4010ES
Technical Presentation
Gregg Lupaczyk
Derek Knerr
Alex Andrews
4010ES Overview
Why are we replacing the 4010?
The current 4010 panel has been losing its competitive edge in the marketplace
over the last several years.
Some competitors’ panels have surpassed the 4010 panel features in many
areas.
• Point Capacity
• Raw Power – Base Panel is 4A
• Software Features
• Network Capability – Cannot take in points on the network.
• Ethernet Connectivity
The current 4010 is also difficult to add new features into
• Not enough Memory
• Limited expansion space
2
Fire Systems Training
4010ES Overview
The Replacement Plan
Redesign Current 4010 and use the same core as the 4100ES
All current features on the 4100ES are also now in the 4010ES (where
applicable)
Bug fixes on the 4100ES are automatically fixed in the 4010ES code (same
code base)
New features built into the 4100ES may be easily added to the 4010ES with
very low R&D effort, market requirements will dictate which features are
ported over.
Use the ES panel programmer
• ability to import an existing 4010 job and uses card and point data to
create a 4010ES job from it. User list, pseudos, custom control and site
information will be lost in the upgrade (demo at the end).
Leverage the vast amount of 4100ES optional features to provide features on
the 4010ES (IDNet, RUI, 4100 COMMs)
Cost reduce as much as possible to keep the 4010ES at a mid-range panel price
3
Fire Systems Training
6
Fire Systems Training
Domestic Canadian
7
Fire Systems Training
Note 1: All Base Panel PIDs will have an equivalent "BA" (Built in America) version in BAAN for jobs that require Built in America (e.g. 4010-9401BA).
BA and non BA products are identical except for where they are built, therefore there are no R&D prints describing the BA panels.
8
Fire Systems Training
9
Fire Systems Training
Note 1: All Base Panel PIDs will have an equivalent "BA" (Built in America) version in BAAN for jobs that require Built in America (e.g. 4010-9401BA).
BA and non BA products are identical except for where they are built, therefore there are no R&D prints describing the BA panels.
10
Fire Systems Training
English 2x40 Display, 120V, Platinum, Two IDNet Channels, Two Bay 9 blocks remaining
4010-9422 743-901
Box
English 2x40 Display, 220V-240V, Red, Two IDNet Channels, Two Bay 9 blocks remaining
4010-9521 743-902
Box
English 2x40 Display, 220V-240V, Platinum, Two IDNet Channels, 9 blocks remaining
4010-9522 743-903
Two Bay Box
English User Interface, 2X40 Display, Dual MX Channels
English 2x40 Display, 220V-240V, Red, Two MX Channels, Two Bay 7 blocks remaining
4010-9523 743-922
Box
English 2x40 Display, 220V-240V, Platinum, Two MX Channels, Two 7 blocks remaining
4010-9524 743-923
Bay Box
Note 1: All Base Panel PIDs will have an equivalent "BA" (Built in America) version in BAAN for jobs that require Built in America (e.g. 4010-9401BA).
BA and non BA products are identical except for where they are built, therefore there are no R&D prints describing the BA panels.
11
Fire Systems Training
Note 1: All Base Panel PIDs will have an equivalent "BA" (Built in America) version in BAAN for jobs that require Built in America (e.g. 4010-9401BA).
BA and non BA products are identical except for where they are built, therefore there are no R&D prints describing the BA panels.
12
Fire Systems Training
Mechanical
13
Fire Systems Training
4010ES Overview
Mechanical Approach
Use the same back-boxes (with some mods) and door as the 4100ES one
and two bay models.
Same look and feel as 4100ES (brand recognition, common family look)
• Platinum and Red Colors
Customers who grow out of the 4010ES Capabilities can easily upgrade
to the 4100ES (wall space is the same)
Replace current dead front (a.k.a. retainer) with hinged design
Easier to service
Can mount hardware on dead front
• More option card space in the back-box
• Side rails not required for UI (cost savings)
Eliminate sheet metal where we can (power supply, for example).
14
Fire Systems Training
Bridge Rectifier
RUI Wiring
Terminal Block
33 Ah Batteries
Door Hinge
15
Fire Systems Training
16
Fire Systems Training
A
B D
A C E G
Dead Front Hinge B D F H
Up to 50Ah Batteries
Door Hinge
17
Fire Systems Training
18
Fire Systems Training
19
Fire Systems Training
20
Fire Systems Training
21
Fire Systems Training
22
Fire Systems Training
23
Fire Systems Training
24
Fire Systems Training
25
Fire Systems Training
26
Fire Systems Training
27
Fire Systems Training
Electrical
28
Fire Systems Training
Electrical Approach
Use the same Core as 4100ES CPU and SPS
minimizes software effort
Cost reduce features not needed
Remove harnessing where we can
Remove expansion supply requirement (lower R&D effort)
Remove sheet metal where we can
Maximize option card space
Leverage 4100ES Option Cards
29
Fire Systems Training
30
Fire Systems Training
31
Fire Systems Training
32
Fire Systems Training
RUI LEDs
RUI
Interface
Note: CPU Card for InfoAlarm is the same but without LCD, piezo, and
membrane interface circuits populated 33
Fire Systems Training
34
Fire Systems Training
35
Fire Systems Training
36
Fire Systems Training
37
Fire Systems Training
RUI Interface
CPU Card Connections (External)
Style 4 or Style 7 Wiring
• If Style 4 wiring is used, must have
Pri-Sec loop back on terminal block
Short and open detection
Same wiring guidelines as 4100ES RUI
circuitry
Wiring gets terminated from the CPU
card to the left side of the box for strain
relief
4010ES RUI Supports
• 4009T
• 4009TPS
• 24 I/O Graphic Annunciator
• 4010ES Remote LCD Annunciator
• Remote InfoAlarm
• 10 Annunciator Maximum –
Software limitation.
38
Fire Systems Training
39
Fire Systems Training
MSS Features
8A of available power - excludes 2X40 CPU card current draw and MSS card
current draw
48 LED Module, InfoAlarm, NAC power, IDNet peripherals current Draw
must be subtracted from the available 8A (1mA alarm, 0.8mA supervisory
per IDNet device) Note: Software does NOT calculate current draw.
Four 3A Class A NACs (No option module required for Class A)
Remember, you still have only 8A of available power.
Battery Charger, up to 110Ah batteries (UL) and 50Ah (ULC) can be charged.
Batteries may need external battery box for larger batteries.
Aux Relay (2A, 32V)
Aux Power (4A Max per MSS) Aux Power tap 2A Max, NACs 2A Max per
NAC.
Standby Power, 5A Max (Same as SPS)
Single Channel, Two Loop IDNet+ Circuit
Mounting space for City Circuit, or Alarm Relay Module
Ordered and installed separately
Earth Detection (10K Ohm minimum)
40
Fire Systems Training
Battery
Connection IDNet
Jumpers
City or
Relay
Option IDNet
Module Status
Earth
Detect
Jumper
Auxiliary
Relay
41
Fire Systems Training
Jumpers
42
Fire Systems Training
MSS LEDs
43
Fire Systems Training
Connects to Connects to
Bridge AC Block
Label next to Bridge Rectifier Molex
Rectifier shows Connection
connections
44
Fire Systems Training
45
Fire Systems Training
46
Fire Systems Training
47
Fire Systems Training
48
Fire Systems Training
LED Kits
4100-9843 743-987 LED kit - 8 Yellow LEDs (for 48 Pluggable LED Module)
4100-9844 743-988 LED kit - 8 Green LEDs (for 48 Pluggable LED Module)
4100-9845 743-989 LED kit - 8 Red LEDs (for 48 Pluggable LED Module)
4100-9855 743-867 LED kit - 8 Blue LEDs (for 48 Pluggable LED Module)
49
Fire Systems Training
50
Fire Systems Training
51
Fire Systems Training
52
Fire Systems Training
53
Fire Systems Training
PDI Connections
4" x 5" Slave
To Dead Front Card Block
MSS
(CPU) (4 Pin) To front door (CPU Card)
Harness TBD
Block A
Spare / Close 4 14 14
Nippled Spare Core-4
Connector 4 Top Bay PDI
6 14 14
To Expansion
Bay (6 pin) Block B
Block D
Standard system: Top Bay PDI only
Expansion System: Top and Expansion PDI
4" x 5" Slave 4" x 5" Slave
Card Block Card Block
0734-052
4" x 5" Slave 4" x 5" Slave 4" x 5" Slave 4" x 5" Slave
Card Block Card Block Card Block Card Block
6 14 14 14 14
Expansion Bay PDI
Close Nippled
Box (no SIG 4 14 14 14 14
Spare / Close power)
4" x 5" Slave 4" x 5" Slave 4" x 5" Slave 4" x 5" Slave
Card Block Card Block Card Block Card Block
Notes:
"4" Denotes the "Core-4" Microfit Connector
"6" Denotes the “Core-6” Microfit Connector
"14" Denotes the Minifit Connector used for PDI access by slave cards and other
modules
54
Fire Systems Training
Optional Modules
Installed Inside the Panel
Option Cards (Local)
4010-9901 743-888 Flat Vesda HLI
* 4010-9902 743-928 Flat Network Card
4010-9903 743-929 Modem Physical Bridge Style 4
4010-9904 743-931 Modem Physical Bridge Style 7
* 4010-9905 743-930 TCP/IP Physical Bridge Style 4
4010-9906 743-932 TCP/IP Physical Bridge Style 7
4010-9818 742-100 Network Card Media Module - Wired
4010-9819 742-101 Network Card Media Module - Fiber
4010-9907 743-890 IDNet+
4010-9908 743-973 4 Point Flat Aux Relay Module
4010-9909 743-974 City Connect Module w/ disconnect switches
4010-9910 743-975 City Connect Module
4010-9911 743-976 Alarm Relay Module
4010-9912 743-982 Serial DACT
* 4010-9913 743-977 SafeLinc
4010-9914 743-978 Building Network Interface Card
4010-9915 743-979 BacPac Grid Connect Module
* 4010-9916 743-980 25V Regulator Module
4010-9917 743-970 MX Loop Card
4010-9918 743-981 Dual RS232 Module
4010-9919 743-990 TrueInsight Remote Service Gateway
* Comes with 8V converter
* 4010-9920 743-983 8 Zone Initiating Device Circuit - Class B Module
Comes with 8V converter
* 4010-9921 743-984 8 Zone Initiating Device Circuit - Class A Module
Items with * have mechanical or electrical changes discussed in this presentation. All other modules
function and install exactly the same as 4100ES equivalent versions.
55
Fire Systems Training
Vesda HLI
Same Card as Flat RS232 Card with alternate software.
Jumpers come default set from factory.
56
Fire Systems Training
57
Fire Systems Training
Port
LEDs
and
Trouble
LED
Reset Switch
Network Protocol
Jumpers
Note: Jumpers, switches and LEDs work the same as they do in 4100ES network card, in alternate locations.
58
Fire Systems Training
59
Fire Systems Training
60
Fire Systems Training
61
Fire Systems Training
62
Fire Systems Training
Only difference in
wiring from 4100ES is
it is terminated at the
Media Module instead
of the motherboard.
63
Fire Systems Training
Serial DACT
Serial DACT uses same electronics and is configured the same as the 4100ES, only
mounting has changed.
Serial DACT always mounts in Block C (designed to hang over the MSS)
Compatible with TL300 (24V model) and C900V2
64
Fire Systems Training
65
Fire Systems Training
66
Fire Systems Training
67
Fire Systems Training
68
Fire Systems Training
69
Fire Systems Training
70
Fire Systems Training
71
Fire Systems Training
72
Fire Systems Training
4190-9022 743-721 Beige Fiber Modem Exp Cabinet w/ Left Port Modem - Single Mode
4190-9023 743-717 Right Port Modem for Exp Cabinet – Single Mode
4190-9024 743-722 Red Fiber Modem Exp Cabinet w/ Left Port Modem – Multimode
4190-9025 743-723 Beige Fiber Modem Exp Cabinet w/ Left Port Modem - Multimode
4190-9026 743-719 Right Port Modem for Expansion Cabinet – Single Mode
Remote Power / Notification
4009-9201 636-867 4009A 120V SPI: 050-091 for accessories
4009-9202CA 636-988 4009A 120V ULC listed model SPI: 050-091 for accessories
4009-9301 636-868 4009A 240V SPI: 050-091 for accessories
4009-9401 636-968 4009T TrueAlert Controller 120V SPI: 050-094 for accessories
4009-9402CA 637-244 4009T TrueAlert Controller 120V w/ Low Battery Cutout SPI: 050-094 for accessories
4009-9501 637-450 4009T TrueAlert Controller 240V SPI: 050-094 for accessories
746-069 Order with 4009-9813 and a
2975-9230 Beige 4009 TPS Cabinet single TPS. SPI: 050-094
746-070 Order with 4009-9813 and a
2975-9229 Red 4009 TPS Cabinet single TPS. SPI: 050-094
743-801 Only usable with 2975-9229 or
4009-9813 Transponder Interface Card 2975-9230. SPI: 050-094
742-659 Only usable with 2975-9229 or
4100-5120 120V Domestic TrueAlert Power Supply 2975-9230.
742-660 Only usable with 2975-9229 or
4100-5121 120V Canadian TrueAlert Power Supply 2975-9230.
742-661 Only usable with 2975-9229 or
4100-5122 220-240V International TrueAlert Power Supply 2975-9230.
73
Fire Systems Training
Remote Annuncition
4100-9401 0743-187 Remote Unit Interface Panel w/FUI – Red – Domestic & Canadian
English
4100-9402 0743-188 Remote Unit Interface Panel w/FUI – Beige – Domestic & Canadian
English
4100-9421 0743-189 Remote Unit Interface Panel w/FUI – Red – Canadian French
4100-9422 0743-190 Remote Unit Interface Panel w/FUI – Beige – Canadian French
4100-9441 0743-191 Remote Unit Interface Panel w/FUI – Red – International
4100-9442 0743-192 Remote Unit Interface Panel w/FUI – Beige – International
4606-9102 0748-696 4010ES RUI LCD Annunciator (English)
*
4606-9102CF 0748-697 4010ES RUI LCD Annunciator (French)
4100-7401 N/A 24 Point I/O Graphic Module (requires mounting cabinet)
64 Switch and 64 LED Driver Module with 32 on-board LED drivers
SPI: See 050-070 for
4100-7402 N/A (requires mounting cabinet)
configuration options.
4100-7403 N/A 32 Point LED Driver Module (requires mounting cabinet)
4100-7404 N/A 32 point Switch Input Module (requires mounting cabinet)
74
Fire Systems Training
75
Fire Systems Training
Software
76
Fire Systems Training
Old 4010 software was totally abandoned. None of it was used for 4010ES.
There is nothing to prevent downloading 4100ES jobs into 4010ES panels and
vice versa. However, panel software will compare CPU card type and Job type.
If they do not align, the panel will crash with ‘Invalid CPU Type’ error.
77
Fire Systems Training
4010ES Differentiation:
Limited to 20 addressable slaves and e-slaves.
Limited to 10 RUI annunciators.
Limit of 3 optional cards in CPU bay. If a 4x10 card is used, limit is 2
optional cards.
Limited to 100 external network points. No limit on public network points.
No Audio or Signal cards.
Limited selection of Monitor, Relay, Annunciator, Interface, and Power
options (mostly due to form fit).
Uses different LCD Annunciator than 4100ES or old 4010.
New cards: MSSI, MSS, 4010IDNet+, 4010LCD, 48 LED Module.
4010ES limited to the 2 loop IDNet+ on MSSI.
International 4010ES allows up to 4 MX Loop or 4010IDNet+ cards (IDNet+
circuit on the MSSI counts against the limitation).
78
Fire Systems Training
79
Fire Systems Training
80
Fire Systems Training
All items that do not translate will be noted in the output as conversion
progresses.
81
Fire Systems Training
82