Sunteți pe pagina 1din 24

21

Transformers

At the end of this chapter you should be able to:

ž understand the principle of operation of a transformer


ž understand the term ‘rating’ of a transformer
ž use V1 /V2 D N1 /N2 D I2 /I1 in calculations on transformers
ž construct a transformer no-load phasor diagram and calculate magnetising and core
loss components of the no-load current
ž state the e.m.f. equation for a transformer E D 4.44 f8m N and use it in calculations
ž construct a transformer on-load phasor diagram for an inductive circuit assuming
the volt drop in the windings is negligible
ž describe transformer construction
ž derive the equivalent resistance, reactance and impedance referred to the primary of
a transformer
ž understand voltage regulation
ž describe losses in transformers and calculate efficiency
ž appreciate the concept of resistance matching and how it may be achieved
ž perform calculations using R1 D N1 /N2 2 RL
ž describe an auto transformer, its advantages/disadvantages and uses
ž describe an isolating transformer, stating uses
ž describe a three-phase transformer
ž describe current and voltage transformers

Losses in transformers are generally low and thus


21.1 Introduction efficiency is high. Being static they have a long life
and are very stable.
A transformer is a device which uses the phe- Transformers range in size from the miniature
nomenon of mutual induction (see Chapter 9) to units used in electronic applications to the large
change the values of alternating voltages and cur- power transformers used in power stations; the prin-
rents. In fact, one of the main advantages of a.c. ciple of operation is the same for each.
transmission and distribution is the ease with which A transformer is represented in Fig. 21.1(a) as
an alternating voltage can be increased or decreased consisting of two electrical circuits linked by a
by transformers. common ferromagnetic core. One coil is termed the

TLFeBOOK
304 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY

Figure 21.1

primary winding which is connected to the supply transformer, the primary and secondary ampere-
of electricity, and the other the secondary winding, turns are equal
which may be connected to a load. A circuit diagram
symbol for a transformer is shown in Fig. 21.1(b) V1 I2
Thus D 2
V2 I1
Combining equations (1) and (2) gives:
21.2 Transformer principle of
operation
V1 N1 I2
= = 3
When the secondary is an open-circuit and an alter- V2 N2 I1
nating voltage V1 is applied to the primary wind-
ing, a small current – called the no-load current
I0 – flows, which sets up a magnetic flux in the The rating of a transformer is stated in terms of the
core. This alternating flux links with both primary volt-amperes that it can transform without overheat-
and secondary coils and induces in them e.m.f.’s of ing. With reference to Fig. 21.1(a), the transformer
E1 and E2 respectively by mutual induction. rating is either V1 I1 or V2 I2 , where I2 is the full-load
The induced e.m.f. E in a coil of N turns is given secondary current.
by E D Nd8/dt volts, where d8 dt is the rate
of change of flux. In an ideal transformer, the rate Problem 1. A transformer has 500 primary
of change of flux is the same for both primary turns and 3000 secondary turns. If the
and secondary and thus E1 /N1 D E2 /N2 i.e. the primary voltage is 240 V, determine the
induced e.m.f. per turn is constant. secondary voltage, assuming an ideal
Assuming no losses, E1 D V1 and E2 D V2 transformer.

V1 V2 V1 N1 For an ideal transformer, voltage ratio D turns ratio


Hence D or D 1 i.e.
N1 N2 V2 N2
V1 N1 240 500
V1 /V2  is called the voltage ratio and N1 /N2  D hence D
the turns ratio, or the ‘transformation ratio’ of V2 N2 V2 3000
the transformer. If N2 is less than N1 then V2 is Thus secondary voltage
less than V1 and the device is termed a step-down
transformer. If N2 is greater then N1 then V2 is 2403000
greater than V1 and the device is termed a step-up V2 D D 1440 V or 1.44 kV
transformer. 500
When a load is connected across the secondary
winding, a current I2 flows. In an ideal transformer Problem 2. An ideal transformer with a
losses are neglected and a transformer is considered turns ratio of 2:7 is fed from a 240 V supply.
to be 100 per cent efficient. Hence input power D Determine its output voltage.
output power, or V1 I1 D V2 I2 i.e. in an ideal

TLFeBOOK
TRANSFORMERS 305

A turns ratio of 2:7 means that the transformer


has 2 turns on the primary for every 7 turns on Problem 5. A 12  resistor is connected
the secondary (i.e. a step-up transformer); thus across the secondary winding of an ideal
N1 /N2  D 2/7. transformer whose secondary voltage is
For an ideal transformer, N1 /N2  D V1 /V2  120 V. Determine the primary voltage if the
hence 2/7 D 240/V2  Thus the secondary voltage supply current is 4 A.

2407 Secondary current I2 D V2 /R2  D 120/12 D


V2 D D 840 V 10 A.
2
V1 /V2  D I2 /I1 , from which the primary
voltage
Problem 3. An ideal transformer has a    
I2 10
turns ratio of 8:1 and the primary current is V1 D V2 D 120 D 300 volts
3 A when it is supplied at 240 V. Calculate I1 4
the secondary voltage and current.
Problem 6. A 5 kVA single-phase
transformer has a turns ratio of 10 : 1 and is
A turns ratio of 8:1 means N1 /N2  D 1/8 i.e. a fed from a 2.5 kV supply. Neglecting losses,
step-down transformer. determine (a) the full-load secondary current,
    (b) the minimum load resistance which can
N1 V1 be connected across the secondary winding
D or secondary voltage to give full load kVA, (c) the primary current
N2 V2
    at full load kVA.
N1 1
V2 D V1 D 240 D 30 volts (a) N1 /N2 D 10/1 and V1 D 2.5 kV D 2500 V.
N2 8    
    N1 V1
N1 I2 Since D , secondary voltage
Also, D hence secondary current N2 V2
N2 I1    
N2 1
    V2 D V1 D 2500 D 250 V
N1 8 N1 10
I2 D I1 D3 D 24 A The transformer rating in volt-amperes D V2 I2
N2 1
(at full load) i.e. 5000 D 250I2
Hence full load secondary current I2 D
Problem 4. An ideal transformer, connected 5000/250 D 20 A.
to a 240 V mains, supplies a 12 V, 150 W (b) Minimum value of load resistance,
lamp. Calculate the transformer turns ratio    
V2 250
and the current taken from the supply. RL D D D 12.5 Z.
V1 20
   
N1 I2
V1 D 240 V, V2 D 12 V, I2 D P/V2  D (c) D from which primary current
150/12 D 12.5 A. N2 I1
   
N1 1
N1 V1 240 I1 D I2 D 20 D 2A
Turns ratio D D D D 20 N2 10
N2 V2 12
  
V1 I2 Now try the following exercise
D , from which,
V2 I1
   
V2 12 Exercise 114 Further problems on the
I1 D I2 D 12.5
V1 240 transformer principle of operation

Hence current taken from the supply, 1 A transformer has 600 primary turns
connected to a 1.5 kV supply. Determine the
12.5 number of secondary turns for a 240 V output
I1 D D 0.625 A voltage, assuming no losses. [96]
20

TLFeBOOK
306 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY

2 An ideal transformer with a turns ratio of 2:9 21.3 Transformer no-load phasor
is fed from a 220 V supply. Determine its
output voltage. [990 V] diagram
3 A transformer has 800 primary turns and The core flux is common to both primary and
2000 secondary turns. If the primary voltage secondary windings in a transformer and is thus
is 160 V, determine the secondary voltage taken as the reference phasor in a phasor diagram.
assuming an ideal transformer. [400 V] On no-load the primary winding takes a small no-
load current I0 and since, with losses neglected, the
4 An ideal transformer with a turns ratio of 3:8 primary winding is a pure inductor, this current lags
is fed from a 240 V supply. Determine its the applied voltage V1 by 90° . In the phasor diagram
output voltage. [640 V] assuming no losses, shown in Fig. 21.2(a), current
I0 produces the flux and is drawn in phase with
5 An ideal transformer has a turns ratio of the flux. The primary induced e.m.f. E1 is in phase
12:1 and is supplied at 192 V. Calculate the opposition to V1 (by Lenz’s law) and is shown 180°
secondary voltage. [16 V] out of phase with V1 and equal in magnitude. The
secondary induced e.m.f. is shown for a 2:1 turns
6 A transformer primary winding connected ratio transformer.
across a 415 V supply has 750 turns. A no-load phasor diagram for a practical trans-
Determine how many turns must be wound former is shown in Fig. 21.2(b). If current flows
on the secondary side if an output of 1.66 kV then losses will occur. When losses are considered
is required. [3000 turns] then the no-load current I0 is the phasor sum of
two components – (i) IM , the magnetising compo-
7 An ideal transformer has a turns ratio of 12:1 nent, in phase with the flux, and (ii) IC , the core
and is supplied at 180 V when the primary loss component (supplying the hysteresis and eddy
current is 4 A. Calculate the secondary current losses). From Fig.21.2(b):
voltage and current. [15 V, 48 A]
No-load current, I0 D IM 2
C IC2 where
8 A step-down transformer having a turns ratio IM D I0 sin f0 and IC D I0 cosf0 .
of 20:1 has a primary voltage of 4 kV and Power factor on no-load D cos 0 D IC /I0 .
a load of 10 kW. Neglecting losses, calculate The total core losses (i.e. iron losses)
the value of the secondary current. [50 A] D V1 I0 cos 0
9 A transformer has a primary to secondary
turns ratio of 1:15. Calculate the primary Problem 7. A 2400 V/400 V single-phase
voltage necessary to supply a 240 V load. If transformer takes a no-load current of 0.5 A
the load current is 3 A determine the primary and the core loss is 400 W. Determine the
current. Neglect any losses. [16 V, 45 A] values of the magnetising and core loss
components of the no-load current. Draw to
10 A 10 kVA, single-phase transformer has a
scale the no-load phasor diagram for the
turns ratio of 12:1 and is supplied from a
transformer.
2.4 kV supply. Neglecting losses, determine
(a) the full load secondary current, (b) the
minimum value of load resistance which can V1 D 2400V, V2 D 400V and I0 D 0.5 A Core loss
be connected across the secondary winding (i.e. iron loss) D 400 D V1 I0 cos 0 .
without the kVA rating being exceeded, and i.e. 400 D 24000.5 cos 0
(c) the primary current.
[(a) 50 A (b) 4  (c) 4.17 A] 400
Hence cos 0 D D 0.3333
24000.5
11 A 20  resistance is connected across the
secondary winding of a single-phase power 0 D cos1 0.3333 D 70.53°
transformer whose secondary voltage is The no-load phasor diagram is shown in Fig. 21.3
150 V. Calculate the primary voltage and Magnetising component,
the turns ratio if the supply current is 5 A, IM D I0 sin 0 D 0.5 sin 70.53° D 0.471 A.
neglecting losses. [225 V, 3:2] Core loss component, IC D I0 cos 0 D 0.5 cos 70.53°
D 0.167 A

TLFeBOOK
TRANSFORMERS 307

Figure 21.2

(b) Power factor at no load,

IC 0.3
cos 0 D D D 0.375
I0 0.8

(c) From the right-angled triangle in Fig. 21.2(b)


and using Pythagoras’ theorem, I20 D I2C C I2M
from which, magnetising current,
 p
IM D I20  I2C D 0.82  0.32 D 0.74 A

Now try the following exercise

Exercise 115 Further problems on the


no-load phasor diagram
Figure 21.3
1 A 500 V/100 V, single-phase transformer takes
a full load primary current of 4 A. Neglecting
losses, determine (a) the full load secondary
Problem 8. A transformer takes a current of current, and (b) the rating of the transformer.
0.8 A when its primary is connected to a 240 [(a) 20 A (b) 2 kVA]
volt, 50 Hz supply, the secondary being on
open circuit. If the power absorbed is 2 A 3300 V/440 V, single-phase transformer
72 watts, determine (a) the iron loss current, takes a no-load current of 0.8 A and the
(b) the power factor on no-load, and (c) the iron loss is 500 W. Draw the no-load phasor
magnetising current. diagram and determine the values of the
magnetising and core loss components of the
no-load current.
I0 D 0.8 A and V D 240 V [0.786 A, 0.152 A]
(a) Power absorbed D total core loss D 72 D 3 A transformer takes a current of 1 A when
V1 I0 cos 0 . Hence 72 D 240I0 cos 0 and iron its primary is connected to a 300 V, 50 Hz
loss current, Ic D I0 cos 0 D 72/240 D 0.30 A supply, the secondary being on open-circuit.

TLFeBOOK
308 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY

If the power absorbed is 120 watts, calculate


Problem 9. A 100 kVA, 4000 V/200 V,
(a) the iron loss current, (b) the power factor
50 Hz single-phase transformer has 100
on no-load, and (c) the magnetising current.
secondary turns. Determine (a) the primary
[(a) 0.4 A (b) 0.4 (c) 0.92 A]
and secondary current, (b) the number of
primary turns, and (c) the maximum value of
the flux.

21.4 E.m.f. equation of a transformer


V1 D 4000 V, V2 D 200 V, f D 50 Hz, N2 D 100
The magnetic flux 8 set up in the core of a trans- turns
former when an alternating voltage is applied to its
primary winding is also alternating and is sinusoidal.
Let 8m be the maximum value of the flux and f (a) Transformer rating D V1 I1 D V2 I2 D 1 00 000 VA
be the frequency of the supply. The time for 1 cycle Hence primary current,
of the alternating flux is the periodic time T, where
T D 1/fseconds 1 00 000 1 00 000
The flux rises sinusoidally from zero to its max- I1 D D D 25 A
imum value in (1/4) cycle, and the time for (1/4) V1 4 000
cycle is 1/4f seconds. Hence the average rate of
change of flux D 8m /1/4f D 4 f8m Wb/s, and and secondary current,
since 1 Wb/s D 1 volt, the average e.m.f. induced in
each turn D 4 f8m volts. As the flux 8 varies sinu- 1 00 000 1 00 000
soidally, then a sinusoidal e.m.f. will be induced in I2 D D D 500 A
each turn of both primary and secondary windings. V 2 200
For a sine wave,
V1 N1
r.m.s. value (b) From equation (3), D from which, pri-
form factor D V 2 N2
average value mary turns,
D 1.11 (see Chapter 14)    
V1 4000
Hence r.m.s. value D form factor ð average value D N1 D N2  D 100 D 2000 turns
V2 200
1.11 ð average value Thus r.m.s. e.m.f. induced in
each turn
(c) From equation (5), E2 D 4.44 f8m N2 from
D 1.11 ð 4 f8m volts which, maximum flux,
D 4.44 f8m volts
E
8m D
Therefore, r.m.s. value of e.m.f. induced in primary, 4.44 fN2
200
E1 = 4.44 f 8m N1 volts 4 D (assuming E2 D V2 
4.4450100

and r.m.s. value of e.m.f. induced in secondary, D 9.01 × 10−3 Wb or 9.01 mWb

[Alternatively, equation (4) could have been used,


E2 = 4.44 f 8m N2 volts 5 where

Dividing equation (4) by equation (5) gives:


    E1 D 4.44 f8m N1 from which,
E1 N1 4000
D , 8m D (assuming E1 D V1 
E2 N2 4.44502000
as previously obtained in Section 21.2 D 9.01 mWb as above]

TLFeBOOK
TRANSFORMERS 309

Problem 10. A single-phase, 50 Hz Problem 12. A 4500 V/225 V, 50 Hz


transformer has 25 primary turns and 300 single-phase transformer is to have an
secondary turns. The cross-sectional area of approximate e.m.f. per turn of 15 V and
the core is 300 cm2 . When the primary operate with a maximum flux of 1.4 T.
winding is connected to a 250 V supply, Calculate (a) the number of primary and
determine (a) the maximum value of the flux secondary turns and (b) the cross-sectional
density in the core, and (b) the voltage area of the core.
induced in the secondary winding.

(a) From equation (4), E1 E2


(a) E.m.f. per turn D D D 15
e.m.f. E1 D 4.44 f8m N1 volts N1 N2
i.e. 250 D 4.44508m (25) from which, maxi-
mum flux density, E1 4500
Hence primary turns, N1 D D D 300
250 15 15
8m D Wb D 0.04505 Wb
4.445025 E2 255
and secondary turns, N2 D D D 15
However, 8m D Bm ðA, where Bm D maximum 15 15
flux density in the core and A D cross-sectional
area of the core (see Chapter 7). Hence (b) E.m.f. E1 D 4.44 f8m N1 from which,
Bm ð 300 ð 104 D 0.04505 from which,
E1 4500
8m D D 0.0676 Wb
0.04505 4.44fN1 4.4450300
maximum flux density, Bm D
300 ð 104
Now flux, 8m D Bm ð A, where A is the cross-
D 1.50 T
  sectional area of the core,
V1 N1 N2
(b) D from which, V2 D V1 i.e.    
V2 N2 N1 8m 0.0676
voltage induced in the secondary winding, hence area, A D D
Bm 1.4
 
300 D 0.0483 m2 or 483 cm2
V2 D 250 D 3000 V or 3 kV
25
Now try the following exercise
Problem 11. A single-phase 500 V/100 V,
50 Hz transformer has a maximum core flux
density of 1.5 T and an effective core
cross-sectional area of 50 cm2 . Determine the Exercise 116 Further problems on the
number of primary and secondary turns. transformer e.m.f. equation
1 A 60 kVA, 1600 V/100 V, 50 Hz, single-phase
The e.m.f. equation for a transformer is E D transformer has 50 secondary windings. Cal-
4.44 f8m N and maximum flux, 8m D B ð A D culate (a) the primary and secondary current,
1.550 ð 104  D 75 ð 104 Wb (b) the number of primary turns, and (c) the
Since E1 D 4.44 f8m N1 then primary turns, maximum value of the flux
[(a) 37.5 A, 600 A (b) 800 (c) 9.0 mWb]
E1 500
N1 D D 2 A single-phase, 50 Hz transformer has 40 pri-
4.44 f8m 4.445075 ð 104 
mary turns and 520 secondary turns. The
D 300 turns cross-sectional area of the core is 270 cm2 .
Since E2 D 4.4 f8m N2 then secondary turns, When the primary winding is connected to a
E2 100 300 volt supply, determine (a) the maximum
N2 D D value of flux density in the core, and (b) the
4.44 f8m 4.445075 ð 104  voltage induced in the secondary winding
D 60 turns [(a) 1.25 T (b) 3.90 kV]

TLFeBOOK
310 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY

3 A single-phase 800 V/100 V, 50 Hz trans- However this does not happen since reduction of the
former has a maximum core flux density of core flux reduces E1 , hence a reflected increase in
1.294 T and an effective cross-sectional area primary current I01 occurs which provides a restoring
of 60 cm2 . Calculate the number of turns on m.m.f. Hence at all loads, primary and secondary
the primary and secondary windings. m.m.f.’s are equal, but in opposition, and the core
[464, 58] flux remains constant. I01 is sometimes called the
‘balancing’ current and is equal, but in the opposite
4 A 3.3 kV/110 V, 50 Hz, single-phase trans- direction, to current I2 as shown in Fig. 21.4. I0 ,
former is to have an approximate e.m.f. per shown at a phase angle 0 to V1 , is the no-load
turn of 22 V and operate with a maximum current of the transformer (see Section 21.3)
flux of 1.25 T. Calculate (a) the number of The phasor sum of I01 and I0 gives the supply
primary and secondary turns, and (b) the cross- current I1 and the phase angle between V1 and I1 is
sectional area of the core shown as 1
[(a) 150, 5 (b) 792.8 cm2 ]

Problem 13. A single-phase transformer has


2000 turns on the primary and 800 turns on
the secondary. Its no-load current is 5 A at a
power factor of 0.20 lagging. Assuming the
21.5 Transformer on-load phasor volt drop in the windings is negligible,
diagram determine the primary current and power
factor when the secondary current is 100 A at
If the voltage drop in the windings of a transformer a power factor of 0.85 lagging.
are assumed negligible, then the terminal voltage V2
is the same as the induced e.m.f. E2 in the secondary.
Similarly, V1 D E1 . Assuming an equal number Let I01 be the component of the primary current
of turns on primary and secondary windings, then which provides the restoring m.m.f. Then
E1 D E2 , and let the load have a lagging phase
angle 2 I01 N1 D I2 N2
i.e. I01 2000 D 100800
100800
from which, I01 D
2000
D 40 A

If the power factor of the secondary is 0.85, then


cos 2 D 0.85, from which, 2 D cos1 0.85 D 31.8°
If the power factor on no-load is 0.20, then
cos 0 D 0.2 and 0 D cos1 0.2 D 78.5°
In the phasor diagram shown in Fig. 21.5, I2 D
100 A is shown at an angle of  D 31.8° to V2 and
I01 D 40 A is shown in anti-phase to I2
The no-load current I0 D 5 A is shown at an angle
of 0 D 78.5° to V1 . Current I1 is the phasor sum
of I01 and I0 , and by drawing to scale, I1 D 44 A
and angle 1 D 37° .
Figure 21.4 By calculation,

I1 cos 1 D 0a C 0b
In the phasor diagram of Fig. 21.4, current I2
lags V2 by angle 2 . When a load is connected D I0 cos 0 C I01 cos 2
across the secondary winding a current I2 flows D 50.2 C 400.85
in the secondary winding. The resulting secondary
e.m.f. acts so as to tend to reduce the core flux. D 35.0 A

TLFeBOOK
TRANSFORMERS 311

Fig. 21.6. The low and high voltage windings


are wound as shown to reduce leakage flux.

Figure 21.5

and I1 sin 1 D 0c C 0d
D I0 sin 0 C I01 sin 2
Figure 21.6
D 5 sin 78.5° C 40 sin 31.8°
D 25.98 A (ii) For power transformers, rated possibly at
p several MVA and operating at a frequency of
Hence the magnitude of I1 D C
35.02 D
25.982 50 Hz in Great Britain, the core material used
43.59 A and tan 1 D 25.98/35.0 from which, is usually laminated silicon steel or stalloy,
f1 D tan1 25.98/35.0 D 36.59° Hence the the laminations reducing eddy currents and
power factor of the primary D cos 1 D cos 36.59° D the silicon steel keeping hysteresis loss to a
0.80 minimum.
Large power transformers are used in the
Now try the following exercise main distribution system and in industrial
supply circuits. Small power transformers have
many applications, examples including welding
Exercise 117 A further problem on the and rectifier supplies, domestic bell circuits,
transformer on-load imported washing machines, and so on.
1 A single-phase transformer has 2400 turns on (iii) For audio frequency (a.f.) transformers, rated
the primary and 600 turns on the secondary. from a few mVA to no more than 20 VA, and
Its no-load current is 4 A at a power factor of operating at frequencies up to about 15 kHz, the
0.25 lagging. Assuming the volt drop in the small core is also made of laminated silicon
windings is negligible, calculate the primary steel. A typical application of a.f. transformers
current and power factor when the secondary is in an audio amplifier system.
current is 80 A at a power factor of 0.8 lagging.
[23.26 A, 0.73] (iv) Radio frequency (r.f.) transformers, operat-
ing in the MHz frequency region have either
an air core, a ferrite core or a dust core. Ferrite
is a ceramic material having magnetic proper-
ties similar to silicon steel, but having a high
21.6 Transformer construction resistivity. Dust cores consist of fine particles
of carbonyl iron or permalloy (i.e. nickel and
(i) There are broadly two types of single-phase iron), each particle of which is insulated from
double-wound transformer constructions – the its neighbour. Applications of r.f. transformers
core type and the shell type, as shown in are found in radio and television receivers.

TLFeBOOK
312 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY

(v) Transformer windings are usually of enamel- the transformer. Resistance R2 in Fig. 21.8 can be
insulated copper or aluminium. replaced by inserting an additional resistance R20 in
the primary circuit such that the power absorbed in
(vi) Cooling is achieved by air in small transform- R20 when carrying the primary current is equal to that
ers and oil in large transformers. in R2 due to the secondary current, i.e.
I21 R20 D I22 R2
 2  2
21.7 Equivalent circuit of a 0 I2 V1
transformer from which, R2 D R2 D R2
I1 V2
Figure 21.7 shows an equivalent circuit of a trans- Then the total equivalent resistance in the primary
former. R1 and R2 represent the resistances of the circuit Re is equal to the primary and secondary
primary and secondary windings and X1 and X2 rep- resistances of the actual transformer.
resent the reactances of the primary and secondary Hence Re D R1 C R20
windings, due to leakage flux.
The core losses due to hysteresis and eddy cur-  2
V1
rents are allowed for by resistance R which takes a i.e. Re = R1 + R2 6
current IC , the core loss component of the primary V2
current. Reactance X takes the magnetising compo-
nent Im . In a simplified equivalent circuit shown in By similar reasoning, the equivalent reactance in the
Fig. 21.8, R and X are omitted since the no-load primary circuit is given by Xe D X1 C X02
current I0 is normally only about 3–5 per cent of
the full load primary current.  2
V1
It is often convenient to assume that all of the i.e. Xe = X1 + X2 7
resistance and reactance as being on one side of V2

Figure 21.7

Figure 21.8

TLFeBOOK
TRANSFORMERS 313

The equivalent impedance Ze of the primary and (b) From equation (7), equivalent reactance,
secondary windings referred to the primary is  2
V1
given by Xe D X1 C X2
V2
  
Ze = Re2 + Xe2 8 600 2
i.e. Xe D 1.0 C 0.04 D 1.64 Z
150
If e is the phase angle between I1 and the volt drop (c) From equation (8), equivalent impedance,
I1 Ze then  p
Ze D Re2 C X2e D 0.412 C 1.642 D 1.69 Z
Re (d) From equation (9),
cos fe = 9
Ze Re 0.41
cos e D D
Ze 1.69
The simplified equivalent circuit of a transformer is 0.41
shown in Fig. 21.9 Hence fe D cos1 D 75.96°
1.69

Problem 14. A transformer has 600 primary


turns and 150 secondary turns. The primary Now try the following exercise
and secondary resistances are 0.25  and
0.01  respectively and the corresponding
leakage reactances are 1.0  and 0.04  Exercise 118 A further problem on the
respectively. Determine (a) the equivalent equivalent circuit of a transformer
resistance referred to the primary winding, 1 A transformer has 1200 primary turns and 200
(b) the equivalent reactance referred to the secondary turns. The primary and secondary
primary winding, (c) the equivalent resistance’s are 0.2  and 0.02  respectively
impedance referred to the primary winding, and the corresponding leakage reactance’s
and (d) the phase angle of the impedance. are 1.2  and 0.05  respectively. Calculate
(a) the equivalent resistance, reactance and
(a) From equation (6), equivalent resistance impedance referred to the primary winding,
and (b) the phase angle of the impedance.
 2 [(a) 0.92 , 3.0 , 3.14  (b) 72.95° ]
V1
Re D R1 C R2
V2
 
600 2
i.e. Re D 0.25 C 0.01
150 21.8 Regulation of a transformer
N1 V1 When the secondary of a transformer is loaded,
D 0.41 Z since D the secondary terminal voltage, V2 , falls. As the
N2 V2

Figure 21.9

TLFeBOOK
314 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY

power factor decreases, this voltage drop increases. i.e. 6 D 240  V2


This is called the regulation of the transformer
and it is usually expressed as a percentage of from which, load voltage, V2 D 2406 D 234 volts
the secondary no-load voltage, E2 . For full-load
conditions:
Now try the following exercise
 
E2 − V2
Regulation = × 100% 10
E2
Exercise 119 Further problems on
regulation
The fall in voltage, (E2  V2 ), is caused by the 1 A 6 kVA, 100 V/500 V, single-phase trans-
resistance and reactance of the windings. Typical former has a secondary terminal voltage of
values of voltage regulation are about 3% in small 487.5 volts when loaded. Determine the reg-
transformers and about 1% in large transformers. ulation of the transformer. [2.5%]
2 A transformer has an open circuit voltage
Problem 15. A 5 kVA, 200 V/400 V, of 110 volts. A tap-changing device operates
single-phase transformer has a secondary when the regulation falls below 3%. Calculate
terminal voltage of 387.6 volts when loaded. the load voltage at which the tap-changer oper-
Determine the regulation of the transformer. ates.
[106.7 volts]
From equation (10):
⎛ ⎞
No load secondary voltage 
⎜ terminal voltage on load ⎟ 21.9 Transformer losses and efficiency
regulation D ⎝ ⎠100%
no load secondary voltage There are broadly two sources of losses in trans-
  formers on load, these being copper losses and iron
400  387.6 losses.
D ð 100%
400 (a) Copper losses are variable and result in a heat-
 
12.4 ing of the conductors, due to the fact that they
D ð 100% possess resistance. If R1 and R2 are the primary
400
and secondary winding resistances then the total
D 3.1% copper loss is I21 R1 C I22 R2
(b) Iron losses are constant for a given value of
Problem 16. The open circuit voltage of a frequency and flux density and are of two
transformer is 240 V. A tap changing device types – hysteresis loss and eddy current loss.
is set to operate when the percentage (i) Hysteresis loss is the heating of the core as
regulation drops below 2.5%. Determine the a result of the internal molecular structure
load voltage at which the mechanism reversals which occur as the magnetic flux
operates. alternates. The loss is proportional to the
area of the hysteresis loop and thus low loss
⎛ ⎞ nickel iron alloys are used for the core since
No load secondary voltage their hysteresis loops have small areas.(See
⎜ terminal voltage on load ⎟
Regulation D ⎝ ⎠100% Chapters 7)
no load secondary voltage
(ii) Eddy current loss is the heating of the
core due to e.m.f.’s being induced not only
  in the transformer windings but also in the
240  V2
Hence 2.5 D ð 100% core. These induced e.m.f.’s set up circulat-
240 ing currents, called eddy currents. Owing to
2.5240 the low resistance of the core, eddy currents
∴ D 240  V2 can be quite considerable and can cause a
100

TLFeBOOK
TRANSFORMERS 315

large power loss and excessive heating of the Half full-load power output D 1/22000.85
core. Eddy current losses can be reduced by D 85 kW.
increasing the resistivity of the core mate- Copper loss (or I2 R loss) is proportional to cur-
rial or, more usually, by laminating the core rent squared. Hence the copper loss at half full-load
(i.e. splitting it into layers or leaves) when 2
is: 12 1500 D 375 W
very thin layers of insulating material can Iron loss D 1000 W (constant)
be inserted between each pair of laminations. Total losses D 375C1000 D 1375 W or 1.375 kW.
This increases the resistance of the eddy cur- Input power at half full-load
rent path, and reduces the value of the eddy D output power at half full-load C losses
current. D 85 C 1.375 D 86.375 kW. Hence
Transformer efficiency,
losses
output power input power - losses efficiency D 1 
D D input power
input power input power  
1.375
D 1
losses 86.375
i.e. h=1− 11
input power D 1  0.01592
D 0.9841 or 98.41%
and is usually expressed as a percentage. It is not
uncommon for power transformers to have efficien-
cies of between 95% and 98% Problem 19. A 400 kVA transformer has
Output power D V2 I2 cos 2 . a primary winding resistance of 0.5  and
Total losses D copper loss C iron losses, a secondary winding resistance of 0.001 .
and input power D output power C losses The iron loss is 2.5 kW and the primary and
secondary voltages are 5 kV and 320 V respec-
Problem 17. A 200 kVA rated transformer tively. If the power factor of the load is 0.85,
has a full-load copper loss of 1.5 kW and an determine the efficiency of the transformer
iron loss of 1 kW. Determine the transformer (a) on full load, and (b) on half load.
efficiency at full load and 0.85 power factor.
(a) Rating D 400 kVA D V1 I1 D V2 I2 . Hence
output power primary current,
Efficiency, D
input power
400 ð 103 400 ð 103
input power  losses I1 D D D 80 A
D V1 5000
input power
and secondary current,
losses
D1
input power 400 ð 103 400 ð 103
I2 D D D 1250 A
Full-load output power D VI cos  D 200 0.85 V2 320
D 170 kW. Total copper loss D I21 R1 C I22 R2 , (where
Total losses D 1.5 C 1.0 D 2.5 kW R1 D 0.5  and R2 D 0.001 
Input power D output power C losses
D 170 C 2.5 D 172.5 kW.
  D 802 0.5 C 12502 0.001
2.5
Hence efficiency D 1  D 1  0.01449 D 3200 C 1562.5 D 4762.5 watts
172.5
On full load, total loss D copper lossCiron loss
D 0.9855 or 98.55%
D 4762.5 C 2500 D 7262.5 W D 7.2625 kW
Problem 18. Determine the efficiency of
the transformer in Problem 17 at half Total output power on full load
full-load and 0.85 power factor.
D V2 I2 cos 2 D 400 ð 103 0.85 D 340 kW

TLFeBOOK
316 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY

Input power D output power C losses (b) Total loss at maximum efficiency
D 340 kW C 7.2625 kW D 347.2625 kW
D 2 ð 2.5 D 5 kW
 
losses Output power D 395.5 kVA ð p.f.
Efficiency,  D 1  ð 100%
input power
  D 395.5 ð 0.75 D 296.625 kW
7.2625
D 1 ð 100% Input power D output power C losses
347.2625
D 296.625 C 5 D 301.625 kW
D 97.91%
Maximum efficiency,
(b) Since the copper loss varies as the square of the  
current, then total copper loss on half load losses
2 D 1 ð 100%
D 4762.5 ð 12 D 1190.625 W. Hence total input power
loss on half load D 1190.625 C 2500 D  
5
3690.625 W or 3.691 kW. D 1 ð 100% D 98.34%
Output power on half full load D 12 340 301.625
D 170 kW.
Input power on half full load
D output power C losses Now try the following exercise

D 170 kW C 3.691 kW
Exercise 120 Further problems on losses
D 173.691 kW and efficiency
Hence efficiency at half full load, 1 A single-phase transformer has a voltage ratio
  of 6:1 and the h.v. winding is supplied at
losses 540 V. The secondary winding provides a full
D 1 ð 100%
input power load current of 30 A at a power factor of 0.8
  lagging. Neglecting losses, find (a) the rating
3.691 of the transformer, (b) the power supplied to
D 1 ð 100% D 97.87%
173.691 the load, (c) the primary current
[(a) 2.7 kVA (b) 2.16 kW (c) 5 A]
2 A single-phase transformer is rated at 40 kVA.
Maximum efficiency The transformer has full-load copper losses of
It may be shown that the efficiency of a transformer 800 W and iron losses of 500 W. Determine
is a maximum when the variable copper loss (i.e. the transformer efficiency at full load and 0.8
I21 R1 C I22 R2 ) is equal to the constant iron losses. power factor [96.10%]
3 Determine the efficiency of the transformer
Problem 20. A 500 kVA transformer has a in problem 2 at half full-load and 0.8 power
full load copper loss of 4 kW and an iron factor [95.81%]
loss of 2.5 kW. Determine (a) the output kVA 4 A 100 kVA, 2000 V/400 V, 50 Hz, single-phase
at which the efficiency of the transformer is a transformer has an iron loss of 600 W and a
maximum, and (b) the maximum efficiency, full-load copper loss of 1600 W. Calculate its
assuming the power factor of the load is 0.75 efficiency for a load of 60 kW at 0.8 power
factor. [97.56%]
(a) Let x be the fraction of full load kVA at which 5 Determine the efficiency of a 15 kVA trans-
the efficiency is a maximum. The correspond- former for the following conditions:
ing total copper loss D 4 kWx 2 . At maxi- (i) full-load, unity power factor
mum efficiency, copper loss D iron loss. Hence (ii) 0.8 full-load, unity power factor
4x 2 D
p 2.5 from which x D 2.5/4 and
2 (iii) half full-load, 0.8 power factor
x D 2.5/4 D 0.791. Assume that iron losses are 200 W and the full-
Hence the output kVA at maximum load copper loss is 300 W
efficiency D 0.791 ð 500 D 395.5 kVA. [(a) 96.77% (ii) 96.84% (iii) 95.62%]

TLFeBOOK
TRANSFORMERS 317

6 A 300 kVA transformer has a primary wind-


ing resistance of 0.4  and a secondary
winding resistance of 0.0015 . The iron
loss is 2 kW and the primary and secondary
voltages are 4 kV and 200 V respectively. If
the power factor of the load is 0.78, determine
the efficiency of the transformer (a) on full
load, and (b) on half load.
[(a) 96.84% (b) 97.17%] Figure 21.10
7 A 250 kVA transformer has a full load copper
loss of 3 kW and an iron loss of 2 kW. Calcu- Thus the equivalent input resistance R1 of the
late (a) the output kVA at which the efficiency transformer is given by:
of the transformer is a maximum, and (b) the  
maximum efficiency, assuming the power fac- N1
tor of the load is 0.80 V2
V1 N2
[(a) 204.1 kVA (b) 97.61%] R1 D D  
I1 N2
I2
N1
 2    2
N1 V2 N1
21.10 Resistance matching D D RL
N2 I2 N2
Varying a load resistance to be equal, or almost
equal, to the source internal resistance is called  2
matching. Examples where resistance matching is N1
i.e. R1 = RL
important include coupling an aerial to a transmitter N2
or receiver, or in coupling a loudspeaker to an
amplifier, where coupling transformers may be used Hence by varying the value of the turns ratio,
to give maximum power transfer. the equivalent input resistance of a transformer can
With d.c. generators or secondary cells, the inter- be ‘matched’ to the internal resistance of a load to
nal resistance is usually very small. In such cases, achieve maximum power transfer.
if an attempt is made to make the load resistance as
small as the source internal resistance, overloading
of the source results. Problem 21. A transformer having a turns
A method of achieving maximum power trans- ratio of 4:1 supplies a load of resistance
fer between a source and a load (see section 13.9, 100 . Determine the equivalent input
page 179), is to adjust the value of the load resis- resistance of the transformer.
tance to ‘match’ the source internal resistance. A
transformer may be used as a resistance matching From above, the equivalent input resistance,
device by connecting it between the load and the

source. N1 2
The reason why a transformer can be used for this R1 D RL
N2
is shown below. With reference to Fig. 21.10:  2
4
V2 V1 D 100 D 1600 Z
RL D and R1 D 1
I2 I1
For an ideal transformer, Problem 22. The output stage of an
  amplifier has an output resistance of 112 .
N1
V1 D V2 Calculate the optimum turns ratio of a
N2 transformer which would match a load
  resistance of 7  to the output resistance of
N2
and I1 D I2 the amplifier.
N1

TLFeBOOK
318 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY

Figure 21.12
Figure 21.11
(a) Turns ratio
       
The circuit is shown in Fig. 21.11 N1 V1 220 1
The equivalent input resistance, R1 of the trans- D D D
N2 V2 1760 8
former needs to be 112  for maximum power
transfer. Equivalent input resistance of the transformer.
 2  2
 2 N1 1
R1 D
N1
RL R1 D RL D 1.28 ð 103  D 20 
N2 N2 8
 2 Total input resistance,
N1 R1 112
Hence D D D 16 RIN D R C R1 D 2 C 20 D 22 
N2 RL 7
N1 p Primary current,
i.e. D 16 D 4
N2 V1 220
I1 D D D 10 A
RIN 22
Hence the optimum turns ratio is 4:1
(b) For an ideal transformer
V1 I2
Problem 23. Determine the optimum value D
of load resistance for maximum power V2 I1
transfer if the load is connected to an from which,
amplifier of output resistance 150  through    
V1 220
a transformer with a turns ratio of 5:1 I2 D I1 D 10 D 1.25 A
V2 1760
The equivalent input resistance R1 of the transformer Power dissipated in load resistor RL ,
needs to be 150  for maximum power transfer. P D I22 RL D 1.252 1.28 ð 103 
 2
N1 D 2000 watts or 2 kW
R1 D RL
N2
 2
N2 Problem 25. An a.c. source of 24 V and
from which, RL D R1
N1 internal resistance 15 k is matched to a
1 2 load by a 25:1 ideal transformer. Determine
D 150 5 D 6 Z (a) the value of the load resistance and
(b) the power dissipated in the load.
Problem 24. A single-phase, 220 V/1760 V
ideal transformer is supplied from a 220 V The circuit diagram is shown in Fig. 21.13
source through a cable of resistance 2 . If
the load across the secondary winding is (a) For maximum power transfer R1 needs to be
1.28 k determine (a) the primary current equal to 15 k.
flowing and (b) the power dissipated in the  2
load resistor. N1
R1 D RL
N2
The circuit diagram is shown in Fig. 21.12 from which, load resistance,

TLFeBOOK
TRANSFORMERS 319

(b) the power dissipated in the load resistance.


[(a) 30 A (b) 4.5 kW]
5 A load of resistance 768  is to be matched
to an amplifier which has an effective output
resistance of 12 . Determine the turns ratio
of the coupling transformer. [1:8]
6 An a.c. source of 20 V and internal resistance
Figure 21.13 20 k is matched to a load by a 16:1 single-
 2  2 phase transformer. Determine (a) the value of
N2 1 the load resistance and (b) the power dissi-
RL D R1 D 15 000 D 24 Z pated in the load.
N1 25
[(a) 78.13  (b) 5 mW]
(b) The total input resistance when the source is
connected to the matching transformer is RIN C
R1 i.e. 15 k C 15 k D 30 k.
Primary current, 21.11 Auto transformers
V 24 An auto transformer is a transformer which has
I1 D D D 0.8 mA part of its winding common to the primary and
30000 30000
secondary circuits. Fig. 21.14(a) shows the circuit
N1 /N2 D I2 /I1 from which, I2 D I1 N1 /N2  D for a double-wound transformer and Fig. 21.14(b)
0.8 ð 103 25/1 D 20 ð 103 A. that for an auto transformer. The latter shows that
Power dissipated in the load RL , the secondary is actually part of the primary, the
current in the secondary being (I2  I1 ). Since
P D I22 RL D 20 ð 103 2 24 the current is less in this section, the cross-sectional
area of the winding can be reduced, which reduces
D 9600 ð 106 W D 9.6 mW the amount of material necessary.

Now try the following exercise

Exercise 121 Further problems on


resistance matching
1 A transformer having a turns ratio of
8:1 supplies a load of resistance 50 . Figure 21.14
Determine the equivalent input resistance of
the transformer. [3.2 k] Figure 21.15 shows the circuit diagram symbol
2 What ratio of transformer is required to make for an auto transformer.
a load of resistance 30  appear to have a
resistance of 270 ? [3:1]
3 Determine the optimum value of load
resistance for maximum power transfer if the Figure 21.15
load is connected to an amplifier of output
resistance 147  through a transformer with Problem 26. A single-phase auto
a turns ratio of 7:2 [12 ] transformer has a voltage ratio 320 V:250 V
4 A single-phase, 240 V/2880 V ideal trans- and supplies a load of 20 kVA at 250 V.
former is supplied from a 240 V source Assuming an ideal transformer, determine
through a cable of resistance 3 . If the the current in each section of the winding.
load across the secondary winding is 720 
determine (a) the primary current flowing and Rating D 20 kVA D V1 I1 D V2 I2 .

TLFeBOOK
320 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY

Hence primary current, 2N1 I1 2N2 I1


D 
20 ð 103 20 ð 103 2N1 I1 2N1 I1
I1 D D D 62.5 A N2
V1 320 D1
N1
and secondary current,
If N2 /N1  D x then
20 ð 103 20 ð 103
I2 D D D 80 A
V2 250
Hence current in common part of the winding (volume of copper in an auto transformer)
D 80  62.5 D 17.5 A = .1 − x / (volume of copper in a double-
The current flowing in each section of the wound transformer) .12/
transformer is shown in Fig. 21.16

If, say, x D 4/5 then (volume of copper in auto


transformer)
(volume of copper in a
D 1  45
double-wound transformer)
D 1
5
(volume in double-wound transformer)

i.e. a saving of 80%.


Similarly, if x D 1/4, the saving is 25 per cent,
Figure 21.16
and so on. The closer N2 is to N1 , the greater the
saving in copper.

Saving of copper in an auto transformer


For the same output and voltage ratio, the auto Problem 27. Determine the saving in the
transformer requires less copper than an ordinary volume of copper used in an auto transformer
double-wound transformer. This is explained below. compared with a double-wound transformer
The volume, and hence weight, of copper required for (a) a 200 V:150 V transformer, and (b) a
in a winding is proportional to the number of turns 500 V:100 V transformer.
and to the cross-sectional area of the wire. In turn
this is proportional to the current to be carried, i.e.
volume of copper is proportional to NI. (a) For a 200 V:150 V transformer,
Volume of copper in an auto transformer V2 150
xD D D 0.75
/ N1  N2 I1 C N2 I2  I1  V1 200
see Fig. 21.14(b) Hence from equation (12), (volume of copper in
auto transformer)
/ N1 I1  N2 I1 C N2 I2  N2 I1
(volume of copper in
/ N1 I1 C N2 I2  2N2 I1 D 1  0.75
double-wound transformer)
/ 2N1 I1  2N2 I1 (since N2 I2 D N1 I1  (volume of copper in
D 0.25
Volume of copper in a double-wound transformer double-wound transformer)

/ N1 I1 C N2 I2 / 2N1 I1 (of copper in a


D 25%
double-wound transformer)
(again, since N2 I2 D N1 I1 ). Hence Hence the saving is 75%
volume of copper in (b) For a 500 V:100 V transformer,
an auto transformer 2N1 I1  2N2 I1
D V2 100
volume of copper in a 2N1 I1 xD D D 0.2
double-wound transformer V1 500

TLFeBOOK
TRANSFORMERS 321

Hence, (volume of copper in auto transformer) for interconnecting systems that are operating at
approximately the same voltage.
(volume of copper in
D 1  0.2
double-wound transformer)
D 0.8 (volume in double-wound transformer) 21.12 Isolating transformers
D 80% of copper in a double-wound transformer Transformers not only enable current or voltage
Hence the saving is 20%. to be transformed to some different magnitude
but provide a means of isolating electrically one
part of a circuit from another when there is
Now try the following exercise no electrical connection between primary and
secondary windings. An isolating transformer is
a 1:1 ratio transformer with several important
applications, including bathroom shaver-sockets,
Exercise 122 Further problems on the portable electric tools, model railways, and so on.
auto-transformer
1 A single-phase auto transformer has a volt-
age ratio of 480 V:300 V and supplies a load 21.13 Three-phase transformers
of 30 kVA at 300 V. Assuming an ideal trans-
former, calculate the current in each section of Three-phase double-wound transformers are mainly
the winding. used in power transmission and are usually of the
[I1 D 62.5 A, I2 D 100 A, (I2  I1  D 37.5 A] core type. They basically consist of three pairs
of single-phase windings mounted on one core, as
2 Calculate the saving in the volume of shown in Fig. 21.17, which gives a considerable
copper used in an auto transformer compared saving in the amount of iron used. The primary and
with a double-wound transformer for (a) secondary windings in Fig. 21.17 are wound on top
a 300 V:240 V transformer, and (b) a of each other in the form of concentric cylinders,
400 V:100 V transformer [(a) 80% (b) 25%] similar to that shown in Fig. 21.6(a). The windings
may be with the primary delta-connected and the
secondary star-connected, or star-delta, star-star or
Advantages of auto transformers delta-delta, depending on its use.
A delta-connection is shown in Fig. 21.18(a) and
The advantages of auto transformers over double-
a star-connection in Fig. 21.18(b).
wound transformers include:
1 a saving in cost since less copper is needed (see Problem 28. A three-phase transformer has
above) 500 primary turns and 50 secondary turns. If
2 less volume, hence less weight the supply voltage is 2.4 kV find the
3 a higher efficiency, resulting from lower I2 R secondary line voltage on no-load when the
losses windings are connected (a) star-delta, (b)
delta-star.
4 a continuously variable output voltage is achiev-
able if a sliding contact is used p
(a) For a star-connection, VL D 3 Vp (see Chap-
5 a smaller percentage voltage regulation.
ter 20). Primary phase voltage,
Disadvantages of auto transformers VL1 2400
Vp D p D p D 1385.64 volts.
The primary and secondary windings are not electri- 3 3
cally separate, hence if an open-circuit occurs in the For a delta-connection, VL D Vp . N1 /N2 D
secondary winding the full primary voltage appears V1 /V2 from which, secondary phase voltage,
across the secondary.
   
N2 50
Uses of auto transformers Vp2 D Vp1 D 1385.64
Auto transformers are used for reducing the voltage N1 500
when starting induction motors (see Chapter 23) and D 138.6 volts

TLFeBOOK
322 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY

Figure 21.17

Figure 21.18

(b) For a delta-connection, VL D Vp hence, primary


phase voltage Vp1 D 2.4 kV D 2400 volts.
Secondary phase voltage, Exercise 123 A further problem on the
    three-phase transformer
N2 50
Vp2 D Vp1 D 2400 D 240 volts 1 A three-phase transformer has 600 primary
N1 500
p turns and 150 secondary turns. If the supply
For a star-connection, VL Dp 3 Vp hence, the voltage is 1.5 kV determine the secondary line
secondary line voltage, VL2 D 3240 voltage on no-load when the windings are
D 416 volts. connected (a) delta-star (b) star-delta
[(a) 649.5 V (b) 216.5 V]

Now try the following exercise

TLFeBOOK
TRANSFORMERS 323

of ammeters giving full-scale deflections of 1 A, 2 A


21.14 Current transformers or 5 A.
For measuring currents in excess of about 100 A For very large currents the transformer core can
a current transformer is normally used. With a be mounted around the conductor or bus-bar. Thus
d.c. moving-coil ammeter the current required to the primary then has just one turn.
give full scale deflection is very small – typically It is very important to short-circuit the secondary
a few milliamperes. When larger currents are to be winding before removing the ammeter. This is
measured a shunt resistor is added to the circuit (see because if current is flowing in the primary,
Chapter 10). However, even with shunt resistors dangerously high voltages could be induced in the
added it is not possible to measure very large secondary should it be open-circuited.
currents. When a.c. is being measured a shunt cannot Current transformer circuit diagram symbols are
be used since the proportion of the current which shown in Fig. 21.20
flows in the meter will depend on its impedance,
which varies with frequency.
In a double-wound transformer:
I1 N2
D
I2 N1
Figure 21.20
from which,
 
N2 Problem 29. A current transformer has a
secondary current I2 = I1
N1 single turn on the primary winding and a
secondary winding of 60 turns. The
In current transformers the primary usually consists secondary winding is connected to an
of one or two turns whilst the secondary can have ammeter with a resistance of 0.15 . The
several hundred turns. A typical arrangement is resistance of the secondary winding is
shown in Fig. 21.19 0.25 . If the current in the primary winding
is 300 A, determine (a) the reading on the
ammeter, (b) the potential difference across
the ammeter and (c) the total load (in VA) on
the secondary.

(a) Reading on the ammeter,


   
N1 1
I2 D I1 D 300 D 5 A.
N2 60
(b) P.d. across the ammeter D I2 RA , (where RA is the
ammeter resistance D 50.15 D 0.75 volts.
(c) Total resistance of secondary circuit D
Figure 21.19 0.15 C 0.25 D 0.40 .
Induced e.m.f. in secondary D 50.40 D 2.0 V.
If, for example, the primary has 2 turns and the Total load on secondary D 2.05 D 10 VA.
secondary 200 turns, then if the primary current is
500 A,
    Now try the following exercise
N2 2
secondary current, I2 D I1 D 500
N1 200
Exercise 124 A further problem on the
D 5A current transformer
Current transformers isolate the ammeter from the 1 A current transformer has two turns on the
main circuit and allow the use of a standard range primary winding and a secondary winding of

TLFeBOOK
324 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY

260 turns. The secondary winding is connected Now try the following exercises
to an ammeter with a resistance of 0.2 .
The resistance of the secondary winding is
0.3 . If the current in the primary winding Exercise 125 Short answer questions on
is 650 A, determine (a) the reading on the transformers
ammeter, (b) the potential difference across 1 What is a transformer?
the ammeter, and (c) the total load in VA on
the secondary [(a) 5 A (b) 1 V (c) 7.5 VA] 2 Explain briefly how a voltage is induced in
the secondary winding of a transformer
3 Draw the circuit diagram symbol for a
transformer
21.15 Voltage transformers 4 State the relationship between turns and volt-
age ratios for a transformer
For measuring voltages in excess of about 500 V it 5 How is a transformer rated?
is often safer to use a voltage transformer. These
are normal double-wound transformers with a large 6 Briefly describe the principle of operation of
number of turns on the primary, which is connected a transformer
to a high voltage supply, and a small number of turns 7 Draw a phasor diagram for an ideal trans-
on the secondary. A typical arrangement is shown former on no-load
in Fig. 21.21
8 State the e.m.f. equation for a transformer
9 Draw an on-load phasor diagram for an ideal
transformer with an inductive load
10 Name two types of transformer construction
11 What core material is normally used for
power transformers
12 Name three core materials used in r.f. trans-
formers
13 State a typical application for (a) a.f. trans-
formers (b) r.f. transformers
Figure 21.21 14 How is cooling achieved in transformers?
15 State the expressions for equivalent resis-
Since tance and reactance of a transformer, referred
to the primary
V1 N1
D 16 Define regulation of a transformer
V2 N2
the secondary voltage, 17 Name two sources of loss in a transformer

V1 N2 18 What is hysteresis loss? How is it minimised


V2 D in a transformer?
V1
19 What are eddy currents? How may they be
Thus if the arrangement in Fig. 21.21 has 4000 reduced in transformers?
primary turns and 20 secondary turns then for a
voltage of 22 kV on the primary, the voltage on the 20 How is efficiency of a transformer calcu-
secondary, lated?
   
N2 20 21 What is the condition for maximum effi-
V2 D V1 D 22 000 D 110 volts ciency of a transformer?
N1 4000
22 What does ‘resistance matching’ mean?

TLFeBOOK
TRANSFORMERS 325

23 State a practical application where matching 1.7A


would be used
24 Derive a formula for the equivalent resistance
of a transformer having a turns ratio of
N1 : N2 and load resistance RL
3.3A
25 What is an auto transformer? V1 p

26 State three advantages and one disadvantage


of an auto transformer compared with a V2
double-wound transformer
27 In what applications are auto transformers Q
used?
Figure 21.22
28 What is an isolating transformer? Give two
applications
4 A 440 V/110 V transformer has 1000 turns on
29 Describe briefly the construction of a three- the primary winding. The number of turns on
phase transformer the secondary is:
30 For what reason are current transformers (a) 550 (b) 250 (c) 4000 (d) 25
used? 5 An advantage of an auto-transformer is that:
31 Describe how a current transformer operates (a) it gives a high step-up ratio
(b) iron losses are reduced
32 For what reason are voltage transformers (c) copper loss is reduced
used? (d) it reduces capacitance between turns
33 Describe how a voltage transformer operates 6 A 1 kV/250 V transformer has 500 turns on
the secondary winding. The number of turns
on the primary is:
(a) 2000 (b) 125 (c) 1000 (d) 250
Exercise 126 Multi-choice questions on 7 The core of a transformer is laminated to:
transformers (Answers on page 376) (a) limit hysteresis loss
(b) reduce the inductance of the windings
1 The e.m.f. equation of a transformer of (c) reduce the effects of eddy current loss
secondary turns N2 , magnetic flux density (d) prevent eddy currents from occurring
Bm , magnetic area of core a, and operating
at frequency f is given by: 8 The power input to a mains transformer is
(a) E2 D 4.44N2 Bm af volts 200 W. If the primary current is 2.5 A, the
secondary voltage is 2 V and assuming no
N2 Bm f losses in the transformer, the turns ratio is:
(b) E2 D 4.44 volts (a) 40:1 step down (b) 40:1 step up
a
(c) 80:1 step down (d) 80:1 step up
N2 Bm f
(c) E2 D volts 9 A transformer has 800 primary turns and 100
a
secondary turns. To obtain 40 V from the
(d) E2 D 1.11N2 Bm a f volts secondary winding the voltage applied to the
2 In the auto-transformer shown in Fig. 21.22, primary winding must be:
the current in section PQ is: (a) 5 V (b) 320 V
(a) 3.3 A (b) 1.7 A (c) 5 A (d) 1.6 A (c) 2.5 V (d) 20 V
3 A step-up transformer has a turns ratio of A 100 kVA, 250 V/10 kV, single-phase trans-
10. If the output current is 5 A, the input former has a full-load copper loss of 800 W
current is: and an iron loss of 500 W. The primary wind-
(a) 50 A (b) 5 A (c) 2.5 A (d) 0.5 A ing contains 120 turns. For the statements in

TLFeBOOK
326 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY

questions 10 to 16, select the correct answer (d) In transformers, eddy current loss is
from the following list: reduced by laminating the core
(a) 81.3 kW (b) 800 W (c) 97.32% 18 An ideal transformer has a turns ratio of 1:5
(d) 80 kW (e) 3 (f) 4800 and is supplied at 200 V when the primary
(g) 1.3 kW (h) 98.40% (i) 100 kW current is 3 A. Which of the following state-
(j) 98.28% (k) 200 W (l) 101.3 kW ments is false?
(m) 96.38% (n) 400 W (a) The turns ratio indicates a step-up trans-
former
10 The total full-load losses
(b) The secondary voltage is 40 V
11 The full-load output power at 0.8 power factor (c) The secondary current is 15 A
(d) The transformer rating is 0.6 kVA
12 The full-load input power at 0.8 power factor (e) The secondary voltage is 1 kV
13 The full-load efficiency at 0.8 power factor (f) The secondary current is 0.6 A
14 The half full-load copper loss 19 Iron losses in a transformer are due to:
(a) eddy currents only
15 The transformer efficiency at half full-load, (b) flux leakage
0.8 power factor (c) both eddy current and hysteresis losses
16 The number of secondary winding turns (d) the resistance of the primary and secondary
windings
17 Which of the following statements is false?
(a) In an ideal transformer, the volts per turn 20 A load is to be matched to an amplifier
are constant for a given value of primary having an effective internal resistance of 10 
voltage via a coupling transformer having a turns
(b) In a single-phase transformer, the hystere- ratio of 1:10. The value of the load resistance
sis loss is proportional to frequency for maximum power transfer is:
(c) A transformer whose secondary current is (a) 100  (b) 1 k
greater than the primary current is a step- (c) 100 m (d) 1 m
up transformer

TLFeBOOK

S-ar putea să vă placă și