ETAP
Project: IEC Example 12.0.0C
Location: Irvine, Califonia Date: 11-20-2012
Contract: 987654321 Revision: Base
Engineer: OTI Cable Manager Config.: Normal
FileName: EXAMPLE-IEC
This info is printed on every output report, 1st remark line. (120 characters)
This info is printed on every output report, 1st comment line. (120 characters)

Cable Selection
DC & AC kV ≤ 1 Yes Branch
3-Phase Yes 1 < kV ≤ 30 No Equipment
1-Phase Yes kV > 30 No UGS
2 of 17

Info

Cond. Size Length Library


Cond./
ID kV / Code
Phase mm2 m Frequency
Cable Source Conductor Insulation
Hertz
FDR LOC A 1 1 3/C 25 25 1330 Heesung 50 CU XLPE 90°C
FDR LOC B 1 1 3/C 25 25 1874 Heesung 50 CU XLPE 90°C

* Size is in kcmil
3 of 17

Physical

Insulation Shield Sheath Armor Jacket


Cond. Cable
Cond./ Cond./ Size O.D. Thick. Thick. Thick. Thick. Thick. O.D.
ID kV Code
Phase Cable Type Y/N Type Type Type
AWG / cm mm mm mm mm mm cm
kcmil
FDR LOC A 1 1 3/C 25 25 0.59 XLPE 0.9 Yes 0.127 Aluminum Sheath 1.8 St Armor/30dg/15w 1 None 0 2.6
FDR LOC B 1 1 3/C 25 25 0.59 XLPE 0.9 Yes 0.127 Aluminum Sheath 1.8 None 0 None 0 2.6

* Size is in kcmil
4 of 17

Impedance

Library G/PE/N Z Zo Library G/PE/N

Cond./ Cond./ Size Size Frequency Unit Z R X L Y Zo Ro Xo Lo Yo Rdc 25 °C R X


ID kV Code
Phase Cable AWG / # AWG / Hertz Length Ohms / Unit Ohms / Unit Ohms / Unit H / Unit S / Unit Ohms / Ohms / Unit Ohms / Unit H / Unit S / Unit uOhms / Unit Ohms / Unit Ohms / Unit
kcmil kcmil Length Length Length Length Length Unit Length Length Length Length Length Length Length
Length
FDR LOC A 1 1 3/C 25 25 0 50 1 km 0.93018 0.927 0.0768 0.0002445 0 741.28 0 0
FDR LOC B 1 1 3/C 25 25 0 50 1 km 0.93018 0.927 0.0768 0.0002445 0 741.28 0 0

* Size is in kcmil
5 of 17

Rac T
°C

90
90
6 of 17

Configuration

Main Cable Aux Cable

Cond./ Cond./ Size Phase Neutral PE Neutral PE


ID kV Code
Phase Cable Armor Sheath Structure
AWG / AWG / AWG / AWG / AWG / AWG /
kcmil kcmil kcmil kcmil kcmil kcmil

FDR LOC A 1 1 3/C 25 25 2 - 25 1 - 25 Yes Yes 1-6 No


FDR LOC B 1 1 3/C 25 25 2 - 25 1 - 25 No No 2-6 No

* Size is in kcmil
7 of 17

Ampacity - Capacity

Base Operating Operating / FLA

Cond./ Cond./ Base Alert Allowable


ID kV Code Size Standard Installation Ta Tc Rho Ta Tc Rho
Phase Cable Amp Option Amp Amp %
AWG / oC oC C.cm / W oC oC C.cm / W
kcmil
FDR LOC A 1 1 3/C 25 25 146 BS 7671 A/G Trays 30 90 35 90 Derated 140.2 1.88 1.3
FDR LOC B 1 1 3/C 25 25 138 IEC 60364 A/G Trays 30 90 35 90 Derated 132.5 0.925 0.7

* Size is in kcmil
8 of 17

Sizing - Phase

Operating Constraints Optimal

Cond. / Cond./ Overload


ID kV Code Size Loading Vd Vst Nom. In SC Current 3rd Harm. Other Cond. / Size
Phase Cable
AWG / Amps % % kA kA % Harm. (Cf) Phase mm²
kcmil
FDR LOC A 1 1 3/C 25 25 3 48.5 4 1.68 1 16
FDR LOC B 1 1 3/C 25 25 3 77 4 0.288 1 25

* Size is in kcmil
9 of 17

Thermal Sizing - Input

Ground Disc. Temp. Main Temp. Aux Temp. Factor k Leakage


Cond. / Cond./ Size Fault Time Cable Cable Armor/Sheath Current
ID kV Code
Phase Cable AWG / kA s mA
Initial Final Initial Final Initial Final Main Cable Aux Cable
kcmil
FDR LOC A 1 1 3/C 25 25 1.25 0.010 90 250 90 250 80 200 Formula Tables 30
FDR LOC B 1 1 3/C 25 25 0.321 0.010 90 250 30 200 Formula Tables 4

* Size is in kcmil
10 of 17

Thermal Sizing - Results

PE Aux PE Armor Sheath K2S2


Size
Cond. / Cond./ AWG/kcmil AWG/kcmil AWG/kcmil AWG/kcmil kA2s
ID kV Code
Phase Cable
AWG / Existing Required Existing Required Existing Required Existing Required Main Cable Aux Cable Armor Sheath
kcmil
FDR LOC A 1 1 3/C 25 25 25 4 6 4 11.8 2.7 136.8 1.5 0.328 0.496 0.016 0.016
FDR LOC B 1 1 3/C 25 25 25 2.5 6 2.5 0.128 0.158

* Size is in kcmil
11 of 17

Shock Protection Input

Resistance
Cond. / Cond./ Size Load Additional Ground/Earth Permissible
ID kV Code Type Vt
Phase Cable AWG / Ohms Ohms
kcmil
FDR LOC A 1 1 3/C 25 25 Distribution Circuit 0.1 0 EN 50122 : 2011
FDR LOC B 1 1 3/C 25 25 Distribution Circuit 0.1 0 IEC 60364

* Size is in kcmil
12 of 17

Shock Protection -Results

Loop Current Disconnect Time Loop Z Touch Voltage (TN or IT 1st Fault) IT 2nd Fault Touch Voltage
Size
Cond. / Cond./ Calculated Permissible Calculated Permissible Calculated Permissible Calculated Permissible Calculated Permissible
ID kV Code
Phase Cable AWG / kA kA s s Ohms Ohms V V V V
kcmil
FDR LOC A 1 1 3/C 25 25 0.196 0.012 0.010 5.000 1.910 31.551 18 865
FDR LOC B 1 1 3/C 25 25 0.321 0.015 0.010 1.000 1.169 25.016 32

* Size is in kcmil
Cable Schedule Summary Cable Configur
Cable General Info
Size Length Lib. Freq. Phase
Cond. / Cond./ Lib. Cond. Insul.
ID kV Code AWG / m Hertz Phase Connection AWG /
Phase Cable Source Type Type
kcmil kcmil
FDR LOC A 1 1 3/C 25 25 1330 Heesung 50 CU XLPE 90°C AC - 2P ABN 2 - 25
FDR LOC B 1 1 3/C 25 25 1874 Heesung 50 CU XLPE 90°C AC - 2P ABN 2 - 25
Cable Configuration Cable Protection Cable Capacity/Ampacity
Configuration Protective Device (PD) Phase Capaci
Neutral PE Aux Neutral Aux PE
Armor Sheath Overload Overcurrent GFCI / RCD Base
AWG / AWG / AWG / AWG / Structure Standard
Device Device Device Amp
kcmil kcmil kcmil kcmil
1 - 25 Yes Yes 1-6 No Fuse LOC A Fuse LOC A None 146 BS 7671
1 - 25 No No 2-6 No Fuse LOC A Fuse LOC A None 138 IEC 60364
e Capacity/Ampacity Phase Constraints Optimal Phase
Phase Capacity / Ampacity Operating Values Phase Conductor - Sizing Constraints Phase - Optimal
Operating Operating Overload Overload SC OC Device Size
Allowable Loading Vd 3rd Harm. Cond./
Installation Tc Ta Type Nom. Amp Op. kA Current Time
Amp Amp % % Phase mm2
ºC ºC In I2 kA sec
A/G Trays 35 90 140.2 3 User Defined 2 4 0.008 1.68 0.01 1 16
A/G Trays 35 90 132.5 3 User Defined 2 4 0.008 0.288 0.01 1 25
timal Phase Earthing - Existing Earthing - Required Electric Shock
Phase - Optimal Ground/Earth Conductors - Existing Ground/Earth Conductors - Required Electric Shock
PE Armor Sheath Aux PE Short Circuit Disconnect PE Armor Sheath Aux PE Loop Disconnect
Derated Vd Earthing
AWG / AWG / AWG / AWG / Current Time AWG / AWG / AWG / AWG / Current Time
Amp % Type
kcmil kcmil kcmil kcmil kA sec kcmil kcmil kcmil kcmil kA sec
103 1.47 25 11.8 136.8 6 1.25 0.010 4 2.7 1.5 4 TN-C-S 0.196 0.010
132 1.54 25 6 0.321 0.010 2.5 2.5 TT 0.321 0.010
Electric Shock
Permissible Loop
Loop Z
Time Permissible Z
Ohms
sec Ohms
5.000 1.910 31.551
1.000 1.169 25.016