Ref. Calculations Output


2yo(H)
6.2.3 Anchor Design

Configuration of Tendons in Webs


2yo(V)
Each web consists of three cables vertically placed as
H
shown in the figure.
2yo(V)
The dimension , 2Yo , should be taken as twice the
smaller of the two configurations mentioned below: 2ypo(V)

a) The distance from the line of action of the 2ypo(H)


force to the nearest concrete.
B
b) Half the distance between the line of action of
the force and the line of action ot its nearest
neighbour anchorage.

Number of strands in each cable = 37.0


Number of Tendons = 3.0
Strands diameter = 15.2 mm
Breaking load per strand = 260 kN
Web width (B) = 750 mm
Deck depth (H) = 1800 mm
Bearing plate width = 420 mm
Bearing plate height = 420 mm
Centre to centre distance b/w anchors = 550 mm
% of breaking load applied as jacking force 75.0 %
Characteristic strength of link reinforcement (fyv) = 500 N/sq.mm

Post tensioning force per tendon (Pk) = 7226 kN

BS5400 - Table 30 - Design Bursting Tensile Forces in End Blocks

ypo/yo 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7
Fbst/Pk 0.23 0.215 0.2 0.185 0.17 0.155 0.14 0.125 0.11

Fbst = design bursting force


Pk = highest load applied to the anchorage during construction

a) Bursting Force Primary Reinforcement Required

Vertical Direction

yo(V) = Half the side of end block in vertical direction = 275 mm


ypo(V) = Half the side of loaded area = 210 mm
vpo(V) / yo(V) = 0.76
Fbst/Pk (From Table 30) = 0.110

Fbst = 795 kN
Area of steel for bursting force [Fbst/(0.87*fyv)] = 1827 sq.mm
Project Job Ref.

Part of Structure Status

Calculated by Date Checked by Date Sheet no Rev. no

Ref. Calculations Output

Horizontal Direction

yo(H) = Half the side of end block in hor. direction = 375 mm


ypo(H) = Half the side of loaded area = 210 mm
vpo(H) / yo(H) = 0.56
Fbst/Pk (From Table 30) = 0.155

Fbst = 1120.0 kN
Area of steel for bursting force [Fbst/(0.87*fyv)] = 2575 sq.mm

Bursting Force Primary Reinforcement Provided

Vertical Direction

Diameter = 20 mm
Number of links = 14
Link legs = 2
Ast(V) (within first 500mm) = 8796 sq.mm => OK

Horizontal Direction

Diameter = 20 mm
Number of links = 14
Link legs = 2
Ast(H) (within first 750mm) assigned for each tendon = 8796 sq.mm => OK

This force, Fbst, shall be distributed in a region extending from 0.2(yo) to 2(yo) from the loaded face of
the end block.

b) Equilibrium Reinforcement for overall end block for multiple tendon anchorages
Project Job Ref.

Part of Structure Status

Calculated by Date Checked by Date Sheet no Rev. no

Ref. Calculations Output

Reinforcement Required
= 4984 mm2

Provided Reinforcement
4 legs-T20@100 c/c
2
= 12560 mm (OK)

CIRIA c) Reinforcement to resist spalling


GUIDE-1
Reinforcement to resist the spalling is required near end face to carry a force
of 0.04 Pk in each of the two directions at right angles to the applied force Pk.

% of jacking load applied as spalling force 4 %

Spalling force (Fsp) = 289 kN

Area of steel for spalling force [Fsp/(0.87*fyv)] = 664 sq.mm

Vertical Direction Horizontal Direction

Diameter = 25 mm Diameter = 20 mm
Number of links = 4 Number of links = 8
Link legs = 1 Link legs = 1
Ast(V)SPALLING = 1963 sq.mm Ast(H)SPALLING = 2513 sq.mm
OK OK
where:
Ast(V)SPALLING Is the total vertical U bars.
Ast(H)SPALLING Is the total horizontal U bars.