1600-SSD is 2-pole model. 3-pole and 4-pole models are for DC special voltage.
(2) 2-pole models are 3-pole models with the central pole removed.
1. Accessories
Table 5-1: Accessories
Internal accessories Function Applicable models Cassette-type of accessories
AL Alarm switch A switch that electrically indicates the trip status of the circuit breaker. NF-C·S·H·U,
NV-C·S·H·U
●
AX Auxiliary switch A switch that electrically indicates the ON-OFF status of the circuit breaker. and MB series
●
SHT
A device that electrically trips the circuit breaker from a remote distance. NF-C·S·H·U
Shunt trip Permissible working voltages are 70 to 110% of the AC rated voltage or and MB series ●
70 to 125% of the DC rated voltage.
UVT
A device that automatically trips the circuit breaker if the voltage is lowered. NF-C·S·H·U, (Note 1)
Undervoltage trip Working voltages are 70 to 35% of the UVT rated voltage. When the voltage NV-C·S·H·U ●
recovers to 85% or higher, you can reset the device and put into operation. and MB series
EAL
A switch that electrically indicates the trip status of the earth leakage circuit
Earth-leakage alarm switch breaker caused by a ground fault. If 250AF and less, This switch is available NV-C·S·H·U –
only for models with the vertical lead-wire terminal unit (SLT).
TBM
This module allows you a remote testing by applying a voltage.
Test button module An external sequence common to SHT can be used. (The standard NV-C·S·H·U –
configuration requires the vertical lead-wire terminal unit (SLT).)
MG Insulation switch
The incorporation of this switch enables the measurement of insulation resistance
between the terminals of the load with the circuit breaker being turned OFF.
NV-C·S·H·U –
PAL Pre-alarm module Indicates that the load current exceeds the pre-alarm setting current. Electronic Types –
OAL Overcurrent trip alarm switch Indicates that the breaker has been tripped by overcurrent or short-circuit current. Electronic Types
(SGW, HGW, RGW, UGW) –
Note: (1) Models NV250-SEW/HEW are excluded. Remark: (1) Accessory terminals are marked by both IEC-based terminal symbols
and conventional symbols, like 98/ALa.
ON MG switch (closed)
AL 1 2
(Note 7) (Note 7)
AX 1 2
(Note 2)
AL + SHT or UVT
(Note 2)
AX + SHT or UVT
(Note 1)
(Note 2)
Accessories AL + AX + SHT or UVT
MG
(Note 7)
AL + MG
AX + MG
(Note 8) (Note 5)
EAL
(Note 8)
TBM
(Note 8)
PAL
NF1000-SS
NF630-CP/SP NF1250-SS
NF400-CP/SP NF630-SEP/HEP/REP NF1600-SS
NF- C/ S/H
NF400-SEP/HEP/REP NF800-CEP/SDP NF1000-SSD
Type NF800-SEP/HEP/REP NF1250-SSD
NF1600-SSD
NF- U NF400- UEP (3P) NF400- UEP (4P), NF630- UEP, NF800- UEP NF1250-UR
Poles 2, 3, 4
Switch type S V
✳3
AL
✳3
1 3 1 5 3 1 3
AX 2 4
2 4 2 6 4 5 6
✳1 ✳1 ✳2
✳2 ✳2
SHT
or
UVT
✳3 ✳3
AL + AX
✳1 ✳1 ✳2
✳2 ✳2
✳3 ✳3
Accessories AL + SHT or UVT ✳4 ✳4
✳1 ✳1 ✳2
✳2 1 3 ✳2
5
✳3 2 4 ✳3
AX + SHT or UVT ✳4 ✳4
1 3 1
3
2 4 2
✳1 ✳1 ✳2
✳2 ✳2
✳3 ✳3
AL + AX + SHT or UVT ✳4 ✳4
✳5 ✳5
PAL
(contact output)
Option for NF630-SEP/HEP/REP/UEP
Option for NF400- SEP/ HEP/ REP/ UEP NF800-CEP/SEP/HEP/REP/UEP
✳6 ✳6
TI
NV630-CP/SP
NV400-CP/SP
Type NV- C/ S/H NV630-SEP/HEP
NV400-SEP/HEP/REP
NV800-SEP/HEP
Poles 3, 4
Switch type S
✳2
AL
✳2
AX
✳1 ✳1
SHT or UVT
✳2 ✳2
AL + AX
✳1 ✳1
✳2 ✳2
✳3 ✳3
Accessories AL + SHT or UVT
✳1 ✳1
✳2 ✳2
✳3 ✳3
AX + SHT or UVT
✳1 ✳1
✳2 ✳2
✳3 ✳3
AL + AX + SHT or UVT
MG
AL + MG
NV630-CP/SP
NV400-CP/SP
Type NV- C/ S/H NV630-SEP/HEP
NV400-SEP/HEP/REP
NV800-SEP/HEP
Poles 3, 4
Switch type S
AX + MG
AL + AX + MG
EAL
Accessories TBL
TBM
✳1 ✳1
TI
Poles 2 3 3 3
Switch type S S S
(Note 7)
AL
1 2 1 2 1 2
(Note 7)
AX 1 3 1 5 3
1 2 1 2 1 2
2 4 2 6 4
Accessories AL + AX 1
(Note 5)
2 1
(Note 5)
2 1
(Note 5)
2
(Note 7) (Note 7) (Note 5) (Note 5)
5
1 2 1 2 1 2
AL + SHT or UVT
1 3 1
3
2 4 2
Notes: (1) If a UVT is used, a UVT voltage module is installed on the lead wire terminal block. (The SHT requires no voltage module.)
(2) If a UVT is used, a UVT voltage module is installed on the lead wire terminal block. (The SHT requires no voltage module.) No cassette is attached to the UVT.
(3) If a UVT is used, the UVT voltage module is externally installed. (The SHT requires no voltage module).
(4) No SHT can be installed.
(5) The 2nd AX can be installed instead of the AL on the left pole.
(6) The standard mounting of the SHT and the UVT is performed on the right pole. If mounting on the left pole is required, instruct us. (The UVTs for interlocks are mounted on the left pole.)
(7) We can manufacture the SLTs used when 3 or more accessories are installed on the left pole and the SLTs used when the AL and the AX are attached on the same pole that is
attached with the SHT or the UVT at your order.
(8) If a UVT is used and an AL, an AX or an AL + an AX are attached to the same pole that is attached with the UVT, the UVT voltage module is separately installed.
AC100-120
1000 • 1250 • 1600 Frame 200-240
NF1000-SS/SSD, NF1250-SS/SSD/UR 380-450 200 70 7~15
NF1600-SS/SSD (50 also 60Hz)
DC100
Notes: (1) Secure a sufficient input power so that the voltage will not drop below the permissible lower working voltage (70% of the lowest rated voltage).
(2) The operating time denotes the time from when the rated voltage is applied to SHT until when the main contact of the breaker starts to open.
NF-C • S • H • U
MB – ● – – ● – ● – ● – – – ● –
32(30) • 63A Frame 125A Frame 160 • 250A Frame
NF400-CP/SP/SEP/HEP/REP, NF630-CP/SP/SEP/HEP/REP,
NF800-SDP/CEP/SEP/HEP/REP, NF400-UEP, NF630-UEP, NF800-UEP – – – ● ● – – – – – – – – ●
NV400-CP/SP/SEP/HEP/REP, NV630-CP/SP/SEP/HEP, NV800-SEP/HEP
NF1000-SS/SSD, NF1250-SS/SSD/UR
● – ● – ● ● – ● – ● ● ● – –
NF1600-SS/SSD
Table 5-12 18
Series NV-C • S • H • U
Compatible to
Input rated
AC100-240/ TBM2
control
DC100-240 TBM1
voltage (V)
(DC24) (Note 1)
92 (Terminal
cover)
10.5
Input control
1VA or less
power (VA)
12.5
7. Lead-wire Specifications
Table 5-13
E
B
8
13.5
F
B
D
25
8
E
13.5
41
A 75
Pre-alarm LED The LED starts blinking on the circuit breaker when load current exceeds the preset current, then changes to continuous glowing
when pre-alarm output is given.
Solid-state relay output Open the upper cover of the circuit breaker, connect the connector of the lead wire packed together and use it as the lead wire
outlet. In this case, only the lead wire outlet of the internal accessories can be attached to the right pole. (For flush plate type,
the outlet is manufactured in advanced as a PAL mount.)
Pre-alarm module SLT is attached as standard and is used as the control power source of 100VAC or 200VAC. In this case, no other internal
accessories can be attached to the right pole. (Auto resetting is also applicable.)
•Pre-alarm characteristics
5
10h
5h 5h
Pre-alarm pick-up current
2h 2h
Pre-alarm pick-up current
1h 1h
30min 30min
20min 20min
14min 14min
10min 10min LTD operating time TL
6min LTD operating time TL 6min 12-60-100-150s ± 20%
4min 12-60-80-100s ± 20% 4min (at 200%)
Operating time
Operating time
(at 200%)
2min 2min
1min 1min
30s 30s
20s 20s
10s 10s Pre-alarm
Pre-alarm
5s 5s pickup current Ip
pickup current Ip
Ir x(0.7-0.75 Ir x(0.7-0.75
2s -0.8-0.85-0.9 ± 10% 2s -0.8-0.85-0.9 ± 10%
-0.95-1.0) -0.95-1.0)
1s Pre-alarm 1s Pre-alarm
0.5s operatiing time Tp 0.5s operatiing time Tp
Tp= TL ± 20%
Tp= TL ± 20% 2
0.2s 2 0.2s (at 200%)
(at 200%)
0.1s 0.1s
60 70 100 125 200 300 400 500 600 700 1000 1500 60 70 100 125 200 300 400 500 600 700 1000 1500
Current Current
Percentage (%) to rated current or preset current rating Percentage (%) to rated current or preset current rating
(NF/NV125,250AF) (NF/NV400,630,800AF)
98
instantaneous(INST) alarm LED
Table 5-19
Phase/ wire type 3 ø 4W
Rated voltage VAC 415
Usable supply voltage VAC 304~484
Usable voltage (line voltage) VAC 380 400 415 440
Total operating overvoltage (phase voltage) (135% of total phase voltage) VAC 296 312 323 343
Tripping
Total non- operating overvoltage (phase voltage) (120% of total phase voltage) VAC 263 277 288 305
characteristics
Total overvoltage operating time (s) 1
Overvoltage non- operating time (s) More than 0.1
Trip indication method Button
Reset method Reset button (open- phase display use)
1c
AC DC
cos ø L/ R
Voltage Voltage
External output contacts 1.0 0.4 0 0.007
100, 120V 7A 7A 30V 7A 6A
200, 240V 7A 7A 125V 0.6A 0.6 A
415V 5A 2A 250V 0.3A 0.3 A
Remark: Using with a shunt- trip device (SHT) equipped breaker will improve tripping and phase protection.
Test button
52
Operation display
68
20
60
83
109
(reset button)
92.5
Current switch
74
52 52
11.5
H
ON
H
ED
PP
TR
I
90
B
F OF
SET
RE
Left Right
Hinge Hinge
Plate
thickness
16 Circuit
1.2–3.2 C D
90 breaker
54 Minimum E
Maximum F X X
● This handle in conjunction with the breaker main ● Mounting-hole Drilling Dimension Diagram
enables the isolation function effective. H X
● The safety standards of EN Standards Circuit breaker Center of the Center of the 0 or more (5H+100) or more
operating handle circuit breaker
(EN60204-1) are satisfied. Center of the
circuit breaker The above illustration shows a view
Center of the circuit
● Degrees of protection (IEC60529) IP65 is operating handle
C
L
breaker operating handle
C
L C
L of the hinges and the circuit breaker
satisfied standardly. when viewed from the direction of
● OFF-position lock only is available for up to three the load.
(Note 1)
commercial padlocks (ø8). ● FrontPlate Drilling
● A door-lock mechanism allows the door to be C C Dimension Diagram
H
H
L L
opened at OFF-position only. Center of the circuit breaker
(Note 1) operating handle
CL ø9
Circuit
J
Either M4×0.7 Either M4×0.7 breaker
G 4
ø5
54
screw or ø5 G G screw or ø5 CL
3-pole 4-pole
Note 1: The drilling at this position is not required for the models of both V2GSW and V2GSWF. 54
Table 5-20: Summary of Dimensions
Number Dimensions (mm)
Type name Applicable models
of poles A B C D E F G H J
3P 75 –
V05SW NF32-SW, NF63-CW/SW/HW, NV32-SW 154 300
4P 100 12.5
NV63-CW/SW/HW, MB30-SW 130 44 61 25 111
MB50-CW/SW 3P 75 –
V05SWF (Note 2) 125 –
4P 100 12.5
–
5
3P 90
V1SW 154 518
NF125-CW/SW/HW, NV125-CW/SW/HW 4P 120 15
130 44 61 30 111
MB100-SW 3P 90 –
V1SWF (Note 2) 125 –
4P 120 15
2P, 3P 105 –
V2SW 154 518
NF160-SW/HW, NF250-CW/SW/HW, NV250-CW/SW/HW 4P 140 17.5
165 46 61 35 126
NV250-SEW/HEW, MB225-SW 2P, 3P 105 –
V2SWF (Note 2) 125 –
4P 140 17.5
2P, 3P 105 –
V2GSW 172 536
4P 140 17.5
NF125-SGW/HGW, NF160-SGW/HGW, NF250-SGW/HGW 165 46 79 35 126
2P, 3P 105 –
V2GSWF (Note 2) 143 –
4P 140 17.5
Notes: (1) This hole is not required for two and three poles.
(2) The last letter of “F” of the type designations of V-type operating handles denotes a fixed type.
Remark: (1) You may contact us for details of the V-type operating handle for the U series.
Handle
M6 screw X X
or 7
N X
104
A
B
O or more P or more
PP
ED
ON Center of H X1 H X2
the circuit
I
TR
breaker Less than 170
104
and the 0 (5H+100) 10 or more
FF
ET O
ES
or more or more
E
S
NR
R ELEA
operating
OPE
10 (5H+120)
handle
or more or more
Plate
● This handle in conjunction with the breaker 104 thickness 1.2–3.2
enables the isolation function effective. 51 A±2
Operating handle
● The standard model is equipped with a safety Front plate
device that prevents the circuit breaker from
● Drilling Dimension Diagram
being turned on if the door is open. (If not
H
desired, please specify so.) Center of the circuit
Circuit breaker
breaker operating handle 4 ø12 Right hinge
● The handle can be locked at either ON or CL
CL Left hinge
circuit
OFF position. (Three padlocks (40mm) can (a) (b)
breaker
Circuit
be installed. OFF-position lock only
0
ø9
breaker
78
C
The above illustration shows a view of
(IP5X with dustproof packing) 78 the hinges and the circuit breaker when
(b) (a)
Remark: (1) Trip action can be displayed when the circuit viewed from the direction of the load.
breaker trips even if ON-position lock is selected D
B
(only in the case of a single padlock (35 mm)).
Table 5-22: Summary of Dimensions
Number Dimensions (mm) Mounting
Type name Applicable models of poles A *1 B C D screws
*2 F05SW2P *3 F05SWR2P NF32-SW, NF63-CW/SW/HW 2P –
(a) Circuit
NF32-SW, NF63-CW/SW/HW, NV32-SW, NV63-SW/HW, MB30-SW, MB50-CW/SW 3P, 4P 111 breaker
*2 F05SW *3 F05SWR 25
NV63-CW/SW 2P, 3P 105 Either mounting screws
*2 F1SW2P *3 F1SWR2P NF125-CW/SW/HW 2P – M4×0.7 (2pcs)
111 screw or ø5 (b) Handle
*2 F1SW *3 F1SWR NF125-CW/SW/HW, NV125-CW/SW/HW, MB100-SW 3P, 4P 30
*2 F2SW *3 F2SWR mounting screws
NF160-SW/HW, NF250-CW/SW/HW, NV250-CW/SW/HW, NV250-SEW/HEW, MB225-SW 2P, 3P, 4P 107 35 126
(2pcs)
*2 F2GSW *3 F2GSWR NF125-SGW/HGW, NF160-SGW/HGW, NF250-SGW/HGW 3P, 4P 125 35 126
*1. Dimensions of both front connection and rear connection are shown. The plug-in type has a different reference plane for mounting the circuit breaker.
*2. The standard type is epuipped with a door-lock mechanism that allows door to be opened only when OFF operation is carried out.
*3. In case of reset opened type use.
Remarks: (1) The test button becomes difficult to press when an operating handle is installed on an NV model. Then, use models with either TBM instead.
(2) Dustproof packings are separately available.
(3) You may consult us for details of the F-type operating handle for the U series.
● Appearance (Color N1.5) ● External dimensions Center of Hinge and Circuit Breaker
Flusf plate Front panel
Left hinge Right hinge
D ON
H X1 H X2
RIEP
TP
● Includes
(a)
as standard a safety device which
● Drilling plan Breaker
H
X1 X2
11
D
112
single padlock (35mm) is used. The figure above shows the relationship
(X)
● Degrees of protection (in accordance with (Y)
between the hinge and breaker viewed
IEC60529): IP3X (IP5X with provision of 112 C
E
from the load side of the breaker.
(b) (c)
dustproof packing).
Table 5-23
Fig Dimensions (mm)
Type Breaker type Number of poles Mounting
External Drilling *5 crews
dimensions plan A B C D E F
*6 F4SPW *7 F4SPWR NF400- CP/ SP/ SEP/ HEP/ REP 2P, 3P, 4P
183 44 194 —
*6 F4SPWNV *7 F4SPWRNV NV400- CP/ SP/ SEP/ HEP/ REP 3P, 4P
*6 F4UPW *7 F4UPWR
NF400- UEP 3P 280 44 234 20
NF630- CP/ SP/ SEP/ HEP/ REP M6 screw
*6 F6SPW *7 F6SPWR 2P, 3P, 4P 53 or ø7
NF800- CEP/ SDP/ SEP/ HEP/ REP (X)
183 70 243 — Breaker
*6 F6SPWNV *7 F6SPWRNV NV630- CP/ SP/ SEP/ HEP, 3P, 4P a b c mounting
NV800- SEP/ HEP
screws
*6 F6UPW *7 F6UPWR NF400- UEP (4P), NF630- UEP, NF800- UEP 3P, 4P 280 70 290 23.5 (4 pcs)
*7 F100 2P, 3P
NF1000-SS/SSD, NF1250-SS/SSD 221 70 375 —
*7 F1004P NF1600-SS/SSD 4P M8 screw
50
*7 F120UR 3P or ø10
NF1250-UR 225 70 375 —
*7 F120UR4P 4P
*1. Handles with NV in the product name include a test button. *5. The figures show the dimensions of the front connection. Some connection and plug-in breakers have a different reference
*2. Dustproof packing is also available as an option. surface for mounting purposes.
*3. Other optional handles can also be mounted. *6. The standard type is equipped with a door-lock mechanism that allows the door to be opened only when OFF operation is
*4. F4SPW~F6UPW are for isolation purposes. carried out.
(Speify OFF lock only.) *7. In case of reset opened type use.
I
TR
TR
When OFF-lock, please turn
OFF
OFF
ON
ED
PP handle in RESET direction.
T
I
T
SE
TR
SE
RE
RE
2
OFF T
SE
RE
The door can be opened with the RESET-position open OFF-position open
operating handle RESET-position OFF-position RESET-position OFF-position
or OFF-position. Lock lever
When the operating handle was
ON ON ON
locked, the panel (door) can not PP
ED
PP
ED
PP
ED
I
I
TR
TR
TR
be opened.
Door opening system
OFF
OFF
OFF
ET
ET
T
SE
RES
RES
RE
Lock plate
Mounting direction Reconstruction to vertically from Vertically type Horizontally type Horizontally type
horizontally can not be (ON side of breaker is upper) (ON side of breaker is left) (ON side of breaker is right)
The top of label is ON side of performed.
breaker
ON side
ON ON ON
5
ED ED ED
PP PP PP
I
I
TR
TR
TR
OFF
OFF
OFF
T
SE
SE
T
SE
RE
RE
RE
Label
of emergency
Yellow color
70
(Note 3)
41.5±4
Max. 95
47 Deviation
ON 70 of 4mm
IP
or less
R
Clasp ø12
OFF T
(Note 1)
114
Front plate deviation of 4mm or less
Center of the circuit breaker
Max. 115
operating handle 100 or more (210 or more
● The handle can be locked at either ON or when the hinge is on the left)
(Note 3)
OFF position. (Three padlocks (40mm) can
80
17 43.5±4 Front plate thickness 1.2–3.2
be installed. Off-position lock only Clasp
(Note 1)
specifications are also acceptable.) Hinge
(Note 2) C±2
(Note 2)
● Digrees of protection (IEC60529) IP5X 45
B±2
A±2
Remark: (1) Trip action can be displayed when the circuit 34 40 110 Clasp
breaker trips even if ON-position lock is selected (option)
(only in the case of a single padlock (35 mm)).
Reference plane for mounting
Table 5-24: Summary of Dimensions the circuit breaker
Dimensions (mm)
Type name Applicable models
A (Note 4) B (Note 4) C (Note 4)
S05SW NF32-SW, NF63-CW/SW/HW, NV32-SW, NV63-CW/SW/HW, MB30-SW, MB50-CW/SW
87 102 104.5
S1SW NF125-CW/SW/HW, NV125-CW/SW/HW, MB100-SW, NV125-RW (Note 5)
NF160-SW/HW, NF250-CW/SW/HW, NV250-CW/SW/HW
S2SW 95 110 112.5
NV250-SEW/HEW, MB225-SW, NV250-RW (Note 5)
S2GSW NF125-SGW/HGW, NF160-SGW/HGW, NF250-SGW/HGW 113 128 130.5
Notes: (1) The clasps are not supplied standardly, and should be prepared by users Details on dimensions and others will be available upon request. Remark: (1) Reset open-type
(2) When the optional clasp is used. (2) These are not suitable for isolation.
(3) The tolerance from the center of ø62 is shown.
(4) The dimensions of the front-face type are shown. Some of the back-face and plug-in types have a different reference plane for mounting the circuit breaker.
(5) The front plate drilling dimensions for the U series differ from those shown above. Please consult us for their details.
● Appearance (Color N1.5) ● External dimensions ● Drilling plan 4- 5.5
Centre of
Front panel Operating plate 62 breaker
D
max. 150
84
Decorative plate
35 ± 5
45
ON
IP
*3
84
TR *1 12
114
Retainer
OFF
*5
Deviation: 2 mm or less
max. 145
130(S4CP·S4SP)
*2
● Degrees of protection (in accordance with (a) Retainer (b)
(option) Reference plane
IEC60529): IP5X. for mounting the breaker
Table 5-25
Fig Dimensions (mm)
Type Breaker type External Drilling plan A✳4 B✳4 C✳4 D
dimensions
S4CP *5 NF400- CP, NV400- CP a b 140 156 — 0
NF400- SP/ SEP/ HEP/ REP, NV400- SP/ SEP/ HEP/ REP
NF630- CP/ SP/ SEP/ HEP/ REP, NV630- CP/ SP/ SEP/ HEP 162 178 —
S4SP *5 NF800- CEP/ SDP/ SEP/ HEP/ REP, NV800- SEP/ HEP a b
NF400- UEP (3P) 259 275 — 20
NF400- UEP (4P), NF630- UEP, NF800- UEP 259 275 — 23.5
NF1000-SS/SSD, NF1250-SS/SSD
199 215 — 0
S100 NF1600-SS/SSD a b
NF1250-UR 203 219 — 0
Notes: *1. Retainers are not included. They must be provided by the customer. Remark: (1) Reset open-type
*2. When using optional retainer.
*3. Shows the tolerance for the distance from the center of a 62mm dia. hole.
*4. The figures show the front-connection dimensions. Some rear-connection and plug-in breakers have a different reference surface for mounting purposes.
*5. S4CP and S4SP are for isolation purposes. (Specify OFF lock only.) The tolerance is less than 5mm. It does not conform to isolation purposes, however, if the deviation is more than 2mm.
●Surface plate interlocking fastening (separately available)
Operation Breaker type Dimensions (mm)
handle series Type Drilling diagram and referential diagram
MCCB ELCB A B
NF32-SW NV32-SW
NF63-CW/SW/HW NV63-CW/SW/HW Fastening ON
NF125-CW/SW/HW NV125-CW/SW/HW
MB100-SW
TG-S1UW NF125-RGW/UGW NV125-RW
TG-S05SP – NV100-SEP, HEP
NF160-SW/HW – –
TG-S2SW NF250-CW/SW/HW NV250-CW/SW/HW
NF250-SEW/HEW,MB225-SW NV250-SEW/HEW Fastening OF
F
ON
Handle
88
B
16 C
D
88 E
H
CL
(Note 1)
J
F Either M4×0.7 Either M4×0.7 F Either M4×0.7
screw or ø5 F F screw or ø5 screw or ø5
Center of the
(a) 2, 3-pole (b) 4-pole operating handle (c)
Note 1: The drilling at this position is not required for the models of R2GSW.
Table 5-26: Summary of Dimensions
Number Fig Dimensions (mm)
Type name Applicable models Drilling
of poles
plan A B C D E F G H J
3P a 90 —
NF125-CW, NF125-SW, NF125-HW 130
R1SW 61 105 142 30 111 —
NV125-CW, NV125-SW, NF125-HW 4P b 120 15
2P, 3P a 105 —
NF125-SGW, NF125-HGW, NF160-SGW, NF160-HGW, 165 79 125 162 35 126 —
R2GSW
NF250-SGW, NF250-HGW 4P b 140 17.5
R2GUW NF125-RGW, NF125-UGW, NF250-RGW, NF250-UGW 3P c 105 240 79 125 162 35 201 37.5 —
Breaker
B
A
M6 screw
or 7
L
E G
D F H (b)
(a) C J
Table 5-27
Breaker type Fig Dimensions (mm)
Type Drilling
MCCB ELCB Outview A B C D E F G H J K L M
plan
NF400- CP, NF400- SP, NF400- SEP,
R4SPW —
NF400- HEP
257 128 140 14 0 25 43 97 174 218 19 4 44 —
R4SPWNV — NV400- CP, NV400- SP,
NV400- SEP, NV400- HEP a b
Ordering information
V 1 SW E F NV F 1 SW A R Y 2P NV
1) 2) 3) 4) 5) 6) 1) 2) 3) 4) 5) 6) 7) 8)
1) V : Operating handle type V······· Variable-depth handle 1) F : Operating handle type
R······· Rotary handle 2) 1 : Frame size of breaker 05····· NF32-SW, NF63-CW/SW/HW,
2) 1 : Frame size of breaker 05····· NF32-SW, NF63-CW/SW/HW, MB30-SW, MB50-CW/SW,
MB30-SW, MB50-CW/SW, DSN32-SW, DSN63-CW/SW,
DSN32-SW, DSN63-CW/SW, NV32-SW, NV63-CW/SW/HW
NV32-SW, NV63-CW/SW/HW 1······· NF125-CW/SW/HW,
1······· NF125-CW/SW/HW, NV125-CW/SW/HW, MB100-SW,
NV125-CW/SW/HW, MB100-SW, DSN125-CW/SW, NV125-RW
DSN125-CW/SW, NV125-RW 2······· NF160-SW/HW, NF250-CW/SW/HW,
2······· NF160-SW/HW, NF250-CW/SW/HW, MB225-SW,
MB225-SW, NV250-CW/SW/HW/SEW/HEW,
NV250-CW/SW/HW/SEW/HEW, DSN250-CW/SW, NV250-RW
DSN250-CW/SW, NV250-RW 2G···· NF125-SGW/HGW,
2G···· NF125-SGW/HGW, NF160-SGW/HGW,
NF160-SGW/HGW, NF250-SGW/HGW, DSN125-SGW,
NF250-SGW/HGW, DSN125-SGW, DSN160-SGW, DSN250-SGW,
DSN160-SGW, DSN250-SGW, NF125-RGW/UGW, NF250-RGW/UGW
NF125-RGW/UGW, NF250-RGW/UGW 4······· NF400-CP/SP/SEP/HEP/REP,
4······· NF400-CP/SP/SEP/HEP/REP, DSN400-CP/SP,
DSN400-CP/SP, NV400/CP/SP/SEP/HEP/REP,
NV400/CP/SP/SEP/HEP/REP NF400-UEP
6······· NF630-CP/SP/SEP/HEP/REP, 6······· NF630-CP/SP/SEP/HEP/REP,
DSN630-CP/SP, DSN800-CP/SP, DSN630-CP/SP, DSN800-CP/SP,
NF800-CEP/SDP/SEP/HEP/REP, NF800-CEP/SDP/SEP/HEP/REP,
NV630-CP/SP/SEP/HEP, NV630/CP/SP/SEP/HEP,
NV800-SEP/HEP NV800-SEP/HEP, NF400-UEP(4P),
3) SW : Series name SW indicate WSS C, S and H series NF630-UEP, NF800-UEP
SPW indicate PSS C, S and H series 3) SW : Series name SW indicate WSS C, S and H series
SPW indicate PSS C, S and H series
UW indicate WSS U series
4) E : For emergency Blank······ For general UW indicate WSS U series
E············ For emergency UPW indicate PSS U series
5) F : Adjustment type of Blank······ Variable type 4) A : Handle lock position Blank······ ON/OFF position lock
depth (For only V-handle) F············ Fix type A············ OFF position lock only
6) NV : Type of breaker NV·········· NV type for 400A frame 5) R : Door open position Blank······ OFF position open
Blank······ The other R············ RESET position open
6) Y : Mounting direction Blank······ Vertically type
(ON side of breaker is upper)
S 1 SW A Y············ Horizontally type
(ON side of breaker is left)
1) 2) 3) 4) Z············ Horizontally type
1) S : Operating handle type (ON side of breaker is right)
2) 1 : Frame size of breaker 05····· NF32-SW, NF63-CW/SW/HW, 7) 2P : Number of poles Blank······ 3 pole and 4 pole
MB30-SW, MB50-CW/SW, 2P···········2 pole
DSN32-SW, DSN63-CW/SW, 8) NV : Type of breaker NV·········· NV type for 400 to 800 A frame
NV32-SW, NV63-CW/SW/HW Blank······ The other
1······· NF125-CW/SW/HW,
NV125-CW/SW/HW, MB100-SW,
DSN125-CW/SW, NV125-RW F 100 4P
2······· NF160-SW/HW, NF250-CW/SW/HW, 1) 2) 3)
MB225-SW,
NV250-CW/SW/HW/SEW/HEW, 1) F : Operating handle type
DSN250-CW/SW, NV250-RW 2) 100 : Frame size of breaker 100········· NF1000-SS/SSD, NF1250-SS/SSD,
2G···· NF125-SGW/HGW, NF1600-SS/SSD
NF160-SGW/HGW, 120UR···· NF1250-UR
NF250-SGW/HGW, DSN125-SGW, 3) 4P : Number of poles Blank······ 2 pole and 3 pole
DSN160-SGW, DSN250-SGW 4P·········· 4 pole
4······· NF400-CP/SP/SEP/HEP/REP,
DSN400-CP/SP,
NV400/CP/SP/SEP/HEP/REP,
NF400-UEP
NF630-CP/SP/SEP/HEP/REP,
DSN630-CP/SP, DSN800-CP/SP,
NF800-CEP/SDP/SEP/HEP/REP,
NV630/CP/SP/SEP/HEP,
NV800-SEP/HEP, NF400-UEP(4P)
NF630-UEP, NF800-UEP
3) SW : Series name SW indicate WSS C, S and H series
CP indicate PSS C series
SP indicate PSS S, H and U series
S 100
1) 2)
1) S : Operating handle type
2) 100 : Frame size of breaker 100·········NF1000-SS/SSD, NF1250-SS/SSD,
NF1600-SS/SSD, NF1250-UR
5. Terminal Cover
Table 5-28
Large terminal cover Small terminal cover Transparent terminal Rear terminal cover Plug-in terminal cover
(TC-L) (TC-S) cover (TTC) (BTC) (PTC)
Breaker type A A A A A
B
C
B
B
C
B
C
B
C
C
Notes: (1) Attach the letter “F” to the end of model designation for models with F-type operating handle. (Those are F-type operating-handle dedicated models,
and screws are used for fixing.)
(2) An F-type operating handle can be installed standardly.
Remarks: (1) Parenthesized numbers denote the outside dimensions (A×B×C in mm).
(2) The terminal cover for a four-pole model can be produced upon request.
Table 5-29
5
Large terminal cover Transparent terminal cover Rear terminal cover Plug- in terminal cover
(TC- L) (TTC) (BTC) (PTC)
A
Breaker type B
C Fig.1
A A A
B B
B
C C
A C
B
C Fig.2
NF400- CP/ SP/ SEP/ HEP/ REP TCL- 4SP3 ✳3 TTC- 4SP3
BTC- 4SP3
PTC- 4SP3
2P, 3P TCL-4SP3W ✳4 BTC-4SP3W ✳4
NV400- CP/ SP/ SEP/ HEP/ REP (171✕104.5✕110) (140✕99.5✕42) (140✕99.5✕42)
(171✕99.5✕110)
Fig. 1
TCL- 4SP3 ✳1 BTC- 4SP3 ✳1
NF400- UEP 3P TCL-4SP3W ✳4 — BTC-4SP3W ✳4 —
(171✕132.5/ 196.5✕110) (140✕132.5/ 196.5✕42)
NF630- CP/ SP/ SEP/ HEP/ REP, NV630- CP/ SP/ SEP/ HEP TCL- 6SP3 ✳5 TTC- 6SP3 BTC- 6SP3 ✳2
2P, 3P —
NF800- CEP/ SDP/ SEP/ HEP/ REP, NV800- SEP/ HEP (224✕103.5✕155) (224✕103.5✕155) (210✕97.5✕32)
NF630- SP/ SEP/ HEP, NV630- SEP TCL- 6SP4 ✳6 TTC- 6SP4 BTC- 6SP4 ✳2
4P —
NF800- SEP/ HEP (294✕103.5✕155) (294✕103.5✕155) (280✕97.5✕32)
NF1000-SS/SSD TCL-10SS3
2P, 3P — — —
NF1250-SS/SSD (220✕139✕150)
NF1000-SS/SSD TCL-10SS4
4P — — —
NF1250-SS/SSD (290✕139✕150)
TCL-12UR3
NF1250-UR 3P — — —
(250✕143✕230)
TCL-12UR4
NF1250-UR 4P — — —
(320✕143✕230)
Table 5-32
NF- C series NF400-CP NF630-CP NF800-CEP — NF400-CP NF630-CP NF800-CEP —
NF400- SP NF1000-SS NF400- SP NF1000-SS
NF400- SEP/ HEP/ REP NF1000-SSD NF400- SEP/ HEP/ REP NF1000-SSD
MCCB NF- S·H series NF630- SP NF1250-SS NF630- SP NF1250-SS
type NF1250-SSD NF1250-SSD
NF630- SEP/ HEP/ REP NF1600-SS NF630- SEP/ HEP/ REP NF1600-SS
NF800- SEP/ HEP/ REP NF1600-SSD NF800- SEP/ HEP/ REP NF1600-SSD
NF- U, MB series NF400-UEP NF630-UEP NF800-UEP NF1250-UR NF400-UEP NF630-UEP NF800-UEP NF1250-UR
NV- C series NV400- CP NV630- CP — NV400- CP NV630- CP —
NV400-SP NV400-SP
ELCB NV400-SEP/HEP/REP NV400-SEP/HEP/REP
type NV- S·H series — —
NV630-SEP/HEP NV630-SEP/HEP
NV800-SEP/HEP NV800-SEP/HEP
MN series — — — —
Electrical operation system Motor-drive type (2) Motor-drive type (2) Spring-charged type Spring-charged type
Rated operating voltage (V) 100/ 110VDC, 100/ 110VAC, 200/ 220VAC
(Allowable voltage range (125VDC, 240VAC)
85~110%) ✳1 OFF ON OFF ON
Operating DC 100/ 110V 3.0 (8.0) 4.0 (8.0) 1.0 (3.0) 8 1.0 (3.0) 9
current
(A, rms)✳2 100/ 110V 4.0 (8.0) 5.0 (10.0) 1.0 (3.0) 10 1.0 (3.0) 10
AC
200/ 220V 2.0 (4.5) 3.5 (7.0) 0.5 (1.5) 8 0.5 (1.5) 8
On 0.05 0.07
Operating time (s) Less than 0.3 (self- holding) Less than 0.3 (self- holding)
O ff Less than 3 (self- holding) Less than 3 (self- holding)
Required transformer capacity (VA) 400 700 700 700
Endurance voltage (V) 1500
✳ 1. ( ) voltages are special options and might require an external resistor. For details, consult your dealer.
✳ 2. ( ) shows starting currents.
Control circuit
The dotted line shows an additional connection for the automatic-
reset type.
95 T2 T2
95
ALa
ALa
M :Motor
X :Relay for ON operation
Y :Relay for OFF operation
Z :Relay for changing Motor polarity
T1 :Timer for antipumping
T2 :Timer for automatic reset
LS :Limit Switch
ALa :Alarm switch for automatic reset (a contact)
Spring-charged type
● Electrical operation Switching OFF a breaker with an electrical-operation device
When the ON switch is closed, the coil is excited to release the installed will take 3s. If instant opening is required, install an SHT or
latch mechanism and the force of the closing spring turns the UVT to the breaker.
breaker ON instantly. ● The breaker contains a built-in pumping-prevention relay.
When the OFF switch is closed, a relay starts the motor which turns
the breaker OFF and charges the spring simultaneously.
● Manual operation
Pressing the ON button will release the latch mechanism and the
force of the closing spring turns the breaker ON instantly.
Pressing the leaf spring, pulling out the manual handle and pumping
it back and forth over 10 times will turn the breaker OFF and charge
the spring at the same time.
● Cautions during electrical operation
Whenever an electrical operation device is to be installed in or
removed from the breaker, the breaker must be tripped and the
device discharged.
Pushing the TRIP button on an MCCB with an electrical-operation Internal structure
device installed will not trip the breaker in the OFF state. This does
not mean the breaker is faulty.
Control circuit
The dotted line shows an additional connection for the automatic-
reset type.
Internal connection
CC.....Coil for making
Y.....Relay for pumping prevention
X.....Relay for self-sustaining on OFF side
Earth terminal LS1...Limit switch interlocking with cam
(DC-) P2 LS3 LS2...Limit switch interlocking with cam
LS3...Limit switch interlocking with OFF lock plate
M....Motor
Operational X
M
power supply
P1 X X LS2
Y
Y
ON S2
LS1
OFF CC
RESET S4 Y
Ala
Dimensions
Front connection
25
45
P1P2 S1S2S4 P1P2 S1S2S4
ø8.5
Remarks:
The 2-pole models are 3-pole models
R1
110–111
with the central pole removed.
8
78
111
130
86
80
The three-pole type only is available
39
41
40
Automatic/ max. 19
manual 3-pole and 4-pole types only are
selection (Conductor thickness available for the model NF125-SW.
switch t=5 max.)
61
ON button 158 Conductor drilling for
60 30 30 30 direct connection
Front plate 163 M4x0.7 screw 88
Trip button 86 86
90 90 Display hole or ø5
90 (Charge/Discharge) 3-pole Drilling plan 4-pole Font-plate cut out
120
Breaker
100
Alarm switch AL
(micro loads use)
45
10
indicator check.
R1
2.2-pole breakers are 3-pole
86
80
78
144
165
126
breakers with the central pole
max. 24
31
33
removed.
32
(Bus t max=7)
3.NF250-CW is available in 2-and
3-pole only.
Terminal block Bus drilling for
ON button for alarm switch AL direct connection MB225-SW is available in 3-
MDS base connection
(M4 screw) 88 pole only.
61
100
24 Circuit breaker
50
45
P1 P2 S1 S2 S4 P1 P2 S1 S2 S4
ø8.5
R1
78
10
86
144
165
126
80
35
32
37
Automatic/
max. 24
manual
selection
switch (Conductor thickness
t=7 max.)
ON button
Conductor drilling for
79 35 35 88 direct connection
Front plate
50
Trip button
70 176 M4x0.7 screw
86 35 or ø5
181 3-pole Drilling plan 4-pole Font-plate cut out
90 86
105 90 Display hole
105 (Charge/Discharge)
140
25
45
P1 P2 S1 S2 S4 P1 P2 S1 S2 S4
ø8.5
R1
110–111
8
78
111
130
86
80
39
40
41
Automatic/ max.19
manual
selection (Conductor thickness
switch t=5 max.)
61
ON button Conductor drilling for
60 30 158
Front plate 163 30 30 88 direct connection
Trip button 86 86 Display hole
90 90 (Charge/Discharge) M4x0.7 screw
90 Test button 3-pole Drilling plan 4-pole or ø5 Font-plate cut out
120
● NV250-SEW, NV250-HEW
Insulating barrier Electrical operation device
Center of MDS Control circuit terminal
(removable) Power supply indicator LED(Red) Hex.socket head
Control circuit terminal (M3.5 screw)
Control circuit M8 bolt
OFFlock TRIP indicator Mounting screw
MANUAL/AUTO plate LED(Yellow) terminal cover
(M3 tapping screw)
switch
Breaker condition's Manual handle MDS Module
Alarm switch AL indicator 24 Center of MDS
15.5
45
P1 P2 S1 S2 S4 P1 P2 S1 S2 S4
ø8.5
R1
80
78
144
165
126
indicator check.
31
32
33
Front connection
● NF400-CP, NF400-SP, NF400-SEP, NF400-HEP, NF400-REP Motor drive type (2)
Center line of electrical operation device Center line of breaker
231
Center line of electrical operation Insulating barrier Conductor thickness t=8 max. 44
device and breaker 8
Breaker Operating circuit terminal Breaker
110
block M3.5 screw
70
194
120
257
277
44
44 44
44 M6
tap or ø7
43
16
94.5
112 22 28
ø14 195 2, 3-pole 4-pole
140 M12 bolt 56
231 255
Trip button 168
185 Drilling plan
2, 3-pole 196
4-pole
Remark: 2 pole models are 3-pole models with the central pole removed.
ø7
47
70
234
297
120
277
257
144
20
ø12.5
ø7
44
44 M6 tap or Ø7
110
141
16
43
191.5
28 292
112 ø14
Drilling plan
352
140 M12 bolt
Trip button
231
194
120
257
277
44 Test button
44 44
44 M6
43
16
94.5 tap or ø7
112 22 28 195
ø14 3-pole 4-pole
140 M12 bolt 56 255
231 168
Trip button
185 Drilling plan
196
3-pole 4-pole
Breaker
70
275
243
120
277
44
Neutral pole
15 32 8
70 M6 70
87
tap or ø7
Trip button 35 40 44
140
210 70 94.5 2,3-pole 4-pole
231 210 ø14 195
280 M12 bolt 255
231 Drilling plan
2, 3-pole
4-pole
Remark: 2 pole models are 3-pole models with the central pole removed.
Front connection
● NF630-UEP (NF400-UEP 4-pole) Motor drive type (2)
Center line of electrical Center line of breaker
Center line of electrical operation Center line of electrical Center line of breaker operation device
device and breaker operation device 143 ø14 143
Center line of breaker 40 Conductor thickness 97 M12 bolt Conductor 97
Insulating barrier t=8 max. thickness
14 8 35 t=8 max. 6.5
8 32 15
Breaker
Breaker
16
ø14
ø14
110
110
Center line of electrical
87
ø7
ø7
48
operation device
15 15
322
290
290
70
322
120
277
275
275
112 112
ø14
ø14
ø7
ø7
44
23.5
48
87
70 M6 tap 140
or ø7
Trip button 140 35 8 35 Neutral pole 6.5
Neutral pole
210 70 141 70 141
3-pole 4-pole
231 210 191.5 210 191.5
Operating circuit
ø14 280 Operating circuit 292 280 292 Drilling plan
M12 bolt terminal block
231 terminal block 352 231 M3.5 screw 352
M3.5 screw
3-pole 4-pole (NF400-UEP 4-pole)
Breaker
110
Breaker
70
275
243
120
277
44
Neutral
pole
15 32 8
70 70
87
M6 tap
5
Test or ø7
Trip button 35 40 44 3-pole 4-pole
140 button
210 70 94.5
231 210 ø14 195 Drilling plan
280 M12 bolt 255
231
3-pole 4-pole
Breaker
70
275
243
120
277
44
Neutral
pole
15 32 8
70 70
87
M6 tap
46 or ø7
Trip button 35 40 2, 3-pole 4-pole
140
210 70 94.5
231 210 ø14 195 Drilling plan
280 M12 bolt 255
231
2, 3-pole 4-pole
Remark: 2 pole models are 3-pole models with the central pole removed.
Breaker
Breaker
110
ø14
8 32
87
operation device
15
322
70
290
290
120
277
275
112
ø14
44
ø7
23.5
87
70 M6 tap 140
Trip button 35 8 or ø7
140 143 3-pole 4-pole
70 Neutral pole
210 191.5
231 210 Operating circuit 292 Drilling plan
280 terminal block 352
ø14
231 M3.5 screw
M12 bolt
3-pole 4-pole
Front connection
● NV800-SEP, NV800-HEP Motor drive type (2)
46
Center line of electrical operation Insulating barrier Conductor thickness
device and breaker 14 Breaker 8
t=12 max.
Breaker
110
87
70
243
120
277
275
Operating circuit
44 terminal block
M3.5 screw
8
70 M6 tap
87
32
46 or ø7
3-pole
Trip button 94.5
15
40
Test button 195 Drilling plan
140
210 255
231 ø14
3-pole M12 bolt
terminal block
M3.5 screw
61
406
120
375
44
13
Neutral pole
8
70 70
80
15 32
59 M8 screw
43 or ø10
Center line of electrical 140
ø13 140 3-pole 4-pole
operation device and 231
M12 bolt 210(3-pole) 3-pole model 290 Drilling plan
15
106
80
80
32
8
61
566
566
406
406
120
120
375
44 44 22.5
Neutral pole
80
80
ø9.5
ø17.5
70 M8 screw 70
or ø10
80
80
15 51
140 70 3-pole 4-pole
Center line of electrical operation 140 Center line 144
210 Center line of electrical
device and breaker 210 of breaker 235
240 operation device Drilling plan
310 294
3-pole 4-pole
(185.5)
(185.5)
M10×65 Breaker
38
Operating circuit
terminal block
61
375
120
406
M3.5 screw
35
44 Center line of electrical 210
operation device 280
210
130
115
70 70 M8 screw
69.5 or ø10
101.5 140
203
304.5 231
263 3-pole 4-pole
364.5 290
Neutral pole Drilling plan
Rear connection
● NF1600-SS (3-pole) Motor drive type (2)
Operating circuit terminal block Mounting angle Stud can be rotated 90° Mounting angle Breaker
M3.5 screw Connection Conductor thickness
allowance t=6×width 75 max.
15
18.5
over 160
20
109
269
61
406
120
under
81.5
ø17.5
ø9.5
100
273
38 15
44
38
60
36
M8 tap
70 or ø10
ø11
140 231 125 38 15 212
M10×50 bolt
210 290 200 3-pole Drilling plan
over 160
20
109
269
61
406
120
273
ø17.5
ø9.5
under 100
81.5
44
54 18
38 5
38 18
231 60 15
70 20 ø11 106 106 M8 tap
290 125 M10×50 bolt 70 or ø10
Center line of electrical 210 318
operation device 280
4-pole Drilling plan
375
406
120
233
38 15
over 175
36
44
ø17.5
38
60
ø11
ø9.5
406
120
233
375
over 175
44
ø17.5
ø9.5
38
38 18
15
231 60
70 ø11 106 106
Center line of electrical 290 125 M10×50 bolt 70 M8 tap
210 318 or ø10
operation device
280
4-pole Drilling plan
13 dimensions.
31
Center of mechanical
50 interlock Please contact us for details.
15 Panel plate thickness Remarks: (1) Please contact us for outside
Stroke (t1~3.2) Center of circuit dimensions of other models of
33
breaker
different specifications.
A
1.5
Breaker
Mechanical
22(30)
44(55)
Mechanical interlock
22
44
interlock
E
Breaker
70 70(100)
Breaker
(t1~3.2mm)
B
and breaker
Gap between panel External dimensions
94.5
and breaker
Mounts to 4-5.5mm-dia hole, Differs with main
External dimensions 7.5mm-dia countersunk (rear)*2 breaker unit drilling plan.
Mounts to 4-5.5mm-dia hole, External dimensions
7.5mm-dia countersunk (rear)*2 Differs with main Breaker
breaker unit drilling plan.
15.5(20)
Mechanical
15.5
Mechanical
31(40)
31
interlock interlock
50
C
Breaker
G
Breaker
50(80)
D
P P
F F
P M6 screws
Mechanical interlock
( ) dimension are shown for NF1600-SS·NF1600-SSD or 7mm-dia
Drilling plan Drilling plan Drilling plan(breaker mount)
Fig.1 Fig.2 Fig.3
S1. Above 400AF, use panel thickness t=1.6~3.2mm.
S2. When the panel thickness is greater than t=2.3mm, use 4-5.5mm-dia 9.5mm dia countersunk (rear).
Appearance
NF30-CS, MB30-CS 2P
LC-03CS HL-05FH — —
NF30-CS, NV30-CS, MB30-CS 3P
NF32-SW, NF63-CW/SW/HW 2P (Note 1) HLS-05SW2P
NF63-SW/HW 4P
NF125-CW/SW 2P
(Note 1) HLS-1SW2P
NF125-HW 2P
— CH-P No.5
HLF-1SW
NF125-CW/SW/HW, NV125-CW/SW/HW LC-1SW
3P HLN-1SW
MB100-SW, NV125-RW HLS-1SW
NF125-SW/HW, NV125-SW/HW 4P
(Note 1)
NF160-SW/HW, NF250-CW/SW/HW, NV250-CW/SW/HW 2P
HLF-2SW
NV250-SEW/HEW, MB225-SW 3P LC-2SW HLS-2SW
HLN-2SW
NV250-RW 4P
NF125-SGW/HGW, NF160-SGW/HGW, NF250-SGW/HGW HLF-2GSW (Note 1)
3P, 4P LC-2GSW HLS-2GSW HLF3-2GSW
NF125-RGW/UGW, NF250-RGW/UGW HLN-2GSW
Notes: (1) HLF types are used for OFF-lock, and HLN types for ON-lock.
(2) HL-S types are used for OFF-lock.
Remark: (1) Users are requested to prepare padlocks for HL and HL-S types. (25mm padlock for HL, and 35mm padlock for HL-S.)
Table 5-36
Product Handle (HT) Handle lock (HL) Handle lock (HL- S) Card holder
5
Breaker type
C
35
35
35
CL CL L
NF32-SW, NF63-CW/SW/HW
2P DIN-05SW Fig.2
NV32-SW, NV63-CW/SW/HW, MB30-SW 5
3P
MB50-CW/SW
4
2P DIN-1SW2 8 1 13
NF125-CW/SW Mounting hook
3P
Fig.3 for IEC 35mm rail
2P DIN-1SW3
NF125-HW, NV125-CW/SW/HW, MB100-SW Fig.1 Fig.2 Fig.3
3P