National Electricity Corporation Volume 02
(NEC), Sudan Oil Fired Boiler
Table of content
1 INSPECTION OF BOILER.......................................................................................................................................1
1 INSPECTION OF BOILER
1.1 Inspection route
1.2 Contents of inspection items
1.3 Inspection frequency
meter continuously
C Slightly open steam valve second stop 1/4 round, and lead steam into
water level meter.
Attention: do not open the water valve and steam valve too wide and too
quick, otherwise safety ball will act and it will block the steam and water
passage: if the safety ball has acted yet, firstly close all valves and then
open them slowly.
D Open all steam valves and water valves
E Carefully watch the water level: boiler water begins to enter into the water
level meter and make the water level rise gradually until the water level
does not change. However, the water level should have slight wave to show
that water and steam pipelines are smooth and operates normally.
F Turn back 1/4 round of steam valve primary stop, water valve primary stop,
heating valve and water-reducing valve in order to avoid valve rod and
backseat stick together.
G Check if no crack in glass and isinglass, no leakage in pressure cover and
valve is normal
2.2.2 Purpose of flushing water level meter
All water level meter must indicate correctly. Local water level meter, electric
connecting point water level meter and water level transformer should indicate the
same data. Check it on site during every duty. The water level high and low
instruments of boiler sleeve and alarm should be reliable and verified periodically.
Under normal condition, the liquid level of local water level meter should indicate
within the range of boiler sleeve normal water level ±50mm with slight wave. The
water level is clear and visible with well illumination.
To avoid blurring or liquid surface stagnation of local water level meter which will
affect the safe operation of boiler, water level meter should be flushed periodically.
At least flush the local water level meter every ten days.
2.2.3 Process of flushing local water level meter
Slightly open water discharge valve. If the liquid surface can flow it is normal,
otherwise it is the false water level.
When local water level meter does not indicate clearly, wash it immediately. If the
indication data of the two local water level meter are different, judge which one has
malfunction in time. Close steam side valve or water side valve, and open water
discharge valve.
2.2.4 Noticeable items on operation and flushing of water level meter
A The job of putting water level meter into operation should be .
B Be cautious of putting water level meter into operation and flushing and then
out of operation in hot state. Do not face up rightly in front of water level meter.
Once having found any leakage, parallel off the water level meter immediately.
C Avoid the impact of external cold wind and water on water level meter during the
operation.
D I f there are serious leakage or blowing up with water level meter during
operation, carry on paralleling off and wear protective mask and glove under
others’ supervision.