5kA type C - MY
C.3
miniature circuit breakers 6kA type B & C - MT MU
Reference calibration
Temperature : 30°C
MT363A
C.4
miniature circuit breakers 10kA type B & C - NB NC
C.5
miniature circuit breakers for
commercial and industrial electrical installation systems
The new architecture of terminal NDN range Voltage rating: 230/400V AC Option:
guarantees an excellent grip of Auxiliaries:
the cables and a good tightening 䡺 Busbar connection: Insulation voltage (Ui): 630V - allows remote indication of
comfort. - on the top with prong busbar main contact position
- on the bottom, the MCBs are Impulse voltage (Uimp): 6kV - allows remote tripping of the
The pull up terminal is a fool- equipped with bi-connect associated device
proof terminal which allows: terminals which allow Durability: 20,000 cycles (O-C)
- to avoid a bad insertion of connection with a fork busbar 䡺 Locking kit to lock the toggle
cables in the product and a supply cable in the Calibration temperature: 30ºC in the ON or OFF position
- to guide the cable in the terminal. The busbar clip-on
terminal mechanically onto the casing Connection capacity: 䡺 Terminal & screw shield and
of the MCB. - 25mm2 flexible conductor interpole barrier
The tripping mechanism is totally - 35mm2 rigid conductor
new. with a fast system of clos- 䡺 Top and bottom removability: Foolproof terminal design 䡺 RCD add-on block
ing, the withstand of contacts on thanks to new Din clips, an
all type of loads is increased. MCB can be added or Tightening torque: 䡺 Busbar and connection
removed easily in a row of 4 Nm nominal accessories
On the MCB, the state of isola- products connected together
tion (according to IEC 60 947-2) with a busbar in case of Screw head: PZ2 and slot 6mm
is clearly indicated by the “OFF” maintenance or extension
mechanical position on the tog- IP rating: IP2x terminals
gle with green colour. 䡺 Identification of the electrical
circuits can be easily done on Standard 35mm DIN rail
the front of all MCBs thanks
to a specific window on each
product.
Breaking capacity according to IEC60898 & IEC60947-2 Breaking capacity according to IEC60947-2 for low ratings
NDN NDN
Number of poles Voltage(V) Breaking Breaking In Breaking
capacity capacity capacity
Icn Icu Icu
IEC 60 898 IEC 60 947-2 IEC 60 947-2
1P 230 to 240 10,000 15kA 0.5 - 2A 80kA
400 to 415 - - 3A - 4A 50kA
2P, 3P, 4P 230 to 240 - 30kA 6A 30kA
400 to 415 10,000 15kA
C.6