DEP 32.37.20.10-Gen.
September 2011
PREFACE
DEP (Design and Engineering Practice) publications reflect the views, at the time of publication, of Shell Global
Solutions International B.V. (Shell GSI) and, in some cases, of other Shell Companies.
These views are based on the experience acquired during involvement with the design, construction, operation and
maintenance of processing units and facilities. Where deemed appropriate DEPs are based on, or reference
international, regional, national and industry standards.
The objective is to set the recommended standard for good design and engineering practice to be applied by Shell
companies in oil and gas production, oil refining, gas handling, gasification, chemical processing, or any other such
facility, and thereby to help achieve maximum technical and economic benefit from standardization.
The information set forth in these publications is provided to Shell companies for their consideration and decision to
implement. This is of particular importance where DEPs may not cover every requirement or diversity of condition at
each locality. The system of DEPs is expected to be sufficiently flexible to allow individual Operating Units to adapt the
information set forth in DEPs to their own environment and requirements.
When Contractors or Manufacturers/Suppliers use DEPs, they shall be solely responsible for such use, including the
quality of their work and the attainment of the required design and engineering standards. In particular, for those
requirements not specifically covered, the Principal will typically expect them to follow those design and engineering
practices that will achieve at least the same level of integrity as reflected in the DEPs. If in doubt, the Contractor or
Manufacturer/Supplier shall, without detracting from his own responsibility, consult the Principal.
The right to obtain and to use DEPs is restricted, and is typically granted by Shell GSI (and in some cases by other Shell
Companies) under a Service Agreement or a License Agreement. This right is granted primarily to Shell companies and
other companies receiving technical advice and services from Shell GSI or another Shell Company. Consequently, three
categories of users of DEPs can be distinguished:
1) Operating Units having a Service Agreement with Shell GSI or another Shell Company. The use of DEPs by
these Operating Units is subject in all respects to the terms and conditions of the relevant Service Agreement.
2) Other parties who are authorised to use DEPs subject to appropriate contractual arrangements (whether as part
of a Service Agreement or otherwise).
3) Contractors/subcontractors and Manufacturers/Suppliers under a contract with users referred to under 1) or 2)
which requires that tenders for projects, materials supplied or - generally - work performed on behalf of the said
users comply with the relevant standards.
Subject to any particular terms and conditions as may be set forth in specific agreements with users, Shell GSI
disclaims any liability of whatsoever nature for any damage (including injury or death) suffered by any company or
person whomsoever as a result of or in connection with the use, application or implementation of any DEP, combination
of DEPs or any part thereof, even if it is wholly or partly caused by negligence on the part of Shell GSI or other Shell
Company. The benefit of this disclaimer shall inure in all respects to Shell GSI and/or any Shell Company, or companies
affiliated to these companies, that may issue DEPs or advise or require the use of DEPs.
Without prejudice to any specific terms in respect of confidentiality under relevant contractual arrangements, DEPs shall
not, without the prior written consent of Shell GSI, be disclosed by users to any company or person whomsoever and
the DEPs shall be used exclusively for the purpose for which they have been provided to the user. They shall be
returned after use, including any copies which shall only be made by users with the express prior written consent of
Shell GSI. The copyright of DEPs vests in Shell Group of companies. Users shall arrange for DEPs to be held in safe
custody and Shell GSI may at any time require information satisfactory to them in order to ascertain how users
implement this requirement.
All administrative queries should be directed to the DEP Administrator in Shell GSI.
DEP 32.37.20.10-Gen.
September 2011
Page 3
TABLE OF CONTENTS
1. INTRODUCTION ........................................................................................................5
1.1 SCOPE........................................................................................................................5
1.2 DISTRIBUTION, INTENDED USE AND REGULATORY CONSIDERATIONS .........5
1.3 DEFINITIONS .............................................................................................................5
1.4 CROSS-REFERENCES .............................................................................................7
1.5 SUMMARY OF MAIN CHANGES...............................................................................7
1.6 COMMENTS ON THIS DEP .......................................................................................7
1.7 DUAL UNITS...............................................................................................................7
2. ELECTRIC CABLING.................................................................................................8
2.1 GENERAL ...................................................................................................................8
2.2 SIGNAL SEGREGATION IN MULTICORE CABLES .................................................8
2.3 SELECTION AND SPECIFICATION OF INSTRUMENT CABLES ............................9
2.4 CABLES FOR DIGITAL AND VIDEO SIGNALS.......................................................11
2.5 CABLES FOR SPECIAL APPLICATIONS................................................................12
2.6 PROTECTION OF CABLES AGAINST FIRE DAMAGE ..........................................12
2.7 FIBRE OPTIC CABLES (signal level class 6 )..........................................................12
2.8 SYSTEM CABLING ..................................................................................................12
3. CABLE SEGREGATION, ROUTING AND INSTALLATION...................................13
3.1 CABLE SEGREGATION...........................................................................................13
3.2 ROUTING..................................................................................................................13
3.3 JUNCTION BOXES FOR MULTICORE CABLES ....................................................14
3.4 CABLE GLANDS ......................................................................................................14
3.5 TRUNKING AND TRAYS..........................................................................................15
3.6 TRENCHES ..............................................................................................................15
3.7 CABLE PULLING AND INSTALLATION ASPECTS ................................................16
3.8 CONTROL ROOM/AUXILIARY AREAS ...................................................................17
4. EARTHING (GROUNDING) AND BONDING ..........................................................18
4.1 GENERAL .................................................................................................................18
4.2 CONNECTIONS TO THE EARTHING (GROUNDING) SYSTEMS .........................18
4.3 EARTHING (GROUNDING) OF INTRINSICALLY SAFE CIRCUITRY ....................19
4.4 EARTHING (GROUNDING) OF CAVITY FLOORS..................................................19
5. LIGHTNING PROTECTION OF INSTRUMENTATION ...........................................20
5.1 GENERAL .................................................................................................................20
5.2 INSTRUMENTATION AND CABLING IN THE FIELD..............................................20
6. PNEUMATIC TUBING..............................................................................................21
6.1 GENERAL .................................................................................................................21
6.2 SELECTION AND SPECIFICATION OF TUBING....................................................21
6.3 JUNCTION BOXES FOR MULTICORE TUBING.....................................................21
6.4 INSTALLATION ........................................................................................................22
7. IDENTIFICATION AND MARKING ..........................................................................23
7.1 IDENTIFICATION OF SYSTEM CABLES ................................................................23
7.2 IDENTIFICATION OF SINGLE CABLES/TUBING ...................................................23
7.3 IDENTIFICATION OF MULTICORES AND JUNCTION BOXES .............................23
7.4 MARKING .................................................................................................................23
8. REFERENCES .........................................................................................................25
DEP 32.37.20.10-Gen.
September 2011
Page 4
APPENDICES
APPENDIX 1 DISTANCE BETWEEN CABLE TRENCHES ..................................................27
APPENDIX 2 ARRANGEMENT OF CABLE TRENCHES .....................................................28
APPENDIX 3 TYPICAL EARTHING (GROUNDING) AT FAR/CCR .....................................30
APPENDIX 4 TYPICAL EARTHING (GROUNDING) OF INSTRUMENT SIGNAL
CABLES IN THE FIELD...................................................................................31
APPENDIX 5 TYPICAL EARTHING (GROUNDING) OF INSTRUMENT SIGNAL
CABLES IN THE MDF .....................................................................................32
DEP 32.37.20.10-Gen.
September 2011
Page 5
1. INTRODUCTION
1.1 SCOPE
This DEP specifies requirements and gives recommendations for the design and
engineering of instrument signal lines and cabling. It covers design, material selection and
installation methods. Cabling for transmitting digital and video signals is also covered in this
DEP.
In the context of this DEP, instrument signal lines include:
a) Electric signal lines (paths), including thermo-electric voltage lines from
thermocouples; lines from transmitters to their receiving instruments, auxiliaries,
logic systems, controllers etc. and the lines from these to the relevant actuating
elements such as solenoid valves, converters, transducers or control valves.
b) Pneumatic signal lines (paths) from pneumatic transmitters to their receiving
instruments, auxiliaries, controllers and the lines from these to the relevant final
control elements.
Signal lines for similar applications such as fire and gas detection and protection systems,
plant communication systems, CCTV systems, plant information systems, maintenance
management systems and plant security systems are also within the scope of this DEP.
This is a revision of the DEP of the same number dated May 2004; see (1.5) regarding the
changes.
1.3 DEFINITIONS
1.3.1 General definitions
The Contractor is the party that carries out all or part of the design, engineering,
procurement, construction, commissioning or management of a project or operation of a
facility. The Principal may undertake all or part of the duties of the Contractor.
The Manufacturer/Supplier is the party that manufactures or supplies equipment and
services to perform the duties specified by the Contractor.
The Principal is the party that initiates the project and ultimately pays for it. The Principal
may also include an agent or consultant authorised to act for, and on behalf of, the
Principal.
The word shall indicates a requirement.
DEP 32.37.20.10-Gen.
September 2011
Page 6
1.3.3 Abbreviations
AL/HDPE/PA Aluminium / high density polyethylene / polyamide (nylon), that
combines overall metal screening with inner sheathing. The
aluminium acts as metal screen and moisture barrier. HDPE and PA
act as chemical barriers, while PA provides also protection against
termite attacks. AL/HDPE/PA is a low cost and lightweight alternative
for lead sheathing.
AWG American Wire Gauge
CCR Central Control Room
CCTV Closed Circuit Television
DCS Distributed Control System
EM Electro magnetic
EMC Electro magnetic compatibility
EMI Electro magnetic interference
FAR Field Auxiliary Room
HDPE High density polyethylene, used as outer sheathing.
HDPE as outer sheathing has a good chemical resistance and water
tightness, but is flammable (acts as torch) and stiff. Furthermore,
HDPE is only UV-resistant, if it is of black colour and contains carbon
black.
IPF Instrumented protective function
IPS Instrumented protective system
MDF Main distribution frame
MESC Material and Equipment Standards and Code
MS Metal screen (with drain wire)
DEP 32.37.20.10-Gen.
September 2011
Page 7
1.4 CROSS-REFERENCES
Where cross-references to other parts of this DEP are made, the referenced section
number is shown in brackets. Other documents referenced by this DEP are listed in (8).
2. ELECTRIC CABLING
2.1 GENERAL
Single cables are used for signal transmission from field instruments to field mounted
junction boxes. Multicore cabling will subsequently transmit the signals from the junction
box to a main distribution frame (MDF) in the central control room (CCR) or field auxillary
room (FAR).
Multicore cabling shall be routed underground, wherever possible and consistent with the
design of other plant facilities. However, above-ground cabling is acceptable, subject to the
Principal's approval, provided a definite cost advantage can be demonstrated, or where it is
the standard local practice.
Outdoor, above-ground and underground cables shall be provided with steel wire braiding
(SWB) or steel wire armouring (SWA) even if they are installed in trenches/trunking or on
cable trays. For North America, armoured cable is not required when laid in cable tray.
Where chemical or moisture attack is possible and HDPE sheathing is not provided,
underground cabling shall be additionally provided with a chemical/moisture barrier.
All products shall be technically qualified to the satisfaction of the Principal and shall be
sourced from Manufacturers acceptable to the Principal.
Note that references to the MESC system are not applicable in North America.
In addition to the above segregation rules for multicore cabling, functional segregation may
be desirable for operability and maintainability reasons.
The design shall cater for spare capacity in multicore cabling. When the design is finalised,
10 % to 15 % of the installed cabling capacity shall be available in each signal level class
and plant area to accommodate unforeseen future plant modifications.
For resistance thermometer elements, the conductor resistance shall be compatible with
the requirements as specified by the Manufacturer of the resistance thermometer elements
and/or the instrument.
Signal wires shall be twisted in pairs. The use of quad cables requires approval by the
Principal.
For North American applications, conductors shall meet the requirements of
DEP 33.64.20.10-Gen.
2.3.2 Cable Construction
2.3.2.1 Cable construction for signal level classes 1/2/3
Instrument signal cabling for signal level classes 1, 2 and 3 of Table 1 (2.2) shall be
specified with a metal screen (shield) and drain wire. Multicore cabling shall be provided
with a collective screen (overall shield); individual pair screening (shielding) shall only be
applied if specifically needed for the application.
Underground cabling shall be provided with an AL/HDPE/PA inner sheathing as a
moisture/chemical barrier. An alternative, subject to Principal’s approval, is using lead
sheathing.
Cable capacitance and inductance shall be verified to function properly when used on
intrinsically safe or non incendive (switched) circuits.
If the ambient temperature is above 90°C (190°F), (e.g., in rotating equipment or in close
proximity to furnaces) thermocouple lead wire shall have Teflon or Kapton insulation.
Length and gauge of thermocouple lead wire shall be sized so that resistance of wire does
not exceed 800 ohms. Splicing of thermocouple extension wires is not acceptable. For
vibrating or flexing service, extension wire from the thermocouple to the first junction box
shall have stranded conductors. For all other services, wire shall use single solid
conductors.
DEP 32.37.20.10-Gen.
September 2011
Page 11
• Pneumatic tubing and cables of signal level classes 5 and 6 may be combined with
any types of electric cable.
3.2 ROUTING
Single cables connecting field instruments to junction boxes shall be supported and
protected against mechanical damage by cable trunking, cable trays, steel angles, beams
etc. as appropriate. With exception of North American application, conduits shall not be
used. Cables shall not be supported from process equipment or piping.
When the above-ground routing for cables is selected, the following aspects shall be
considered:
a) Constructability and cost: make optimum use of structures for process equipment,
pipe racks etc. The need for special passages/ducts and crossings will also affect
the route selection.
b) Required cable length and associated cost.
c) EMC aspects: apply cable segregation (3.1) and do not route cabling through areas
classified as severe EM environments; route cabling through areas that are
protected against direct lightning strikes. Cable routing along and in the direct
vicinity of earthed steel structures and piping shall be considered. Avoid obstructing
other users: layout shall not obstruct traffic or interfere with the accessibility of
process equipment (pumps, compressors, motors, heat exchanger bundles, etc.).
d) Accessibility: layout shall guarantee sufficient access for cable pulling and
maintenance.
e) Prevent cable damage: the layout shall be selected so that the cables are not
prone to damage. This involves at least the following:
• Cabling shall be routed through low fire risk areas.
• Cabling shall not be routed in the vicinity of sample points, drains, vents,
hot pipes and hot surfaces.
• Where riser points are liable to damage by traffic, they shall be protected
by free standing, sturdy mechanical structures.
DEP 32.37.20.10-Gen.
September 2011
Page 14
The route selection for underground cable trenches shall take the following rules into
consideration:
• Maintain an appropriate distance from power and lighting cables. For separation
distances, see Appendix 1. When power cables intersect instrument signal cables,
the crossing shall be at right angles, with a minimum separation distance of 0.3 m.
• Trenches shall be kept away from buried hot surfaces (e.g. pipes) so that the
properties of the cable shall not be adversely affected. The minimum separation
distance shall be 0.2 m plus 0.1 m for every 100 °C temperature of the
non-insulated surface.
The conceptual design for the cable routing shall be submitted to the Principal for approval.
In corrosive environments that lead to the corrosion of brass, stainless steel cable glands
shall be used.
Cable glands on plant instruments shall be located at the bottom as first choice, but never
at the top, to prevent ingress of water. Alternatively, if cable glands are installed in the side
wall of the instruments, the cables shall enter from below. Cables coming from above shall
first drop to below the elevation of the gland. The entry thread of the cable glands shall be
ISO metric. For North American application NPT shall be used. Cables shall be clamped
just below the cable glands to prevent excessive force on the cable gland.
DEP 32.37.20.10-Gen.
September 2011
Page 15
A special case applies if cable glands are used for electric signal cables entering potentially
hydrocarbon filled spaces (e.g. flying leads of vibration probes on rotating equipment). In
addition to the above requirements, these glands shall be of a blocking type to prevent oil
leakage from the inner casing to the outside environment.
3.6 TRENCHES
With the exception of North America where DEP 36.64.20.10-Gen. should be followed,
underground instrument signal cables shall be laid in dedicated trenches and their routing
shall be indicated by above-ground markers. Cross-sectional drawings of trenches shall
show the location and laying pattern of each group of cables.
The trenches shall have such a depth that the signal cables are not damaged by traffic
passing over them. The bottom of the trench shall be kept above the ground water level.
For general construction details for trenches in paved and unpaved areas, refer to
Appendix 2 and Standard Drawings S 19.001, S 19.002 and S 68.009. The distance
between cables, as indicated on Standard Drawing S 68.009, does not apply to instrument
cables of signal level classes 1 through 4: they may be laid without spacing.
DEP 32.37.20.10-Gen.
September 2011
Page 16
The bottom of the trench shall not have a slope of more than 10 degrees and the transition
of horizontal surfaces shall have a smooth curvature. Where trenches for signal cables
pass under roads or below other cable trenches or pipes, protective DN 100 or DN 150
pipes or concrete ducting shall be provided to facilitate future cable laying. Such
pipes/ducting shall be capped or plugged at the ends.
Particularly for cables entering buildings, a detailed proposal shall be made by the
Contractor with respect to supporting the cables
NOTES: 1. Backfilling of the trenches shall be carried out with sand, free of stones to grade 2-5 mm, and shall
contain no contaminants which may cause deterioration of the cable.
2. The top cable layer shall be covered with protective material, such as tiles, to provide mechanical
protection. Alternatively plastic cover plates may be applied, provided the same degree of
protection is obtained.
3. The procedure for jointing cables underground shall be submitted for approval to the Principal,
detailing as a minimum the materials to be used, work method, supervision, inspection, testing and
labelling.
Where large quantities of signal cables cross or branch off, the trench depth shall be
increased locally.
The curvature of the corners in trenches shall be selected so that the permissible bending
radius of the cables is not exceeded.
(secondary) to prevent the process fluids from entering the conduit or cable system, if the
primary seal fails.
Secondary seals shall meet the temperature and pressure conditions to which they will be
subjected upon failure of the primary seal.
Drains, vents, or other devices shall be provided so that primary seal leakage is obvious.
When the design is finalised, the cable entry in buildings shall have at least 20 % spare
space to accommodate additional cables for unforeseen future plant modifications.
When a cellar type of auxiliary room is used with the control room above it, the
interconnecting cabling shall be routed through riser cabinets, connecting the cavity floors
of these rooms.
All signal, power and earthing (grounding) cables shall be routed and connected via the
cavity floor and shall enter cabinets from the bottom. Cabinets/racks requiring rear access
shall not be placed against the walls of auxiliary rooms.
The bottom of the cabinets shall be sealed to prevent dust entry from the cavity floor into
the cabinets.
Signal marshalling shall take place in MDF cabinets only; system cabling shall interconnect
MDFs and instrument cabinets.
Remote input/output cards of systems such as DCS can also be located in MDFs.
Thermocouple compensation cable shall be used up to the device where the cold junction
compensation resides (usually the input card).
Instrument cabinets shall be designed to terminate the full capacity (including spare
capacity) of the cabinet on system cables, organised in a logical fashion (input/output card
channels modularly into system cables). Thus any input or output from any instrument
cabinet shall be marshalled at the MDFs only. The final design of instrument cabinets shall
provide a minimum of 20 % spare capacity.
Cable glands are not required for cable terminations in control/auxiliary room cabinets.
Cables shall be suitably anchored with clamps and fixtures to take their weight and for EMC
purposes, before they are connected to terminals or sockets.
DEP 32.37.20.10-Gen.
September 2011
Page 18
4.1 GENERAL
Earthing (grounding) systems are the responsibility of the Electrical Engineering discipline
and provisions for earthing (grounding) are covered by DEP 33.64.10.10-Gen. For North
American application, refer to DEP 33.64.20.10-Gen.. This Section identifies aspects
affecting personnel safety and proper functioning of instruments and instrument systems.
The number of earthing (grounding) types shall be limited to two, i.e. Safety earth (ground)
and Instrument Earth (ground), unless Manufacturers require a dedicated earth (ground).
Grounds for control and safety systems and field digitial communication systems
associated with instrumentation shall follow industry standards and Manufacturer
recommendations.
For a typical configuration of a safety earth and instrument earth system at the FAR/CCR,
refer to Appendix 3. Instrument earth cables shall connect the instrument earth bar to MDFs
and instrument cabinets, using one cable for each MDF/cabinet. The cross-sectional area
of these cables shall be at least 6 mm2 and the terminal insulation colour shall be
yellow/black. For North American application, the minimum wire size of the earth cable shall
be 10 AWG and the colour shall be green with a yellow stripe. Each instrument earth cable
shall be properly identified at the side of the instrument earth bar, showing the MDF/cabinet
number it is connected to.
NOTE: Earthing (grounding) bolts shall have a diameter of at least 10 mm.
• For screened cables between the CCR and FAR, the screens shall be earthed at
the MDF in the CCR.
• For screened system cabling running inside the FAR or CCR, the screens shall be
earthed at the MDF.
• If screened cabling is run between two MDFs or between two instrument cabinets,
the 'star' method requires the screen to be earthed at one of the MDFs/cabinets
only.
4.2.2 Connections to safety earth
Steel wire armouring, steel wire braiding and metal sheathing of cables shall be connected
to safety earth, at least at both ends.
For typical safety earthing (grounding) installation details, refer to Appendices 3 through 5.
Instrument housings, junction boxes, local panels and local cabinets shall be bonded to
cable trunking/steel angles etc. In addition, earthing (grounding) or mounting bolts of
instrument housings shall be fitted with two shark rings to allow low resistance bonding to
plant structures/safety earth. Junction boxes, local panels and local cabinets shall be
provided with earthing (grounding) bolts to enable a proper earthing (grounding) connection
to plant structures/safety earth.
Any outside earthing (grounding) connection shall comply with IEC 60079-0.
5.1 GENERAL
The lightning protection for instruments described in this Section assumes that plants are
equipped with lightning protection as specified in DEP 33.64.10.10-Gen. For North
American applications, DEP 33.64.20.10-Gen. shall apply.
Protective measures shall not adversely affect the protection of the instrument or
instrument system against ignition of a surrounding explosive atmosphere.
Protective measures against lightning are subject to the approval of the Principal.
Long communication lines shall use fibre optic cabling, unless signal type requires coaxial
or twisted pair cabling. Where coaxial or twisted pair cabling is applied, galvanic isolation
shall be used.
DEP 32.37.20.10-Gen.
September 2011
Page 21
6. PNEUMATIC TUBING
6.1 GENERAL
Single tubing shall be used for signal transmission from field instruments to field mounted
junction boxes. They shall be routed above ground through low fire risk regions and shall
be provided with protection against mechanical damage. Multicore tubing will subsequently
transmit the signals from the junction box to an MDF in the CCR or FAR.
Multicore tubing shall be routed underground, wherever possible and consistent with the
design of other plant facilities. However, the use of above-ground tubing is acceptable,
subject to the Principal's approval, provided a definite cost advantage can be
demonstrated, or where it is standard local practice.
The design shall cater for spare capacity in multicore tubing. When the design is finalised,
10-15% of the installed tubing capacity shall be available to accommodate unforeseen
future plant modifications.
Tubing in fire protection and depressuring duties shall be provided with protection against
fire damage.
The design intent of (2.6) and (3) for electric signal lines applies equally to pneumatic signal
lines, except for electrical aspects.
6.4 INSTALLATION
All fittings shall be brass or plastic, of the compression type and be suitable for the size and
material of the tubing. Refer to MESC series 76.40.xx.xxx.1.
Where air lines leave trunking, bulkhead unions shall be applied. If feasible the bulkhead
unions shall be of the angle type. If tubing serves instruments without instrument air supply
(e.g. to a control valve not having a positioner or booster), the tubing shall be clamped to a
25 mm dummy pipe or angle iron firmly attached to a structure.
DEP 32.37.20.10-Gen.
September 2011
Page 23
7.4 MARKING
Signal conductors shall be individually marked on each termination side with the
corresponding terminal number.
Instrument tubing shall be marked with the instrument tag number at the point of connection
to the multitube.
DEP 32.37.20.10-Gen.
September 2011
Page 24
Junction boxes shall be identified with an engraved nameplate of synthetic material. For
details of nameplate requirements, refer to DEP 32.31.00.32-Gen. and Standard Drawing
S 37.601.
Cable and tubing markers shall show at least the cable/tubing number.
Underground cables and tubing shall be marked at intervals of approximately 5 m by
means of lead or stainless steel strips. For long cable stretches (e.g. alongside roads or in
tank farms), marking at 10 m to 15 m intervals shall be provided.
Above-ground cables and tubing shall be marked at their termination points (outside the
instrument and junction box) with a suitable label of engraved or embossed material.
DEP 32.37.20.10-Gen.
September 2011
Page 25
8. REFERENCES
In this DEP reference is made to the following publications:
NOTES: 1. Unless specifically designated by date, the latest issue of each publication shall be used (together
with any amendments/supplements/revisions thereof).
2. The DEPs and most referenced external standards are available for Shell users on the SWW
(Shell Wide Web) at address http://sww.shell.com/standards.
SHELL STANDARDS
Hydraulic systems for the operation of on/off valves DEP 31.36.10.30-Gen.
in protective functions
Instruments for measurement and control DEP 32.31.00.32-Gen.
Instrumentation of depressuring systems DEP 32.45.10.10-Gen.
Structured cabling systems for telecommunications DEP 32.71.00.30-Gen.
Instrumented protective functions (IPF) DEP 32.80.10.10-Gen.
Electrical engineering design DEP 33.64.10.10-Gen.
Electrical engineering design for North American DEP 33.64.20.10-Gen.
application
Assessment of the fire safety of onshore installations DEP 80.47.10.30-Gen.
Material and Equipment Standards and Code MESC
STANDARD DRAWINGS
Electrical and instrument cable trenches in concrete S 19.001
paved areas
Cable routing in unpaved, brick-paved or tiled areas S 19.002
and crossing roads
Instrument name plates S 37.601
Junction box construction S 37.603
Instrument cable trunking S 37.604
Typical arrangements of cable trenches in plant S 68.009
areas
AMERICAN STANDARDS
Recommended Practice for Wiring Methods for Hazardous ISA RP 12.06.01
(Classified) Locations Instrumentation Part 1: Intrinsic Safety
Requirements for Process Sealing Between Electrical Systems ISA 12.27.01
and Flammable or Combustible Process Fluids
Issued by:
The International Society of Automation
67 Alexander Drive
PO Box 12277
Research Triangle Park, NC 27709, USA
INTERNATIONAL STANDARDS
Explosive atmospheres
Part 0 : General requirements IEC 60079-0
Part 14: Electrical installations design, selection IEC 60079-14
and erection
Degrees of protection provided by enclosures (IP Code) IEC 60529
Thermocouples – Part 3: Extension and compensating IEC 60584-3
cables -Tolerances and identification system
DEP 32.37.20.10-Gen.
September 2011
Page 26