Documente Academic
Documente Profesional
Documente Cultură
18 MARCH 2009
Nkosinathi Buthelezi
Senior Consultant: Power Transformers and Reactors
Presentation Content
Philosophy
All transformers are specified, designed,
tested, maintained and operated to
meet at least the expected operational
life span of approximately 40 years when
used in normal operation.
Interchangeability and standardization
Tapping Ranges
+5% to -15% of HV voltage has been adopted as the
standard for transformers based on the following;
• The electricity act states that supply voltages shall
not vary by more than ±5% from the nominal.
8
6
N u m b er
Value(s)
4
Target
2
0
2000 2001 2002 2003 2004-April
Year
CORE
11
Tapping Winding
3
a2
MV Winding
A13
12
HV Winding
Adoption of this arrangement
• This winding arrangement was originally
adopted to ensure almost constant impedance
throughout the tapping range in order to
achieve the full rated power across the whole
tapping range. Furthermore, it ensured
maximum impedance occurring in the minimum
tap-position, which is advantageous for LV fault
MVA consideration. This is due to the fact that
previously Eskom had a policy to supply the
rural and farm communities from the tertiary
terminals of the main autotransformer.
Adoption of this arrangement, Cont
300
200
100
∆ VRW (kV)
0
0 20 40 60 80 100 120 140 160 180 200
-100
-200
-300
without with MOV's t (mys)
Investigation for a new solution
3A2 a2 3 11 A13
Tertiary Winding
CORE
MV Winding
Tap Winding
HV Winding
12
Challenges
20
18
16
Im p e d a n c e (% )
14
12
10
8
6
old design
4
new design
2
0
1 3 5 7 9 11 13 15 17
Tap position
The new Specification
SERVICE CONDITIONS
• The rated nominal frequency shall be 50Hz.
Temperature Rise.
• Temperature rises must be in accordance with IEC
60076 standards. It has to be considered that the annual
average rated ambient temperature has been changed
from 25°C to 30°C.
Winding Rise.
• The average winding rise above ambient at nameplate
MVA rating shall not exceed 55°C for oil natural flow
through the windings, and shall not exceed 60°C for oil
forced directed flow through the winding.
• Temperature Rise of Metallic Parts at Rated
MVA.
• The hot spot temperature rise above ambient of
metallic parts in contact with cellulose material
outside the winding block shall not exceed
68°C. The rise above ambient of other metallic
parts in contact with oil including core and tank
shall not exceed 75°C for the surface in contact
with the oil.
The new Specification
• ELECTRICAL DESIGN
Winding Arrangement
• Arrangement of windings.
• Describe type of windings to be
used.
• Conductor configuration in each
winding.
• Location and type of tap windings or
tap sections to be used.
Factors considered during the design
reviews
Insulation Clearances and Configuration of Insulation.
MECHANICAL DESIGN
Tanks
• Construction
• Joint design and welding to prevent leaks.
Factors considered during the design
reviews
• TEST PROGRAM
– Review requirements in the specifications
and standards.
– Review test plans for the transformer.
– Accuracy of loss measurement methods.
– Temperature tests including review of
allowed gas in oil increases during
temperature tests.
– Impulse and partial discharge testing.
Discuss acceptance criteria.
• Check points during testing.
Workshop Inspection- Individual windings
Workshop Inspection- Assembly line
Workshop Inspection-Top Lining up
Workshop Inspection- Winding inspection
Workshop Inspection- Winding assembly
Workshop Inspection- Core section
Workshop Inspection- Active part before tanking
Workshop Inspection
Quality control
Focus area is on
• Tests to prove that the transformer has been built
correctly: This include ratio, polarity, resistance and
taphange operation.
• Tests to prove the guarantees: These are the losses,
impedance, and temperature rise and noise level.
• Test to prove that the transformer will be satisfactory in
service for at least 35 years. The tests in this category
are the most important and the most difficult to frame.
• These tests are performed as per IEC 60076-3
Transformer testing