Sunteți pe pagina 1din 11

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO.

3, JULY 2011 1873

A Protection Strategy and Microprocessor-Based


Relay for Low-Voltage Microgrids
M. Amin Zamani, Student Member, IEEE, Tarlochan S. Sidhu, Fellow, IEEE, and
Amirnaser Yazdani, Senior Member, IEEE

Abstract—One of the major challenges associated with micro- of the traditional philosophy of protection which assumes a
grid protection is to devise an appropriate protection strategy that radial network structure with a unidirectional flow of power
is effective in the grid-connected as well as islanded mode of op- [3], [4].
eration. This paper proposes a protection strategy based on mi-
croprocessor-based relays for low-voltage microgrids. Further, the
The protection scheme of a microgrid must ensure safe op-
structure of a new relay enabling the proposed protection strategy eration of the microgrid in both modes of operation, that is, the
is presented. One of the salient feature of the developed protec- grid-connected mode and the islanded mode. In the grid-con-
tion scheme is that it does not require communications or adaptive nected mode, fault currents are large due to the contribution of
protective devices. Moreover, it is to a large extent independent of the host grid. This allows the employment of the conventional
the fault current magnitude and the mode of operation. Transient overcurrent relays, despite the fact that the protection coordina-
time-domain simulation studies are conducted to demonstrate the
effectiveness of the proposed protection strategy and its enabling tion may be compromised or even entirely lost in some cases,
relay, using the PSCAD/EMTDC software package. due to the existence of DRs [4]–[9]. In the islanded mode, how-
ever, fault currents may be significantly smaller than those ex-
Index Terms—Distributed generation, electronically coupled
distributed generators, microgrid, microprocessor-based relays, perienced in the grid-connected mode, due to the limited cur-
power system protection. rent contribution of EC-DRs. Moreover, depending on the ratio
of the power generated by rotating-machine-based DRs to the
power generated by EC-DRs, the fault current magnitude can
I. INTRODUCTION vary over a fairly wide range. Consequently, the conventional
overcurrent protection is ineffective for the islanded mode of

O NE of the most drastic changes that the electric


power system is undergoing is the integration of
small-/medium-scale distributed resources (DRs) into electric
operation [10]–[19].
In [5], an adaptive strategy has been proposed for protecting
distribution systems with high penetration of DRs. The strategy
distribution networks. Most modern DRs employ non-con-
proposed in [5] is based on communications amongst the equip-
ventional energy resources and are interfaced with the host
ment, does not accommodate the islanded mode of operation,
utility grid through power-electronic converters. The increasing
and is applicable only if the penetration of DRs is high. Ref-
proliferation of electronically coupled DRs (EC-DRs), such as
erences [6]–[8] present communication-based protection strate-
photovoltaic systems, micro gas turbines, wind power systems,
gies for grid-connected microgrids, based on the assumption of
and fuel cells, is expected to inevitably challenge the traditional
large fault currents (due to the host grid) and coordinated em-
operating principles of the power system. An emerging and
ployment of overcurrent relays to isolate the faults within the
promising philosophy of operation to mitigate the technical
microgrid; if a fault impacts the utility grid, the microgrid is
issues associated with widespread proliferation of DRs, and
disconnected from the upstream network and operated in the is-
to offer additional values, is to designate relatively small
landed mode, whereas if a fault takes place within the islanded
areas of a distribution network that embed DRs and loads,
microgrid, all embedded DRs are dropped after a prespecified
and to operate them in a deliberate and controlled way. Such
delay. Although an option, especially for those microgrids that
subnetworks, referred to as microgrids [1], should be able
do not embed sensitive loads, the protection strategies proposed
to operate independently, as well as in conjunction with the
in [6]–[8] do not offer a method for fault detection in the is-
rest of the distribution network; they are expected to enhance
landed mode of operation, nor do they allow operation of the
the continuity of service and to offer superior power quality,
microgrid in the islanded mode if a fault occurs within the is-
higher reliability, and operational optimality [2]. Adoption
landed microgrid. Reference [9] proposes a simple and effective
of the microgrid concept results in a cellular structure within
strategy for coordination of protective devices in a typical radial
low-voltage (LV) distribution networks, and warrants a revision
distribution network that embeds DRs. The strategy proposed in
[9] does not require communications or adaptive protective de-
Manuscript received September 29, 2010; revised January 03, 2011; accepted vices. However, it does not consider the network as a microgrid.
February 18, 2011. Date of publication April 11, 2011; date of current version
June 24, 2011. Paper no. TPWRD-00749-2010
Reference [10] proposes the post-fault switching of the
The authors are with the Department of Electrical and Computer Engineering, operational mode of a microgrid, to the islanded mode, and
the University of Western Ontario, London, ON N6A 5B9 Canada (e-mail: mza- protecting the islanded microgrid based on current sequence
mani2@uwo.ca; sidhu@eng.uwo.ca; ayazdani@eng.uwo.ca).
Color versions of one or more of the figures in this paper are available online
components. However, the proposed method does not enable
at http://ieeexplore.ieee.org. single-phase tripping and also fails to ensure full protection
Digital Object Identifier 10.1109/TPWRD.2011.2120628 against three-phase faults. The employment of differential
0885-8977/$26.00 © 2011 IEEE
1874 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011

relays for protecting microgrids has been suggested in some maximum of several megavolt amperes. It is further assumed
papers [11]–[13]. Expanding on the ideas proposed in [11] that microgrid loads are supplied by a number of radial sec-
and [12], reference [13] proposes a protection scheme using ondary mains (SMs), which may be branched by one or more
communication-assisted digital relays, for protection of mi- laterals, and that the presence of single-phase loads and/or DRs
crogrids with customer-owned DRs. However, the proposed makes the LV microgrid an inherently unbalanced network.
strategy, which relies on differential currents, is expected to
be costly, and assumes technical features that are absent in B. Conventional Protection
the state-of-the-art equipment. Another approach proposed for In general, simple overcurrent devices, most commonly in the
protection of microgrids is the use of voltage measurements form of fuses, are employed in secondary distribution networks
[14]–[16]; in particular, [16] presents a voltage-based protec- to protect equipment and ensure safety. Secondary network con-
tion method in a rotating frame, which seems suitable for ductors are typically protected by the so-called limiters. A lim-
islanded microgrids. However, the proposed method does not iter is a high-capacity fuse that is installed on each phase con-
consider the grid-connected mode of operation, single-phase ductor of the SMs at each junction point. The step-down trans-
tripping, and high-impedance faults; further, it assumes com- former is protected by a network protector, which is an LV air
munications. circuit breaker with a tripping/closing mechanism controlled by
In [17], a fault detection method has been proposed for mi- a self-contained relay. In addition, the network protector has
crogrids with a high penetration of EC-DRs. The method, how- fuses that provide backup protection for the step-down trans-
ever, does not consider the grid-connected mode of operation. former [22]. Since the fault should be rapidly isolated by the
Moreover, no study results have been presented to validate the limiters, before the network protector operates, the time-current
proposed strategy. References [18] and [19] propose the inte- characteristics of the limiters must be coordinated with those
gration of energy storage devices with a high short-circuit ca- of the network protector [22], [23]. This practice ensures that
pacity (e.g., a flywheel energy storage unit) into the microgrid. the smallest possible area of the secondary network is de-en-
The proposed approach makes it possible to rely on the (modi- ergized in response to a fault incident. The secondary side of
fied) traditional overcurrent protection, but needs adaptive pro- the step-down transformer may not necessarily be protected by
tective devices. Moreover, the cost associated with a dedicated dedicated equipment, as the SMs are commonly equipped with
energy storage device with a boosted short-circuit capacity is corresponding dedicated network fuses [21]. Hereafter, due to
disadvantageous. its more common usage, the term “network fuse” or “fuse” is
This paper proposes a strategy for protection of LV micro- used instead of limiter.
grids, in both modes of operation, based on programmable mi-
croprocessor-based relays and directional elements. The pro- C. Grounding Practices
posed strategy aims to detect and isolate the faults that impact An LV microgrid is subject to the same safety requirements
the host microgrid, in a selective (coordinated) manner. The and standards as those set for a conventional secondary distri-
paper also presents the concept and structure of a new relay that bution network. In a microgrid, a fault incident may result in a
enables the proposed protection strategy. The salient features of substantial ground voltage, even if the DRs operate at low volt-
the proposed strategy (and the relay) are that it does not require ages [24]. Moreover, the neutral grounding practice in a micro-
communications, and is fairly independent of the fault current grid can affect protection. Therefore, the grounding strategies of
magnitudes and the mode of operation. The effectiveness of the the equipment in an LV microgrid must be adopted judiciously.
proposed strategy and relay is demonstrated by simulation study Typically, a (delta/grounded wye) winding configu-
cases conducted on a detailed model of an example LV micro- ration is used for the step-down transformer. Thus, either of the
grid, in the PSCAD/EMTDC software environment. two grounding strategies TT and TN [24] can be adopted, since
the ground will be available at the LV side of the step-down
II. CHARACTERISTICS OF LOW-VOLTAGE DISTRIBUTION transformer, even if the microgrid is islanded. However, com-
NETWORKS AND ASSUMPTIONS MADE pared to the TT method, fault currents are higher in the TN ap-
The following subsections introduce some important charac- proach, due to the low-impedance return path (neutral or protec-
teristics of a secondary (LV) distribution network, as they per- tive earth conductor) that exists in the TN method. The reason is
tain to the operation and protection of a microgrid. The charac- that, in the TN approach only a small fraction of the fault current
teristics will be considered in Sections III and IV, for the devel- is diverted to the ground, but the rest flows through the neutral
opment of the proposed protection strategy. path. This characteristic enables the use of ground-fault relays
in the TN approach, for the neutral conductor of an SM. For
A. Structure the reason mentioned above, the popularity of TN method [19],
An LV microgrid is based on a designated area of a secondary and the system safety requirements, the TN-C-S [25] grounding
distribution network which is supplied by a step-down trans- configuration of Fig. 1 is assumed in this paper.
former. By assumption, the designated area embeds sufficient
amount of generation and is thus able to operate in isolation D. DR Interface Mechanisms
from the rest of the network. The rating of the step-down trans- The DRs of an LV microgrid can be of the single-phase
former, which connects the primary (MV) network to the sec- or three-phase type, based on rotating machines or interfaced
ondary (LV) network, is typically from a few hundred kilovolt through power-electronic converters of the voltage-sourced
amperes to several megavolt amperes [20], [21]; thus the peak converter (VSC) types. A single-phase DR is connected be-
power demand of an LV microgrid is assumed to be limited to a tween a phase conductor and the neutral conductor, typically
ZAMANI et al.: PROTECTION STRATEGY AND MICROPROCESSOR-BASED RELAY 1875

is located at the microgrid interface point (i.e., where the mi-


crogrid is interfaced with the utility grid). Moreover, this paper
proposes replacing the fuses that are located at the beginning
of the SMs by relays, but to maintain all other network fuses;
the remaining fuses and the added relays shall be coordinated
for the grid-connected mode of operation; this is discussed in
Section IV. As mentioned, each circuit breaker is controlled by
a corresponding microprocessor-based relay which, hereafter, is
referred to as the “microgrid protection relay” (MPR). The relay
Fig. 1. TN-C-S grounding configuration in an LV network. that is installed at the microgrid interface point is referred to as
the “interface microgrid protection relay” (IMPR). The intro-
duction of those relays provides an acceptable system reliability
through a single-phase isolation transformer. Thus, the TN-C-S
for the host LV microgrid; however, if the same number of iso-
grounding strategy ensures that the DR can contribute to a
lation points as those possible in the grid-connected mode were
line-to-ground fault current, through the low-impedance path
required, more fuses should be replaced by circuit breakers/re-
of the fault current loop. The TN-C-S grounding configuration
lays. Section III-E deals with such a scenario.
can also be adopted for a three-phase DR for which a
It is further proposed in this paper that the circuit breakers
interconnection transformer is employed.
installed at the beginning of the SMs have the single-phase trip-
E. DR Control Strategies ping capability, to only isolate the smallest possible part of the
In this paper, the droop-based voltage/frequency regulation network. By contrast, the circuit breaker located at the micro-
grid interface point is intended for three-phase tripping. Addi-
strategy has been employed for the DRs. It is also assumed that
tionally, it is assumed that each DR is dropped out if the net-
the control scheme of each DR embeds a respective synchro-
nization mechanism for safe reconnection of the islanded mi- work frequency and/or voltage are not within their permissable
crogrid to the utility grid. To ensure that traditional basic pro- ranges, for a prespecified period of time. This is ensured by the
tection functions, more specifically the directional function, can corresponding anti-islanding mechanism which intervenes and
also be employed here, the built-in controls of DRs are designed disconnects a DR, as required by IEEE Std. 1547 [29].
in such a way that the DRs behave similarly to the conventional C. Fault Detection
synchronous machines, in the sense that they more or less main-
tain the balance of their terminal voltages when an asymmetrical 1) Solid Faults: A fault within an islanded microgrid results
fault strikes the network; in an EC-DR, of course, the magnitude in a network-wide voltage drop, which can be utilized for fault
of the terminal voltage drops to limit the fault current contribu- detection. In addition, an instantaneous overcurrent relay, which
tion [26]. is set based on the thermal properties of the conductors, can pro-
vide preliminary redundant protection for solid faults, despite
III. PROPOSED PROTECTION STRATEGY FOR THE ISLANDED the fact that the fault current may not be large in the islanded
MODE OF OPERATION mode of operation.
2) Medium-Impedance Faults: For a medium-impedance
A. Household Consumer Protection fault, neither the voltage drop nor the fault current may be
Traditionally, household consumers are protected by small large. Consequently, the protection scheme may not be able
fuses or miniature circuit breakers. Commonly, the devices are to distinguish a faulty condition from a network overload
of 6-A, 16-A, and 32-A current ratings, for a 208-V network condition. Therefore, this paper proposes an additional fault
[27], and there is no need to replace them. The reason is that detection strategy that serves as a main redundant mechanism
the fault current contributed by the DRs is expected to be suf- should the protection functions mentioned in Section III-C-1
ficiently large to force the fuses to act in about 5 cycles from fail to operate. This paper proposes to extract the zero- and
the fault inception, even in the islanded mode of operation [27], negative-sequence components of the currents, and to utilize
[28]. them as a redundant fault detection mechanism. Thus, if the
sequence components exceed their respective thresholds for
B. Network Protection a certain time period, an algorithm issues a trip command.
As discussed in Section II-B, secondary distribution networks To circumvent false detection due to network voltage/current
are generally protected by network protectors and fuses, such imbalance, the trip thresholds should be selected judiciously.
that they are coordinated for the grid-connected mode of op- It is assumed in this paper that appropriate voltage regulation
eration. However, due to inadequate fault currents, the coordi- strategies are employed by the DRs to maintain the network
nation may be compromised in the islanded mode of operation voltage imbalance down to the standard limits ( 2%) [30]; in
(i.e., small fault currents can result in a slow operation of net- this study, a 1.5% voltage imbalance and a 25% load imbal-
work overcurrent devices). Consequently, this paper proposes ance have been assumed. The trip thresholds are specified in
that some of the network protective devices of the LV micro- Appendix A.
grid be replaced by circuit breakers that are governed by a suit- 3) High-Impedance Faults: A reliable protection scheme
able relaying scheme; replacement of all protective devices by must also be able to detect high-impedance faults (HIFs), which
circuit-breakers/relays is costly and time-consuming. Thus, the may have current magnitudes similar to those of normal loads
paper proposes to replace by a relay the network protector that and, therefore, not cause any noticeable voltage drop. Even
1876 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011

ground-fault relays may not be able to detect HIFs, especially in


systems with multiple grounded points where the earth return
current can take various pathes. Almost all of the methods
proposed for HIF detection rely on extracting HIF current
waveform characteristics, such as the energy level [31], high
frequency components [32], and harmonic content [33]. This
paper adopts the method proposed in [31] for the HIF detection
module that is incorporated in the MPRs.

D. Protection Coordination
1) Grading: In an islanded microgrid, the voltage drop caused Fig. 2. Diagram showing the coordination of MPRs in the islanded mode.
by a fault appears more or less across the entire network, due to
the limited geographical span. Therefore, it is almost impossible
to coordinate protective devices based on voltage profile. To en- conceptually emulates the angle of the effective impedance
sure coordination, this paper proposes the use of a directional ele- of the SM, which also includes the impedance of the current
ment, in conjunction with fault detection modules. The combina- transformer. In addition, should have a minimum discrepancy
tion of a fault detection module and a directional element, with form either of the two bounds specified by (1), before the direc-
proper definite time delays for forward and reverse faults, can tional decision is endorsed. This requirement avoids erroneous
offer an acceptable protection coordination. decisions if either the voltage or the current is so small that its
Since no damaging large fault current is expected to exist in the angle is unreliable. Moreover, since the voltage magnitude is
islanded mode of operation, a definite-time grading technique, very small for close-in faults, a memory voltage is used for the
starting at the load side of an SM and ending at the generation voltage of the SM, to overcome operation failure [35].
side of the SM (microgrid interface point), can ensure a suit- 3) Negative-Sequence Directional Element: The aforemen-
able coordination. In other words, a longer fault clearance time tioned direction detection strategy may need some additional
at the generation side of the grading path is unlikely to damage provisions if a fault does not involve all three phases and the
the microgrid equipment. Thus, inverse-time grading is not nec- fault current magnitude approaches that of the load. For ex-
essary for the islanded microgrid; however, the traditional in- ample, for line-to-line faults, the directional element described
verse-time overcurrent relays are also employed for the grid-con- before may fail to detect the correct direction. Thus, in addition
nected mode of operation, as will be discussed in Section IV. The to the three directional elements of each SM (one for each
upper limits for the definite time delays at the generation side of phase), a negative-sequence directional element is also em-
the grading paths are determined based on constraints such as ployed. The negative-sequence directional element is based on
the sensitivity of the critical loads to voltage disturbances, the the same algorithm as the one described for a regular directional
duration over which an EC-DR can contribute to the fault cur- element, except that the algorithm output is logically inverted,
rent, and the stability of rotating-machine-based DRs. compared to the positive-sequence directional element.
The proposed grading method requires incorporation of di- 4) Secondary Mains Without DR: If an SM does not include
rectional elements in each MPR, to preclude false tripping when any DRs, or it includes an insignificant amount of generation,
a fault impacts a neighboring SM. Thus, the directional elements the directional decision is not reliable, since the power drawn
of a sound SM rapidly block their respective circuit breaker(s), by the loads in such SMs is considerably larger than the power
for a prespecified period of time, to allow the protective devices generated by the DRs. Thus, the directional element may er-
of the faulty SM to isolate the fault. The blockage, however, does roneously declare a forward direction and disconnect the SM
not continue for any longer than the duration of the relay reverse for a fault that is in a neighboring SM. In order to overcome
definite time; afterwards, the circuit breaker(s) of the sound SM this issue, this paper proposes to supplement the aforementioned
is commanded to open, as a backup protection. This concept is directional decision-making strategy with a current-magnitude
illustrated by Fig. 2 in which and respectively denote comparison technique. Thus, the directional decision for a for-
the relay forward and reverse definite time delays. It is noted that ward fault is endorsed if the current magnitude of the host SM
the reverse definite time delay is larger than its forward coun- is larger than its full-load current magnitude. The reason for
terpart, by a suitable grading margin, . It is also remembered this condition is that, in a healthy SM the current magnitude
that the circuit breaker installed at the microgrid interface point drops remarkably in the phase(s) that corresponds to the affected
is open in the islanded mode of operation. phase(s) of a neighboring faulty SM.
2) Directional Element: The directional characteristic func- 5) Substation Bus Protection: One potential issue that may
tion has been realized in this paper by a comparator whose in- arise due to the inclusion of directional elements is that the pro-
puts are derived from the voltage and current of the SM [34]. tection may be lost if a fault directly impacts the substation. To
The comparator identifies a fault as a forward fault, that is, circumvent this condition, all circuit breakers of the SMs that
1, if embed a DR must be commanded to open after a time delay,
once their directional elements simultaneously detect a reverse
(1) fault. For an LV microgrid with SMs that all of which have
DR(s), this function is realized by the logic circuit illustrated in
where denotes the output of the directional element, is the Fig. 3; through denote the outputs of the directional el-
phase difference between the voltage and current of the SM, and ements for SM#1 through SM# , respectively.
ZAMANI et al.: PROTECTION STRATEGY AND MICROPROCESSOR-BASED RELAY 1877

Fig. 3. Symbolic logic circuit for substation bus protection.

Fig. 5. Traditional coordination of fuses and relays in a typical distribution


network.

Fig. 4. Extending the protection scheme for SMs including four MPRs.

E. Protection Scheme Extension

As explained in Section III-B, the introduction of an MPR at


the beginning of each SM ensures sufficient reliability for the Fig. 6. Coordination of the IMPR and MPRs for a grid fault.
host LV microgrid. However, one may prefer to extend the pro-
tection scheme and utilize multiple MPRs along the radial SMs,
to enhance the system reliability. In case a radial SM contains IV. PROPOSED PROTECTION STRATEGY FOR THE
more than one MPR, it is necessary to coordinate them through GRID-CONNECTED MODE OF OPERATION
a suitable grading method. Fig. 4 shows the basics of the defi-
nite-time grading method, for a sample LV microgrid with two As mentioned earlier, the conventional overcurrent protec-
SMs that employs more than one (four, in this example) MPR tion can still be employed for the protection of a microgrid in
in each radial SM. the grid-connected mode of operation. Fig. 5 illustrates an ex-
Each MPR in Fig. 4 has its own forward and reverse time ample of the conventional coordination practice for two fuses,
delays and is intended to protect a protection zone; the time one main relay, and one backup relay for a typical distribution
delays used for forward and reverse operations of the MPRs network. The figure indicates that the devices are coordinated in
are also indicated in the figure. Fig. 4 shows that for a forward such a way that for all fault currents between (minimum
fault at location Flt1, MPR11 operates first with a delay of . fault current of the feeder) and (maximum fault current
This time delay is chosen in such a way that it allows the lateral of the feeder), the minimum melting time (MMT) curve and the
protection to clear the fault if it is within the household/lateral total clearing time (TCT) curve of the fuses lie below the char-
installations. If MPR11 fails to operate, MPRs 12, 13, and 14, in acteristic curves of the relays to ensure that the fuses will op-
sequence, are expected to clear the fault through their delayed erate before the relays intervene [9]. In addition, coordination
operations. The same grading strategy is employed to coordinate must also be made between the fuses (the characteristic curves
the MPRs for the reverse path (e.g., for a fault at location Flt2). of the protective devices are described in [9]). If the fuses fail
The same coordination grading scheme can also be employed to operate for a fault, the main relay will back them up by op-
for a microgrid with several (more than two) SMs. erating according to its inverse-time characteristic. The backup
Assuming that: 1) the maximum time required for the fault relay will operate only if the main relay and the fuses fail to act.
detection (i.e., ) is about 15 (60-Hz) cycles, 2) the time consid- Hence, to maintain the coordination, one has to ensure that the
ered for the margin (i.e., ) is about 10 cycles, and 3) the time fault current passing through the devices has a value between
needed by a circuit breaker to open is about 5 cycles, it takes and .
a maximum of 2 s for MPR11 to clear a fault at location Flt2 The addition of a DR to an SM, anywhere downstream of the
in the reverse direction, if all MPRs fail to operate. If this oper- relay, affects and and also causes the fuse current to
ating time is not acceptable (e.g., in view of the system safety), exceed the current seen by the relay [4]. Reference [9] has pro-
the microgrid can be divided into smaller islanded systems [17]. posed an effective solution to accommodate the impact of DRs
1878 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011

Fig. 7. Simplified schematic diagram of the proposed MPR (or IMPR).

on the coordination of protective devices (including reclosers) the microgrid interface point (i.e., IMPR). To address this short-
in a conventional distribution network. The method proposed in coming, the IMPR must also employ the islanded-mode protec-
[9] utilizes microprocessor-based relays, but does not require tion strategy of Section III, despite the fact that it always op-
communications or adaptive protective devices. Therefore, it is erates in the grid-connected mode. The only difference is that
also adopted in this paper as the coordination method for the definite-time grading of the IMPR starts at the microgrid inter-
fuses and MPRs in the grid-connected mode of operation. Due face point and ends at the load side of the SMs. Fig. 6 illustrates
to their limited fault current contributions, EC-DRs cannot sig- the process for two adjacent SMs with their respective MPRs.
nificantly affect the protection coordination. In addition, it is
assumed in this paper that the secondary distribution network B. Neutral Voltage Displacement Protection
does not include any recloser [22], [23]. Thus, the coordination Another issue concerning the IMPR may arise when the mi-
of protective devices for the grid-connected mode of operation crogrid operates in the islanded mode of operation. Although
of an LV microgrid whose DRs are predominantly of the elec- the neutral grounding of the LV microgrid is preserved due to
tronically coupled type is more straightforward than the general the LV-side star winding configuration of the step-down trans-
example analyzed in [9]. former, the MV side of the step-down transformer, which is still
energized, becomes ungrounded in the islanded mode of oper-
A. External Faults ation. Therefore, overvoltages may be experienced if a ground
fault impacts the ungrounded MV side of the step-down trans-
For a fault taking place outside of the microgrid jurisdic- former (area “ ” in Fig. 8), in the islanded mode of operation.
tion, a low fault current may be contributed by the (grid-con- To address this issue and to detect such faults, this paper pro-
nected) microgrid, which does not guarantee the operation of poses the use of a neutral voltage displacement (NVD) protec-
the overcurrent protection scheme of the relay that is located at tion function in the IMPR [36].
ZAMANI et al.: PROTECTION STRATEGY AND MICROPROCESSOR-BASED RELAY 1879

Fig. 8. Single-line diagram of the study LV microgrid.

V. PROPOSED MICROGRID PROTECTION RELAY (MPR) the materials presented in Section IV are the base for the im-
plementation of the grid-connected-mode protection block. It
The protection strategy proposed in Sections III and IV can must be noted that the forward and reverse time delays are gen-
be implemented through a microprocessor-based relay. The erally different in the islanded mode of operation, compared to
present-day digital relays typically offer standard overcurrent, the grid-connected mode of operation. It is pointed out that HIF
overvoltage/undervoltage, and overfrequency/underfrequency detection algorithm, which provides protection against HIFs, is
protection functions. In addition, they are self metering, have fairly slow compared to other modules [31]. This, however, does
oscillographic event reporters and communication links, and not pose a serious problem since HIF currents are very small.
offer logic programming capabilities [37], [38]. The three-phase protection module in the MPR of Fig. 7 oper-
Fig. 7 illustrates a simplified block diagram of the proposed ates with a prespecified delay should the phase protection mod-
MPR, showing the relay functional modules and that the MPR ules fail to clear the fault (see Section III-C-2). In addition, an
consists of three distinct phase modules which independently NVD protection element is employed to help the IMPR detect
protect the corresponding phases of the host SM. This ensures a faults at the MV side of the step-down transformer. A synchro-
continuous supply for the single-phase loads that are connected nism-check relay is also used in the IMPR, to ensure safe recon-
to sound phase(s), enhancing the security of supply. Fig. 7 also nection of the (islanded) microgrid to the utility grid. The time
indicates that an additional module, the three-phase protection delays assumed in this paper are specified in Appendix A.
module, is employed to provide a redundant protection based on
zero-/negative-sequence components. The three-phase module A. Special Case
works only through three-phase tripping, as Fig. 7 shows. Fur- Typically, settings of the inverse-time overcurrent relays are
ther, an interface module is included in the IMPR to enable re- determined in a manner to provide coordination for a fairly wide
connection of the islanded microgrid to the utility grid. In ad- range of the short-circuit capacity of the utility grid. This is per-
dition, a module has also been dedicated to negative-sequence formed through the proper selection of and [4], [9].
directional function. Finally, a tripping module determines the However, if the utility grid is so weak that the fault current mag-
type of the trip signal that will be sent out by an MPR or the nitudes are comparable in both modes of operation, the grid-
IMPR. connected-mode protection block of Fig. 7 is not necessarily
Fig. 7 further shows that three different blocks, namely, the is- needed, and one can deactivate it through assigning fairly large
landed-mode protection block, the grid-connected-mode protec- values to time delays TD_GF and TD_GR. Otherwise, it will
tion block, and the HIF protection block, are included in a phase operate with a delay and may interfere with the islanded-mode
module. The islanded-mode protection block is implemented protection block, which is now responsible for protection of the
based on the discussions of Sections III-C-1 and III-D, whereas microgrid in both modes of operation. It is remembered that an
1880 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011

TABLE I
OPERATING TIMES OF PRIMARY AND BACKUP PROTECTION FOR SELECTED FAULT LOCATIONS IN THE ISLANDED MODE OF OPERATION

instantaneous overcurrent relay (with a prespecified time delay, As Fig. 8 shows, the backbone of the study microgrid is a
TD_IOC) is also utilized in the islanded-mode protection block 208-V, four-SM, distribution subsystem, which is connected to
(see Fig. 7). the main utility grid through a step-down transformer
and an 11-kV radial feeder. The distribution substation is
VI. SIMULATION RESULTS equipped with four banks of three-phase shunt capacitors,
To demonstrate the effectiveness of the proposed protection each with the capacity of 15 kVA, which can be switched
scheme and the MPRs/IMPR, a realistic LV microgrid system on or off, either automatically or by the system operator.
has been simulated in the PSCAD/EMTDC software environ- The grid is represented by an 11-kV bus with a short-circuit
ment [39]. The structure of the simulated micogrid which, here- capacity of 80 MVA. A combination of different three-phase
inafter, is referred to as “study microgrid,” is described next, and and single-phase loads is energized through the four radial
then study cases are presented. SMs. The system also includes two three-phase EC-DRs (i.e.,
DR1 and DR2), connected to SM1 and SM2, respectively; a
A. Study Microgrid conventional three-phase synchronous-machine-based DR (i.e.,
Fig. 8 shows a single-line diagram of the study microgrid, DR4), connected to SM4; and seven single-phase EC-DRs
of which basic configuration and majority of parameters are (i.e., dr31 through dr37), connected to SM3. The units DR1,
taken from the benchmark system presented in [20] and [21]; DR2, and dr31 through dr37 utilize VSCs as their interface
some modifications have been made to allow for the operation media, whereas DR4 is directly interfaced with the network.
of the microgrid in the islanded mode, in the context of the North The three-phase DRs are interfaced with the network through
American power system. respective interconnection transformers, and the
ZAMANI et al.: PROTECTION STRATEGY AND MICROPROCESSOR-BASED RELAY 1881

TABLE II
OPERATING TIMES OF PRIMARY AND BACKUP PROTECTION FOR SELECTED FAULT LOCATIONS IN THE GRID-CONNECTED MODE OF OPERATION

single-phase DRs utilize single-phase interconnection trans- in the islanded mode of operation a fault results in an insuffi-
formers. The EC-DRs are of the wind, photovoltaic, battery, and cient fault current, the network fuses take a relatively long time
fuel cell types, as indicated in Fig. 8. To protect the microgrid, to operate. Therefore, the faults are cleared by the MPRs. For
five MPRs, four at the beginning of the SMs and one at the solid faults, the voltage drop across the microgrid is significant
interface point, have been used. Fuses and traditional relaying and the undervoltage protection can detect and clear the faults.
functions are modeled in this paper based on the analytical However, for high-impedance faults, only three-phase protec-
equations presented in [9]. tion modules (3-Ph) or HIF detection modules (HIF) operate, as
no voltage dip is detected by the undervoltage protection func-
B. Study Cases tion. The HIF detection module ensures protection against HIFs
even if zero-/negative-sequence current components are smaller
1) Islanded Mode of Operation: System studies have been than the threshold values required for detection.
performed, with the MPR settings and time delays calculated To demonstrate the effectiveness of the proposed method and
based on the strategy proposed in Sections III and IV. Let us MPR for the fault scenarios in which the fault currents are very
assume that a fault impacts the microgrid at 1.5 s, in the small, SM4 was disconnected from the substation and, there-
islanded mode of operation. Table I reports the primary and fore, the synchronous-machine-based DR (DR4) was sent out
backup relay operating times for different fault scenarios. Since of service, assuming that, for example, a fault had impacted the
1882 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011

TABLE III TABLE IV


TIME DELAYS FOR MPRS TIME DELAYS FOR THE IMPR

TABLE V
INVERSE-TIME OVERCURRENT RELAY PARAMETERS
SM. Then, similar fault studies were conducted, and the results FOR MPRS AND THE IMPR
were found to be very similar to those of the previous cases in
which DR4 was connected to the microgrid. However, due to
space limitations, only a selected number of scenarios have been
reported in Table I.
2) Grid-Connected Mode of Operation: Several cases have
also been simulated for the grid-connected mode of operation
but, due to space limitations, the results of only a limited number
of them have been reported in Table II. Table II shows the pri-
mary and backup relay operating times for different internal and
external faults, at various locations; all faults are assumed to
strike the network at 1.5 s. Similar to the islanded mode of
operation, it is observed that if the MPR, which is responsible
for the primary protection, fails to operate, other MPRs provide
suitable backup protection. TABLE VI
THREE-PHASE PROTECTION MODULE PARAMETERS FOR MPRS AND THE IMPR
VII. CONCLUSION
This paper proposed a protection strategy and an enabling
relay for protection of low-voltage microgrids in the islanded
mode as well as grid-connected mode of operation. The
proposed protection strategy can be implemented through
programmable microprocessor-based relays with directional
elements, and can address protection issues of a microgrid
in both modes of operation. The proposed strategy does not TABLE VII
DEVICE/FUNCTION NUMBERS
require communication links or adaptive protective devices.
More important, its effectiveness is to a large extent indepen-
dent of the fault current levels, the mode of operation, as well
as the type and size of distributed energy resource units, subject
to the modified relay settings for the grid-connected mode of
operation. Further, the proposed protection strategy enables
single-phase tripping to increase security of supply. Several
study cases were presented based on digital time-domain sim-
ulation of a model microgrid, to demonstrate the effectiveness
of the proposed protection scheme and the enabling relay.

APPENDIX A REFERENCES
RELAY SETTINGS [1] R. H. Lasseter, “Microgrids,” in Proc. IEEE Power Eng. Soc. Winter
The parameters of the MPRs and the IMPR are reported in Meeting, Jan. 2002, vol. 1, pp. 305–308.
[2] C. L. Smallwood, “Distributed generation in autonomous and non-au-
Tables III–VI. tonomous microgrids,” in Proc. IEEE Rural Elect. Power Conf., May
2002, pp. 1–6.
[3] N. Hadjsaid, J. F. Canard, and F. Dumas, “Disperse generation impact
APPENDIX B on distribution network,” IEEE Comput. Appl. Power, vol. 12, no. 2,
DEVICE/FUNCTION NUMBERS pp. 22–28, Apr. 1999.
[4] A. Girgis and S. M. Brahma, “Effect of distributed generation on pro-
Table VII shows the standard device/function numbers em- tective device coordination in distribution system,” in Proc. Large Eng.
ployed in this paper [40]. Syst. Conf. Power Eng., Jul. 2001, pp. 115–119.
ZAMANI et al.: PROTECTION STRATEGY AND MICROPROCESSOR-BASED RELAY 1883

[5] S. M. Brahma and A. A. Girgis, “Development of adaptive protection [31] R. C. Christie, H. Zadehgol, and M. M. Habib, “High impedance fault
scheme for distribution systems with high penetration of distributed detection in low voltage netwoks,” IEEE Trans. Power Del., vol. 8, no.
deneration,” IEEE Trans. Power Del., vol. 19, no. 1, pp. 56–63, Jan. 4, pp. 1829–1836, Oct. 1993.
2004. [32] B. M. Aucoin and B. D. Russell, “Distribution high impedance fault
[6] H. Wan, K. K. Li, and K. P. Wong, “A multi-agent approach to protec- detection utilizing high frequency current components,” IEEE Trans.
tion relay coordination with distributed generators in industrial power Power App. Syst., vol. PAS-101, no. 6, pp. 1596–1606, Jun. 1982.
distribution system,” in Proc. Ind. Appl. Conf. 40th Ind. Appl. Soc. [33] D. I. Jeerings and J. R. Linders, “Unique aspects of distribution system
Annu. Meeting, Oct. 2005, pp. 830–836. harmonics due to high impedance ground faults,” IEEE Trans. Power
[7] B. Hadzi-Kostova and Z. Styczynski, “Network protection in distri- Del., vol. 5, no. 2, pp. 1086–1094, Apr. 1990.
bution systems with dispersed generation,” in Proc. Transm. Distrib. [34] T. S. M. Rao, Power System Protection: Static Relays With Micropro-
Conf. Exhibit., May 2006, pp. 1–6. cessor Applications, 2nd ed. New Delhi, India: McGraw-Hill, 1989.
[8] B. Li, Y. Li, Z. Bo, and A. Kilmek, “Design of protection and control [35] J. Roberts and A. Guzman, “Directional element design and evaluation,”
scheme for microgrid systems,” in Proc. 44th Intl. Univ. Power Eng. in Proc. 21st Annu. Western Protective Relay Conf., 1994, pp. 1–27.
Conf., Sep. 2009, pp. 1–5. [36] CEE Relays, Connection and setting of neutral voltage displacement
[9] M. A. Zamani, T. S. Sidhu, and A. Yazdani, “A strategy for protection (NVD) relays. Jun. 2010. [Online]. Available: http://www.ceere-
coordination in radial distribution networks with distributed genera- lays.co.uk/RelayFAQs/NVD.htm
tors,” in Proc. IEEE Power Energy Soc. Gen. Meeting, Jul. 2010, pp. [37] A. T. Johns and S. K. Salman, Digital Protection for Power Systems,
1–8. ser. Inst. Elect. Eng. Power Eng. Series 15. London, U.K.: Peregrinus
[10] H. Nikkhajoei and R. Lasseter, “Microgrid protection,” in Proc. IEEE Ltd., 1995.
Power Eng. Soc. Gen. Meeting, Jun. 2007, pp. 1–6. [38] Schweitzer Engineering Laboratories, SEL-751A feeder protection
[11] E. Sortomme, G. J. Mapes, B. A. Foster, and S. S. Venkata, “Fault anal- relay. Jun. 2010. [Online]. Available: www.selinc.com/WorkArea/
ysis and protection of a microgrid,” in Proc. 40th North Amer. Power DownloadAs-set.aspx?id=2822
Symp., Sep. 2008, pp. 1–6. [39] PSCAD/EMTDC V. 4.2 Manitoba HVDC Research Ctr. Winnipeg,
[12] H. H. Zeineldin, E. F. El-Saadany, and M. M. A. Salama, “Distributed MB, Canada.
generation microgrid operation: Control and protection,” in Proc. [40] IEEE Standard for Electrical Power System Device Function Numbers,
Power Syst. Conf., Mar. 2006, pp. 105–112. Acronyms, and Contact Designations, IEEE Std. C37.2-2008, 2008.
[13] E. Sortomme, S. S. Venkata, and J. Mitra, “Microgrid protection using
communication-assisted digital relays,” IEEE Trans. Power Del., vol.
25, no. 4, pp. 2789–2796, Oct. 2010.
[14] R. M. Tumilty, M. Brucoli, and T. C. Green, “Approaches to network M. Amin Zamani (S’09) received the B.Sc. degree
protection for inverter dominated electrical distribution systems,” in in electrical engineering from the Iran University
Proc. 3rd IET Int. Conf. Power Electron., Mach., Drives, Apr. 2006, of Science and Technology (IUST), Tehran, Iran,
pp. 622–626. in 2003, the M.Sc. degree in electrical engineering
[15] H. Al-Nasseri, M. Redfern, and F. Li, “A voltage based protection from Shahid Chamran University (SCU), Ahvaz,
for microgrids containing power electronic converters,” in Proc. IEEE Iran, in 2005, and is currently pursuing the Ph.D.
Power Eng. Soc. Gen. Meeting, Jun. 2006, pp. 1–7. degree at the University of Western Ontario, London,
[16] M. A. Redfern and H. Al-Nasseri, “Protection of microgrids domi- ON, Canada.
nated by distributed generation using solid state converters,” in Proc. His research interests include power system pro-
9th Int. IET Conf. Developments Power Syst. Protection, Mar. 2008, tection, control, and monitoring; distributed genera-
pp. 670–674. tion; electronic power converters; and microgrids.
[17] T. Loix, T. Wijnhoven, and G. Deconinck, “Protection of microgrids
with a high penetration of inverter-coupled energy sources,” in Proc.
IEEE Power Energy Soc./CIGRE Symp., Jun. 2009, pp. 1–6.
[18] N. Jayawarna, C. Jones, M. Barnes, and N. Jenkins, “Operating micro- Tarlochan S. Sidhu (M’90–SM’94–F’04) is a
grid energy storage control during network faults,” in Proc. IEEE Int. Professor and Chair of the Electrical and Computer
Conf. Syst. Syst. Eng., Apr. 2007, pp. 1–7. Engineering Department, University of Western
[19] N. Jayawarna, N. Jenkins, M. Barnes, M. Lorentzou, S. Papthanassiou, Ontario, London, ON, Canada. He is also the
and N. Hatziargyriou, “Safety analysis of a microgrid,” in Proc. Int. NSERC/Hydro One Networks Senior Industrial
Conf. Future Power Syst., Nov. 2005, pp. 1–7. Research Chair in Power System Engineering. From
[20] K. Strunz, R. H. Fletcher, R. Campbell, and F. Gao, “Developing 1990 to 2002, he was a Professor and Graduate
benchmark models for low-voltage distribution feeders,” in Proc. Chairman with the Department of Electrical Engi-
IEEE Power Energy Soc. Gen. Meeting, Jul. 2009, pp. 1–3. neering, University of Saskatchewan, Saskatoon,
[21] S. Papathanassiou, N. Hatziargyriou, and K. Strunz, “A benchmark low SK. His research interests include power system
voltage microgrid network,” in CIGRE Symp., Apr. 2005, pp. 1–8. protection, monitoring, control, and automation.
[22] T. Gonen, Electric Power Distribution System Engineering, 2nd ed. Prof. Sidhu is a Fellow of the Institution of Engineers (India) and a Fellow of
Boca Raton, FL: CRC, 2008. the Institution of Electrical Engineers (U.K.). He is a Registered Professional
[23] Electric Utility Engineering Reference Book: Distribution Systems. Engineer in the Province of Ontario and a Chartered Engineer in the U.K.
East Pittsburgh, PA: , 1965, vol. 3, Westinghouse Electric Corp..
[24] R. Calvas and B. Lacroix, System Earthing in LV Schneider Electric,
Cahier Technique no. 172, 2000.
[25] E. Lakervi and E. J. Holmes, Electricity Distribution Network Design, Amirnaser Yazdani (M’05–SM’09) received
ser. IEE Power Eng. Ser. 21, 2nd ed. London, U.K.: Peregrinus Ltd., the Ph.D. degree from the University of Toronto,
1995. Toronto, ON, Canada, in 2005.
[26] M. B. Delghavi and A. Yazdani, “A control strategy for islanded oper- He was with Digital Predictive Systems (DPS)
ation of a distributed resource (DR) unit,” in Proc. IEEE Power Energy Inc., Mississauga, ON. Currently, he is an Assistant
Soc. Gen. Meeting, Jul. 2009, pp. 1–8. Professor with the University of Western Ontario,
[27] British Standard Fuses BS 1361-3. Jun. 2010. [Online]. Available: London. His research interests include dynamic
http://en.wikipedia.org/wiki/BS_1362#Fuses and http://en.wikipedia. modeling and control of electronic power converters,
org/wiki/Fuse_(electrical). distributed power generation and energy storage, re-
[28] F. Shawmut, LV Fuse Link and holder catalogues. Jun. 2010. [Online]. newable energy, and microgrids. He is the co-author
Available: http://us.ferrazshawmut.com/ of the book Voltage-Sourced Converters in Power
[29] IEEE Application Guide for IEEE Standard for Interconnecting Dis- Systems (IEEE/Wiley, 2010).
tributed Resources With Electric Power Systems, IEEE Std. 1547.2- Dr. Yazdani is the Chairman of the IEEE Task Force on Modeling and Anal-
2008, 2008. ysis of Electronically-Coupled Distributed Energy Resources, an Associate Ed-
[30] IEEE Recommended Practice for Monitoring Electric Power Quality, itor of the IEEE TRANSACTIONS ON POWER DELIVERY, and a Professional En-
IEEE Std. 1159-2009, 2009. gineer in the Province of Ontario.

S-ar putea să vă placă și