PARAMETER LIST

Automatic Genset Controller, AGC-4


● Alarm list
● Parameter list

DEIF A/S · Frisenborgvej 33 · DK-7800


Skive Tel.: +45 9614 9614 · Fax: +45 9614 Document no.: 4189340688O
9615 info@deif.com · www.deif.com SW version: 4.59.x or later
DEIF Page 1 of 210
AGC-4 parameter list 4189340688 UK

Table of contents
1. General information ......................................................................................................................................... 5
1.1 Warnings, legal information and safety ................................................................................................................... 5
1.1.1 Warnings and notes ........................................................................................................................................... 5
1.1.2 Legal information and disclaimer ..................................................................................................................... 5
1.1.3 Safety issues ....................................................................................................................................................... 5
1.1.4 Electrostatic discharge awareness .................................................................................................................. 5
1.1.5 Factory settings .................................................................................................................................................. 5
1.2 About the Parameter List........................................................................................................................................... 6
1.2.1 General purpose of the Parameter List ........................................................................................................... 6
1.2.2 Intended users .................................................................................................................................................... 6
1.2.3 Contents and overall structure.......................................................................................................................... 6
2. Alarm list ........................................................................................................................................................... 7
2.1 General information about the alarm list ................................................................................................................. 7
2.1.1 Alarm list features and options ......................................................................................................................... 7
2.2 Protection parameters................................................................................................................................................ 9
2.2.1 Reverse power and overcurrent protection..................................................................................................... 9
2.2.2 Voltage protections .......................................................................................................................................... 14
2.2.3 Frequency protections ..................................................................................................................................... 17
2.2.4 Busbar voltage protections.............................................................................................................................. 20
2.2.5 Busbar frequency protections ......................................................................................................................... 23
2.2.6 Mains failure protections ................................................................................................................................. 26
2.2.7 Overload protections ........................................................................................................................................ 28
2.2.8 Current unbalance protection ......................................................................................................................... 30
2.2.9 Voltage unbalance protection ......................................................................................................................... 31
2.2.10 Reactive power import (loss of excitation) protection ............................................................................... 32
2.2.11 Reactive power export (overexcitation) protection .................................................................................... 32
2.2.12 Negative sequence ........................................................................................................................................ 33
2.2.13 Zero sequence ................................................................................................................................................ 34
2.2.14 Directional overcurrent protection ................................................................................................................ 35
2.2.15 Busbar unbalance voltage ............................................................................................................................ 36
2.2.16 Time-dependent undervoltage ..................................................................................................................... 37
2.2.17 Power-dependent reactive power import .................................................................................................... 40
2.2.18 Power-dependent reactive power export .................................................................................................... 41
2.2.19 Non-essential load trip (load shedding)....................................................................................................... 42
2.2.20 Undervoltage and reactive power low ......................................................................................................... 45
2.3 Control parameters - synchronisation.................................................................................................................... 47
2.3.1 Synchronisation and breaker alarms ............................................................................................................. 47
2.3.2 Mains sync. inhibit ............................................................................................................................................ 51
2.4 Control parameters - regulation .............................................................................................................................. 52
2.4.1 Regulation alarms ............................................................................................................................................ 52
2.5 Input/output parameters - binary input setup ........................................................................................................ 54
2.5.1 Digital input 23-27 setup .................................................................................................................................. 54
2.5.2 Digital input 43-55 setup .................................................................................................................................. 55
2.5.3 Digital input 91-97 setup .................................................................................................................................. 56
2.5.4 Digital input 102-108 setup ............................................................................................................................. 57
2.5.5 Digital input 112-117 setup ............................................................................................................................. 58
2.5.6 Emergency stop ................................................................................................................................................ 59
2.5.7 Digital input 127-133 setup ............................................................................................................................. 59
2.5.8 M-Logic alarm 1-5 setup .................................................................................................................................. 60
2.6 Input/output parameters - analogue input setup .................................................................................................. 61
2.6.1 Analogue input setup (option M15.6)............................................................................................................. 61
2.6.2 Analogue input setup (option M15.8)............................................................................................................. 65
2.6.3 Analogue input setup (option M16.6)............................................................................................................. 69
2.6.4 Analogue input setup (option M16.8)............................................................................................................. 80
2.7 Multi-functional analogue input setup .................................................................................................................... 90
2.7.1 Multi-input no. 102 ............................................................................................................................................ 90
2.7.2 Multi-input no. 105 ............................................................................................................................................ 95
2.7.3 Multi-input no. 108 .......................................................................................................................................... 100
2.7.4 Speed and running feedback setup ............................................................................................................. 105
2.7.5 Differential measurement .............................................................................................................................. 108

DEIF Page 2 of 210


AGC-4 parameter list 4189340688 UK

2.7.6 Aux. supply setup ........................................................................................................................................... 113


2.8 System parameters - general setup ..................................................................................................................... 115
2.8.1 Stop coil wirebreak and internal communication alarms........................................................................... 115
2.8.2 Engine heater failure ...................................................................................................................................... 115
2.8.3 Running detection .......................................................................................................................................... 116
2.8.4 Battery tests .................................................................................................................................................... 116
2.8.5 Max. ventilation ............................................................................................................................................... 119
2.8.6 Switchboard error - Block and Stop ............................................................................................................. 120
2.8.7 Switchboard error - Not in auto..................................................................................................................... 121
2.8.8 Oil renewal....................................................................................................................................................... 121
2.8.9 Avg U BB ......................................................................................................................................................... 122
2.9 System parameters - communication .................................................................................................................. 123
2.9.1 External communication error ....................................................................................................................... 123
2.9.2 Engine interface communication alarms ..................................................................................................... 124
2.9.3 Power management communication error .................................................................................................. 128
2.9.4 Internal CAN communication error............................................................................................................... 129
2.10 External I/O parameters ...................................................................................................................................... 130
2.10.1 External I/O alarm setup.............................................................................................................................. 130
2.10.2 Analogue inputs ............................................................................................................................................ 130
2.10.3 External analogue input scale .................................................................................................................... 131
2.10.4 Digital inputs ................................................................................................................................................. 131
3. Parameter list ................................................................................................................................................ 132
3.1 General information about the parameter list ..................................................................................................... 132
3.1.1 Parameter list settings ................................................................................................................................... 132
3.2 Control parameters - synchronisation.................................................................................................................. 133
3.2.1 Synchronisation .............................................................................................................................................. 133
3.3 Control parameters - regulation ............................................................................................................................ 136
3.3.1 Regulation ....................................................................................................................................................... 136
3.4 Control parameters - output setup ....................................................................................................................... 143
3.4.1 Digital output setup ........................................................................................................................................ 143
3.5 Control parameters - analogue output ................................................................................................................. 148
3.5.1 Analogue output limits ................................................................................................................................... 148
3.6 Control parameters - transducer outputs ............................................................................................................ 149
3.6.1 Transducer outputs ........................................................................................................................................ 149
3.7 Control parameters - analogue regulator output setup ..................................................................................... 154
3.7.1 Regulator output selection ............................................................................................................................ 154
3.8 System parameters ................................................................................................................................................ 154
3.9 System parameters - general setup ..................................................................................................................... 155
3.9.1 General setup ................................................................................................................................................. 155
3.9.2 Counters and timers ....................................................................................................................................... 158
3.9.3 Alarm horn ....................................................................................................................................................... 159
3.9.4 Run coil setup ................................................................................................................................................. 159
3.9.5 Running, start and stop ................................................................................................................................. 160
3.9.6 Breaker control................................................................................................................................................ 161
3.9.7 Power derate ................................................................................................................................................... 162
3.9.8 Idle start ........................................................................................................................................................... 163
3.9.9 Engine heater.................................................................................................................................................. 164
3.9.10 Analogue load sharing lines output............................................................................................................ 164
3.9.11 Master clock .................................................................................................................................................. 165
3.9.12 Cooling ventilation ........................................................................................................................................ 165
3.9.13 Summer/winter time ..................................................................................................................................... 165
3.9.14 Fuel transfer pump logic .............................................................................................................................. 166
3.9.15 Fan logic ........................................................................................................................................................ 167
3.9.16 Diagnostics .................................................................................................................................................... 169
3.9.17 I thermal demand ......................................................................................................................................... 169
3.9.18 Pulse counter ................................................................................................................................................ 170
3.9.19 Alarm jump .................................................................................................................................................... 170
3.9.20 Tank capacity ................................................................................................................................................ 170
3.9.21 Command timers .......................................................................................................................................... 171
3.10 System parameters - mains setup ..................................................................................................................... 172
3.10.1 Mains setup ................................................................................................................................................... 172
3.10.2 Test ................................................................................................................................................................ 173

DEIF Page 3 of 210


AGC-4 parameter list 4189340688 UK

3.10.3 Controller settings ........................................................................................................................................ 173


3.10.4 Mains failure .................................................................................................................................................. 174
3.10.5 Y1(X1) droop curve ...................................................................................................................................... 175
3.10.6 Y2(X2) droop curve ...................................................................................................................................... 176
3.10.7 Power offset .................................................................................................................................................. 177
3.10.8 Cosphi offset ................................................................................................................................................. 177
3.11 System parameters - external communication ................................................................................................. 178
3.11.1 External communication .............................................................................................................................. 178
3.11.2 Power management internal communication ........................................................................................... 178
3.12 System parameters - engine interface communication ................................................................................... 179
3.12.1 Engine interface communication ................................................................................................................ 179
3.12.2 Digital AVR parameters (option T2) ........................................................................................................... 180
3.12.3 CAN port setup ............................................................................................................................................. 183
3.13 System parameters - external I/O communication setup................................................................................ 184
3.13.1 External I/O communication setup ............................................................................................................. 184
3.14 System parameters - power management setup ............................................................................................. 185
3.14.1 Power management setup .......................................................................................................................... 185
3.15 System parameters - jump menus ..................................................................................................................... 194
3.15.1 Jump menus ................................................................................................................................................. 194
3.15.2 9000 Software version ................................................................................................................................. 194
3.15.3 9010 Display character test ........................................................................................................................ 194
3.15.4 9020 Service port ......................................................................................................................................... 194
3.15.5 9030 Scaling ................................................................................................................................................. 194
3.15.6 9070 M4 software version ........................................................................................................................... 195
3.15.7 9100 Device type.......................................................................................................................................... 195
3.15.8 911x Password ............................................................................................................................................. 195
3.15.9 9120 Service menu ...................................................................................................................................... 196
3.15.10 9130 AC config. .......................................................................................................................................... 196
3.15.11 9140 Angle compensation BB/G.............................................................................................................. 196
3.15.12 9150 Backlight dimmer .............................................................................................................................. 196
3.15.13 9160 Application drawing .......................................................................................................................... 197
3.15.14 9170 Internal CAN protocol ...................................................................................................................... 197
3.15.15 9180 Quick setup (AGC diesel generator) ............................................................................................. 197
3.15.16 9180 Quick setup (AGC mains) ............................................................................................................... 198
3.15.17 9190 Application broadcast ...................................................................................................................... 198
3.15.18 9230 Memory backup ................................................................................................................................ 199
3.16 System parameters - utility software ................................................................................................................. 199
3.16.1 GSM settings ................................................................................................................................................ 199
3.17 System parameters - RMI inputs........................................................................................................................ 200
3.17.1 RMI 102 ......................................................................................................................................................... 200
3.17.2 RMI 105 ......................................................................................................................................................... 201
3.17.3 RMI 108 ......................................................................................................................................................... 201
3.17.4 Multi-input selections 102, 105, 108 .......................................................................................................... 202
3.17.5 Multi-input selections option M16.6 ........................................................................................................... 203
3.17.6 Multi-input selections M16.8 ....................................................................................................................... 204
3.17.7 4-20 mA input scaling .................................................................................................................................. 204
3.17.8 Parameter ID................................................................................................................................................. 205
3.18 System parameters - external digital outputs ................................................................................................... 205
3.18.1 External digital outputs ................................................................................................................................ 205
3.18.2 External module status ................................................................................................................................ 205
3.18.3 13000 SuperVision ....................................................................................................................................... 206
3.18.4 14000 AC average ....................................................................................................................................... 206

DEIF Page 4 of 210


AGC-4 parameter list 4189340688 UK

1. General information
1.1 Warnings, legal information and safety
1.1.1 Warnings and notes
Throughout this document, a number of warnings and notes with helpful user information will be presented.
To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener-
al text.

Warnings

Warnings indicate a potentially dangerous situation, which could result in death, personal in-
jury or damaged equipment, if certain guidelines are not followed.

Notes

Notes provide general information, which will be helpful for the reader to bear in mind.

1.1.2 Legal information and disclaimer


DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how
to install or operate the engine/generator controlled by the Multi-line 2 unit, the company responsible for the
installation or the operation of the set must be contacted.

The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the war-
ranty will be lost.

Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.

The English version of this document always contains the most recent and up-to-date information about the
product. DEIF does not take responsibility for the accuracy of translations, and translations might not be
updated at the same time as the English document. If there is a discrepancy, the English version prevails.

1.1.3 Safety issues


Installing and operating the Multi-line 2 unit may imply work with dangerous currents and voltages. Therefore,
the installation should only be carried out by authorised personnel who understand the risks involved in work-
ing with live electrical equipment.

Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-
puts as this could lead to injury or death.

1.1.4 Electrostatic discharge awareness


Sufficient care must be taken to protect the terminals against static discharges during the installation. Once
the unit is installed and connected, these precautions are no longer necessary.

1.1.5 Factory settings


The Multi-line 2 unit is delivered from factory with certain factory settings. These are based on average values
and are not necessarily the correct settings for matching the engine/generator set in question. Precautions
must be taken to check the settings before running the engine/generator set.

DEIF Page 5 of 210


AGC-4 parameter list 4189340688 UK

1.2 About the Parameter List


1.2.1 General purpose of the Parameter List
This document is a complete parameter list including all parameters, which means that some of the option
parameters included may not be accessible in the system in question.

The document includes a complete standard alarm list and a complete standard parameter list for setup.
Therefore, this document is to be used for reference, when information about specific alarms and parameters
is needed.

Please make sure to read this document before starting to work with the Multi-line 2 unit and
the genset to be controlled. Failure to do this could result in human injury or damage to the
equipment.

1.2.2 Intended users


This Parameter List is mainly intended for the person responsible for the unit parameter setup. In most cases,
this would be a panel builder designer. Naturally, other users might also find useful information here.

1.2.3 Contents and overall structure


This document is divided into chapters, and in order to make the structure simple and easy to use, each
chapter will begin from the top of a new page.

DEIF Page 6 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2. Alarm list
2.1 General information about the alarm list
2.1.1 Alarm list features and options

In the following, these abbreviations are used:


G: Generator
GB: Generator breaker
TB: Tie breaker (for mains unit)
MB: Mains breaker
BTB: Bus tie breaker
BA: Busbar A (BTB unit)
BB: Busbar (BTB unit: Busbar B)
N/A: Not available

This chapter includes a complete alarm list, including all possible options. Therefore, this chapter is to be
used for reference when specific information about the individual parameters is needed for the unit setup.

The table consists of the following possible adjustments:

Set point: The alarm set point is adjusted in the set point menu. The setting is a percentage of the
nominal values.

Delay: The timer setting is the time that must expire from the alarm level is reached until the
alarm occurs.

Relay output A: A relay can be activated by output A.

Relay output B: A relay can be activated by output B.

An alarm is activated if no relay output, A or B, is selected.

Do not select Limits/Limit relay if you want an alarm to be raised together with a relay output A or B.

Enable: The alarm can be activated or deactivated.

Fail class: When the alarm occurs the unit will react depending on the selected fail class.

Fail classes are:

Fail class DG (diesel generator) Mains unit BTB (bus tie breaker)
F1 Block Block Block
F2 Warning Warning Warning
F3 Trip GB Trip TB Trip BTB
F4 Trip + Stop Trip MB N/A
F5 Shutdown N/A N/A
F6 Trip MB N/A N/A
F7 Safety stop N/A N/A
F8 Trip MB/GB N/A N/A
F9 Controlled stop N/A N/A

Small differences due to the character of the parameters may exist between the individual tables.

DEIF Page 7 of 210


AGC-4 parameter list 4189340688 UK Alarm list

It is also possible to configure the parame-


ters by using the PC utility software. It will
be possible to make the same configura-
tions as described above.

By using the PC utility software, extra func-


tionality is available. For all the protections,
it is possible to make an automatic acknowl-
edgement of the alarm.

DEIF Page 8 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2 Protection parameters


2.2.1 Reverse power and overcurrent protection
No. Setting Min. Factory Notes Ref. Description
Max. setting
1000 Reverse power 1
1001 –P> 1 Set- -200.0% -5.0% Design- The alarm and fail class are acti-
point 0.0% er’s Ref- vated when the reverse power
1002 –P> 1 Timer 0.1 s 5.0 s erence has been continuously above the
100.0 s Hand- programmed value during the
book programmed delay.
1003 –P> 1 Relay Not used Not
output Option- used
A depend-
ent
1004 –P> 1 Relay Not used Not
output Option- used
B depend-
ent
1005 –P> 1 Ena- OFF ON
ble ON
1006 –P> 1 Fail F1…F9 Trip GB
class (F3)
1010 Reverse power 2
1011 –P> 2 Set- -200.0% -5.0% Design- The alarm and fail class are acti-
point 0.0% er’s Ref- vated when the reverse power
1012 –P> 2 Timer 0.1 s 10.0 s erence has been continuously above the
100.0 s Hand- programmed value during the
book programmed delay.
1013 –P> 2 Relay Not used Not
output Option- used
A depend-
ent
1014 –P> 2 Relay Not used Not
output Option- used
B depend-
ent
1015 –P> 2 Ena- OFF ON
ble ON
1016 –P> 2 Fail F1…F9 Trip GB
class (F3)

DEIF Page 9 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1030 Overcurrent 1
1031 I> 1 Set- 50.0% 115.0% Design- The alarm and fail class are acti-
point 200.0% er’s Ref- vated when the current has been
1032 I> 1 Timer 0.1 s 10.0 s erence continuously above the program-
3200.0 s Hand- med value during the program-
book med delay.
1033 I> 1 Relay Not used Not
output Option- used
A depend-
ent
1034 I> 1 Relay Not used Not
output Option- used
B depend-
ent
1035 I> 1 Ena- OFF ON
ble ON
1036 I> 1 Fail F1…F9 Warning
class (F2)
1040 Overcurrent 2
1041 I> 2 Set- 50.0% 120.0% Design- The alarm and fail class are acti-
point 200.0% er’s Ref- vated when the current has been
1042 I> 2 Timer 0.1 s 5.0 s erence continuously above the program-
3200.0 s Hand- med value during the program-
book med delay.
1043 I> 2 Relay Not used Not
output Option- used
A depend-
ent
1044 I> 2 Relay Not used Not
output Option- used
B depend-
ent
1045 I> 2 Ena- OFF ON
ble ON
1046 I> 2 Fail F1…F9 Trip GB
class (F3)
1050 Overcurrent 3
1051 I> 3 Set- 50.0% 115.0% Design- The alarm and fail class are acti-
point 200.0% er’s Ref- vated when the current has been
1052 I> 3 Timer 0.1 s 10.0 s erence continuously above the program-
3200.0 s Hand- med value during the program-
book med delay.
1053 I> 3 Relay Not used Not
output Option- used
A depend-
ent

DEIF Page 10 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1054 I> 3 Relay Not used Not
output Option- used
B depend-
ent
1055 I> 3 Enable OFF ON
ON
1056 I> 3 Fail F1…F9 Trip GB
class (F3)
1060 Overcurrent 4
1061 I> 4 Set- 50.0% 120.0% Design- The alarm and fail class are acti-
point 200.0% er’s Ref- vated when the current has been
1062 I> 4 Timer 0.1 s 5.0 s erence continuously above the program-
3200.0 s Hand- med value during the program-
book med delay.
1063 I> 4 Relay Not used Not
output Option- used
A depend-
ent
1064 I> 4 Relay Not used Not
output Option- used
B depend-
ent
1065 I> 4 Enable OFF ON
ON
1066 I> 4 Fail F1…F9 Trip GB
class (F3)
1080 G I> inverse
1081 G I> inv. Set 0 IEC Design- Option C2 is required.
Type point 6 Inverse er’s Ref-
1082 G I> inv. Set 50 % 110 % erence Type selections are:
Limit point 200 % Hand-
0. IEC Inverse
book
1083 G I> inv. Set 0.01 1.00 1. IEC Very Inverse
TMS point 100 2. IEC Extremely Inv.
3. IEEE Moderately Inv.
1084 G I> inv. Set 0.00 s 0.14 s
4. IEEE Very Inverse
k point 32 s
5. IEEE Extremely Inv.
1085 G I> inv. Set 0s 0s 6. Custom
c point 32 s
1086 G I> inv. Set 0.00 0.02
a point 32
1091 G I> inv. Out- Not used Not
OA put A Variant- used
dep.
1092 G I> inv. Out- Not used Not
OB put B Variant- used
dep.
1093 G I> inv. Enable ON OFF
OFF

DEIF Page 11 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1094 G I> inv. Fail F1…F9 Trip GB
class (F3)
1100 Voltage-dependent overcurrent curve setting
1101 G Iv > Set- 50.0% 110.0% Design- The different percentages in the
(50%) point 200.0% er’s Ref- specific parameters are related to
I1 erence the nom. voltage.
1102 G Iv > Set- 50.0% 125.0% Hand-
(60%) point 200.0% book Settings relate to nominal genera-
I2 tor current. The condition has to
be true i.e. I1<I2<I3<I4<I5<I6. If
1103 G Iv > Set- 50.0% 140.0%
this is not fulfilled, the worst-case
(70%) point 200.0%
setpoint I1 will be used.
I3
Setpoints 3 to 6 include Relay
1104 G Iv > Set- 50.0% 155.0% output A and B.
(80%) point 200.0%
I4
1105 G Iv > Set- 50.0% 170.0%
(90%) point 200.0%
I5
1106 G Iv > Set- 50.0% 200.0%
(100%) point 200.0%
I6
1110 Voltage-dependent overcurrent alarm
1110 G Iv > Set- 50.0% 110.0% Design- The alarm and fail class are acti-
point 200.0% er’s Ref- vated when the overcurrent has
1111 G Iv > Timer 0.1 s 1.0 s erence been continuously above the pro-
300.0 s Hand- grammed value during the pro-
book grammed delay. The setpoint val-
1112 G Iv > Relay Not used Not ue is calculated automatically by
output Option- used
the values in menus 1101-1106.
A depend-
ent
1113 G Iv > Relay Not used Not
output Option- used
B depend-
ent
1114 G Iv > Acti- OFF ON
vate ON
1115 G Iv > Fail F1...F9 Trip GB
class (F3)
1130 Fast overcurrent 1
1131 I>> 1 Set- 150.0% 150.0% Design- The alarm settings relate to the
point 350.0% er’s Ref- nominal current setting. The
1132 I>> 1 Timer 0.0 s 2.0 s erence alarm and fail class are activated
100.0 s Hand- when the current has been con-
book tinuously above the programmed
1133 I>> 1 Re- Not used Not
value during the programmed de-
play Option- used
lay.
output depend-
A ent

DEIF Page 12 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1134 I>> 1 Relay Not used Not
output Option- used
B depend-
ent
1135 I>> 1 Ena- OFF OFF
ble ON
1136 I>> 1 Fail F1...F9 Trip GB
class (F3)
1140 Fast overcurrent 2
1141 I>> 2 Set- 150.0% 200% Design- The alarm and fail class are acti-
point 350.0% er’s Ref- vated when the current has been
1142 I>> 2 Delay 0.0 s 0.5 s erence continuously above the program-
100.0 s Hand- med value during the program-
book med delay
1143 I>> 2 Re- Not used Not
play Option- used
output depend-
A ent
1144 I>> 2 Relay Not used Not
output Option- used
B depend-
ent
1145 I>> 2 Ena- OFF OFF
ble ON
1146 I>> 2 Fail F1...F9 Trip GB
class (F3)

DEIF Page 13 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.2 Voltage protections


No. Setting Min. Factory Notes Ref. Description
Max. setting
1150 G/M/BA overvoltage 1
1151 G/M/BA Set- 100.0% 103.0% Designer’s The alarm and fail class are
U> 1 point 120.0% Reference activated when the voltage
1152 G/M/BA Timer 0.1 s 10.0 s Handbook has been continuously above
U> 1 100.0 s the programmed value during
the programmed delay.
1153 G/M/BA Relay Not used Not used
U> 1 output Option-
A dep.
1154 G/M/BA Relay Not used Not used
U> 1 output Option-
B dep.
1155 G/M/BA Enable OFF OFF
U> 1 ON
1156 G/M/BA Fail F1…F9 Warning
U> 1 class (F2)
1160 G/M/BA overvoltage 2
1161 G/M/BA Set- 100.0% 105.0% Designer’s The alarm and fail class are
U> 2 point 120.0% Reference activated when the voltage
1162 G/M/BA Timer 0.1 s 5.0 s Handbook has been continuously above
U> 2 100.0 s the programmed value during
the programmed delay.
1163 G/M/BA Relay Not used Not used
U> 2 output Option-
A dep.
1164 G/M/BA Relay Not used Not used
U> 2 output Option-
B dep.
1165 G/M/BA Enable OFF OFF
U> 2 ON
1166 G/M/BA Fail F1…F9 Warning
U> 2 class (F2)
1170 G/M/BA undervoltage 1
1171 G/M/BA Set- 40.0% 97% Designer’s The alarm and fail class are
U< 1 point 100.0% Reference activated when the voltage
1172 G/M/BA Timer 0.1 s 10.0 s Handbook has been continuously under
U< 1 100.0 s the programmed value during
the programmed delay.
1173 G/M/BA Relay Not used Not used
U< 1 output Option-
A dep.

DEIF Page 14 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1174 G/M/BA Relay Not used Not used
U< 1 output Option-
B dep.
1175 G/M/BA Enable OFF OFF
U< 1 ON
1176 G/M/BA Fail F1…F9 Warning
U< 1 class (F2)
1180 G/M/BA undervoltage 2
1181 G/M/BA Set- 40.0% 95.0% Designer’s The alarm and fail class are
U< 2 point 100.0% Reference activated when the voltage
1182 G/M/BA Timer 0.1 s 5.0 s Handbook has been continuously under
U< 2 100.0 s the programmed value during
the programmed delay.
1183 G/M/BA Relay Not used Not used
U< 2 output Option-
A dep.
1184 G/M/BA Relay Not used Not used
U< 2 output Option-
B dep.
1185 G/M/BA Enable OFF OFF
U< 2 ON
1186 G/M/BA Fail F1…F9 Warning
U< 2 class (F2)
1190 G/M/BA undervoltage 3
1191 G/M/BA Set- 40.0% 95.0% Designer’s The alarm and fail class are
U< 3 point 100.0% Reference activated when the voltage
1192 G/M/BA Timer 0.1 s 5.0 s Handbook has been continuously under
U< 3 100.0 s the programmed value during
the programmed delay.
1193 G/M/BA Relay Not used Not used
U< 3 output Option-
A dep.
1194 G/M/BA Relay Not used Not used
U< 3 output Option-
B dep.
1195 G/M/BA Enable OFF OFF
U< 3 ON
1196 G/M/BA Fail F1...F9 Warning
U< 3 class (F2)

DEIF Page 15 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1200 Calculation method
1201 G/M/BA Set- Ph-Ph Ph-Ph Designer’s Selection between phase-
voltage point Ph-N Reference phase or phase-neutral volt-
trip Handbook age detection.
When phase-phase tripping is
selected, the voltage alarms
relate to the nominal voltage.
When phase-neutral tripping
is selected, the voltage
alarms relate to the nominal
voltage divided by √3.
1202 BB Set- Ph-Ph Ph-Ph
voltage point Ph-N
trip
1203 Unbalan- Set- Ref. to Ref. to
ce I point nominal nominal
Ref. to
average

1204 Frequen- Set- L1 L1 or L2 Selection of the phase the


cy trip point L1 and L2 or L3 controller uses for over-/
type and L3 under-frequency alarms.

DEIF Page 16 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.3 Frequency protections

Frequency settings relate to the nominal frequency setting.

No. Setting Min. Factory Notes Ref. Description


Max. setting
1210 G/M/BA overfrequency 1
1211 G/M/ Set- 100.0% 103.0% Designer’s The alarm and fail class are
BA f> point 120.0% Reference activated when the frequency
1 Handbook has been continuously above
1212 G/M/ Timer 0.2 s 10.0 s the programmed value during
BA f> 100.0 s the programmed delay. Fre-
1 quency settings relate to nomi-
nal frequency setting.
1213 G/M/ Relay Not used Not used
BA f> output Option-de-
1 A pendent
1214 G/M/ Relay Not used Not used
BA f> output Option-de-
1 B pendent
1215 G/M/ Enable OFF OFF
BA f> ON
1
1216 G/M/ Fail F1…F9 Warning
BA f> class (F2)
1
1220 G/M/BA overfrequency 2
1221 G/M/ Set- 100.0% 105.0% Designer’s The alarm and fail class are
BA f> point 120.0% Reference activated when the frequency
2 Handbook has been continuously above
1222 G/M/ Timer 0.2 s 5.0 s the programmed value during
BA f> 100.0 s the programmed delay.
2
1223 G/M/ Relay Not used Not used
BA f> output Option-de-
2 A pendent
1224 G/M/ Relay Not used Not used
BA f> output Option-de-
2 B pendent
1225 G/M/ Enable OFF OFF
BA f> ON
2
1226 G/M/ Fail F1…F9 Warning
BA f> class (F2)
2

DEIF Page 17 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1230 G/M/BA overfrequency 3
1231 G/M/ Set- 100.0% 105.0% Designer’s The alarm and fail class are
BA f> point 120.0% Reference activated when the frequency
3 Handbook has been continuously above
1232 G/M/ Timer 0.2 s 5.0 s the programmed value during
BA f> 100.0 s the programmed delay.
3
1233 G/M/ Relay Not used Not used
BA f> output Option-de-
3 A pendent
1234 G/M/ Relay Not used Not used
BA f> output Option-de-
3 B pendent
1235 G/M/ Enable OFF OFF
BA f> ON
3
1236 G/M/ Fail F1…F9 Warning
BA f> class (F2)
3
1240 G/M/BA underfrequency 1
1241 G/M/ Set- 80.0% 97.0% Designer’s The alarm and fail class are
BA f<1 point 100.0% Reference activated when the frequency
1242 G/M/ Timer 0.2 s 10.0 s Handbook has been continuously under
BA f<1 100.0 s the programmed value during
the programmed delay.
1243 G/M/ Relay Not used Not used
BA f<1 output Option-de-
A pendent
1244 G/M/ Relay Not used Not used
BA f<1 output Option-de-
B pendent
1245 G/M/ Enable OFF OFF
BA f<1 ON
1246 G/M/ Fail F1…F9 Warning
BA f<1 class (F2)
1250 G/M/BA underfrequency 2
1251 G/M/ Set- 80.0% 95.0% Designer’s The alarm and fail class are
BA f<2 point 100.0% Reference activated when the frequency
1252 G/M/ Timer 0.2 s 5.0 s Handbook has been continuously under
BA f<2 100.0 s the programmed value during
the programmed delay.
1253 G/M/ Relay Not used Not used
BA f<2 output Option-de-
A pendent
1254 G/M/ Relay Not used Not used
BA f<2 output Option-de-
B pendent

DEIF Page 18 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1255 G/M/ Enable OFF OFF
BA f<2 ON
1256 G/M/ Fail F1…F9 Warning
BA f<2 class (F2)
1260 G/M/BA underfrequency 3
1261 G/M/ Set- 80.0% 95.0% Designer’s The alarm and fail class are
BA f<3 point 100.0% Reference activated when the frequency
1262 G/M/ Timer 0.2 s 5.0 s Handbook has been continuously under
BA f<3 100.0 s the programmed value during
the programmed delay.
1263 G/M/ Relay Not used Not used
BA f<3 output Option-de-
A pendent
1264 G/M/ Relay Not used Not used
BA f<3 output Option-de-
B pendent
1265 G/M/ Enable OFF OFF
BA f<3 ON
1266 G/M/ Fail F1…F9 Warning
BA f<3 class (F2)

DEIF Page 19 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.4 Busbar voltage protections

Voltage settings relate to the nominal voltage setting.

No. Setting Min. Factory Notes Ref. Description


Max. setting
1270 Busbar overvoltage 1
1271 BB U> Set- 100.0% 103.0% Designer’s The alarm and fail class are
1 point 120.0% Reference activated when the voltage
1272 BB U> Timer 0.0 s 10.0 s Handbook has been continuously above
1 99.99 s the programmed value during
the programmed delay.
1273 BB U> Relay Not used Not used
1 output Option-de-
A pendent
1274 BB U> Relay Not used Not used
1 output Option-de-
B pendent
1275 BB U> Enable OFF OFF
1 ON
1276 BB U> Fail F1…F9 Warning
1 class (F2)
1280 Busbar overvoltage 2
1281 BB U> Set- 100.0% 105.0% Designer’s The alarm and fail class are
2 point 120.0% Reference activated when the voltage
1282 BB U> Timer 0.0 s 5.0 s Handbook has been continuously above
2 99.99 s the programmed value during
the programmed delay.
1283 BB U> Relay Not used Not used
2 output Option-de-
A pendent
1284 BB U> Relay Not used Not used
2 output Option-de-
B pendent
1285 BB U> Enable OFF OFF
2 ON
1286 BB U> Fail F1…F9 Warning
2 class (F2)
1290 Busbar overvoltage 3
1291 BB U> Set- 100.0% 105.0% Designer’s The alarm and fail class are
3 point 120.0% Reference activated when the voltage
1292 BB U> Timer 0.0 s 5.0 s Handbook has been continuously above
3 99.99 s the programmed value during
the programmed delay.
1293 BB U> Relay Not used Not used
3 output Option-de-
A pendent
1294 BB U> Relay Not used Not used
3 output Option-de-
B pendent

DEIF Page 20 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1295 BB U> Enable OFF OFF
3 ON
1296 BB U> Fail F1…F9 Warning
3 class (F2)
1300 Busbar undervoltage 1
1301 BB U< Set- 40.0% 97.0% Designer’s The alarm and fail class are
1 point 100.0% Reference activated when the voltage
1302 BB U< Timer 0.00 s 10.00 s Handbook has been continuously under
1 99.99 s the programmed value during
the programmed delay.
1303 BB U< Relay Not used Not used
1 output Option-de-
A pendent
1304 BB U< Relay Not used Not used
1 output Option-de-
B pendent
1305 BB U< Enable OFF OFF
1 ON
1306 BB U< Fail F1…F9 Warning
1 class (F2)
1310 Busbar undervoltage 2
1311 BB U< Set- 40.0% 95.0% Designer’s The alarm and fail class are
2 point 100.0% Reference activated when the voltage
1312 BB U< Timer 0.00 s 5.0 s Handbook has been continuously under
2 99.99 s the programmed value during
the programmed delay.
1313 BB U< Relay Not used Not used
2 output Option-de-
A pendent
1314 BB U< Relay Not used Not used
2 output Option-de-
B pendent
1315 BB U< Enable OFF OFF
2 ON
1316 BB U< Fail F1…F9 Warning
2 class (F2)
1320 Busbar undervoltage 3
1321 BB U< Set- 40.0% 97.0% Designer’s The alarm and fail class are
3 point 100.0% Reference activated when the voltage
1322 BB U< Timer 0.00 s 10.0 s Handbook has been continuously under
3 99.99 s the programmed value during
the programmed delay.
1323 BB U< Relay Not used Not used
3 output Option-de-
A pendent
1324 BB U< Relay Not used Not used
3 output Option-de-
B pendent

DEIF Page 21 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1325 BB U< Enable OFF OFF
3 ON
1326 BB U< Fail F1…F9 Warning
3 class (F2)
1330 Busbar undervoltage 4
1331 BB U< Set- 40.0% 95.0% Designer’s The alarm and fail class are
4 point 100.0% Reference activated when the voltage
1332 BB U< Timer 0.00 s 5.0 s Handbook has been continuously under
4 99.99 s the programmed value during
the programmed delay.
1333 BB U< Relay Not used Not used
4 output Option-
A dep.
1334 BB U< Relay Not used Not used
4 output Option-
B dep.
1335 BB U< Enable OFF OFF
4 ON
1336 BB U< Fail F1...F9 Warning
4 class (F2)
1340 Busbar voltage trip
1341 BB Set- Ph-Ph Ph-Ph Designer’s Selection between phase-
volt- point Ph-N Reference phase or phase-neutral volt-
age Handbook age detection.
trip

DEIF Page 22 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.5 Busbar frequency protections

Frequency settings relate to the nominal frequency setting.

No. Setting Min. Factory Notes Ref. Description


Max. setting
1350 Busbar overfrequency 1
1351 BB f> Set- 100.0% 103.0% Designer’s The alarm and fail class are ac-
1 point 120.0% Reference tivated when the frequency has
1352 BB f> Timer 0.0 s 10.0 s Handbook been continuously above the
1 99.99 s programmed value during the
programmed delay.
1353 BB f> Relay Not used Not used
1 output Option-
A dep.
1354 BB f> Relay Not used Not used
1 output Option-
B dep.
1355 BB f> Enable OFF OFF
1 ON
1356 BB f> Fail F1…F9 Warning
1 class (F2)
1360 Busbar overfrequency 2
1361 BB f> Set- 100.0% 105.0% Designer’s The alarm and fail class are ac-
2 point 120.0% Reference tivated when the frequency has
1362 BB f> Timer 0.00 s 5.0 s Handbook been continuously above the
2 99.99 s programmed value during the
programmed delay.
1363 BB f> Relay Not used Not used
2 output Option-
A dep.
1364 BB f> Relay Not used Not used
2 output Option-
B dep.
1365 BB f> Enable OFF OFF
2 ON
1366 BB f> Fail F1…F9 Warning
2 class (F2)
1370 Busbar overfrequency 3
1371 BB f> Set- 100.0% 105.0% Designer’s The alarm and fail class are ac-
3 point 120.0% Reference tivated when the frequency has
1372 BB f> Timer 0.00 s 5.0 s Handbook been continuously above the
3 99.99 s programmed value during the
programmed delay.
1373 BB f> Relay Not used Not used
3 output Option-
A dep.
1374 BB f> Relay Not used Not used
3 output Option-
B dep.

DEIF Page 23 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1375 BB f> Enable OFF OFF
3 ON
1376 BB f> Fail F1…F9 Warning
3 class (F2)
1380 Busbar underfrequency 1
1381 BB f< Set- 80.0% 97.0% Designer’s The alarm and fail class are ac-
1 point 100.0% Reference tivated when the frequency has
1382 BB f< Timer 0.00 s 10.0 s Handbook been continuously under the
1 99.99 s programmed value during the
programmed delay.
1383 BB f< Relay Not used Not used
1 output Option-
A dep.
1384 BB f< Relay Not used Not used
1 output Option-
B dep.
1385 BB f< Enable OFF OFF
1 ON
1386 BB f< Fail F1…F9 Warning
1 class (F2)
1390 Busbar underfrequency 2
1391 BB f< Set- 80.0% 95.0% Designer’s The alarm and fail class are ac-
2 point 100.0% Reference tivated when the frequency has
1392 BB f< Timer 0.00 s 5.0 s Handbook been continuously under the
2 99.99 s programmed value during the
programmed delay.
1393 BB f< Relay Not used Not used
2 output Option-
A dep.
1394 BB f< Relay Not used Not used
2 output Option-
B dep.
1395 BB f< Enable OFF OFF
2 ON
1396 BB f< Fail F1…F9 Warning
2 class (F2)
1400 Busbar underfrequency 3
1401 BB f< Set- 80.0% 97.0% Designer’s The alarm and fail class are ac-
3 point 100.0% Reference tivated when the frequency has
1402 BB f< Timer 0.00 s 10.0 s Handbook been continuously under the
3 99.99 s programmed value during the
programmed delay.
1403 BB f< Relay Not used Not used
3 output Option-
A dep.
1404 BB f< Relay Not used Not used
3 output Option-
B dep.

DEIF Page 24 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1405 BB f< Enable OFF OFF
3 ON
1406 BB f< Fail F1…F9 Warning
3 class (F2)
1410 Busbar underfrequency 4
1411 BB f< Set- 80.0% 95.0% Designer’s The alarm and fail class are ac-
4 point 100.0% Reference tivated when the frequency has
1412 BB f< Timer 0.00 s 5.0 s Handbook been continuously under the
4 99.99 s programmed value during the
programmed delay.
1413 BB f< Relay Not used Not used
4 output Option-
A dep.
1414 BB f< Relay Not used Not used
4 output Option-
B dep.
1415 BB f< Enable OFF OFF
4 ON
1416 BB f< Fail F1...F9 Warning
4 class (F2)

DEIF Page 25 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.6 Mains failure protections


No. Setting Min. Factory Notes Ref. Descri
Max. setting ption

1420 Df/dt (ROCOF)


1421 Df/dt Set- 1.5 Hz/s 5.0 Hz/s Option The alarm and fail class are
(RO- point 10.0 Hz/s A1 activated when the df/dt rate has
COF) been continuously above the
1422 Df/dt Timer 3 periods 6 periods programmed value during the
(RO- 20 peri- programmed number of periods
COF) ods (delay).

1423 Df/dt Relay Not used Not


(RO- output Option- used
COF) A dep.
1424 Df/dt Relay Not used Not
(RO- output Option- used
COF) B dep.
1425 Df/dt Enable OFF OFF
(RO- ON
COF)
1426 Df/dt Fail F1…F9 Trip MB
(RO- class (F6)
COF)
1430 Vector jump
1431 Vector Set- 1.0 deg. 10.0 Option The alarm and fail class are
jump point 90.0 deg. deg. A1 activated when a vector jump is
1432 Vector Relay Not used Not detected.
jump output Option- used
A dep.
1433 Vector Relay Not used Not
jump output Option- used
B dep.
1434 Vector Enable OFF OFF
jump ON
1435 Vector Fail F1…F9 Trip MB
jump class (F6)
1440 Busbar positive sequence voltage low
1441 BB pos Set- 10.0% 70.0% Option The alarm and fail class are
seq volt point 110.0% A4 activated when the symmetrical
(positive sequence) voltage has
1442 BB pos Timer 1 period 2 peri- been continuously below the
seq volt 9 periods ods programmed value during the
programmed delay.
1443 BB pos Relay Not used Not The timer factory setting is set to 2
seq volt output Option- used periods. This means that the error
A dep. has to be active in 2 whole periods
1444 BB pos Relay Not used Not before the alarm will be tripped.
seq volt output Option- used E.g. in a 50 Hz system, the alarm
B dep. will be activated if the positive

DEIF Page 26 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Descri


Max. setting ption

1445 BB pos Enable OFF OFF sequence is below 70% of U


seq volt ON nominal voltage for 40 ms. The
1446 BB pos Fail F1…F9 Trip MB alarm will trip the fail class as soon
seq volt class (F6) as possible after this delay.

DEIF Page 27 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.7 Overload protections


No. Setting Min. Factory Notes Ref. Description
Max. setting
1450 Overload 1
1451 P> 1 Set -200.0 % 100.0 % Designer’s Settings relate to nominal power.
point 200.0 % Reference The alarm and fail class are activa-
1452 P> 1 Timer 0.1 s 10.0 s Handbook ted when the power has been con-
3200.0 s tinuously above the programmed
value during the programmed de-
1453 P> 1 Relay Not used Not
lay.
output Option- used
A dep.
1454 P> 1 Relay Not used Not
output Option- used
B dep.
1455 P> 1 Enable OFF OFF
ON
1456 P> 1 Fail F1…F9 Warn-
class ing (F2)
1460 Overload 2
1461 P> 2 Set -200.0 % 110.0 % Designer’s The alarm and fail class are activa-
point 200.0 % Reference ted when the power has been con-
1462 P> 2 Timer 0.1 s 5.0 s Handbook tinuously above the programmed
3200.0 s value during the programmed de-
lay.
1463 P> 2 Relay Not used Not
output Option- used
A dep.
1464 P> 2 Relay Not used Not
output Option- used
B dep.
1465 P> 2 Enable OFF OFF
ON
1466 P> 2 Fail F1…F9 Trip GB
class (F3)
1470 Overload 3
1471 P> 3 Set -200.0 % 100.0 % Designer’s The alarm and fail class are activa-
point 200.0 % Reference ted when the power has been con-
1472 P> 3 Timer 0.1 s 10.0 s Handbook tinuously above the programmed
3200.0 s value during the programmed de-
lay.
1473 P> 3 Relay Not used Not
output Option- used
A dep.
1474 P> 3 Relay Not used Not
output Option- used
B dep.

DEIF Page 28 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1475 P> 3 Enable OFF OFF
ON
1476 P> 3 Fail F1…F9 Trip GB
class (F3)
1480 Overload 4
1481 P> 4 Set -200.0 % 110.0 % Designer’s The alarm and fail class are activa-
point 200.0 % Reference ted when the power has been con-
1482 P> 4 Timer 0.1 s 5.0 s Handbook tinuously above the programmed
3200.0 s value during the programmed de-
lay.
1483 P> 4 Relay Not used Not
output Option- used
A dep.
1484 P> 4 Relay Not used Not
output Option- used
B dep.
1485 P> 4 Enable OFF OFF
ON
1486 P> 4 Fail F1…F9 Trip GB
class (F3)
1490 Overload 5
1491 P> 5 Set -200.0 % 100.0 % Designer’s The alarm and fail class are activa-
point 200.0 % Reference ted when the power has been con-
1492 P> 5 Timer 0.1 s 10.0 s Handbook tinuously above the programmed
3200.0 s value during the programmed de-
lay.
1493 P> 5 Relay Not used Not
output Option- used
A dep.
1494 P> 5 Relay Not used Not
output Option- used
B dep.
1495 P> 5 Enable OFF OFF
ON
1496 P> 5 Fail F1...F9 Trip GB
class (F3)

DEIF Page 29 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.8 Current unbalance protection


No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
1500 Unbalanced current
1501 Unbal- Set- 0.0% 30.0% Design- Settings relate to nominal generator
ance point 100.0% er’s Ref- current. The alarm and fail class are
curr. erence activated when the difference be-
1502 Unbal- Timer 0.1 s 10.0 s Handbook tween the max. reading and the min.
ance 100.0 s reading of the 3 measured currents
curr. has been continuously above the
programmed value during the pro-
1503 Unbal- Relay Not used Not
grammed delay.
ance output Option- used
curr. A dep.
1504 Unbal- Relay Not used Not
ance output Option- used
curr. B dep.
1505 Unbal- Enable OFF OFF
ance ON
curr.
1506 Unbal- Fail F1…F9 Trip GB
ance class (F3)
curr.

DEIF Page 30 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.9 Voltage unbalance protection


No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
1510 Unbalanced voltage
1511 Unbal- Set- 0.0% 10.0% Design- Settings relate to nominal voltage.
ance point 50.0% er’s Refer- The alarm and fail class are activated
volt. ence when the difference between the
1512 Unbal- Timer 0.1 s 10.0 s Handbook max. reading and the min. reading of
ance 100.0 s the 3 measured generator voltages
volt. has been continuously above the pro-
grammed value during the program-
1513 Unbal- Relay Not Not
med delay.
ance output used used
volt. A Option-
dep.
1514 Unbal- Relay Not Not
ance output used used
volt. B Option-
dep.
1515 Unbal- Enable OFF OFF
ance ON
volt.
1516 Unbal- Fail F1…F9 Trip GB
ance class (F3)
volt.

DEIF Page 31 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.10 Reactive power import (loss of excitation) protection


No. Setting Min. Factory Notes Ref. Description
Max. setting
1520 Reactive power import (loss of excitation)
1521 –Q> Setpoint 0.0% 50.0% Designer’s Settings relate to nominal power.
150.0% Reference The alarm and fail class are acti-
1522 –Q> Timer 0.1 s 10.0 s Handbook vated when imported VAr has
100.0 s been continuously above the pro-
grammed value during the pro-
1523 –Q> Relay Not used Not used
grammed delay.
output Option-
A dep.
1524 –Q> Relay Not used Not used
output Option-
B dep.
1525 –Q> Enable OFF OFF
ON
1526 –Q> Fail F1…F9 Warning
class (F2)

2.2.11 Reactive power export (overexcitation) protection


No. Setting Min. Factory Notes Ref. Description
Max. setting
1530 Reactive power export (overexcitation)
1531 Q> Setpoint 0.0% 60.0% Designer’s Settings relate to nominal power.
100.0% Reference The alarm and fail class are activa-
1532 Q> Timer 0.1 s 10.0 s Handbook ted when exported VAr has been
100.0 s continuously above the program-
med value during the programmed
1533 Q> Relay Not used Not used
delay.
output A Option-
dep.
1534 Q> Relay Not used Not used
output B Option-
dep.
1535 Q> Enable OFF OFF
ON
1536 Q> Fail F1…F9 Warning
class (F2)

DEIF Page 32 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.12 Negative sequence


No. Setting Min. Factory Notes Ref. Description
Max. setting
1540 Negative sequence current
1541 Neg Set- 1.0% 20.0% Option Settings relate to nominal current.
seq I point 100.0% C2 The alarm and fail class are activa-
1542 Neg Timer 0.2 s 0.5 s ted when the negative sequence
seq I 100.0 s has been continuously above the
programmed value during the pro-
1543 Neg Relay Not used Not used
grammed delay.
seq I output Option-
A dep.
1544 Neg Relay Not used Not used
seq I output Option-
B dep.
1545 Neg Enable OFF OFF
seq I ON
1546 Neg Fail F1…F9 Trip MB
seq I class (F6)
1550 G/M/BA negative sequence voltage
1551 G/M/BA Set- 1.0% 5.0% Option Settings relate to nominal voltage.
neg seq point 100.0% C2 The alarm and fail class are activa-
U ted when the negative sequence
1552 G/M/BA Timer 0.2 s 0.5 s has been continuously above the
neg seq 100.0 s programmed value during the pro-
U grammed delay.

1553 G/M/BA Relay Not used Not used


neg seq output Option-
U A dep.
1554 G/M/BA Relay Not used Not used
neg seq output Option-
U B dep.
1555 G/M/BA Enable OFF OFF
neg seq ON
U
1556 G/M/BA Fail F1…F9 Trip MB
neg seq class (F6)
U
1560 Negative sequence selection
1561 Neg Set- G/M/BA G/M/BA Option Selection between generator or
seq se- point measure- meas- C2 busbar measurement of negative
lect ment urement sequence voltage.
BB meas-
urement

DEIF Page 33 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.13 Zero sequence


No. Setting Min. Factory Notes Ref. Description
Max. setting
1570 Zero sequence current
1571 Zero Set- 0.0% 20.0% Option Settings relate to nominal current.
seq I point 100.0% C2 The alarm and fail class are activa-
1572 Zero Timer 0.2 s 0.5 s ted when the zero sequence has
seq I 100.0 s been continuously above the pro-
grammed value during the pro-
1573 Zero Relay Not used Not
grammed delay.
seq I output Option- used
A dep.
1574 Zero Relay Not used Not
seq I output Option- used
B dep.
1575 Zero Enable OFF OFF
seq I ON
1576 Zero Fail F1…F9 Trip MB
seq I class (F6)
1580 G/M/BA zero sequence voltage
1581 G/M/BA Set- 0.0% 5.0% Option Settings relate to nominal voltage.
zero point 100.0% C2 The alarm and fail class are activa-
seq U ted when the zero sequence has
1582 G/M/BA Timer 0.2 s 0.5 s been continuously above the pro-
zero 100.0 s grammed value during the pro-
seq U grammed delay.

1583 G/M/BA Relay Not used Not


zero output Option- used
seq U A dep.
1584 G/M/BA Relay Not used Not
zero output Option- used
seq U B dep.
1585 G/M/BA Enable OFF OFF
zero ON
seq U
1586 G/M/BA Fail F1…F9 Trip MB
zero class (F6)
seq U
1590 Zero sequence selection
1591 Zero Set- G/M/BA G/M/BA Option Selection between generator or
seq se- point measure- meas- C2 busbar measurement of zero se-
lect ment urement quence voltage.
BB meas-
urement

DEIF Page 34 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.14 Directional overcurrent protection


No. Setting Min. Factory Notes Ref. Description
Max. setting
1600 Directional overcurrent 1
1601 I> di- Set- -200.0% 120.0% Op- Settings relate to nominal current.
rect 1 point 200.0% tion The alarm and fail class are activated
1602 I> di- Timer 0.0 s 0.1 s A5 when the directional current has been
rect 1 100.0 s continuously above the programmed val-
ue during the programmed delay.
1603 I> di- Relay Not used Not used
The current measurement is positive
rect 1 output Option-
when current is supplied from the mains
A dep.
to the plant. The current measurement is
1604 I> di- Relay Not used Not used negative when current is being supplied
rect 1 output Option- to the mains.
B dep.
1605 I> di- Ena- OFF OFF
rect 1 ble ON
1606 I> di- Fail F1…F9 Trip MB
rect 1 class (F6)
1610 Directional overcurrent 2
1611 I> di- Set- -200.0% 130.0% Op- Settings relate to nominal current.
rect 2 point 200.0% tion The alarm and fail class are activated
1612 I> di- Timer 0.0 s 0.1 s A5 when the directional current has been
rect 2 100.0 s continuously above the programmed val-
ue during the programmed delay.
1613 I> di- Relay Not used Not used
The current measurement is positive
rect 2 output Option-
when current is supplied from the mains
A dep.
to the plant. The current measurement is
1614 I> di- Relay Not used Not used negative when current is being supplied
rect 2 output Option- to the mains.
B dep.
1615 I> di- Ena- OFF OFF
rect 2 ble ON
1616 I> di- Fail F1…F9 Trip MB
rect 2 class (F6)

DEIF Page 35 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.15 Busbar unbalance voltage


No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
1620 BB unbalance U
1621 BB un- Set- 0.0% 6.0% Design- Settings relate to average actual volt-
bal- point 50.0% er’s Refer- age.
ance U ence The alarm and fail class are activated
1622 BB un- Timer 0.1 s 10.0 s Handbook when the difference between the
bal- 100.0 s max. reading and the min. reading of
ance U the 3 measured busbar voltages has
been continuously above the pro-
1623 BB un- Relay Not Not
grammed value during the program-
bal- output used used
med delay.
ance U A Option-
dep.
1624 BB un- Relay Not Not
bal- output used used
ance U B Option-
dep.
1625 BB un- Enable OFF OFF
bal- ON
ance U
1626 BB un- Fail F1…F9 Warn-
bal- class ing (F2)
ance U

DEIF Page 36 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.16 Time-dependent undervoltage


No. Setting Min. Factory Notes Ref. Description
Max. setting
1630 Time-dependent undervoltage 1 1-3
1631 Ut < Setting 30.0% 30.0% Option Curve setting for time-dependent under-
1 1 120.0% A1 voltage.
1632 Ut < Delay 1 0.00 s 0.15 s Settings relate to nominal generator
1 20.00 s voltage.
The condition has to be true i.e.
1633 Ut < Setting 30.0% 70.0%
Ut(1)1≤Ut(2)≤Ut(3)≤Ut(4)≤Ut(5)≤Ut(6).
1 2 120.0%
If this is not fulfilled, the worst-case set-
1634 Ut < Delay 2 0.00 s 0.15 s point Ut(6) will be used.
1 20.00 s
1635 Ut < Setting 30.0% 70.0%
1 3 120.0%
1636 Ut < Delay 3 0.00 s 0.70 s
1 20.00 s
1640 Time-dependent undervoltage 1 4-6
1641 Ut < Setting 30.0% 90.0% Option Curve setting for time-dependent under-
1 4 120.0% A1 voltage.
1642 Ut < Delay 4 0.00 s 1.50 s Settings relate to nominal generator
1 20.00 s voltage.
The condition has to be true i.e.
1643 Ut < Setting 30.0% 90.0%
Ut(1)1≤Ut(2)≤Ut(3)≤Ut(4)≤Ut(5)≤Ut(6).
1 5 120.0%
If this is not fulfilled, the worst-case set-
1644 Ut < Delay 5 0.00 s 2.00 s point Ut(6) will be used.
1 20.00 s
1645 Ut < Setting 30.0% 90.0%
1 6 120.0%
1646 Ut < Delay 6 0.00 s 3.00 s
1 20.00 s
1650 Time-dependent undervoltage 1 activation
1651 Ut < Acti- 30.0% 90% Option Activate is the voltage value where the
act 1 vate 120.0% A1 function timer starts.
1652 Ut < Recov- 30.0% 95% Reset is the value where the function
act 1 ery 120.0% timer is reset to 0 ms.
Delay is the delay timer for the reset.
1653 Ut < Delay 0.0 s 1.00 s
The relay outputs will activate immedi-
act 1 320.0 s
ately when the function timer starts.
1654 Ut < Relay Not used Not
act 1 output Option- used
A dep.
1655 Ut < Relay Not used Not
act 1 output Option- used
B dep.
1656 Ut < Enable OFF OFF
act 1 ON

DEIF Page 37 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1660 Time-dependent undervoltage 1
1661 Ut < Relay Not used Not Option The alarm and fail class is activated in-
1 output Option- used A1 stantaneously when the voltage value is
A dep. under the programmed value curve.
1662 Ut < Relay Not used Not
1 output Option- used
B dep.
1663 Ut < Enable OFF OFF
1 ON
1664 Ut < Fail F1…F9 Trip MB
1 class (F6)
1670 Time-dependent undervoltage 2 1-3
1671 Ut < Setting 30.0% 30.0% Option Curve setting for time-dependent under-
2 1 120.0% A1 voltage.
1672 Ut < Delay 1 0.00 s 0.15 s Settings relate to nominal generator
2 20.00 s voltage.
The condition has to be true i.e.
1673 Ut < Setting 30.0% 70.0%
Ut(1)1≤Ut(2)≤Ut(3)≤Ut(4)≤Ut(5)≤Ut(6).
2 2 120.0%
If this is not fulfilled, the worst-case set-
1674 Ut < Delay 2 0.00 s 0.15 s point Ut(6) will be used.
2 20.00 s
1675 Ut < Setting 30.0% 70.0%
2 3 120.0%
1676 Ut < Delay 3 0.00 s 0.70 s
2 20.00 s
1680 Time-dependent undervoltage 2 4-6
1681 Ut < Setting 30.0% 90.0% Option Curve setting for time-dependent under-
2 4 120.0% A1 voltage.
1682 Ut < Delay 4 0.00 s 1.50 s Settings relate to nominal generator
2 20.00 s voltage.
The condition has to be true i.e.
1683 Ut < Setting 30.0% 90.0%
Ut(1)1≤Ut(2)≤Ut(3)≤Ut(4)≤Ut(5)≤Ut(6).
2 5 120.0%
If this is not fulfilled, the worst-case set-
1684 Ut < Delay 5 0.00 s 2.00 s point Ut(6) will be used.
2 20.00 s
1685 Ut < Setting 30.0% 90.0%
2 6 120.0%
1686 Ut < Delay 6 0.00 s 3.00 s
2 20.00 s
1690 Time-dependent undervoltage 2 activation
1691 Ut < Acti- 30.0% 90% Option Activate is the voltage value where the
act 2 vate 120.0% A1 function timer starts.
1692 Ut < Recov- 30.0% 95% Reset is the value where the function
act 2 ery 120.0% timer is reset to 0 ms.

DEIF Page 38 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1693 Ut < Delay 0.0 s 1.00 s Delay is the delay timer for the reset.
act 2 320.0 s The relay outputs will activate
1694 Ut < Relay Not used Not immediately when the function timer
act 2 output Option- used starts.
A dep.
1695 Ut < Relay Not used Not
act 2 output Option- used
B dep.
1696 Ut < Enable OFF OFF
act 2 ON
1700 Time-dependent undervoltage 2
1701 Ut < Relay Not used Not Option The alarm and fail class is activated in-
2 output Option- used A1 stantaneously when the voltage value is
A dep. under the programmed value curve.
1702 Ut < Relay Not used Not
2 output Option- used
B dep.
1703 Ut < Enable OFF OFF
2 ON
1704 Ut < Fail F1…F9 Trip MB
2 class (F6)

DEIF Page 39 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.17 Power-dependent reactive power import


No. Setting Min. Factory Notes Ref. Descrip-
Max. setting tion
1740 G P dep Q< 1-3
1741 G P dep Q< Setpoint 0% 20% Designer's Refer-
Q1 100% ence Handbook
1742 G P dep Q< Setpoint 0% 0%
P1 100%
1743 G P dep Q< Setpoint 0% 22%
Q2 100%
1744 G P dep Q< Setpoint 0% 7%
P2 100%
1745 G P dep Q< Setpoint 0% 27%
Q3 100%
1746 G P dep Q< Setpoint 0% 12%
P3 100%
1750 G P dep Q< 4-6
1751 G P dep Q< Setpoint 0% 18% Designer's Refer-
Q4 100% ence Handbook
1752 G P dep Q< Setpoint 0% 55%
P4 100%
1753 G P dep Q< Setpoint 0% 21%
Q5 100%
1754 G P dep Q< Setpoint 0% 97%
P5 100%
1755 G P dep Q< Setpoint 0% 1%
Q6 100%
1756 G P dep Q< Setpoint 0% 100%
P6 100%
1760 G P dep Q<
1761 G P dep Q< Timer 0.1 s 1.0 s Designer's Refer-
300.0 s ence Handbook
1762 G P dep Q< Relay out- Not used Not used
put A Variant-dep.
1763 G P dep Q< Relay out- Not used Not used
put B Variant-dep.
1764 G P dep Q< Enable OFF OFF
ON
1765 G P dep Q< Fail class F1...F9 Trip GB
(F3)
1766 G P dep Q< S 10-20000 kVA 600 kVA

DEIF Page 40 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.18 Power-dependent reactive power export


No. Setting Min. Factory Notes Ref. Descrip-
Max. setting tion
1770 G P dep Q> 1-3
1771 G P dep Q> Setpoint 0% 88% Designer's Refer-
Q1 100% ence Handbook
1772 G P dep Q> Setpoint 0% 0%
P1 100%
1773 G P dep Q> Setpoint 0% 86%
Q2 100%
1774 G P dep Q> Setpoint 0% 24%
P2 100%
1775 G P dep Q> Setpoint 0% 77%
Q3 100%
1776 G P dep Q> Setpoint 0% 53%
P3 100%
1780 G P dep Q> 4-6
1781 G P dep Q> Setpoint 0% 60% Designer's Refer-
Q4 100% ence Handbook
1782 G P dep Q> Setpoint 0% 80%
P4 100%
1783 G P dep Q> Setpoint 0% 33%
Q5 100%
1784 G P dep Q> Setpoint 0% 95%
P5 100%
1785 G P dep Q> Setpoint 0% 1%
Q6 100%
1786 G P dep Q> Setpoint 0% 100%
P6 100%
1790 G P dep Q>
1791 G P dep Q> Timer 0.1 s 1.0 s Designer's Refer-
300.0 s ence Handbook
1792 G P dep Q> Relay out- Not used Not used
put A Variant-dep.
1793 G P dep Q> Relay out- Not used Not used
put B Variant-dep.
1794 G P dep Q> Enable OFF OFF
ON
1795 G P dep Q> Fail class F1...F9 Trip GB
(F3)
1796 G P dep Q> S 10-20000 kVA 600 kVA

DEIF Page 41 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.19 Non-essential load trip (load shedding)

Setting values relate to the nominal setting.

No. Setting Min. Factory Notes Ref. Description


Max. setting
1800 NEL 1 overcurrent
1801 NEL 1 I> Setpoint 50.0% 100.0% Designer’s Trip of non-essential load
200.0% Reference due to overcurrent. This
1802 NEL 1 I> Timer 0.1 s 5.0 s Handbook function activates NEL
100.0 s group 1.

1803 NEL 1 I> Enable OFF OFF


ON
1810 NEL 2 overcurrent
1811 NEL 2 I> Setpoint 50.0% 100.0% Designer’s Trip of non-essential load
200.0% Reference due to overcurrent. This
1812 NEL 2 I> Timer 0.1 s 8.0 s Handbook function activates NEL
100.0 s group 2.

1813 NEL 2 I> Enable OFF OFF


ON
1820 NEL 3 overcurrent
1821 NEL 3 I> Setpoint 50.0% 100.0% Designer’s Trip of non-essential load
200.0% Reference due to overcurrent. This
1822 NEL 3 I> Timer 0.1 s 10.0 s Handbook function activates NEL
100.0 s group 3.

1823 NEL 3 I> Enable OFF OFF


ON
1830 NEL 1 busbar underfrequency
1831 NEL 1 Setpoint 70.0% 95.0% Designer’s Trip of non-essential load
bus f< 100.0% Reference due to low frequency. This
1832 NEL 1 Timer 0.1 s 5.0 s Handbook function activates NEL
bus f< 100.0 s group 1.

1835 NEL 1 Enable OFF OFF


bus f< ON
1840 NEL 2 busbar underfrequency
1841 NEL 2 Setpoint 70.0% 95.0% Designer’s Trip of non-essential load
bus f< 100.0% Reference due to low frequency. This
1842 NEL 2 Timer 0.1 s 8.0 s Handbook function activates NEL
bus f< 100.0 s group 2.

1845 NEL 2 Enable OFF OFF


bus f< ON

DEIF Page 42 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1850 NEL 3 busbar underfrequency
1851 NEL 3 Setpoint 70.0% 95.0% Designer’s Trip of non-essential load
bus f< 100.0% Reference due to low frequency. This
1852 NEL 3 Timer 0.1 s 10.0 s Handbook function activates NEL
bus f< 100.0 s group 3.

1855 NEL 3 Enable OFF OFF


bus f< ON
1860 NEL 1 overload
1861 NEL 1 Setpoint 10.0% 100.0% Designer’s Trip of non-essential load
P> 200.0% Reference due to overload. This func-
1862 NEL 1 Timer 0.1 s 5.0 s Handbook tion activates NEL group 1.
P> 100.0 s
1865 NEL 1 Enable OFF OFF
P> ON
1870 NEL 2 overload
1871 NEL 2 Setpoint 10.0% 100.0% Designer’s Trip of non-essential load
P> 200.0% Reference due to overload. This func-
1872 NEL 2 Timer 0.1 s 8.0 s Handbook tion activates NEL group 2.
P> 100.0 s
1875 NEL 2 Enable OFF OFF
P> ON
1880 NEL 3 overload
1881 NEL 3 Setpoint 10.0% 100.0% Designer’s Trip of non-essential load
P> 200.0% Reference due to overload. This func-
1882 NEL 3 Timer 0.1 s 10.0 s Handbook tion activates NEL group 3.
P> 100.0 s
1885 NEL 3 Enable OFF OFF
P> ON
1890 NEL 1 high overload
1891 NEL 1 Setpoint 10.0% 110.0% Designer’s Trip of non-essential load
P>> 200.0% Reference due to high overload. This
1892 NEL 1 Timer 0.1 s 1.0 s Handbook function activates NEL
P>> 999.9 s group 1.

1895 NEL 1 Enable OFF OFF


P>> ON
1900 NEL 2 high overload
1901 NEL 2 Setpoint 10.0% 110.0% Designer’s Trip of non-essential load
P>> 200.0% Reference due to high overload. This
1902 NEL 2 Timer 0.1 s 1.0 s Handbook function activates NEL
P>> 999.9 s group 2.

1905 NEL 2 Enable OFF OFF


P>> ON

DEIF Page 43 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
1910 NEL 3 high overload
1911 NEL 3 Setpoint 10.0% 110.0% Designer’s Trip of non-essential load
P>> 200.0% Reference due to high overload. This
1912 NEL 3 Timer 0.1 s 1.0 s Handbook function activates NEL
P>> 999.9 s group 3.

1915 NEL 3 Enable OFF OFF


P>> ON

DEIF Page 44 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.2.20 Undervoltage and reactive power low


No. Setting Min. Factory Notes Ref. Description
Max. setting
1960 U and Q < 1
1961 U and Set 40.0 % 85.0 % Option A1 The setting relates to the genera-
Q<1 point 100.0 % tor nominal voltage.
1962 U and Timer 0.1 s 0.5 s The condition for trip is that the ac-
Q<1 3200.0 s tual voltage drops below the set-
ting value and the reactive power
1963 U and Relay Option- Not
is ≤ 0 kVAr.
Q<1 output dep. used
A
1964 U and Relay Option- Not
Q<1 output dep. used
B
1965 U and Enable OFF OFF
Q<1 ON
1966 U and Fail F1…F9 Warning
Q<1 class (F2)
1970 U and Q < 2
1971 U and Set 40.0 % 85.0 % Option A1 The setting relates to the genera-
Q<2 point 100.0 % tor nominal voltage.
1972 U and Timer 0.1 s 0.5 s The condition for trip is that the ac-
Q<2 3200.0 s tual voltage drops below the set-
ting value and the reactive power
1973 U and Relay Option- Not
is ≤ 0 kVAr.
Q<2 output dep. used
A
1974 U and Relay Option- Not
Q<2 output dep. used
B
1975 U and Enable OFF OFF
Q<2 ON
1976 U and Fail F1…F9 Warning
Q<2 class (F2)
1980 GB/MB external trip
1981 GB ext. Enable OFF ON Design- The generator breaker or the
trip ON er's Refer- mains breaker has been tripped by
1982 GB ext. Fail F1...F9 Warning ence an external device.
trip class (F2) Handbook

1983 MB ext. Enable OFF ON


trip ON
1984 MB ext. Fail F1...F9 Warning
trip class (F2)

DEIF Page 45 of 210


AGC-4 parameter list 4189340688 UK Alarm list

Minimum current and minimum Phi angle

No. Setting Min. Factory Notes Ref. Description


Max. setting
1990 U and Q< 1
1991 I Min. 1 Set 0% 0% Option Settings relate to U and Q< parameters
point 20 % A1 1960 and 1970.
1992 Angle 1 Set 0° 0° Condition for "U and Q<" trip is that the
point 6° current exceeds the I Min. set point.
Min. Phi angle expands the tripping win-
dow.
1990 U and Q< 2
1993 I Min. 2 Set 0% 0% Option Settings relate to U and Q< parameters
point 20 % A1 1960 and 1970.
1994 Angle 2 Set 0° 0° Condition for "U and Q<" trip is that the
point 6° current exceeds the I Min. set point.
Min. Phi angle expands the tripping win-
dow.

DEIF Page 46 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.3 Control parameters - synchronisation


2.3.1 Synchronisation and breaker alarms
No. Setting Min. Factory Notes Ref. Description
Max. setting
2120 Synchronisation window
2121 Sync window Set- 2.0% 15.0% Designer’s The alarm will activate if
point 20.0% Reference the actual voltage devi-
2122 Sync window Timer 0.1 s 0.5 s Handbook ates from nominal voltage
2.0 s with the set percentage.

2123 Sync window Relay Not used Not used


output Option-
A dep.
2124 Sync window Relay Not used Not used
output Option-
B dep.
2125 Sync window Enable OFF OFF
ON
2130 GB/TB/BTB breaker synchronisation failure
2131 GB/TB/BTB Timer 5.0 s 60.0 s Designer’s The controller has unsuc-
sync failure 999.9 s Reference cessfully tried to syn-
2132 GB/TB/BTB Relay Not used Not used Handbook chronise the breaker to
sync failure output Option- the busbar within the time
A dep. delay.

2133 GB/TB/BTB Relay Not used Not used


sync failure output Option-
B dep.
2134 GB/TB/BTB Enable OFF ON
sync failure ON
2135 GB/TB/BTB Fail F1…F9 Block
sync failure class (F1)
2140 Mains breaker synchronisation failure
2141 MB sync failure Timer 5.0 s 60.0 s Designer’s The controller has unsuc-
999.9 s Reference cessfully tried to syn-
2142 MB sync failure Relay Not used Not used Handbook chronise the breaker to
output Option- the busbar within the time
A dep. delay.

2143 MB sync failure Relay Not used Not used


output Option-
B dep.
2144 MB sync failure Enable OFF ON
ON
2145 MB sync failure Fail F1…F9 Warning
class (F2)

DEIF Page 47 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
2150 Phase sequence error DG/Mains/Busbar A
2151 Phase seq er- Relay Not used Not used Designer’s The controller has detec-
ror output Option- Reference ted that the rotation direc-
A dep. Handbook tion is the opposite of the
2152 Phase seq er- Relay Not used Not used selected direction.
ror output Option- Compares phase rotation
B dep. to expected direction at all
times, not only during syn-
2153 Phase seq er- Fail F1…F9 Block
chronisation.
ror class (F1)
2154 Phase rotation Set- L1L2L3 L1L2L3
point L1L3L2
2155 Phase sequence error BB/Busbar B
2155 Phase seq er- Relay Not used Not used The controller has detec-
ror output Option- ted that the rotation direc-
A dep. tion is the opposite of the
selected direction.
Compares phase rotation
to expected direction at all
2156 Phase seq er- Fail F1…F9 Block times, not only during syn-
ror class (F1) chronisation.
2160 GB/TB/BTB open failure
2161 GB/TB/BTB Timer 1.0 s 2.0 s Designer’s The breaker open failure
open fail 10.0 s Reference will occur if the unit has
2162 GB/TB/BTB Relay Not used Not used Handbook transmitted a breaker
open fail output Option- open signal and the
A dep. breaker feedback has not
changed position from ON
2163 GB/TB/BTB Relay Not used Not used
to OFF within the time de-
open fail output Option-
lay.
B dep.
2164 GB/TB/BTB Enable OFF ON
open fail ON
2165 GB/TB/BTB Fail F1…F9 Warning
open fail class (F2)
2170 GB/TB/BTB breaker close failure
2171 GB/TB/BTB Timer 1.0 s 2.0 s Designer’s The breaker close failure
close fail 5.0 s Reference will occur if the unit has
2172 GB/TB/BTB Relay Not used Not used Handbook transmitted a breaker
close fail output Option- close signal and the
A dep. breaker feedback has not
changed position from
2173 GB/TB/BTB Relay Not used Not used
OFF to ON within the time
close fail output Option-
delay.
B dep.
2174 GB/TB/BTB Enable OFF ON
close fail ON
2175 GB/TB/BTB Fail F1…F9 Warning
close fail class (F2)

DEIF Page 48 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
2180 GB/TB/BTB breaker position failure
2181 GB/TB/BTB Timer 1.0 s 1.0 s Designer’s This alarm will occur if the
pos fail 5.0 s Reference breaker feedbacks for ON
2182 GB/TB/BTB Relay Not used Not used Handbook and OFF are both missing
pos fail output Option- or active for more than the
A dep. time delay.

2183 GB/TB/BTB Relay Not used Not used


pos fail output Option-
B dep.
2184 GB/TB/BTB Enable OFF ON
pos fail ON
2185 GB/TB/BTB Fail F1…F9 Warning
pos fail class (F2)
2200 MB open failure
2201 MB open fail Timer 1.0 s 2.0 s Designer’s The breaker open failure
10.0 s Reference will occur if the unit has
2202 MB open fail Relay Not used Not used Handbook transmitted a breaker
output Option- open signal and the
A dep. breaker feedback has not
changed position from ON
2203 MB open fail Relay Not used Not used
to OFF within the time de-
output Option-
lay.
B dep.
2204 MB open fail Enable ON ON
2205 MB open fail Fail F1…F9 Warning
class (F2)
2210 MB close failure
2211 MB close fail Timer 1.0 s 2.0 s Designer’s The breaker close failure
5.0 s Reference will occur if the unit has
2212 MB close fail Relay Not used Not used Handbook transmitted a breaker
output Option- close signal and the
A dep. breaker feedback has not
changed position from
2213 MB close fail Relay Not used Not used
OFF to ON within the time
output Option-
delay.
B dep.
2214 MB close fail Enable ON ON
2215 MB close fail Fail F1…F9 Warning
class (F2)
2220 MB position failure
2221 MB pos fail Timer 1.0 s 1.0 s Designer’s This alarm will occur if the
5.0 s Reference breaker feedbacks for ON
2222 MB pos fail Relay Not used Not used Handbook and OFF are both missing
output Option- or active for more than the
A dep. time delay.

DEIF Page 49 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
2223 MB pos fail Relay Not used Not used
output Option-
B dep.
2224 MB pos fail Enable ON ON
2225 MB pos fail Fail F1…F9 Warning
class (F2)
2270 Close before excitation failure
2271 Cl.bef.exc.fail Timer 0.0 s 5.0 s Designer’s This alarm will occur if the
999.0 s Reference generator and breaker are
2272 Cl.bef.exc.fail Relay Not used Not used Handbook not operating within the
output Option- limits of the Close Before
A dep. Excitation. The alarm will
open the generator break-
2273 Cl.bef.exc.fail Relay Not used Not used
er and enable the regula-
output Option- tion synchronising the
B dep. generator in a normal
2274 Cl.bef.exc.fail Enable OFF ON way.
ON
2275 Cl.bef.exc.fail Fail F1…F9 Warning
class (F2)

DEIF Page 50 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.3.2 Mains sync. inhibit


No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
2280 Mains sync. inhibit settings
2281 M sync. Low 80% 85% Designer's This function is used to inhibit the
inh. U limit U 100% Reference synchronising of the mains breaker
2282 M sync. High 100% 110% Handbook after blackout.
inh. U limit U 120%
2283 M sync. Low 90% 95%
inh. F limit F 100%
2284 M sync. High 100% 101%
inh. F limit F 110%
2285 M sync. Enable OFF OFF
inh. ON
2286 M sync. Fail F1…F9 Trip
inh. class GB
2290 Mains sync. inhibit recovery settings
2291 Delay Recov- 0s 3s Designer's After blackout, the timer in menu
act. re2 ery se- 20 s Reference 2291 will start to run, and if the
lection Handbook mains voltage and frequency are
timer inside the tolerance ranges (menus
2292 Recov- Delay 0s 5s 2281-2282) before the timer runs
ery del. time 60 s out, the short interruption timer
1 (menu 2292) will be started.
When the timers have run out, the
2293 Recov- Relay Not Not
synchronising of MB will start.
ery del. output used used
1 A Option-
dep.
2294 Recov- Delay 0s 60 s
ery del. time 900 s
2
2295 Recov- Relay Not Not
ery del. output used used
2 A Option-
dep.

DEIF Page 51 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.4 Control parameters - regulation


2.4.1 Regulation alarms
No. Setting Min. Factory Notes Ref. Description
Max. setting
2300 Section P>
2301 Sec- MW 0 0 Option T1 Short-circuit limitation: Used to limit
tion P> 30000 the power on the busbar in a power
2302 Sec- KW 0 0 management system.
tion P> 999
Setpoint in menus 2301+2302 are
2303 Sec- Delay 0s 1s used as limit value for max. al-
tion P> 999 s lowed power in the system.
2304 Sec- Relay Not used Not
tion P> output Option- used These values are all common set-
A dep. point in the power management
system.
2305 Sec- Enable On Off
tion P> Off
2306 Sec- Fail F1...F9 Warn-
tion P> class ing (F2)
2310 Section P>
2311 Sec- Factor 1.00 1.0 Option T1 This value is used as a weighing
tion P> 25.5 factor for the Pnom. value KW) of
each transformer or generator in
the power management system. In
case of two equal sized.
2560 Governor regulation fail
2561 Gov. Dead 1.0% 30.0% Design- The alarm is activated if the differ-
reg fail band 100.0% er’s Ref- ence between the measured value
2562 Gov. Timer 10.0 s 60.0 s erence and the setpoint is outside the
reg fail 300.0 s Hand- dead band for longer than the time
book delay.
2563 Gov. Relay Not used Not
reg fail output Option- used
A dep.
2564 Gov. Relay Not used Not
reg fail output Option- used
B dep.
2565 Gov. Fail F1…F9 Warn-
reg fail class ing (F2)
2630 Deload error
2631 Deload Timer 0.0 s 10.0 s Design- The alarm is activated if the gener-
error 60.0 s er’s Ref- ator fails to deload within the time
2632 Deload Relay Not used Not erence delay.
error output Option- used Hand-
A dep. book

2633 Deload Relay Not used Not


error output Option- used
B dep.

DEIF Page 52 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
2634 Deload Enable OFF ON
error ON
2635 Deload Fail F1…F9 Warn-
error class ing (F2)
2680 AVR regulation failure
2681 AVR Dead 1.0% 30.0% Option D1 The alarm is activated if the differ-
reg. band 100.0% ence between the measured value
failure and the setpoint is outside the set-
2682 AVR Timer 10.0 s 60.0 s ting "Dead band" for a longer time
reg. 300.0 s period than specified in the timer
failure setpoint.

1153 AVR Relay Not used Not


reg. output Option- used
failure A dep.
1154 AVR Relay Not used Not
reg. output Option- used
failure B dep.
1155 AVR Fail F1…F9 Warn-
reg. class ing (F2)
failure

These parameters are used when a digital input is used as protection input or to activate a limit
relay.

DEIF Page 53 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.5 Input/output parameters - binary input setup


2.5.1 Digital input 23-27 setup
No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
3000 Digital input 23
3001 Dig. Timer 0.0 s 10.0 s Designer’s The input is configurable and can
input 100.0 s Reference have different functions in different
23 Handbook units.
3002 Dig. Relay Not Not Inputs 24-27 are by default used for
input output used used breaker feedback. These inputs are
23 A Option- only available if no MB or TB is
dep. present in the application.

3003 Dig. Relay Not Not


input output used used
23 B Option-
dep.
3004 Dig. Enable OFF OFF
input ON
23
3005 Dig. Fail F1…F9 Warn-
input class ing
23 (F2)
3006 Dig. High OFF ON
input Alarm ON
23

The same settings apply to inputs 24-27, menus 3010 to 3040.

DEIF Page 54 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.5.2 Digital input 43-55 setup


No. Setting Min. Factory Notes Ref. Description
Max. setting
3130 Digital input 43
3131 Dig. input Timer 0.0 s 10.0 s Option The input is configurable and
43 100.0 s M12 can have different functions
3132 Dig. input Relay out- Not used Not used in different units.
43 put A Option-
dep.
3133 Dig. input Relay out- Not used Not used
43 put B Option-
dep.
3134 Dig. input Enable OFF OFF
43 ON
3135 Dig. input Fail class F1…F9 Warning
43 (F2)
3136 Dig. input High OFF ON
43 Alarm ON

The same settings apply to inputs 44-55, menus 3140 to 3250.

DEIF Page 55 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.5.3 Digital input 91-97 setup


No. Setting Min. Factory Notes Ref. Description
Max. setting
3330 Digital input 91
3331 Dig. in- Timer 0.0 s 10.0 s Option The input is configurable
put 91 100.0 s M13.6 and can have different func-
3332 Dig. in- Relay out- Not used Not used tions in different units.
put 91 put A Option-
dep.
3333 Dig. in- Relay out- Not used Not used
put 91 put B Option-
dep.
3334 Dig. in- Enable OFF OFF
put 91 ON
3335 Dig. in- Fail class F1…F9 Warning
put 91 (F2)
3336 Dig. in- High OFF ON
put 91 Alarm ON

The same settings apply to inputs 92-97, menus 3340 to 3390.

DEIF Page 56 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.5.4 Digital input 102-108 setup


No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
3400 Digital input 102
3401 Wire Enable OFF OFF Designer’s The input is configurable and can
fail 102 ON Reference have different functions in different
3402 Dig. in- Timer 0.0 s 10.0 s Handbook units.
put 102 100.0 s (Only available if multi-input 102 is
configured to "binary" in menu
3403 Dig. in- Relay Not Not
10980).
put 102 output used used
A Option-
dep.
3404 Dig. in- Relay Not Not
put 102 output used used
B Option-
dep.
3405 Dig. in- Enable OFF OFF
put 102 ON
3406 Dig. in- Fail F1…F9 Warn-
put 102 class ing
(F2)
3410 Digital input 105
3411 Wire Enable OFF OFF Designer’s The input is configurable and can
fail 105 ON Reference have different functions in different
3412 Dig. in- Timer 0.0 s 10.0 s Handbook units.
put 105 100.0 s (Only available if multi-input 105 is
configured to "binary" in menu
3413 Dig. in- Relay Not Not
10990).
put 105 output used used
A Option-
dep.
3414 Dig. in- Relay Not Not
put 105 output used used
B Option-
dep.
3415 Dig. in- Enable OFF OFF
put 105 ON
3416 Dig. in- Fail F1…F9 Warn-
put 105 class ing
(F2)
3420 Digital input 108
3421 Wire Enable OFF OFF Designer’s The input is configurable and can
fail 108 ON Reference have different functions in different
3422 Dig. in- Timer 0.0 s 10.0 s Handbook units.
put 108 100.0 s

DEIF Page 57 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
3423 Dig. in- Relay Not Not (Only available if multi-input 108 is
put 108 output used used configured to "binary" in menu
A Option- 11000).
dep.
3424 Dig. in- Relay Not Not
put 108 output used used
B Option-
dep.
3425 Dig. in- Enable OFF OFF
put 108 ON
3426 Dig. in- Fail F1…F9 Warn-
put 108 class ing
(F2)

2.5.5 Digital input 112-117 setup


No. Setting Min. Factory Notes Ref. Description
Max. setting
3430 Digital input 112
3431 Dig. in- Timer 0.0 s 10.0 s Designer’s The input is configurable
put 112 100.0 s Reference and can have different
3432 Dig. in- Relay Not used Not used Handbook functions in different units.
put 112 output A Option-
dep.
3433 Dig. in- Relay Not used Not used
put 112 output B Option-
dep.
3434 Dig. in- Enable OFF OFF
put 112 ON
3435 Dig. in- Fail class F1…F9 Warning
put 112 (F2)
3436 Dig. in- High OFF ON
put 112 Alarm ON

The same settings apply to inputs 113-117, menus 3440 to 3480.

DEIF Page 58 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.5.6 Emergency stop


No. Setting Min. Factory Notes Ref. Description
Max. setting
3490 Emergency stop
3491 Emer. Timer 0.0 s 0.0 s Designer’s Emergency stop input is
stop 60.0 s Reference intended for a normally
3492 Emer. Relay Not used Not used Handbook closed contact.
stop output A Option-
dependent
3493 Emer. Relay Not used Not used
stop output B Option-de-
pendent
3494 Emer. Enable OFF ON
stop ON
3495 Emer. Fail class F1…F9 Shut-
stop down
(F5)

2.5.7 Digital input 127-133 setup


No. Setting Min. Factory Notes Ref. Description
Max. setting
3500 Digital input 127
3501 Dig. in- Timer 0.0 s 10.0 s Option The input is configurable
put 127 100.0 s M13.8 and can have different func-
3502 Dig. in- Relay out- Not used Not used tions in different units.
put 127 put A Option-
dep.
3503 Dig. in- Relay out- Not used Not used
put 127 put B Option-
dep.
3504 Dig. in- Enable OFF OFF
put 127 ON
3505 Dig. in- Fail class F1…F9 Warning
put 127 (F2)
3506 Dig. in- High OFF ON
put 127 Alarm ON

The same settings apply to inputs 128-133, menus 3510 to 3560.

DEIF Page 59 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.5.8 M-Logic alarm 1-5 setup


No. Setting Min. Factory Notes Ref. Description
Max. setting
3570 Mlogic alarm 1
3570 Mlogic alarm 1 Timer 0.0 s 10.0 s The input is configura-
100.0 s ble.
3571 Mlogic alarm 1 Relay output Not used Not used
A Option-dep.
3572 Mlogic alarm 1 Relay output Not used Not used
B Option-dep.
3573 Mlogic alarm 1 Enable OFF OFF
ON
3574 Mlogic alarm 1 Fail class F1…F9 Warning
(F2)
3575 Mlogic alarm 1 High alarm OFF ON
ON

The same settings apply to alarm inputs 2-5, menus 3580 to 3610.

DEIF Page 60 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.6 Input/output parameters - analogue input setup


2.6.1 Analogue input setup (option M15.6)
No. Setting Min. Factory Notes Ref. Description
Max. setting
4000 4-20 mA 91.1
4001 4-20 mA Setpoint 4 mA 10 mA Option M15.6: Configurable analogue
91.1 20 mA 4 x 4-20 mA in- input.
4002 4-20 mA Timer 0.0 s 120.0 s puts
91.1 600.0 s
4003 4-20 mA Relay Not used Not used
91.1 output A Option-
dep.
4004 4-20 mA Relay Not used Not used
91.1 output B Option-
dep.
4005 4-20 mA Enable OFF OFF
91.1 ON
4006 4-20 mA Fail class F1…F9 Warning
91.1 (F2)
4010 4-20 mA 91.2
4011 4-20 mA Setpoint 4 mA 10 mA Option M15.6: Configurable analogue
91.2 20 mA 4 x 4-20 mA in- input.
4012 4-20 mA Timer 0.0 s 120.0 s puts
91.2 600.0 s
4013 4-20 mA Relay Not used Not used
91.2 output A Option-
dep.
4014 4-20 mA Relay Not used Not used
91.2 output B Option-
dep.
4015 4-20 mA Enable OFF OFF
91.2 ON
4016 4-20 mA Fail class F1…F9 Warning
91.2 (F2)
4020 Wire fail 4-20 mA 91
4021 W. fail Relay Not used Not used Option M15.6: The wire fault will de-
ana 91 output A Option- 4 x 4-20 mA in- tect if the current drops
dep. puts below 2 mA or ex-
4022 W. fail Relay Not used Not used ceeds 22 mA. In both
ana 91 output B Option- cases the alarm will be
dep. activated.

4023 W. fail Enable OFF OFF


ana 91 ON
4024 W. fail Fail class F1…F9 Warning
ana 91 (F2)

DEIF Page 61 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4030 4-20 mA 93.1
4031 4-20 mA Setpoint 4 mA 10 mA Option M15.6: Configurable analogue
93.1 20 mA 4 x 4-20 mA in- input.
4032 4-20 mA Timer 0.0 s 120.0 s puts
93.1 600.0 s
4033 4-20 mA Relay Not used Not used
93.1 output A Option-
dep.
4034 4-20 mA Relay Not used Not used
93.1 output B Option-
dep.
4035 4-20 mA Enable OFF OFF
93.1 ON
4036 4-20 mA Fail class F1…F9 Warning
93.1 (F2)
4040 4-20 mA 93.2
4041 4-20 mA Setpoint 4 mA 10 mA Option M15.6: Configurable analogue
93.2 20 mA 4 x 4-20 mA in- input.
4042 4-20 mA Timer 0.0 s 120.0 s puts
93.2 600.0 s
4043 4-20 mA Relay Not used Not used
93.2 output A Option-
dep.
4044 4-20 mA Relay Not used Not used
93.2 output B Option-
dep.
4045 4-20 mA Enable OFF OFF
93.2 ON
4046 4-20 mA Fail class F1…F9 Warning
93.2 (F2)
4050 Wire fail 4-20 mA 93
4051 W. fail Relay Not used Not used Option M15.6: The wire fault will de-
ana 93 output A Option- 4 x 4-20 mA in- tect if the current drops
dep. puts below 2 mA or ex-
4052 W. fail Relay Not used Not used ceeds 22 mA. In both
ana 93 output B Option- cases the alarm will be
dep. activated.

4053 W. fail Enable OFF OFF


ana 93 ON
4054 W. fail Fail class F1…F9 Warning
ana 93 (F2)

DEIF Page 62 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4060 4-20 mA 95.1
4061 4-20 mA Setpoint 4 mA 10 mA Option M15.6: Configurable analogue
95.1 20 mA 4 x 4-20 mA in- input.
4062 4-20 mA Timer 0.0 s 120.0 s puts
95.1 600.0 s
4063 4-20 mA Relay Not used Not used
95.1 output A Option-
dep.
4064 4-20 mA Relay Not used Not used
95.1 output B Option-
dep.
4065 4-20 mA Enable OFF OFF
95.1 ON
4066 4-20 mA Fail class F1…F9 Warning
95.1 (F2)
4070 4-20 mA 95.2
4071 4-20 mA Setpoint 4 mA 10 mA Option M15.6: Configurable analogue
95.2 20 mA 4 x 4-20 mA in- input.
4072 4-20 mA Timer 0.0 s 120.0 s puts
95.2 600.0 s
4073 4-20 mA Relay Not used Not used
95.2 output A Option-
dep.
4074 4-20 mA Relay Not used Not used
95.2 output B Option-
dep.
4075 4-20 mA Enable OFF OFF
95.2 ON
4076 4-20 mA Fail class F1…F9 Warning
95.2 (F2)
4080 Wire fail 4-20 mA 95
4081 W. fail Relay Not used Not used Option M15.6: The wire fault will de-
ana 95 output A Option- 4 x 4-20 mA in- tect if the current drops
dep. puts below 2 mA or ex-
4082 W. fail Relay Not used Not used ceeds 22 mA. In both
ana 95 output B Option- cases the alarm will be
dep. activated.

4083 W. fail Enable OFF OFF


ana 95 ON
4084 W. fail Fail class F1…F9 Warning
ana 95

DEIF Page 63 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4090 4-20 mA 97.1
4091 4-20 mA Setpoint 4 mA 10 mA Option M15.6: Configurable analogue
97.1 20 mA 4 x 4-20 mA in- input.
4092 4-20 mA Timer 0.0 s 120.0 s puts
97.1 600.0 s
4093 4-20 mA Relay Not used Not used
97.1 output A Option-
dep.
4094 4-20 mA Relay Not used Not used
97.1 output B Option-
dep.
4095 4-20 mA Enable OFF OFF
97.1 ON
4096 4-20 mA Fail class F1…F9 Warning
97.1 (F2)
4100 4-20 mA 97.2
4101 4-20 mA Setpoint 4 mA 10 mA Option M15.6: Configurable analogue
97.2 20 mA 4 x 4-20 mA in- input.
4102 4-20 mA Timer 0.0 s 120.0 s puts
97.2 600.0 s
4103 4-20 mA Relay Not used Not used
97.2 output A Option-
dep.
4104 4-20 mA Relay Not used Not used
97.2 output B Option-
dep.
4105 4-20 mA Enable OFF OFF
97.2 ON
4106 4-20 mA Fail class F1…F9 Warning
97.2 (F2)
4110 Wire fail 4-20 mA 97
4111 W. fail Relay Not used Not used Option M15.6: The wire fault will de-
ana 97 output A Option- 4 x 4-20 mA in- tect if the current drops
dep. puts below 2 mA or ex-
4112 W. fail Relay Not used Not used ceeds 22 mA. In both
ana 97 output B Option- cases the alarm will be
dep. activated.

4113 W. fail Enable OFF OFF


ana 97 ON
4114 W. fail Fail class F1…F9 Warning
ana 97 (F2)

DEIF Page 64 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.6.2 Analogue input setup (option M15.8)


No. Setting Min. Factory Notes Ref. Description
Max. setting
4800 4-20 mA 127.1
4801 4-20 mA Setpoint 4 mA 10 mA Option: Configurable ana-
127.1 20 mA 4 x 4-20 mA in- logue input.
4802 4-20 mA Timer 0.0 s 120.0 s puts (M15.8)
127.1 600.0 s
4803 4-20 mA Relay Not used Not used
127.1 output A Option-
dep.
4804 4-20 mA Relay Not used Not used
127.1 output B Option-
dep.
4805 4-20 mA Enable OFF OFF
127.1 ON
4806 4-20 mA Fail F1…F9 Warning
127.1 class (F2)
4810 4-20 mA 127.2
4811 4-20 mA Setpoint 4 mA 10 mA Option: Configurable ana-
127.2 20 mA 4 x 4-20 mA in- logue input.
4812 4-20 mA Timer 0.0 s 120.0 s puts (M15.8)
127.2 600.0 s
4813 4-20 mA Relay Not used Not used
127.2 output A Option-
dep.
4814 4-20 mA Relay Not used Not used
127.2 output B Option-
dep.
4815 4-20 mA Enable OFF OFF
127.2 ON
4816 4-20 mA Fail F1…F9 Warning
127.2 class (F2)
4820 wire fail 4-20 mA 127
4821 W. fail Relay Not used Not used Option: The wire fault will de-
ana 127 output A Option- 4 x 4-20 mA in- tect if the current
dep. puts (M15.8) drops below 2 mA or
4822 W. fail Relay Not used Not used exceeds 22 mA. In
ana 127 output B Option- both cases the alarm
dep. will be activated.

4823 W. fail Enable OFF OFF


ana 127 ON
4824 W. fail Fail F1…F9 Warning
ana 127 class (F2)

DEIF Page 65 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4830 4-20 mA 129.1
4831 4-20 mA Setpoint 4 mA 10 mA Option: Configurable ana-
129.1 20 mA 4 x 4-20 mA in- logue input.
4832 4-20 mA Timer 0.0 s 120.0 s puts (M15.8)
129.1 600.0 s
4833 4-20 mA Relay Not used Not used
129.1 output A Option-
dep.
4834 4-20 mA Relay Not used Not used
129.1 output B Option-
dep.
4835 4-20 mA Enable OFF OFF
129.1 ON
4836 4-20 mA Fail F1…F9 Warning
129.1 class (F2)
4840 4-20 mA 129
4841 4-20 mA Setpoint 4 mA 10 mA Option: Configurable ana-
129 20 mA 4 x 4-20 mA in- logue input.
4842 4-20 mA Timer 0.0 s 120.0 s puts (M15.8)
129 600.0 s
4843 4-20 mA Relay Not used Not used
129 output A Option-
dep.
4844 4-20 mA Relay Not used Not used
129 output B Option-
dep.
4845 4-20 mA Enable OFF OFF
129 ON
4846 4-20 mA Fail F1…F9 Warning
129 class (F2)
4850 Wire fail 4-20 mA 129.2
4851 W. fail Relay Not used Not used Option: The wire fault will de-
ana 129 output A Option- 4 x 4-20 mA in- tect if the current
dep. puts (M15.8) drops below 2 mA or
4852 W. fail Relay Not used Not used exceeds 22 mA. In
ana 129 output B Option- both cases the alarm
dep. will be activated.

4853 W. fail Enable OFF OFF


ana 129 ON
4854 W. fail Fail F1…F9 Warning
ana 129 class (F2)

DEIF Page 66 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4860 4-20 mA 131.1
4861 4-20 mA Setpoint 4 mA 10 mA Option: Configurable ana-
131.1 20 mA 4 x 4-20 mA in- logue input.
4862 4-20 mA Timer 0.0 s 120.0 s puts (M15.8)
131.1 600.0 s
4863 4-20 mA Relay Not used Not used
131.1 output A Option-
dep.
4864 4-20 mA Relay Not used Not used
131.1 output B Option-
dep.
4865 4-20 mA Enable OFF OFF
131.1 ON
4866 4-20 mA Fail F1…F9 Warning
131.1 class (F2)
4870 4-20 mA 131.2
4871 4-20 mA Setpoint 4 mA 10 mA Option: Configurable ana-
131.2 20 mA 4 x 4-20 mA in- logue input.
4872 4-20 mA Timer 0.0 s 120.0 s puts (M15.8)
131.2 600.0 s
4873 4-20 mA Relay Not used Not used
131.2 output A Option-
dep.
4874 4-20 mA Relay Not used Not used
131.2 output B Option-
dep.
4875 4-20 mA Enable OFF OFF
131.2 ON
4876 4-20 mA Fail F1…F9 Warning
131.2 class (F2)
4880 Wire fail 4-20 mA 131
4881 W. fail Relay Not used Not used Option: The wire fault will de-
ana 131 output A Option- 4 x 4-20 mA in- tect if the current
dep. puts (M15.8) drops below 2 mA or
4882 W. fail Relay Not used Not used exceeds 22 mA. In
ana 131 output B Option- both cases the alarm
dep. will be activated.

4883 W. fail Enable OFF OFF


ana 131 ON
4884 W. fail Fail F1…F9 Warning
ana 131 class (F2)

DEIF Page 67 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4890 4-20 mA 133.1
4891 4-20 mA Setpoint 4 mA 10 mA Option: Configurable ana-
133.1 20 mA 4 x 4-20 mA in- logue input.
4892 4-20 mA Timer 0.0 s 120.0 s puts (M15.8)
133.1 600.0 s
4893 4-20 mA Relay Not used Not used
133.1 output A Option-
dep.
4894 4-20 mA Relay Not used Not used
133.1 output B Option-
dep.
4895 4-20 mA Enable OFF OFF
133.1 ON
4896 4-20 mA Fail F1…F9 Warning
133.1 class (F2)
4900 4-20 mA 133.2
4901 4-20 mA Setpoint 4 mA 10 mA Option: Configurable ana-
133.2 20 mA 4 x 4-20 mA in- logue input.
4902 4-20 mA Timer 0.0 s 120.0 s puts (M15.8)
133.2 600.0 s
4903 4-20 mA Relay Not used Not used
133.2 output A Option-
dep.
4904 4-20 mA Relay Not used Not used
133.2 output B Option-
dep.
4905 4-20 mA Enable OFF OFF
133.2 ON
4906 4-20 mA Fail F1…F9 Warning
133.2 class (F2)
4910 Wire fail 4-20 mA 133
4911 W. fail Relay Not used Not used Option: The wire fault will de-
ana 133 output A Option- 4 x 4-20 mA in- tect if the current
dep. puts (M15.8) drops below 2 mA or
4912 W. fail Relay Not used Not used exceeds 22 mA. In
ana 133 output B Option- both cases the alarm
dep. will be activated.

4913 W. fail Enable OFF OFF


ana 133 ON
4914 W. fail ana Fail F1…F9 Warning
133 class (F2)

DEIF Page 68 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.6.3 Analogue input setup (option M16.6)


No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
4000 4-20 mA 91.1
4001 4-20 Set- 4 mA 10 mA Three different input The value shown in this
mA point 20 mA types are available parameter group is
91.1 with Option M16.6: available when 4-20 mA
4002 4-20 Timer 0.0 s 120.0 s ● 4-20 mA is selected in parameter
mA 600.0 s ● 0-5 V 11120.
91.1 ● Pt100

4003 4-20 Relay Not used Not


mA output Option- used
91.1 A dep.
4004 4-20 Relay Not used Not
mA output Option- used
91.1 B dep.
4005 4-20 Enable OFF OFF
mA ON
91.1
4006 4-20 Fail F1…F9 Warn-
mA class ing
91.1 (F2)
4000 VDC 91.1
4001 VDC Set- 0V 2V Three different input The value shown in this
91.1 point 5V types are available parameter group are
4002 VDC Timer 0.0 s 120.0 s with Option M16.6: available when 0-5 V is
91.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11120.
4003 VDC Relay Not used Not
● Pt100
91.1 output Option- used
A dep.
4004 VDC Relay Not used Not
91.1 output Option- used
B dep.
4005 VDC Enable OFF OFF
91.1 ON
4006 VDC Fail F1…F9 Warn-
91.1 class ing
(F2)
4000 Pt100 91.1
4001 Pt100 Set- -49°C 80°C Three different input The value shown in this
91.1 point 482°C types are available parameter group is
with Option M16.6: available when Pt100 is
selected in parameter

DEIF Page 69 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4002 Pt100 Timer 0.0 s 120.0 s ● 4-20 mA 11120.
91.1 600.0 s ● 0-5 V
● Pt100
4003 Pt100 Relay Not used Not
91.1 output Option- used
A dep.
4004 Pt100 Relay Not used Not
91.1 output Option- used
B dep.
4005 Pt100 Enable OFF OFF
91.1 ON
4006 Pt100 Fail F1…F9 Warn-
91.1 class ing
(F2)
4010 4-20 mA 91.2
4011 4-20 Set- 4 mA 10 mA Three different input The value shown in this
mA point 20 mA types are available parameter group is
91.2 with Option M16.6: available when 4-20 mA
4012 4-20 Timer 0.0 s 120.0 s ● 4-20 mA is selected in parameter
mA 600.0 s ● 0-5 V 11120.
91.2 ● Pt100

4013 4-20 Relay Not used Not


mA output Option- used
91.2 A dep.
4014 4-20 Relay Not used Not
mA output Option- used
91.2 B dep.
4015 4-20 Enable OFF OFF
mA ON
91.2
4016 4-20 Fail F1…F9 Warn-
mA class ing
91.2 (F2)
4010 VDC 91.2
4011 VDC Set- 0V 2V Three different input The value shown in this
91.2 point 5V types are available parameter group is
4012 VDC Timer 0.0 s 120.0 s with Option M16.6: available when 0-5 V is
91.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11120.
4013 VDC Relay Not used Not
● Pt100
91.2 output Option- used
A dep.
4014 VDC Relay Not used Not
91.2 output Option- used
B dep.

DEIF Page 70 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4015 VDC Enable OFF OFF
91.2 ON
4016 VDC Fail F1…F9 Warn-
91.2 class ing
(F2)
4010 Pt100 91.2
4011 Pt100 Set- -49°C 80°C Three different input The value shown in this
91.2 point 482°C types are available parameter group is
4012 Pt100 Timer 0.0 s 120.0 s with Option M16.6: available when Pt100 is
91.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11120.
4013 Pt100 Relay Not used Not
● Pt100
91.2 output Option- used
A dep.
4014 Pt100 Relay Not used Not
91.2 output Option- used
B dep.
4015 Pt100 Enable OFF OFF
91.2 ON
4016 Pt100 Fail F1…F9 Warn-
91.2 class ing
(F2)
4020 Wire fail 91
4021 W. fail Relay Not used Not Option M16.6 For function descriptio-
ana 91 output Option- used no of wire fail, see the
A dep. Option M16 manual.
4022 W. fail Relay Not used Not
ana 91 output Option- used
B dep.
4023 W. fail Enable OFF OFF
ana 91 ON
4024 W. fail Fail F1…F9 Warn-
ana 91 class ing
(F2)
4030 4-20 mA 93.1
4031 4-20 Set- 4 mA 10 mA Three different input The value shown in this
mA point 20 mA types are available parameter group is
93.1 with Option M16.6: available when 4-20 mA
4032 4-20 Timer 0.0 s 120.0 s ● 4-20 mA is selected in parameter
mA 600.0 s ● 0-5 V 11130.
93.1 ● Pt100

4033 4-20 Relay Not used Not


mA output Option- used
93.1 A dep.
4034 4-20 Relay Not used Not
mA output Option- used
93.1 B dep.

DEIF Page 71 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4035 4-20 Enable OFF OFF
mA ON
93.1
4036 4-20 Fail F1…F9 Warn-
mA class ing
93.1 (F2)
4030 VDC 93.1
4031 VDC Set- 0V 2V Three different input The value shown in this
93.1 point 5V types are available parameter group is
4032 VDC Timer 0.0 s 120.0 s with Option M16.6: available when 0-5 V is
93.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11130.
4033 VDC Relay Not used Not
● Pt100
93.1 output Option- used
A dep.
4034 VDC Relay Not used Not
93.1 output Option- used
B dep.
4035 VDC Enable OFF OFF
93.1 ON
4036 VDC Fail F1…F9 Warn-
93.1 class ing
(F2)
4030 Pt100 93.1
4031 Pt100 Set- -49°C 80°C Three different input The value shown in this
93.1 point 482°C types are available parameter group is
4032 Pt100 Timer 0.0 s 120.0 s with Option M16.6: available when Pt100 is
93.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11130.
4033 Pt100 Relay Not used Not
● Pt100
93.1 output Option- used
A dep.
4034 Pt Relay Not used Not
93.1 output Option- used
B dep.
4035 Pt100 Enable OFF OFF
93.1 ON
4036 Pt100 Fail F1…F9 Warn-
93.1 class ing
(F2)

DEIF Page 72 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4040 4-20 mA 93.2
4041 4-20 Set- 4 mA 10 mA Three different input The value shown in this
mA point 20 mA types are available parameter group is
93.2 with Option M16.6: available when 4-20 mA
4042 4-20 Timer 0.0 s 120.0 s ● 4-20 mA is selected in parameter
mA 600.0 s ● 0-5 V 11130.
93.2 ● Pt100

4043 4-20 Relay Not used Not


mA output Option- used
93.2 A dep.
4044 4-20 Relay Not used Not
mA output Option- used
93.2 B dep.
4045 4-20 Enable OFF OFF
mA ON
93.2
4046 4-20 Fail F1…F9 Warn-
mA class ing
93.2 (F2)
4040 VDC 93.2
4041 VDC Set- 0V 2V Three different input The value shown in this
93.2 point 5V types are available parameter group is
4042 VDC Timer 0.0 s 120.0 s with Option M16.6: available when 0-5 V is
93.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11130.
4043 VDC Relay Not used Not
● Pt100
93.2 output Option- used
A dep.
4044 VDC Relay Not used Not
93.2 output Option- used
B dep.
4045 VDC Enable OFF OFF
93.2 ON
4046 VDC Fail F1…F9 Warn-
93.2 class ing
(F2)
4040 Pt100 93.2
4041 Pt100 Set- -49°C 80°C Three different input The value shown in this
93.2 point 482°C types are available parameter group is
4042 Pt100 Timer 0.0 s 120.0 s with Option M16.6: available when Pt100 is
93.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11130.
4043 Pt100 Relay Not used Not ● Pt100
93.2 output Option- used
A dep.
4044 Pt100 Relay Not used Not
93.2 output Option- used
B dep.

DEIF Page 73 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4045 Pt100 Enable OFF OFF
93.2 ON
4046 Pt100 Fail F1…F9 Warn-
93.2 class ing
(F2)
4050 Wire fail 93
4051 W. fail Relay Not used Not Option M15.6 For function description
ana 93 output Option- used of wire fail, see the Op-
A dep. tion M16 manual.
4052 W. fail Relay Not used Not
ana 93 output Option- used
B dep.
4053 W. fail Enable OFF OFF
ana 93 ON
4054 W. fail Fail F1…F9 Warn-
ana 93 class ing
(F2)
4060 4-20 mA 95.1
4061 4-20 Set- 4 mA 10 mA Three different input The value shown in this
mA point 20 mA types are available parameter group is
95.1 with Option M16.6: available when 4-20 mA
4062 4-20 Timer 0.0 s 120.0 s ● 4-20 mA is selected in parameter
mA 600.0 s ● 0-5 V 11140.
95.1 ● Pt100

4063 4-20 Relay Not used Not


mA output Option- used
95.1 A dep.
4064 4-20 Relay Not used Not
mA output Option- used
95.1 B dep.
4065 4-20 Enable OFF OFF
mA ON
95.1
4066 4-20 Fail F1…F9 Warn-
mA class ing
95.1 (F2)
4060 VDC 95.1
4061 VDC Set- 0V 2V Three different input The value shown in this
95.1 point 5V types are available parameter group is
with Option M16.6: available when 0-5 V is
4062 VDC Timer 0.0 s 120.0 s ● 4-20 mA selected in parameter
95.1 600.0 s ● 0-5 V 11140.
● Pt100

DEIF Page 74 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4060 VDC 95.1
4063 VDC Relay Not used Not
95.1 output Option- used
A dep.
4064 VDC Relay Not used Not
95.1 output Option- used
B dep.
4065 VDC Enable OFF OFF
95.1 ON
4066 VDC Fail F1…F9 Warn-
95.1 class ing
(F2)
4060 Pt100 95.1
4061 Pt100 Set- -49°C 80°C Three different input The value shown in this
95.1 point 482°C types are available parameter group is
4062 Pt100 Timer 0.0 s 120.0 s with Option M16.6: available when Pt100 is
95.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11140.
4063 Pt Relay Not used Not
● Pt100
95.1 output Option- used
A dep.
4064 Pt Relay Not used Not
95.1 output Option- used
B dep.
4065 Pt100 Enable OFF OFF
95.1 ON
4066 Pt100 Fail F1…F9 Warn-
95.1 class ing
(F2)
4070 4-20 mA 95.2
4071 4-20 Set- 4 mA 10 mA Three different input The value shown in this
mA point 20 mA types are available parameter group is
95.2 with Option M16.6: available when 4-20 mA
4072 4-20 Timer 0.0 s 120.0 s ● 4-20 mA is selected in parameter
mA 600.0 s ● 0-5 V 11140.
95.2 ● Pt100

4073 4-20 Relay Not used Not


mA output Option- used
95.2 A dep.
4074 4-20 Relay Not used Not
mA output Option- used
95.2 B dep.
4075 4-20 Enable OFF OFF
mA ON
95.2

DEIF Page 75 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4076 4-20 Fail F1…F9 Warn-
mA class ing
95.2 (F2)
4070 VDC 95.2
4071 VDC Set- 0V 2V Three different input The value shown in this
95.2 point 5V types are available parameter group is
4072 VDC Timer 0.0 s 120.0 s with Option M16.6: available when 0-5 V is
95.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11140.
4073 VDC Relay Not used Not
● Pt100
95.2 output Option- used
A dep.
4074 VDC Relay Not used Not
95.2 output Option- used
B dep.
4075 VDC Enable OFF OFF
95.2 ON
4076 VDC Fail F1…F9 Warn-
95.2 class ing
(F2)
4070 Pt100 95.2
4071 Pt100 Set- -49°C 80°C Three different input The value shown in this
95.2 point 482°C types are available parameter group is
4072 Pt100 Timer 0.0 s 120.0 s with Option M16.6: available when Pt100 is
95.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11140.
4073 Pt100 Relay Not used Not
● Pt100
95.2 output Option- used
A dep.
4074 Pt Relay Not used Not
95.2 output Option- used
B dep.
4075 Pt100 Enable OFF OFF
95.2 ON
4076 Pt100 Fail F1…F9 Warn-
95.2 class ing
(F2)
4080 Wire fail 95
4081 W. fail Relay Not used Not Option M16.6 For function description
ana 95 output Option- used of wire fail, see the Op-
A dep. tion M16 manual.
4082 W. fail Relay Not used Not
ana 95 output Option- used
B dep.
4083 W. fail Enable OFF OFF
ana 95 ON
4084 W. fail Fail F1…F9 Warn-
ana 95 class ing

DEIF Page 76 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4090 4-20 mA 97.1
4091 4-20 Set- 4 mA 10 mA Three different input The value shown in this
mA point 20 mA types are available parameter group is
97.1 with Option M16.6: available when 4-20 mA
4092 4-20 Timer 0.0 s 120.0 s ● 4-20 mA is selected in parameter
mA 600.0 s ● 0-5 V 11150.
97.1 ● Pt100

4093 4-20 Relay Not used Not


mA output Option- used
97.1 A dep.
4094 4-20 Relay Not used Not
mA output Option- used
97.1 B dep.
4095 4-20 Enable OFF OFF
mA ON
97.1
4096 4-20 Fail F1…F9 Warn-
mA class ing
97.1 (F2)
4090 VDC 97.1
4091 VDC Set- 0V 2V Three different input The value shown in this
97.1 point 5V types are available parameter group is
4092 VDC Timer 0.0 s 120.0 s with Option M16.6: available when 0-5 V is
97.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11150.
4093 VDC Relay Not used Not
● Pt100
97.1 output Option- used
A dep.
4094 VDC Relay Not used Not
97.1 output Option- used
B dep.
4095 VDC Enable OFF OFF
97.1 ON
4096 VDC Fail F1…F9 Warn-
97.1 class ing
(F2)
4090 Pt100 97.1
4091 Pt100 Set- -49°C 80°C Three different input The value shown in this
97.1 point 482°C types are available parameter group is
4092 Pt100 Timer 0.0 s 120.0 s with Option M16.6: available when Pt100 is
97.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11150.
4093 Pt100 Relay Not used Not ● Pt100
97.1 output Option- used
A dep.
4094 Pt100 Relay Not used Not
97.1 output Option- used
B dep.

DEIF Page 77 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4095 Pt100 Enable OFF OFF
97.1 ON
4096 Pt100 Fail F1…F9 Warn-
97.1 class ing
(F2)
4100 4-20 mA 97.2
4101 4-20 Set- 4 mA 10 mA Three different input The value shown in this
mA point 20 mA types are available parameter group is
97.2 with Option M16.6: available when 4-20 mA
4102 4-20 Timer 0.0 s 120.0 s ● 4-20 mA is selected in parameter
mA 600.0 s ● 0-5 V 11150.
97.2 ● Pt100

4103 4-20 Relay Not used Not


mA output Option- used
97.2 A dep.
4104 4-20 Relay Not used Not
mA output Option- used
97.2 B dep.
4105 4-20 Enable OFF OFF
mA ON
97.2
4106 4-20 Fail F1…F9 Warn-
mA class ing
97.2 (F2)
4100 VDC 97.2
4101 VDC Set- 0V 2V Three different input The value shown in this
97.2 point 5V types are available parameter group is
4102 VDC Timer 0.0 s 120.0 s with Option M16.6: available when 0-5 V is
97.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11150.
4103 VDC Relay Not used Not ● Pt100
97.2 output Option- used
A dep.
4104 VDC Relay Not used Not
97.2 output Option- used
B dep.
4105 VDC Enable OFF OFF
97.2 ON
4106 VDC Fail F1…F9 Warn-
97.2 class ing
(F2)
4100 Pt100 97.2
4101 Pt100 Set- -49°C 80°C Three different input The value shown in this
97.2 point 482°C types are available parameter group is
4102 Pt100 Timer 0.0 s 120.0 s with Option M16.6: available when Pt100 is
97.2 600.0 s ● 4-20 mA selected in parameter

DEIF Page 78 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4103 Pt100 Relay Not used Not ● 0-5 V 11150.
97.2 output Option- used ● Pt100
A dep.
4104 Pt100 Relay Not used Not
97.2 output Option- used
B dep.
4105 Pt100 Enable OFF OFF
97.2 ON
4106 Pt100 Fail F1…F9 Warn-
97.2 class ing
(F2)
4110 Wire fail 97
4111 W. fail Relay Not used Not Option M15.6 For function description
ana 97 output Option- used or wire fail, see the Op-
A dep. tion M16 manual.
4112 W. fail Relay Not used Not
ana 97 output Option- used
B dep.
4113 W. fail Enable OFF OFF
ana 97 ON
4114 W. fail Fail F1…F9 Warn-
ana 97 class ing
(F2)

DEIF Page 79 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.6.4 Analogue input setup (option M16.8)


No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
4800 4-20 mA 127.1
4801 4-20 mA Set- 4 mA 10 mA Three different input The value shown in this
127.1 point 20 mA types are available parameter group is
4802 4-20 mA Timer 0.0 s 120.0 s with Option M16.8: available when 4-20 mA
127.1 600.0 s ● 4-20 mA is selected in parameter
● 0-5 V 11160.
4803 4-20 mA Relay Not used Not
● Pt100
127.1 output Option- used
A dep.
4804 4-20 mA Relay Not used Not
127.1 output Option- used
B dep.
4805 4-20 mA Enable OFF OFF
127.1 ON
4806 4-20 mA Fail F1…F9 Warn-
127.1 class ing
(F2)
4800 VDC 127.1
4801 VDC Set- 0V 2V Three different input The value shown in this
127.1 point 5V types are available parameter group are
4802 VDC Timer 0.0 s 120.0 s with Option M16.8: available when 0-5 V is
127.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11160.
4803 VDC Relay Not used Not
● Pt100
127.1 output Option- used
A dep.
4804 VDC Relay Not used Not
127.1 output Option- used
B dep.
4805 VDC Enable OFF OFF
127.1 ON
4806 VDC Fail F1…F9 Warn-
127.1 class ing
(F2)
4800 Pt100 127.1
4801 Pt100 Set- -49°C 80°C Three different input The value shown in this
127.1 point 482°C types are available parameter group is
4802 Pt100 Timer 0.0 s 120.0 s with Option M16.8: available when Pt100 is
127.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11160.
4803 Pt100 Relay Not used Not ● Pt100
127.1 output Option- used
A dep.
4804 Pt100 Relay Not used Not
127.1 output Option- used
B dep.

DEIF Page 80 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4805 Pt100 Enable OFF OFF
127.1 ON
4806 Pt100 Fail F1…F9 Warn-
127.1 class ing
(F2)
4810 4-20 mA 127.2
4811 4-20 mA Set- 4 mA 10 mA Three different input The value shown in this
127.2 point 20 mA types are available parameter group is
4812 4-20 mA Timer 0.0 s 120.0 s with Option M16.8: available when 4-20 mA
1271.2 600.0 s ● 4-20 mA is selected in parameter
● 0-5 V 11160.
4813 4-20 mA Relay Not used Not
● Pt100
127.2 output Option- used
A dep.
4814 4-20 mA Relay Not used Not
127.2 output Option- used
B dep.
4815 4-20 mA Enable OFF OFF
127.2 ON
4816 4-20 mA Fail F1…F9 Warn-
127.2 class ing
(F2)
4810 VDC 127.2
4811 VDC Set- 0V 2V Three different input The value shown in this
127.2 point 5V types are available parameter group is
4812 VDC Timer 0.0 s 120.0 s with Option M16.8: available when 0-5 V is
127.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11160.
4813 VDC Relay Not used Not
● Pt100
127.2 output Option- used
A dep.
4814 VDC Relay Not used Not
127.2 output Option- used
B dep.
4815 VDC Enable OFF OFF
127.2 ON
4816 VDC Fail F1…F9 Warn-
127.2 class ing
(F2)
4810 Pt100 127.2
4811 Pt100 Set- -49°C 80°C Three different input The value shown in this
127.2 point 482°C types are available parameter group is
4812 Pt100 Timer 0.0 s 120.0 s with Option M16.8: available when Pt100 is
127.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11160.
4813 Pt100 Relay Not used Not
● Pt100
127.2 output Option- used
A dep.

DEIF Page 81 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4810 Pt100 127.2
4814 Pt100 Relay Not used Not
127.2 output Option- used
B dep.
4815 Pt100 Enable OFF OFF
127.2 ON
4816 Pt100 Fail F1…F9 Warn-
127.2 class ing
(F2)
4820 Wire fail 127
4821 W. fail Relay Not used Not Option M16.8 For function descriptio-
ana 127 output Option- used no of wire fail, see the
A dep. Option M16 manual.
4822 W. fail Relay Not used Not
ana 127 output Option- used
B dep.
4823 W. fail Enable OFF OFF
ana 127 ON
4824 W. fail Fail F1…F9 Warn-
ana 127 class ing
(F2)
4830 4-20 mA 129.1
4831 4-20 mA Set- 4 mA 10 mA Three different input The value shown in this
129.1 point 20 mA types are available parameter group is
4832 4-20 mA Timer 0.0 s 120.0 s with Option M16.8: available when 4-20 mA
129.1 600.0 s ● 4-20 mA is selected in parameter
● 0-5 V 11170.
4833 4-20 mA Relay Not used Not
● Pt100
129.1 output Option- used
A dep.
4834 4-20 mA Relay Not used Not
129.1 output Option- used
B dep.
4835 4-20 mA Enable OFF OFF
129.1 ON
4836 4-20 mA Fail F1…F9 Warn-
129.1 class ing
(F2)
4830 VDC 129.1
4831 VDC Set- 0V 2V Three different input The value shown in this
129.1 point 5V types are available parameter group is
4832 VDC Timer 0.0 s 120.0 s with Option M16.8: available when 0-5 V is
129.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11170.
4833 VDC Relay Not used Not ● Pt100
129.1 output Option- used
A dep.

DEIF Page 82 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4834 VDC Relay Not used Not
129.1 output Option- used
B dep.
4835 VDC Enable OFF OFF
129.1 ON
4836 VDC Fail F1…F9 Warn-
129.1 class ing
(F2)
4830 Pt100 129.1
4831 Pt100 Set- -49°C 80°C Three different input The value shown in this
129.1 point 482°C types are available parameter group is
4832 Pt100 Timer 0.0 s 120.0 s with Option M16.8: available when Pt100 is
129.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11170.
4833 Pt Relay Not used Not
● Pt100
129.1 output Option- used
A dep.
4834 Pt100 Relay Not used Not
129.1 output Option- used
B dep.
4835 Pt100 Enable OFF OFF
129.1 ON
4836 Pt100 Fail F1…F9 Warn-
129.1 class ing
(F2)
4840 4-20 mA 129.2
4841 4-20 mA Set- 4 mA 10 mA Three different input The value shown in this
129.2 point 20 mA types are available parameter group is
4842 4-20 mA Timer 0.0 s 120.0 s with Option M16.8: available when 4-20 mA
129.2 600.0 s ● 4-20 mA is selected in parameter
● 0-5 V 11170.
4843 4-20 mA Relay Not used Not ● Pt100
129.2 output Option- used
A dep.
4844 4-20 mA Relay Not used Not
129.2 output Option- used
B dep.
4845 4-20 mA Enable OFF OFF
129.2 ON
4846 4-20 mA Fail F1…F9 Warn-
129.2 class ing
(F2)

DEIF Page 83 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4840 VDC 129.2
4841 VDC Set- 0V 2V Three different input The value shown in this
129.2 point 5V types are available parameter group is
4842 VDC Timer 0.0 s 120.0 s with Option M16.8: available when 0-5 V is
129.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11170.
4843 VDC Relay Not used Not
● Pt100
129.2 output Option- used
A dep.
4844 VDC Relay Not used Not
129.2 output Option- used
B dep.
4845 VDC Enable OFF OFF
129.2 ON
4846 VDC Fail F1…F9 Warn-
129.2 class ing
(F2)
4840 Pt100 129.2
4841 Pt100 Set- -49°C 80°C Three different input The value shown in this
129.2 point 482°C types are available parameter group is
4842 Pt100 Timer 0.0 s 120.0 s with Option M16.8: available when Pt100 is
129.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11170.
4843 Pt100 Relay Not used Not
● Pt100
129.2 output Option- used
A dep.
4844 Pt100 Relay Not used Not
129.2 output Option- used
B dep.
4845 Pt100 Enable OFF OFF
129.2 ON
4846 Pt100 Fail F1…F9 Warn-
129.2 class ing
(F2)
4850 Wire fail 129
4851 W. fail Relay Not used Not Option M16.8 For function description
ana 129 output Option- used of wire fail, see the Op-
A dep. tion M16 manual.
4852 W. fail Relay Not used Not
ana 129 output Option- used
B dep.
4853 W. fail Enable OFF OFF
ana 129 ON
4854 W. fail Fail F1…F9 Warn-
ana 129 class ing
(F2)

DEIF Page 84 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4860 4-20 mA 131.1
4861 4-20 mA Set- 4 mA 10 mA Three different input The value shown in this
131.1 point 20 mA types are available parameter group is
4862 4-20 mA Timer 0.0 s 120.0 s with Option M16.8: available when 4-20 mA
131.1 600.0 s ● 4-20 mA is selected in parameter
● 0-5 V 11180.
4863 4-20 mA Relay Not used Not
● Pt100
131.1 output Option- used
A dep.
4864 4-20 mA Relay Not used Not
131.1 output Option- used
B dep.
4865 4-20 mA Enable OFF OFF
131.1 ON
4866 4-20 mA Fail F1…F9 Warn-
131.1 class ing
(F2)
4860 VDC 131.1
4861 VDC Set- 0V 2V Three different input The value shown in this
131.1 point 5V types are available parameter group is
4862 VDC Timer 0.0 s 120.0 s with Option M16.8: available when 0-5 V is
131.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11180.
4863 VDC Relay Not used Not
● Pt100
131.1 output Option- used
A dep.
4864 VDC Relay Not used Not
131.1 output Option- used
B dep.
4865 VDC Enable OFF OFF
131.1 ON
4866 VDC Fail F1…F9 Warn-
131.1 class ing
(F2)
4860 Pt100 131.1
4861 Pt100 Set- -49°C 80°C Three different input The value shown in this
131.1 point 482°C types are available parameter group is
4862 Pt100 Timer 0.0 s 120.0 s with Option M16.8: available when Pt100 is
131.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11180.
4863 Pt100 Relay Not used Not ● Pt100
131.1 output Option- used
A dep.
4864 Pt100 Relay Not used Not
131.1 output Option- used
B dep.
4865 Pt100 Enable OFF OFF
131.1 ON

DEIF Page 85 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4866 Pt100 Fail F1…F9 Warn-
131.1 class ing
(F2)
4870 4-20 mA 131.2
4871 4-20 mA Set- 4 mA 10 mA Three different input The value shown in this
131.2 point 20 mA types are available parameter group is
4872 4-20 mA Timer 0.0 s 120.0 s with Option M16.8: available when 4-20 mA
131.2 600.0 s ● 4-20 mA is selected in parameter
● 0-5 V 11180.
4873 4-20 mA Relay Not used Not
● Pt100
131.2 output Option- used
A dep.
4874 4-20 mA Relay Not used Not
131.2 output Option- used
B dep.
4875 4-20 mA Enable OFF OFF
131.2 ON
4876 4-20 mA Fail F1…F9 Warn-
131.2 class ing
(F2)
4870 VDC 131.2
4871 VDC Set- 0V 2V Three different input The value shown in this
131.2 point 5V types are available parameter group is
4872 VDC Timer 0.0 s 120.0 s with Option M16.8: available when 0-5 V is
131.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11180.
4873 VDC Relay Not used Not
● Pt100
131.2 output Option- used
A dep.
4874 VDC Relay Not used Not
131.2 output Option- used
B dep.
4875 VDC Enable OFF OFF
131.2 ON
4876 VDC Fail F1…F9 Warn-
131.2 class ing
(F2)
4870 Pt100 131.2
4871 Pt100 Set- -49°C 80°C Three different input The value shown in this
131.2 point 482°C types are available parameter group is
4872 Pt100 Timer 0.0 s 120.0 s with Option M16.8: available when Pt100 is
131.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11180.
4873 Pt100 Relay Not used Not
● Pt100
131.2 output Option- used
A dep.

DEIF Page 86 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4874 Pt100 Relay Not used Not
131.2 output Option- used
B dep.
4875 Pt100 Enable OFF OFF
131.2 ON
4876 Pt100 Fail F1…F9 Warn-
131.2 class ing
(F2)
4880 Wire fail 131
4881 W. fail Relay Not used Not Option M16.8 For function description
ana 131 output Option- used of wire fail, see the Op-
A dep. tion M16 manual.
4882 W. fail Relay Not used Not
ana 131 output Option- used
B dep.
4883 W. fail Enable OFF OFF
ana 131 ON
4884 W. fail Fail F1…F9 Warn-
ana 131 class ing
(F2)
4890 4-20 mA 133.1
4891 4-20 mA Set- 4 mA 10 mA Three different input The value shown in this
133.1 point 20 mA types are available parameter group is
4892 4-20 mA Timer 0.0 s 120.0 s with Option M16.8: available when 4-20 mA
133.1 600.0 s ● 4-20 mA is selected in parameter
● 0-5 V 11190.
4893 4-20 mA Relay Not used Not ● Pt100
133.1 output Option- used
A dep.
4894 4-20 mA Relay Not used Not
133.1 output Option- used
B dep.
4895 4-20 mA Enable OFF OFF
133.1 ON
4896 4-20 mA Fail F1…F9 Warn-
133.1 class ing
(F2)
4890 VDC 133.1
4891 VDC Set- 0V 2V Three different input The value shown in this
133.1 point 5V types are available parameter group is
4892 VDC Timer 0.0 s 120.0 s with Option M16.8: available when 0-5 V is
133.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11190.
4893 VDC Relay Not used Not ● Pt100
133.1 output Option- used
A dep.

DEIF Page 87 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4890 VDC 133.1
4894 VDC Relay Not used Not
133.1 output Option- used
B dep.
4895 VDC Enable OFF OFF
133.1 ON
4896 VDC Fail F1…F9 Warn-
133.1 class ing
(F2)
4890 Pt100 133.1
4891 Pt100 Set- -49°C 80°C Three different input The value shown in this
133.1 point 482°C types are available parameter group is
4892 Pt100 Timer 0.0 s 120.0 s with Option M16.8: available when Pt100 is
133.1 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11190.
4893 Pt100 Relay Not used Not ● Pt100
133.1 output Option- used
A dep.
4894 Pt Relay Not used Not
133.1 output Option- used
B dep.
4895 Pt100 Enable OFF OFF
133.1 ON
4896 Pt100 Fail F1…F9 Warn-
133.1 class ing
(F2)
4900 4-20 mA 133.2
4901 4-20 mA Set- 4 mA 10 mA Three different input The value shown in this
133.2 point 20 mA types are available parameter group is
4902 4-20 mA Timer 0.0 s 120.0 s with Option M16.8: available when 4-20 mA
133.2 600.0 s ● 4-20 mA is selected in parameter
● 0-5 V 11190.
4903 4-20 mA Relay Not used Not ● Pt100
133.2 output Option- used
A dep.
4904 4-20 mA Relay Not used Not
133.2 output Option- used
B dep.
4905 4-20 mA Enable OFF OFF
133.2 ON
4906 4-20 mA Fail F1…F9 Warn-
133.2 class ing
(F2)

DEIF Page 88 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
4900 VDC 133.2
4901 VDC Set- 0V 2V Three different input The value shown in this
133.2 point 5V types are available parameter group is
4902 VDC Timer 0.0 s 120.0 s with Option M16.8: available when 0-5 V is
133.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11190.
4903 VDC Relay Not used Not
● Pt100
133.2 output Option- used
A dep.
4904 VDC Relay Not used Not
133.2 output Option- used
B dep.
4905 VDC Enable OFF OFF
133.2 ON
4906 VDC Fail F1…F9 Warn-
133.2 class ing
(F2)
4900 Pt100 133.2
4901 Pt100 Set- -49°C 80°C Three different input The value shown in this
133.2 point 482°C types are available parameter group is
4902 Pt100 Timer 0.0 s 120.0 s with Option M16.8: available when Pt100 is
133.2 600.0 s ● 4-20 mA selected in parameter
● 0-5 V 11190.
4903 Pt100 Relay Not used Not ● Pt100
133.2 output Option- used
A dep.
4904 Pt100 Relay Not used Not
133.2 output Option- used
B dep.
4905 Pt100 Enable OFF OFF
133.2 ON
4906 Pt100 Fail F1…F9 Warn-
133.2 class ing
(F2)
4910 Wire fail 133
4911 W. fail Relay Not used Not Option M16.8 For function description
ana 133 output Option- used or wire fail, see the Op-
A dep. tion M16 manual.
4912 W. fail Relay Not used Not
ana 133 output Option- used
B dep.
4913 W. fail Enable OFF OFF
ana 133 ON
4914 W. fail Fail F1…F9 Warn-
ana 133 class ing
(F2)

DEIF Page 89 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.7 Multi-functional analogue input setup


2.7.1 Multi-input no. 102

The available menus for multi-input no. 102 depend on the input type configured in the PC utili-
ty software (menu 10980).

No. Setting Min. Factory Notes Ref. Description


Max. setting
4120 4-20 mA 102.1
4121 4-20 mA Setpoint 4 mA 10 mA Designer’s The multi-input 102 has been
102.1 20 mA Reference configured as 4-20 mA.
4122 4-20 mA Timer 0.0 s 120.0 s Handbook
102.1 999.0 s
4123 4-20 mA Relay Not used Not
102.1 output Option- used
A dep.
4124 4-20 mA Relay Not used Not
102.1 output Option- used
B dep.
4125 4-20 mA Enable OFF OFF
102.1 ON
4126 4-20 mA Fail F1…F9 Warning
102.1 class (F2)
4130 4-20 mA 102.2
4131 4-20 mA Setpoint 4 mA 10 mA Designer’s The multi-input 102 has been
102.2 20 mA Reference configured as 4-20 mA.
4132 4-20 mA Timer 0.0 s 120.0 s Handbook
102.2 999.0 s
4133 4-20 mA Relay Not used Not
102.2 output Option- used
A dep.
4134 4-20 mA Relay Not used Not
102.2 output Option- used
B dep.
4135 4-20 mA Enable OFF OFF
102.2 ON
4136 4-20 mA Fail F1…F9 Warning
102.2 class (F2)
4140 V DC 102.1
4141 V DC Setpoint 0.0V DC 20.0V Designer’s The multi-input 102 has been
102.1 40.0V DC Reference configured as V DC.
DC Handbook
4142 V DC Timer 0.2 s 10.0 s
102.1 999.0 s
4143 V DC Relay Not used Not
102.1 output Option- used
A dep.

DEIF Page 90 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4144 V DC Relay Not used Not
102.1 output Option- used
B dep.
4145 V DC Enable OFF OFF
102.1 ON
4146 V DC Fail F1…F9 Warning
102.1 class (F2)
4150 V DC 102.2
4151 V DC Setpoint 0.0V DC 20.0V Designer’s The multi-input 102 has been
102.2 40.0V DC Reference configured as V DC.
DC Handbook
4152 V DC Timer 0.2 s 10.0 s
102.2 999.0 s
4153 V DC Relay Not used Not
102.2 output Option- used
A dep.
4154 V DC Relay Not used Not
102.2 output Option- used
B dep.
4155 V DC Enable OFF OFF
102.2 ON
4156 V DC Fail F1…F9 Warning
102.2 class (F2)
4160 Pt100 102.1
4161 PT Setpoint -49 80 Designer’s The multi-input 102 has been
102.1 482 Reference configured as Pt100.
4162 PT Timer 0.0 s 5.0 s Handbook Pt100 setpoint can be in deg.
102.1 999.0 s C or Fahrenheit, dependent on
the unit selection (menu
4163 PT Relay Not used Not
10970).
102.1 output Option- used
A dep.
4164 PT Relay Not used Not
102.1 output Option- used
B dep.
4165 PT Enable OFF OFF
102.1 ON
4166 PT Fail F1…F9 Warning
102.1 class (F2)

4170 Pt100 102.2


4171 PT Setpoint -49 80 Designer’s The multi-input 102 has
102.2 482 Reference been configured as Pt100.
4172 PT Timer 0.0 s 10.0 s Handbook
102.2 999.0 s

DEIF Page 91 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4173 PT Relay Not used Not Pt100 setpoint can be in deg.
102.2 output Option- used C or Fahrenheit, dependent
A dep. on the unit selection (menu
4174 PT Relay Not used Not 10970).
102.2 output Option- used
B dep.
4175 PT Enable OFF OFF
102.2 ON
4176 PT Fail F1…F9 Warning
102.2 class (F2)
4180 RMI oil 102.1
4181 RMI oil Setpoint 0.0 4.0 Designer’s The multi-input 102 has been
102.1 145.0 Reference configured as RMI oil pres-
4182 RMI oil Timer 0.0 s 5.0 s Handbook sure.
102.1 999.0 s Oil pressure setpoint can be in
Bar or PSI, dependent on the
4183 RMI oil Relay Not used Not
unit selection (menu 10970).
102.1 output Option- used
A dep.
4184 RMI oil Relay Not used Not
102.1 output Option- used
B dep.
4185 RMI oil Enable OFF OFF
102.1 ON
4186 RMI oil Fail F1…F9 Warning
102.1 class (F2)
4190 RMI oil 102.2
4191 RMI oil Setpoint 0.0 5.0 Designer’s The multi-input 102 has been
102.2 145.0 Reference configured as RMI oil pres-
4192 RMI oil Timer 0.0 s 5.0 s Handbook sure.
102.2 999.0 s Oil pressure setpoint can be in
Bar or PSI, dependent on the
4193 RMI oil Relay Not used Not
unit selection (menu 10970).
102.2 output Option- used
A dep.
4194 RMI oil Relay Not used Not
102.2 output Option- used
B dep.
4195 RMI oil Enable OFF OFF
102.2 ON
4196 RMI oil Fail F1…F9 Warning
102.2 class (F2)

DEIF Page 92 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4200 RMI water 102.1
4201 RMI Setpoint -49 100 Designer’s The multi-input 102 has been
water 482 Reference configured as RMI water tem-
102.1 Handbook perature.
4202 RMI Timer 0.0 s 5.0 s Water temperature setpoint
water 999.0 s can be in deg. C or F, depend-
102.1 ent on the unit selection (menu
10970).
4203 RMI Relay Not used Not
water output Option- used
102.1 A dep.
4204 RMI Relay Not used Not
water output Option- used
102.1 B dep.
4205 RMI Enable OFF OFF
water ON
102.1
4206 RMI Fail F1…F9 Warning
water class (F2)
102.1
4210 RMI water 102.2
4211 RMI Setpoint -49 110 Designer’s The multi-input 102 has been
water 482 Reference configured as RMI water tem-
102.2 Handbook perature.
4212 RMI Timer 0.0 s 5.0 s Water temperature setpoint
water 999.0 s can be in deg. C or F, depend-
102.2 ent on the unit selection (menu
10970).
4213 RMI Relay Not used Not
water output Option- used
102.2 A dep.
4214 RMI Relay Not used Not
water output Option- used
102.2 B dep.
4215 RMI Enable OFF OFF
water ON
102.2
4216 RMI Fail F1…F9 Warning
water class (F2)
102.2
4220 RMI fuel level 102.1
4221 RMI Setpoint 0% 10% Designer’s The multi-input 102 has been
fuel 100% Reference configured as RMI fuel level.
102.1 Handbook
4222 RMI Timer 0.0 s 10.0 s
fuel 999.0 s
102.1

DEIF Page 93 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4223 RMI Relay Not used Not
fuel output Option- used
102.1 A dep.
4224 RMI Relay Not used Not
fuel output Option- used
102.1 B dep.
4225 RMI Enable OFF OFF
fuel ON
102.1
4226 RMI Fail F1…F9 Warning
fuel class (F2)
102.1
4230 RMI fuel level 102.2
4231 RMI Setpoint 0% 5% Designer’s The multi-input 102 has been
fuel 100% Reference configured as RMI fuel level.
102.2 Handbook
4232 RMI Timer 0.0 s 10.0 s
fuel 999.0 s
102.2
4233 RMI Relay Not used Not
fuel output Option- used
102.2 A dep.
4234 RMI Relay Not used Not
fuel output Option- used
102.2 B dep.
4235 RMI Enable OFF OFF
fuel ON
102.2
4236 RMI Fail F1…F9 Warning
fuel class (F2)
102.2
4240 Wire fail 102
4241 W. fail Relay Not used Not Designer’s The wire break fault detection
102 output Option- used Reference is activated.
A dep. Handbook
4242 W. fail Relay Not used Not
102 output Option- used
B dep.
4243 W. fail Enable OFF OFF
102 ON

4244 W. fail Fail F1…F9 Warning


102 class (F2)

DEIF Page 94 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.7.2 Multi-input no. 105

The available menus for multi-input no. 105 depend on the input type configured in the PC utili-
ty software (menu 10990).

No. Setting Min. Factory Notes Ref. Description


Max. setting
4250 4-20 mA 105.1
4251 4-20 mA Setpoint 4 mA 10 mA Designer’s The multi-input 105 has been
105.1 20 mA Reference configured as 4-20 mA.
4252 4-20 mA Timer 0.0 s 120.0 s Handbook
105.1 999.0 s
4253 4-20 mA Relay Not used Not
105.1 output Option- used
A dep.
4254 4-20 mA Relay Not used Not
105.1 output Option- used
B dep.
4255 4-20 mA Enable OFF OFF
105.1 ON
4256 4-20 mA Fail F1…F9 Warning
105.1 class (F2)
4260 4-20 mA 105.2
4261 4-20 mA Setpoint 4 mA 10 mA Designer’s The multi-input 105 has been
105.2 20 mA Reference configured as 4-20 mA.
4262 4-20 mA Timer 0.0 s 120.0 s Handbook
105.2 999.0 s
4263 4-20 mA Relay Not used Not
105.2 output Option- used
A dep.
4264 4-20 mA Relay Not used Not
105.2 output Option- used
B dep.
4265 4-20 mA Enable OFF OFF
105.2 ON
4266 4-20 mA Fail F1…F9 Warning
105.2 class (F2)
4270 V DC 105.1
4271 V DC Setpoint 0.0V DC 20.0V Designer’s The multi-input 105 has been
105.1 40.0V DC Reference configured as V DC.
DC Handbook
4272 V DC Timer 0.2 s 10.0 s
105.1 999.0 s
4273 V DC Relay Not used Not
105.1 output Option- used
A dep.
4274 V DC Relay Not used Not
105.1 output Option- used
B dep.

DEIF Page 95 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4275 V DC Enable OFF OFF
105.1 ON
4276 V DC Fail F1…F9 Warning
105.1 class (F2)
4280 V DC 105.2
4281 V DC Setpoint 0.0V DC 20.0V Designer’s The multi-input 105 has been
105.2 40.0V DC Reference configured as V DC.
DC Handbook
4282 V DC Timer 0.2 s 10.0 s
105.2 999.0 s
4283 V DC Relay Not used Not
105.2 output Option- used
A dep.
4284 V DC Relay Not used Not
105.2 output Option- used
B dep.
4285 V DC Enable OFF OFF
105.2 ON
4286 V DC Fail F1…F9 Warning
105.2 class (F2)
4290 Pt100 105.1
4291 PT Setpoint -49 80 Designer’s The multi-input 105 has been
105.1 482 Reference configured as Pt100.
4292 PT Timer 0.0 s 5.0 s Handbook Pt100 setpoint can be in deg.
105.1 999.0 s C or F, dependent on the unit
selection (menu 10970).
4293 PT Relay Not used Not
105.1 output Option- used
A dep.
4294 PT Relay Not used Not
105.1 output Option- used
B dep.
4295 PT Enable OFF OFF
105.1 ON
4296 PT Fail F1…F9 Warning
105.1 class (F2)
4300 Pt100 105.2
4301 PT Setpoint -49 80 Designer’s The multi-input 105 has been
105.2 482 Reference configured as Pt100.
4302 PT Timer 0.0 s 10.0 s Handbook Pt100 setpoint can be in deg.
105.2 999.0 s C or F, dependent on the unit
selection (menu 10970).
4303 PT Relay Not used Not
105.2 output Option- used
A dep.
4304 PT Relay Not used Not
105.2 output Option- used
B dep.

DEIF Page 96 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4305 PT Enable OFF OFF
105.2 ON
4306 PT Fail F1…F9 Warning
105.2 class (F2)
4310 RMI oil 105.1
4311 RMI oil Setpoint 0.0 4.0 Designer’s The multi-input 105 has been
105.1 145.0 Reference configured as RMI oil pres-
4312 RMI oil Timer 0.0 s 5.0 s Handbook sure.
105.1 999.0 s Oil pressure setpoint can be in
Bar or PSI, dependent on the
4313 RMI oil Relay Not used Not
unit selection (menu 10970).
105.1 output Option- used
A dep.
4314 RMI oil Relay Not used Not
105.1 output Option- used
B dep.
4315 RMI oil Enable OFF OFF
105.1 ON
4316 RMI oil Fail F1…F9 Warning
105.1 class (F2)
4320 RMI oil 105.2
4321 RMI oil Setpoint 0.0 5.0 Designer’s The multi-input 105 has been
105.2 145.0 Reference configured as RMI oil pres-
4322 RMI oil Timer 0.0 s 5.0 s Handbook sure.
105.2 999.0 s Oil pressure setpoint can be in
Bar or PSI, dependent on the
4323 RMI oil Relay Not used Not
unit selection (menu 10970).
105.2 output Option- used
A dep.
4324 RMI oil Relay Not used Not
105.2 output Option- used
B dep.
4325 RMI oil Enable OFF OFF
105.2 ON
4326 RMI oil Fail F1…F9 Warning
105.2 class (F2)
4330 RMI water 105.1
4331 RMI Setpoint -49 100 Designer’s The multi-input 105 has been
water 482 Reference configured as RMI water tem-
105.1 Handbook perature.
4332 RMI Timer 0.0 s 5.0 s Water temperature setpoint
water 999.0 s can be in deg. C or F, depend-
105.1 ent on the unit selection (menu
10970).
4333 RMI Relay Not used Not
water output Option- used
105.1 A dep.

DEIF Page 97 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4334 RMI Relay Not used Not
water output Option- used
105.1 B dep.
4335 RMI Enable OFF OFF
water ON
105.1
4336 RMI Fail F1…F9 Warning
water class (F2)
105.1
4340 RMI water 105.2
4341 RMI Setpoint -49 110 Designer’s The multi-input 105 has been
water 482 Reference configured as RMI water tem-
105.2 Handbook perature.
4342 RMI Timer 0.0 s 5.0 s Water temperature setpoint
water 999.0 s can be in deg. C or F, depend-
105.2 ent on the unit selection (menu
10970).
4343 RMI Relay Not used Not
water output Option- used
105.2 A dep.
4344 RMI Relay Not used Not
water output Option- used
105.2 B dep.
4345 RMI Enable OFF OFF
water ON
105.2
4346 RMI Fail F1…F9 Warning
water class (F2)
105.2
4350 RMI fuel level 105.1
4351 RMI Setpoint 0% 10% Designer’s The multi-input 105 has been
fuel 100% Reference configured as RMI fuel level.
105.1 Handbook
4352 RMI Timer 0.0 s 10.0 s
fuel 999.0 s
105.1
4353 RMI Relay Not used Not
fuel output Option- used
105.1 A dep.
4354 RMI Relay Not used Not
fuel output Option- used
105.1 B dep.
4535 RMI Enable OFF OFF
fuel ON
105.1
4356 RMI Fail F1…F9 Warning
fuel class (F2)
105.1

DEIF Page 98 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4360 RMI fuel level 105.2
4361 RMI Setpoint 0% 5% Designer’s The multi-input 105 has been
fuel 100% Reference configured as RMI fuel level.
105.2 Handbook
4362 RMI Timer 0.0 s 10.0 s
fuel 999.0 s
105.2
4363 RMI Relay Not used Not
fuel output Option- used
105.2 A dep.
4364 RMI Relay Not used Not
fuel output Option- used
105.2 B dep.
4365 RMI Enable OFF OFF
fuel ON
105.2
4366 RMI Fail F1…F9 Warning
fuel class (F2)
105.2
4370 Wire fail 105
4371 W. fail Relay Not used Not Designer’s The wire break fault detection
105 output Option- used Reference is activated.
A dep. Handbook
4372 W. fail Relay Not used Not
105 output Option- used
B dep.
4373 W. fail Enable OFF OFF
105 ON
4374 W. fail Fail F1…F9 Warning
105 class (F2)

DEIF Page 99 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.7.3 Multi-input no. 108


The available menus for multi-input no. 108 depend on the input type configured in the PC utili-
ty software (menu 11000).

No. Setting Min. Factory Notes Ref. Description


Max. setting
4380 4-20 mA 108.1
4381 4-20 mA Setpoint 4 mA 10 mA Designer’s The multi-input 108 has been
108.1 20 mA Reference configured as 4-20 mA.
4382 4-20 mA Timer 0.0 s 120.0 s Handbook
108.1 999.0 s
4383 4-20 mA Relay Not used Not
108.1 output Option- used
A dep.
4384 4-20 mA Relay Not used Not
108.1 output Option- used
B dep.
4385 4-20 mA Enable OFF OFF
108.1 ON
4386 4-20 mA Fail F1…F9 Warning
108.1 class (F2)
4390 4-20 mA 108.2
4391 4-20 mA Setpoint 4 mA 10 mA Designer’s The multi-input 108 has been
108.2 20 mA Reference configured as 4-20 mA.
4392 4-20 mA Timer 0.0 s 120.0 s Handbook
108.2 999.0 s
4393 4-20 mA Relay Not used Not
108.2 output Option- used
A dep.
4394 4-20 mA Relay Not used Not
108.2 output Option- used
B dep.
4395 4-20 mA Enable OFF OFF
108.2 ON
4396 4-20 mA Fail F1…F9 Warning
108.2 class (F2)
4400 V DC 108.1
4401 V DC Setpoint 0.0V DC 20.0V Designer’s The multi-input 108 has been
108.1 40.0V DC Reference configured as V DC.
DC Handbook
4402 V DC Timer 0.2 s 10.0 s
108.1 999.0 s
4403 V DC Relay Not used Not
108.1 output Option- used
A dep.
4404 V DC Relay Not used Not
108.1 output Option- used
B dep.

DEIF Page 100 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4405 V DC Enable OFF OFF
108.1 ON
4406 V DC Fail F1…F9 Warning
108.1 class (F2)
4410 V DC 108.2
4411 V DC Setpoint 0.0V DC 20.0V Designer’s The multi-input 108 has been
108.2 40.0V DC Reference configured as V DC.
DC Handbook
4412 V DC Timer 0.2 s 10.0 s
108.2 999.0 s
4413 V DC Relay Not used Not
108.2 output Option- used
A dep.
4414 V DC Relay Not used Not
108.2 output Option- used
B dep.
4415 V DC Enable OFF OFF
108.2 ON
4416 V DC Fail F1…F9 Warning
108.2 class (F2)
4420 Pt100 108.1
4421 PT Setpoint -49 80 Designer’s The multi-input 108 has been
108.1 482 Reference configured as Pt100.
4422 PT Timer 0.0 s 5.0 s Handbook Pt100 setpoint can be in deg.
108.1 999.0 s C or F, dependent on the unit
selection (menu 10970).
4423 PT Relay Not used Not
108.1 output Option- used
A dep.
4424 PT Relay Not used Not
108.1 output Option- used
B dep.
4425 PT Enable OFF OFF
108.1 ON
4426 PT Fail F1…F9 Warning
108.1 class (F2)
4430 Pt100 108.2
4431 PT Setpoint -49 80 Designer’s The multi-input 108 has been
108.2 482 Reference configured as Pt100.
4432 PT Timer 0.0 s 10.0 s Handbook Pt100 setpoint can be in deg.
108.2 999.0 s C or F, dependent on the unit
selection (menu 10970).
4433 PT Relay Not used Not
108.2 output Option- used
A dep.
4434 PT Relay Not used Not
108.2 output Option- used
B dep.

DEIF Page 101 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4435 PT Enable OFF OFF
108.2 ON
4436 PT Fail F1…F9 Warning
108.2 class (F2)
4440 RMI oil 108.1
4441 RMI oil Setpoint 0.0 4.0 Designer’s The multi-input 108 has been
108.1 145.0 Reference configured as RMI oil pres-
4442 RMI oil Timer 0.0 s 5.0 s Handbook sure.
108.1 999.0 s Oil pressure setpoint can be in
Bar or PSI, dependent on the
4443 RMI oil Relay Not used Not
unit selection (menu 10970).
108.1 output Option- used
A dep.
4444 RMI oil Relay Not used Not
108.1 output Option- used
B dep.
4445 RMI oil Enable OFF OFF
108.1 ON
4446 RMI oil Fail F1…F9 Warning
108.1 class (F2)
4450 RMI oil 108.2
4451 RMI oil Setpoint 0.0 5.0 Designer’s The multi-input 108 has been
108.2 145.0 Reference configured as RMI oil pres-
4452 RMI oil Timer 0.0 s 5.0 s Handbook sure.
108.2 999.0 s Oil pressure setpoint can be in
Bar or PSI, dependent on the
4453 RMI oil Relay Not used Not
unit selection (menu 10970).
108.2 output Option- used
A dep.
4454 RMI oil Relay Not used Not
108.2 output Option- used
B dep.
4455 RMI oil Enable OFF OFF
108.2 ON
4456 RMI oil Fail F1…F9 Warning
108.2 class (F2)
4460 RMI water 108.1
4461 RMI Setpoint -49 100 Designer’s The multi-input 108 has been
water 482 Reference configured as RMI water tem-
108.1 Handbook perature.
4462 RMI Timer 0.0 s 5.0 s Water temperature setpoint
water 999.0 s can be in deg. C or F, depend-
108.1 ent on the unit selection (menu
10970).
4463 RMI Relay Not used Not
water output Option- used
108.1 A dep.

DEIF Page 102 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4460 RMI water 108.1
4464 RMI Relay Not used Not
water output Option- used
108.1 B dep.
4465 RMI Enable OFF OFF
water ON
108.1
4466 RMI Fail F1…F9 Warning
water class (F2)
108.1
4470 RMI water 108.2
4471 RMI Setpoint -49 110 Designer’s The multi-input 108 has been
water 482 Reference configured as RMI water tem-
108.2 Handbook perature.
4472 RMI Timer 0.0 s 5.0 s Water temperature setpoint
water 999.0 s can be in deg. C or F, depend-
108.2 ent on the unit selection (menu
10970).
4473 RMI Relay Not used Not
water output Option- used
108.2 A dep.
4474 RMI Relay Not used Not
water output Option- used
108.2 B dep.
4475 RMI Enable OFF OFF
water ON
108.2
4476 RMI Fail F1…F9 Warning
water class (F2)
108.2
4480 RMI fuel level 108.1
4481 RMI Setpoint 0% 10% Designer’s The multi-input 108 has been
fuel 100% Reference configured as RMI fuel level.
108.1 Handbook
4482 RMI Timer 0.0 s 10.0 s
fuel 999.0 s
108.1
4483 RMI Relay Not used Not
fuel output Option- used
108.1 A dep.
4484 RMI Relay Not used Not
fuel output Option- used
108.1 B dep.
4485 RMI Enable OFF OFF
fuel ON
108.1

DEIF Page 103 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4486 RMI Fail F1…F9 Warning
fuel class (F2)
108.1
4490 RMI fuel level 108.2
4491 RMI Setpoint 0% 5% Designer’s The multi-input 108 has been
fuel 100% Reference configured as RMI fuel level.
108.2 Handbook
4492 RMI Timer 0.0 s 10.0 s
fuel 999.0 s
108.2
4493 RMI Relay Not used Not
fuel output Option- used
108.2 A dep.
4494 RMI Relay Not used Not
fuel output Option- used
108.2 B dep.
4495 RMI Enable OFF OFF
fuel ON
108.2
4496 RMI Fail F1…F9 Warning
fuel class (F2)
108.2
4500 Wire fail 108
4501 W. fail Relay Not used Not Designer’s The wire break fault detection
108 output Option- used Reference is activated.
A dep. Handbook
4502 W. fail Relay Not used Not
108 output Option- used
B dep.
4503 W. fail Enable OFF OFF
108 ON
4504 W. fail Fail F1…F9 Warning
108 class (F2)

DEIF Page 104 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.7.4 Speed and running feedback setup


No. Setting Min. Factory Notes Ref. Description
Max. setting
4510 Overspeed 1
4511 Over- Set- 100.0% 110.0% Designer’s The setpoint in percentage
speed 1 point 150.0% Reference relates to nominal RPM.
4512 Over- Timer 0.0 s 5.0 s Handbook
speed 1 100.0 s
4513 Over- Relay Not used Not used
speed 1 output Option-
A dep.
4514 Over- Relay Not used Not used
speed 1 output Option-
B dep.
4515 Over- Enable OFF OFF
speed 1 ON
4516 Over- Fail F1…F9 Warning
speed 1 class (F2)
4520 Overspeed 2
4521 Over- Set- 100.0% 120.0% Designer’s The setpoint in percentage
speed 2 point 150.0% Reference relates to nominal RPM.
4522 Over- Timer 0.0 s 1.0 s Handbook
speed 2 100.0 s
4523 Over- Relay Not used Not used
speed 2 output Option-
A dep.
4524 Over- Relay Not used Not used
speed 2 output Option-
B dep.
4525 Over- Enable OFF OFF
speed 2 ON
4526 Over- Fail F1…F9 Wg
speed 2 class (F5)
4530 Crank failure
4531 Crank Set- 1 RPM 50 RPM Designer’s If MPU is chosen as the pri-
failure point 400 RPM Reference mary running feedback, this
4532 Crank Timer 0.0 s 2.0 s Handbook alarm will be raised if the
failure 20.0 s specified RPM is not
reached before the delay
4533 Crank Relay Not used Not used
has expired.
failure output Option-
A dep.
4534 Crank Relay Not used Not used
failure output Option-
B dep.
4535 Crank Enable OFF OFF
failure ON
4536 Crank Fail F1…F9 Warning
failure class (F2)

DEIF Page 105 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4540 Running feedback failure
4541 Run Timer 0.0 s 2.0 s Designer’s If running is detected on the
feedb. 20.0 s Reference frequency (secondary), but
fail Handbook the primary running feed-
4542 Run Relay Not used Not used back, e.g. digital input, has
feedb. output Option- not detected running, this
fail A dep. alarm will be raised after the
adjusted delay time.
4543 Run Relay Not used Not used
feedb. output Option-
fail B dep.
4544 Run Enable ON ON
feedb.
fail
4545 Run Fail F1...F9 Warning
feedb. class (F2)
fail
4550 Magnetic pick-up wirebreak
4551 MPU Relay Not used Not used Designer’s The wirebreak monitoring is
wire- output Option- Reference only active when the engine
break A dep. Handbook is at standstill.
4552 MPU Relay Not used Not used
wire- output Option-
break B dep.
4553 MPU Enable OFF OFF
wire- ON
break
4554 MPU Fail F1...F9 Warning
wire- class (F2)
break
4560 Hz/voltage failure
4561 Hz/V fail- Timer 1.0 s 30.0 s Designer’s If the frequency and voltage
ure 99.0 s Reference are not within the limits after
4562 Hz/V fail- Relay Not used Not used Handbook the running feedback is re-
ure output Option- ceived, this alarm will be
A dep. raised when the delay time
has expired. Limits are
4563 Hz/V fail- Relay Not used Not used placed in menu 2110 (Sync.
ure output Option-
blackout).
B dep.
4564 Hz/V fail- Enable OFF ON
ure ON
4565 Hz/V fail- Fail F1...F9 Shut-
ure class down
(F5)

DEIF Page 106 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4570 Start failure
4571 Start fail- Relay Not used Not used Designer’s The start failure alarm oc-
ure output Option- Reference curs if the genset has not
A dep. Handbook started after the number of
4572 Start fail- Relay Not used Not used start attempts.
ure output Option-
B dep.
4573 Start fail- Fail F1…F9 Block
ure class (F1)
4580 Stop failure
4581 Stop fail- Timer 10.0 s 30.0 s Designer’s A stop failure alarm will ap-
ure 120.0 s Reference pear if the primary running
4582 Stop fail- Relay Not used Not used Handbook feedback or the generator
ure output Option- voltage and frequency are
A dep. still present after the delay
time has expired.
4583 Stop fail- Relay Not used Not used
ure output Option-
B dep.
4584 Stop fail- Enable OFF ON
ure ON
4585 Stop fail- Fail F1…F9 Shut-
ure class down
(F5)
4590 Underspeed 1
4591 Under- Set- 50.0% 90.0% Designer’s The setpoint in percentage
speed point 100.0% Reference relates to nominal RPM.
4592 Under- Timer 0.0 s 5.0 s Handbook
speed 100.0 s
4593 Under- Relay Not used Not used
speed output Option-
A dep.
4594 Under- Relay Not used Not used
speed output Option-
B dep.
4595 Under- Enable OFF OFF
speed ON
4596 Under- Fail F1…F9 Warning
speed class (F2)

DEIF Page 107 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.7.5 Differential measurement


No. Setting Min. Factory Notes Ref. Description
Max. setting
4600 Delta analogue 1.1
4601 Delta Input Multi-input Multi-in- Designer’s Inputs for differential
Ana1 102-EIC put 102 Reference measurements can be
InpA Handbook chosen as the list below
4602 Delta Input Multi-input Multi-in- shows:
Ana1 102-EIC put 102
Input:
InpB
- Multi-input 102
4603 Delta Input Multi-input Multi-in- - Multi-input 105
Ana2 102-EIC put 102 - Multi-input 108
InpA - Ext. I/O analog In 1-8
4604 Delta Input Multi-input Multi-in- - EIC oil pressure
Ana2 102-EIC put 102 - EIC cooling water temp.
InpB - EIC oil temp.
- EIC ambient temp.
4605 Delta Input Multi-input Multi-in-
- EIC intercool temp.
Ana3 102-EIC put 102
- EIC fuel temp.
InpA
- EIC fuel delivery press
4606 Delta Input Multi-input Multi-in- - EIC air filter f1 diff. press.
Ana3 102-EIC put 102 - EIC air filter f2 diff. press.
InpB - EIC fuel supply pump
press.
- EIC fuel filter diff. press.
- EIC oil filter diff. press.
- EIC T. exhaust left
- EIC T. exhaust right
- EIC P. fuel f diff.
4610 Delta analogue 1.1
4611 Delta Setpoint -9999 10 Designer’s Delta analogue alarm set-
Ana1.1 9999 Reference ting 1.1
4612 Delta Timer 0.0 s 5.0 s Handbook
Ana1.1 999.0 s
4613 Delta Relay Not used Not
Ana1.1 output Option- used
A dep.
4614 Delta Relay Not used Not
Ana1.1 output Option- used
B dep.
4615 Delta Enable OFF OFF
Ana1.1 ON
4616 Delta Fail F1…F9 Warning
Ana1.1 class (F2)
4620 Delta analogue 1.2
4621 Delta Setpoint -9999 10 Designer’s Delta analogue alarm set-
Ana1.2 9999 Reference ting 1.2
4622 Delta Timer 0.0 s 5.0 s Handbook
Ana1.2 999.0 s

DEIF Page 108 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4623 Delta Relay Not used Not
Ana1.2 output Option- used
A dep.
4624 Delta Relay Not used Not
Ana1.2 output Option- used
B dep.
4625 Delta Enable OFF OFF
Ana1.2 ON
4626 Delta Fail F1…F9 Warning
Ana1.2 class (F2)
4630 Delta analogue 2.1
4631 Delta Setpoint -9999 10 Designer’s Delta analogue alarm set-
Ana2.1 9999 Reference ting 2.1
4632 Delta Timer 0.0 s 5.0 s Handbook
Ana2.1 999.0 s
4633 Delta Relay Not used Not
Ana2.1 output Option- used
A dep.
4634 Delta Relay Not used Not
Ana2.1 output Option- used
B dep.
4635 Delta Enable OFF OFF
Ana2.1 ON
4636 Delta Fail F1…F9 Warning
Ana2.1 class (F2)
4640 Delta analogue 2.2
4641 Delta Setpoint -9999 10 Designer’s Delta analogue alarm set-
Ana2.2 9999 Reference ting 2.2
4642 Delta Timer 0.0 s 5.0 s Handbook
Ana2.2 999.0 s
4643 Delta Relay Not used Not
Ana2.2 output Option- used
A dep.
4644 Delta Relay Not used Not
Ana2.2 output Option- used
B dep.
4645 Delta Enable OFF OFF
Ana2.2 ON
4646 Delta Fail F1...F9 Warning
Ana2.2 class (F2)
4650 Delta analogue 3.1
4651 Delta Setpoint -9999 10 Designer’s Delta analogue alarm set-
Ana3.1 9999 Reference ting 3.1
4652 Delta Timer 0.0 s 5.0 s Handbook
Ana3.1 999.0 s

DEIF Page 109 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4653 Delta Relay Not used Not
Ana3.1 output Option- used
A dep.
4654 Delta Relay Not used Not
Ana3.1 output Option- used
B dep.
4655 Delta Enable OFF OFF
Ana3.1 ON
4656 Delta Fail F1...F9 Warning
Ana3.1 class (F2)
4660 Delta analogue 3.2
4661 Delta Setpoint -9999 10 Designer’s Delta analogue alarm set-
Ana3.2 9999 Reference ting 3.2
4662 Delta Timer 0.0 s 5.0 s Handbook
Ana3.2 999.0 s
4663 Delta Relay Not used Not
Ana3.2 output Option- used
A dep.
4664 Delta Relay Not used Not
Ana3.2 output Option- used
B dep.
4665 Delta Enable OFF OFF
Ana3.2 ON
4666 Delta Fail F1...F9 Warning
Ana3.2 class (F2)
4670 Delta analog input 4, 5, 6
4671 Delta Input Multi-input Multi-in- Designer’s Inputs for differential
Ana4 102-EIC put 102 Reference measurements can be
InpA Handbook chosen as the list below
4672 Delta Input Multi-input Multi-in- shows:
Ana4 102-EIC put 102
Input:
InpB
- Multi-input 102
4673 Delta Input Multi-input Multi-in- - Multi-input 105
Ana5 102-EIC put 102 - Multi-input 108
InpA - Ext. I/O analog In 1-8
4674 Delta Input Multi-input Multi-in- - EIC oil pressure
Ana5 102-EIC put 102 - EIC cooling water temp.
InpB - EIC oil temp.
- EIC ambient temp.
4675 Delta Input Multi-input Multi-in-
- EIC intercool temp.
Ana6 102-EIC put 102
- EIC fuel temp.
InpA
- EIC fuel delivery press
4676 Delta Input Multi-input Multi-in- - EIC air filter f1 diff. press.
Ana6 102-EIC put 102 - EIC air filter f2 diff. press.
InpB - EIC fuel supply pump
press.
- EIC fuel filter diff. press.
- EIC oil filter diff. press.

DEIF Page 110 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
- EIC T. exhaust left
- EIC T. exhaust right
- EIC P. fuel f diff.
4680 Delta analogue 4.1
4681 Delta Setpoint -9999 10 Designer’s Delta analogue alarm set-
Ana4.1 9999 Reference ting 4.1
4682 Delta Timer 0.0 s 5.0 s Handbook
Ana4.1 999.0 s
4683 Delta Relay Not used Not
Ana4.1 output Option- used
A dep.
4684 Delta Relay Not used Not
Ana4.1 output Option- used
B dep.
4685 Delta Enable OFF OFF
Ana4.1 ON
4686 Delta Fail F1…F9 Warning
Ana4.1 class (F2)
4690 Delta analogue 4.2
4691 Delta Setpoint -9999 10 Designer’s Delta analogue alarm set-
Ana4.2 9999 Reference ting 4.2
4692 Delta Timer 0.0 s 5.0 s Handbook
Ana4.2 999.0 s
4693 Delta Relay Not used Not
Ana4.2 output Option- used
A dep.
4694 Delta Relay Not used Not
Ana4.2 output Option- used
B dep.
4695 Delta Enable OFF OFF
Ana4.2 ON
4696 Delta Fail F1…F9 Warning
Ana4.2 class (F2)
4700 Delta analogue 5.1
4701 Delta Setpoint -9999 10 Designer’s Delta analogue alarm set-
Ana5.1 9999 Reference ting 5.1
4702 Delta Timer 0.0 s 5.0 s Handbook
Ana5.1 999.0 s
4703 Delta Relay Not used Not
Ana5.1 output Option- used
A dep.
4704 Delta Relay Not used Not
Ana5.1 output Option- used
B dep.
4705 Delta Enable OFF OFF
Ana5.1 ON
4706 Delta Fail F1…F9 Warning
Ana5.1 class (F2)

DEIF Page 111 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4710 Delta analogue 5.2
4711 Delta Setpoint -9999 10 Designer’s Delta analogue alarm set-
Ana5.2 9999 Reference ting 5.2
4712 Delta Timer 0.0 s 5.0 s Handbook
Ana5.2 999.0 s
4713 Delta Relay Not used Not
Ana5.2 output Option- used
A dep.
4714 Delta Relay Not used Not
Ana5.2 output Option- used
B dep.
4715 Delta Enable OFF OFF
Ana5.2 ON
4716 Delta Fail F1...F9 Warning
Ana5.2 class (F2)
4720 Delta analogue 6.1
4721 Delta Setpoint -9999 10 Designer’s Delta analogue alarm set-
Ana6.1 9999 Reference ting 6.1
4722 Delta Timer 0.0 s 5.0 s Handbook
Ana6.1 999.0 s
4653 Delta Relay Not used Not
Ana6.1 output Option- used
A dep.
4724 Delta Relay Not used Not
Ana6.1 output Option- used
B dep.
4725 Delta Enable OFF OFF
Ana6.1 ON
4726 Delta Fail F1...F9 Warning
Ana6.1 class (F2)
4730 Delta analogue 6.2
4731 Delta Setpoint -9999 10 Designer’s Delta analogue alarm set-
Ana6.2 9999 Reference ting 6.2
4732 Delta Timer 0.0 s 5.0 s Handbook
Ana6.2 999.0 s
4733 Delta Relay Not used Not
Ana6.2 output Option- used
A dep.
4734 Delta Relay Not used Not
Ana6.2 output Option- used
B dep.
4735 Delta Enable OFF OFF
Ana6.2 ON
4736 Delta Fail F1...F9 Warning
Ana6.2 class (F2)

DEIF Page 112 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.7.6 Aux. supply setup


No. Setting Min. Factory Notes Ref. Description
Max. setting
4960 U< auxiliary power supply terminal 1
4961 U< aux. Setpoint 8.0V DC 18.0V Designer’s The power supply on terminal
term. 1 32.0V DC DC Reference 1 and 2 has been continuous-
4962 U< aux. Timer 0.0 s 1.0 s Handbook ly below the adjusted setpoint
term. 1 999.0 s during the programmed de-
lay.
4963 U< aux. Relay Not used Not
term. 1 output A Option- used
dep.
4964 U< aux. Relay Not used Not
term. 1 output B Option- used
dep.
4965 U< aux. Enable OFF ON
term. 1 ON
4966 U< aux. Fail F1…F9 Warning
term. 1 class (F2)
4970 U> auxiliary power supply terminal 1
4971 U> aux. Setpoint 12.0V DC 30.0V Designer’s The power supply on terminal
term. 1 36.0V DC DC Reference 1 and 2 has been continuous-
4972 U> aux. Timer 0.0 s 1.0 s Handbook ly above the adjusted set-
term. 1 999.0 s point during the programmed
delay.
4973 U> aux. Relay Not used Not
term. 1 output A Option- used
dep.
4974 U> aux. Relay Not used Not
term. 1 output B Option- used
dep.
4975 U> aux. Enable OFF ON
term. 1 ON
4976 U> aux. Fail F1…F9 Warning
term. 1 class (F2)
4980 U< auxiliary power supply terminal 98
4981 U> aux. Setpoint 8.0V DC 18.0V Designer’s The power supply on terminal
term. 98 32.0V DC DC Reference 98 and 99 has been continu-
4982 U> aux. Timer 0.0 s 1.0 s Handbook ously below the adjusted set-
term. 98 999.0 s point during the programmed
delay.
4983 U> aux. Relay Not used Not
term. 98 output A Option- used
dep.
4984 U> aux. Relay Not used Not
term. 98 output B Option- used
dep.
4985 U> aux. Enable OFF ON
term. 98 ON
4986 U> aux. Fail F1…F9 Warning
term. 98 class (F2)

DEIF Page 113 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
4990 U> auxiliary power supply terminal 98
4991 U> aux. Setpoint 12.0V DC 30.0V Designer’s The power supply on terminal
term. 98 36.0V DC DC Reference 98 and 99 has been continu-
4992 U> aux. Timer 0.0 s 1.0 s Handbook ously above the adjusted set-
term. 98 999.0 s point during the programmed
delay.
4993 U> aux. Relay Not used Not
term. 98 output A Option- used
dep.
4994 U> aux. Relay Not used Not
term. 98 output B Option- used
dep.
4995 U> aux. Enable OFF ON
term. 98 ON
4996 U> aux. Fail F1…F9 Warning
term. 98 class (F2)

DEIF Page 114 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.8 System parameters - general setup


2.8.1 Stop coil wirebreak and internal communication alarms
No. Setting Min. Factory Notes Ref. Description
Max. setting
6270 Stop coil wirebreak
6271 Stop coil Relay Not Not used Designer’s The wirebreak monitoring is
wirebreak output A used Reference only active when the stop
Option- Handbook coil output is deactivated.
dep.
6272 Stop coil Relay Not Not used
wirebreak output B used
Option-
dep.
6273 Stop coil Enable OFF OFF
wirebreak ON
6274 Stop coil Fail F1…F9 Warning
wirebreak class (F2)
6280 Internal communication fail
6281 Int. Relay Not Not used Designer’s This is the alarm for commu-
comm. fail output A used Reference nication fail between the
Option- Handbook main processor and the en-
dep. gine interface processor.
6282 Int. Relay Not Not used The alarm will also occur if
comm. fail output B used there is no supply on termi-
Option- nal 98-99 for Option M4.
dep.
6283 Int. Fail F1…F9 Warning
comm. fail class (F2)

2.8.2 Engine heater failure


No. Setting Min. Factory Notes Ref. Descrip-
Max. setting tion
6330 Engine heater 1
6331 Engine heater Set point 10 deg 30 deg Designer’s Refer-
1 250 deg ence Handbook
6332 Engine heater Timer 1.0 s 10.0 s
1 300.0 s
6333 Engine heater Relay out- Not used Not used
1 put A Option-dep.
6334 Engine heater Relay out- Not used Not used
1 put B Option-dep.
6335 Engine heater Enable OFF OFF
1 ON
6336 Engine heater Fail class F1…F9 Warning
1 (F2)

DEIF Page 115 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.8.3 Running detection


No. Setting Min. Factory Notes Ref. Descrip-
Max. setting tion
6350 Running detection
6351 Running Timer 1.0 s 10.0 s Designer’s Refer-
detection 1200.0 s ence Handbook
6352 Ext. eng. Stop Timer 1.0 s 10.0 s
1200.0 s
6353 Ext. eng. Stop Enable OFF ON
ON
6354 Ext. eng. Stop Fail class F1…F9 Warning
(F2)

2.8.4 Battery tests


No. Setting Min. Factory Notes Ref. Description
Max. setting
6410 Battery test
6411 Battery Setpoint 8.0 V 18.0 V Designer’s If the battery voltage
test 32.0 V Reference drops below setpoint
Handbook during crank test the
6412 Battery Timer 1s 20 s
test 300 s alarm activates.

6413 Battery Type Power supply Power


test Multi-input 102 supply If configured with “+
Multi-input105 Start Sequence”, the
Multi-input 108 timer is disabled and
the number of start
Power supply
98/99 attempts configured
in “Start attempts”
- “+ Start
(channel 6190) is run
Sequence”
without activating the
6414 Battery Relay Not used Not used run coil. After the
test output A Option-dep. sequence, the alarm
6415 Battery Enable OFF OFF “Start failure”
test ON (channel 4570) is
activated.
6416 Battery Fail F1…F9 Warning
test class (F2)
6420 Auto battery test
6421 Auto batt Enable On Off Designer’s Automatic battery
test Off Reference test time setting.
Handbook
6422 Auto batt Day Monday Monday
test Sunday
6423 Auto batt Hours 0h 10h
test 23 h
6424 Auto batt Week 1 52
test 52
6425 Auto batt Relay Not used Not used
test output A Option-dep.

DEIF Page 116 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
6430 Battery asymmetry
6431 Batt. T1 Power sup- Multi-in- Designer’s Battery asymmetry in-
asymme- ply put 105 Reference put selections.
try Multi-input Handbook
102
Multi-input
105
Multi-input
108
Power sup-
ply 98/99
6432 Batt. RF1 Power sup- Power
asymme- ply supply
try Multi-input
102
Multi-input
105
Multi-input
108
Power sup-
ply 98/99
6433 Batt. T2 Power sup- Multi-in-
asymme- ply put 108
try Multi-input
102
Multi-input
105
Multi-input
108
Power sup-
ply 98/99
6434 Batt. RF2 Power sup- Multi-in-
asymme- ply put 102
try Multi-input
102
Multi-input
105
Multi-input
108
Power sup-
ply 98/99

DEIF Page 117 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Description


Max. setting
6440 Battery asymmetry 1
6441 Battery Setpoint 0.1 V 1.0 V Designer’s If the battery voltage
asym 1 15.0 V Reference asymmetry between
6442 Battery Timer 0.0 s 1.0 s Handbook the single batteries ex-
asym 1 10.0 s ceeds the setting, the
alarm will activate.
6443 Battery Relay Not used Not used
asym 1 output A Option-dep.
6444 Battery Relay Not used Not used
asym 1 output B Option-dep.
6445 Battery Enable OFF OFF
asym 1 ON
6450 Battery asymmetry 2
6451 Battery Setpoint 0.1 V 1.0 V Designer’s If the battery voltage
asym 2 15.0 V Reference asymmetry between
6452 Battery Timer 0.0 s 1.0 s Handbook the single batteries ex-
asym 2 10.0 s ceeds the setting, the
alarm will activate.
6453 Battery Relay Not used Not used
asym 2 output A Option-dep.
6454 Battery Relay Not used Not used
asym 2 output B Option-dep.
6455 Battery Enable OFF OFF
asym 2 ON

DEIF Page 118 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.8.5 Max. ventilation


No. Setting Min. Factory Notes Ref. Description
Max. setting
6470 Max vent 1
6471 Max Set 20 deg 95 deg Designer’s If the cooling fans fail to oper-
vent 1 point 250 deg Reference ate and the coolant tempera-
6472 Max Timer 0.0 s 1.0 s Handbook ture exceeds the setting, the
vent 1 60.0 s alarm will activate.

6473 Max Relay Not used Not


vent 1 output A Option- used
dep.
6474 Max Relay Not used Not
vent 1 output B Option- used
dep.
6475 Max Enable OFF OFF
vent 1 ON
6476 Max Fail F1…F9 Warning
vent 1 class (F2)
6480 Max vent 2
6481 Max Set 20 deg 98 deg Designer’s If the cooling fans fail to oper-
vent 2 point 250 deg Reference ate and the coolant tempera-
6482 Max Timer 0.0 s 1.0 s Handbook ture exceeds the setting, the
vent 2 60.0 s alarm will activate.

6483 Max Relay Not used Not


vent 2 output A Option- used
dep.
6484 Max Relay Not used Not
vent 2 output B Option- used
dep.
6485 Max Enable OFF OFF
vent 2 ON
6486 Max Fail F1…F9 Shut-
vent 2 class down
(F5)

DEIF Page 119 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.8.6 Switchboard error - Block and Stop


No. Setting Min. Factory Notes Ref. Description
Max. setting
6500 Block switchboard error
6501 Blk. Timer 0.0 s 10.0 s Designer’s If the binary input “switchboard
swbd er- 999.0 s Reference error” activates, a stopped gen-
ror Handbook erator will be blocked for start.
6502 Blk. Parallel ON OFF Parameter 6502:
swbd er- OFF OFF: Only AMF start is affec-
ror ted.
ON: All starts are affected.
6503 Blk. Relay Not Not
swbd er- output used used
ror A Option-
dep.
6504 Blk. Relay Not Not
swbd er- output used used
ror B Option-
dep.
6505 Blk. Enable OFF OFF
swbd er- ON
ror
6506 Blk. Fail F1…F9 Warning
swbd er- class (F2)
ror
6510 Stop switchboard error
6511 Stp. Timer 0.0 s 1.0 s Designer’s If the binary input “switchboard
swbd er- 999.0 s Reference error” activates, the generator
ror Handbook will be stopped.
6512 Stp. Relay Not Not
swbd er- output used used
ror A Option-
dep.
6513 Stp. Relay Not Not
swbd er- output used used
ror B Option-
dep.
6514 Stp. Enable OFF OFF
swbd er- ON
ror
6515 Stp. Fail F1…F9 Shut-
swbd er- class down
ror (F5)

DEIF Page 120 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.8.7 Switchboard error - Not in auto


No. Setting Min. Factory Notes Ref. Descrip-
Max. setting tion
6540 Not in auto
6541 Not in auto Timer 10.0 s 300.0 s Designer’s Reference
900.0 s Handbook
6542 Not in auto Relay output Not used Not used
A Option-dep.
6543 Not in auto Relay output Not used Not used
B Option-dep.
6544 Not in auto Enable OFF OFF
ON
6545 Not in auto Fail class F1…F9 Warning
(F2)

2.8.8 Oil renewal


No. Setting Min. Factory Notes Ref. Description
Max. setting
6890 Oil renewal
6891 Oil renewal Setpoint 1h 750 h Designer's Ref- Setup of oil re-
999 h erence Hand- newal.
6892 Oil renewal Relay output Not used Not used book
A Option-dep.
6893 Oil renewal Relay output Not used Not used
B Option-dep.
6894 Adj. reset Password Basic Basic
value level Customer
Service

DEIF Page 121 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.8.9 Avg U BB
No. Setting Min. Factory Notes Ref. Description
Max. setting
7480 Avg U BB> 1
7481 Avg U Setpoint 100.0% 110.0% Option Busbar overvoltage alarm
BB> 1 120.0% A1 based on average measure-
7482 Avg U Timer 0.1 s 10.0 s ment of the voltage of the
BB> 1 3200.0 s busbar.

7483 Avg U Relay Not used Not used


BB> 1 output A Option-dep.
7484 Avg U Enable OFF OFF
BB> 1 ON
7485 Avg U Fail F1...F9 Warning
BB> 1 class (F2)
7486 Avg U AVG 30.0 s 600.0 s
BB> 1 timer 900.0 s
7490 Avg U BB> 2
7491 Avg U Setpoint 100.0% 110.0% Option Busbar overvoltage alarm
BB> 2 120.0% A1 based on average measure-
7492 Avg U Timer 0.1 s 10.0 s ment of the voltage of the
BB> 2 3200.0 s busbar.

7493 Avg U Relay Not used Not used


BB> 2 output A Option-dep.
7494 Avg U Enable OFF OFF
BB> 2 ON
7495 Avg U Fail F1...F9 Warning
BB> 2 class (F2)
7496 Avg U AVG 30.0 s 600.0 s
BB> 2 timer 900.0 s

DEIF Page 122 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.9 System parameters - communication


2.9.1 External communication error
No. Setting Min. Factory Notes Ref. Description
Max. setting
7520 External communication error
7521 Ext. Delay 1.0 s 10.0 s Option: Supervision of the
comm. 100.0 s Modbus external communication
error (H2) line.
7522 Ext. Relay Not used Not Profibus The alarm will occur
comm. output A Option- used (H3) when there has not been
error dep. any communication
during the time delay.
7523 Ext. Relay Not used Not
comm. output B Option- used
error dep.
7524 Ext. Enable OFF OFF
comm. ON
error
7525 Ext. Fail F1…F9 Warning
comm. class (F2)
error
7530 Internal communication ID
Designer’s The mode decides the
7532 Int. CAN Manual Manual Reference reaction of the power
comm. fail. Semi auto Handbook management system in
ID mode No mode case of different errors on
change the CAN communication
lines.
7533 Int. Missing F1…F9 Warning
Mode:
comm. all units (F2)
- Manual
ID
- Semi auto
7534 Int. Fatal CAN F1…F9 Warning - No mode change
comm. error (F2)
ID
7535 Int. Any DG F1…F9 Warning
comm. missing (F2)
ID
7536 Int. Any F1…F9 Warning
comm. mains (F2)
ID missing

DEIF Page 123 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.9.2 Engine interface communication alarms


No. Setting Min. Factory Notes Ref. Descrip-
Max. setting tion
7570 EI comm. error
7571 EI comm. Timer 0.0 s 0.0 s Option: Supervi-
error 100.0 s J1939 and MTU ADEC/ sion of
7572 EI comm. Relay Not used Not used MDEC (H5) the EIC
error output A Option-dep. Cummins Modbus (H6) communi-
J1939 (H7) cation
7573 EI comm. Relay Not used Not used
line. The
error output B Option-dep.
alarm will
7574 EI comm. Enable OFF ON occur
error ON when
7575 EI comm. Fail F1…F9 Warning there has
error class (F2) not been
any com-
munica-
tion dur-
ing the
time de-
lay.
7580 EIC warning
7581 EIC warn- Timer 0.0 s 0.0 s Option:
ing 100.0 s J1939 and MTU ADEC/
7582 EIC warn- Relay Not used Not used MDEC (H5)
ing output A Option-dep. Cummins Modbus (H6)
J1939 (H7)
7583 EIC warn- Relay Not used Not used
ing output B Option-dep.
7584 EIC warn- Enable OFF ON
ing ON
7585 EIC warn- Fail F1…F9 Warning
ing class (F2)
7590 EIC shutdown
7591 EIC shut- Timer 0.0 s 0.0 s Option:
down 100.0 s J1939 and MTU ADEC/
7592 EIC shut- Relay Not used Not used MDEC (H5)
down output A Option-dep. Cummins Modbus (H6)
J1939 (H7)
7593 EIC shut- Relay Not used Not used
down output B Option-dep.
7594 EIC shut- Enable OFF OFF
down ON
7595 EIC shut- Fail F1…F9 Shutdown
down class (F5)

DEIF Page 124 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Descrip-


Max. setting tion
7600 EIC overspeed
7601 EIC over- Setpoint 100.0% 110.0% Option:
speed 150.0% J1939 and MTU ADEC/
7602 EIC over- Timer 0.0 s 5.0 s MDEC (H5)
speed 100.0 s Cummins Modbus (H6)
J1939 (H7)
7603 EIC over- Relay Not used Not used
speed output A Option-dep.
7604 EIC over- Relay Not used Not used
speed output B Option-dep.
7605 EIC over- Enable OFF OFF
speed ON
7606 EIC over- Fail F1…F9 Warning
speed class (F2)
7610 EIC coolant temp. 1
7611 EIC coolant Setpoint -40 deg 100 deg Option:
t. 1 410 deg J1939 and MTU ADEC/
7612 EIC coolant Timer 0.0 s 5.0 s MDEC (H5)
t. 1 100.0 s Cummins Modbus (H6)
J1939 (H7)
7613 EIC coolant Relay Not used Not used
t. 1 output A Option-dep.
7614 EIC coolant Relay Not used Not used
t. 1 output B Option-dep.
7615 EIC coolant Enable OFF OFF
t. 1 ON
7616 EIC coolant Fail F1…F9 Warning
t. 1 class (F2)
7620 EIC coolant temp. 2
7621 EIC coolant Setpoint -40 deg 110 deg Option:
t. 2 410 deg J1939 and MTU ADEC/
7622 EIC coolant Timer 0.0 s 5.0 s MDEC (H5)
t. 2 100.0 s Cummins Modbus (H6)
J1939 (H7)
7623 EIC coolant Relay Not used Not used
t. 2 output A Option-dep.
7624 EIC coolant Relay Not used Not used
t. 2 output B Option-dep.
7625 EIC coolant Enable OFF OFF
t. 2 ON
7626 EIC coolant Fail F1…F9 Warning
t. 2 class (F2)
7630 EIC oil pressure 1
7631 EIC oil Setpoint 0.0 bar 2.0 bar Option:
press. 1 145.0 bar J1939 and MTU ADEC/
7632 EIC oil Timer 0.0 s 5.0 s MDEC (H5)
press. 1 100.0 s

DEIF Page 125 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Descrip-


Max. setting tion
7633 EIC oil Relay Not used Not used Cummins Modbus (H6)
press. 1 output A Option-dep. J1939 (H7)
7634 EIC oil Relay Not used Not used
press. 1 output B Option-dep.
7635 EIC oil Enable OFF OFF
press. 1 ON
7636 EIC oil Fail F1…F9 Warning
press. 1 class (F2)
7640 EIC oil pressure 2
7641 EIC oil Setpoint 0.0 bar 1.0 bar Option:
press. 2 145.0 bar J1939 and MTU ADEC/
7642 EIC oil Timer 0.0 s 5.0 s MDEC (H5)
press. 2 100.0 s Cummins Modbus (H6)
J1939 (H7)
7643 EIC oil Relay Not used Not used
press. 2 output A Option-dep.
7644 EIC oil Relay Not used Not used
press. 2 output B Option-dep.
7645 EIC oil Enable OFF OFF
press. 2 ON
7646 EIC oil Fail F1…F9 Shutdown
press. 2 class (F5)
7650 EIC oil temp 1
7651 EIC oil Setpoint 0 deg 40 deg Option:
temp. 1 410 deg J1939 and MTU ADEC/
7652 EIC oil Timer 0.0 s 5.0 s MDEC (H5)
temp. 1 100.0 s Cummins Modbus (H6)
J1939 (H7)
7653 EIC oil Relay Not used Not used
temp. 1 output A Option-dep.
7654 EIC oil Relay Not used Not used
temp. 1 output B Option-dep.
7655 EIC oil Enable OFF OFF
temp. 1 ON
7656 EIC oil Fail F1…F9 Warning
temp. 1 class (F2)
7660 EIC oil temp 2
7661 EIC oil Setpoint 0 deg 50 deg Option:
temp. 2 410 deg J1939 and MTU ADEC/
MDEC (H5)
7662 EIC oil Timer 0.0 s 5.0 s
temp. 2 100.0 s Cummins Modbus (H6)
J1939 (H7)
7663 EIC oil Relay Not used Not used
temp. 2 output A Option-dep.
7664 EIC oil Relay Not used Not used
temp. 2 output B Option-dep.

DEIF Page 126 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Descrip-


Max. setting tion
7665 EIC oil Enable OFF OFF
temp. 2 ON
7666 EIC oil Fail F1…F9 Shutdown
temp. 2 class (F5)
7670 EIC coolant level 1
7671 EIC coolant Setpoint 0% 20% Designer's Reference
level 1 100% Handbook/option:
7672 EIC coolant Timer 0.0 s 5.0 s Cummins Modbus (H6)
level 1 100.0 s J1939 and MTU ADEC/
MDEC (H5)
7673 EIC coolant Relay Not used Not used
J1939 (H7)
level 1 output A Variant-
dep.
7674 EIC coolant Relay Not used Not used
level 1 output B Variant-
dep.
7675 EIC coolant Enable OFF OFF
level 1 ON
7676 EIC coolant Fail F1...F9 Warning
level 1 class (F2)
7680 EIC coolant level 2
7681 EIC coolant Setpoint 0% 10% Designer's Reference
level 2 100% Handbook/option:
7682 EIC coolant Timer 0.0 s 5.0 s Cummins Modbus (H6)
level 2 100.0 s J1939 and MTU ADEC/
MDEC (H5)
7683 EIC coolant Relay Not used Not used
J1939/H7)
level 2 output A Variant-
dep.
7684 EIC coolant Relay Not used Not used
level 2 output B Variant-
dep.
7685 EIC coolant Enable OFF OFF
level 2 ON
7686 EIC coolant Fail F1...F9 Shutdown
level 2 class (F5)
7690 EIC Cyl dif. 1
7691 EIC Cyl dif. Setpoint 0 100 deg Option:
1 9999 J1939 and MTU ADEC/
MDEC (H5)
7692 EIC Cyl dif. Timer 0.0 s 5.0 s
Cummins Modbus (H6)
1 100.0 s
J1939 (H7)
7693 EIC Cyl dif. Relay Not used Not used
1 output A Option-dep.
7694 EIC Cyl dif. Relay Not used Not used
1 output B Option-dep.
7695 EIC Cyl dif. Enable OFF OFF
1 ON

DEIF Page 127 of 210


AGC-4 parameter list 4189340688 UK Alarm list

No. Setting Min. Factory Notes Ref. Descrip-


Max. setting tion
7696 EIC Cyl dif. Fail F1…F9 Warning
1 class (F2)
7700 EIC Cyl dif. 2
7701 EIC Cyl dif. Setpoint 0 110 deg Option:
2 9999 J1939 and MTU ADEC/
7702 EIC Cyl dif. Timer 0.0 s 5.0 s MDEC (H5)
2 100.0 s Cummins Modbus (H6)
J1939 (H7)
7703 EIC Cyl dif. Relay Not used Not used
2 output A Option-dep.
7704 EIC Cyl dif. Relay Not used Not used
2 output B Option-dep.
7705 EIC Cyl dif. Enable OFF OFF
2 ON
7706 EIC Cyl dif. Fail F1…F9 Warning
2 class (F2)

2.9.3 Power management communication error


No. Setting Min. Factory Notes Ref. Description
Max. setting
7870 Any BTB missing/appl hazard
7871 Any Fail F1…F9 Warning Designer’s The “Any BTB missing” alarm is
BTB class (F2) Reference activated if the communication to
missing Handbook any BTB unit failed.
7872 Appl Enable ON ON The application hazard alarm is
hazard OFF activated if different applications
are installed in the controllers.
7873 Appl Fail F1…F9 Warning
hazard class (F2)

DEIF Page 128 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.9.4 Internal CAN communication error


No. Setting Min. Factory Notes Ref. Description
Max. setting
7930 CAN1 communication error
7931 CAN1 Timer 10.0 s 10.0 s Option: If both options H8.x are
com error 600.0 s External I/O present, an error on any
7932 CAN1 Relay Not used Not used modules of these will activate the
com error output A Option- (H8.2) alarm.
dep.
7933 CAN1 Relay Not used Not used
com error output B Option-
dep.
7934 CAN1 Enable OFF ON
com error ON
7935 CAN1 Fail F1…F9 Warning
com error class (F2)
7940 CAN2 comm error
7941 CAN2 Timer 10.0 s 10.0 s Option: If both options H8.x are
comm er- 600.0 s External I/O present, an error on any
ror modules of these will activate the
7942 CAN2 Relay Not used Not used (H8.2) alarm.
comm er- output A Option-
ror dep.
7943 CAN2 Relay Not used Not used
comm er- output B Option-
ror dep.
7944 CAN2 Enable OFF ON
comm er- ON
ror
7945 CAN2 Fail F1…F9 Warning
comm er- class (F2)
ror

DEIF Page 129 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.10 External I/O parameters


2.10.1 External I/O alarm setup

The alarms based on external I/O modules can only be configured using the PC utility software.

2.10.2 Analogue inputs


No. Setting Min. Factory Notes Ref. Descrip-
Max. setting tion
12000 Ext. Ain 1.1
Ext. Ain 1.1 Setpoint 0 10 Option:
10 External I/O modules
Ext. Ain 1.1 Timer 0.0 s 10.0 s (H8.x)
600.0 s
Ext. Ain 1.1 Fail class F1…F9 Warning
(F2)
Ext. Ain 1.1 Relay output Not used Not used
A Option-dep.
Ext. Ain 1.1 Relay output Not used Not used
B Option-dep.
Ext. Ain 1.1 Enable OFF OFF
ON
12010 Ext. Ain 1.2
Ext. Ain 1.2 Setpoint 0 10 Option:
10 External I/O modules
Ext. Ain 1.2 Timer 0.0 s 10.0 s (H8.x)
600.0 s
Ext. Ain 1.2 Fail class F1…F9 Warning
(F2)
Ext. Ain 1.2 Relay output Not used Not used
A Option-dep.
Ext. Ain 1.2 Relay output Not used Not used
B Option-dep.
Ext. Ain 1.2 Enable OFF OFF
ON

The same settings apply to external analogue inputs 2-8, menus 12030-12220.

DEIF Page 130 of 210


AGC-4 parameter list 4189340688 UK Alarm list

2.10.3 External analogue input scale


No. Setting Min. Factory Notes Ref. Description
Max. setting
12230 4-20 mA Ext in 1 scale
4-20 mA Setpoint No deci- One dec- Option: Selecting "Enable" and
Ext in 1 mal imal External I/O writing the new setpoint
scale Two deci- modules will scale the associated
mal (H8.x) min., max. and value auto-
4-20 mA Enable OFF OFF matically.
Ext in 1 ON
scale

2.10.4 Digital inputs


No. Setting Min. Factory Notes Ref. Descrip-
Max. setting tion
12540 Ext. dig. in 1
Ext. dig. in 1 Timer 0.0 s 10.0 s Option:
100.0 s External I/O modules
Ext. dig. in 1 Fail class F1…F9 Warning (H8.x)
(F2)
Ext. dig. in 1 Relay output Not used Not used
A Option-dep.
Ext. dig. in 1 Relay output Not used Not used
B Option-dep.
Ext. dig. in 1 Enable OFF OFF
ON
Ext. dig. in 1 High alarm OFF ON
ON

The same settings apply to external digital inputs 2-16, menus 12550-12690.

DEIF Page 131 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3. Parameter list
3.1 General information about the parameter list
3.1.1 Parameter list settings
The parameter list contains settings for regulators and other non-alarm-related settings.

DEIF Page 132 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.2 Control parameters - synchronisation


3.2.1 Synchronisation
No. Setting Min. Factory Notes Ref. Description
Max. setting
2000 Sync type
2001 Sync. Type Dynamic Dynamic Designer’s Static sync aims at a fre-
type sync sync Reference quency difference of 0 Hz.
Static Handbook Dynamic sync aims at a
sync frequency difference (mid-
point between setting
2021 dfMax. and 2022
dfMin.).
OFF = dynamic sync,
ON = static sync.
2020 Dynamic sync
2021 Dynamic dfMax 0.0 Hz 0.3 Hz Designer’s Menu 2020 is only appli-
sync 0.5 Hz Reference cable if "Dynamic sync." is
2022 Dynamic dfMin -0.5 Hz 0.0 Hz Handbook chosen in menu 2001.
sync 0.3 Hz
2023 Dynamic dUMax 2% 5%
sync 10%
2024 Dynamic Sync t. 40 ms 50 ms
sync GB/BTB/ 300 ms
TB
2025 Dynamic Sync t. 40 ms 50 ms
sync MB 300 ms
2030 Static sync
2031 Static dfMax 0.00 Hz 0.10 Hz Designer’s Menu 2030 is only appli-
sync 0.50 Hz Reference cable if "Static sync" is
2032 Static dUMax 1% 5% Handbook chosen in menu 2001.
sync 10%
2033 Static Close win- 0.1 deg 10.0 deg
sync dow 20.0 deg
2034 Static Timer 0.1 s 1.0 s
sync 99.0 s
2035 Static GB sync. Breaker Breaker
sync type Infinite
sync.
2036 Static MB sync. Breaker Breaker
sync type Infinite
sync.
2040 Frequency synchronisation control analogue
2041 f sync f Kp 0.00 2.50 Option E1, PID controller for dynamic
60.00 E2, EF2, sync.
2042 f sync f Ti 0.00 s 1.50 s EF4, EF5 This menu is only applica-
60.00 s ble if “analogue” or “EIC”
is selected in menu 2780.
2043 f sync f Td 0.00 s 0.00 s
2.00 s

DEIF Page 133 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
2050 Frequency synchronisation control relay
2051 f sync Kp 0 10 Designer’s This menu is only applica-
100 Reference ble if “relay” is selected in
Handbook menu 2780.
2060 Phase sync analogue
2061 Phase Phase Kp 0.00 0.50 Designer’s PID controller for static
sync 60.00 Reference sync.
2062 Phase Phase Ti 0.00 s 3.00 s Handbook This menu is only applica-
sync 60.00 s ble if “analogue” or “EIC”
is selected in menu 2780.
2063 Phase Phase Td 0.00 s 0.00 s
sync 2.00 s
2070 Phase control relay
2071 Phase Kp 0 10 Designer’s This menu is only applica-
100 Reference ble if “relay” is selected in
Handbook menu 2780.
2110 Synchronisation blackout
2111 Sync dfMax 0.0 Hz 3.0 Hz Designer’s Settings are accepted lim-
blackout 5.0 Hz Reference its for closing of the
2112 Sync dUMax 2% 5% Handbook breaker, referring to nomi-
blackout 10% nal frequency and volt-
age.
2240 Separate synchronisation relay
2241 Sep sync Relay out- Not used Not used Designer’s The output activates dur-
relay put A Option- Reference ing synchronisation and
dep. Handbook thereby a separate syn-
2242 Sep sync Relay out- Not used Not used chronising unit can be ac-
relay put B Option- tivated.
dep.
2250 Close before excitation
2251 Close Setpoint 0 rpm 400 rpm Designer’s If set ON the function will
bef. exc. 4000 rpm Reference close the breaker at the
2252 Close Timer 0.0 s 5.0 s Handbook selected speed. The relay
bef. exc. 999.0 s output is used for the ex-
citation ON signal. Re-
2253 Close Relay out- Not used Not used
member to set the selec-
bef. exc. put A Option-
ted relay in “Limit” mode.
dep.
2554 Close Enable OFF OFF
bef. exc. ON
2260 Breaker sequence
2261 Breaker Break Close GB Close Designer’s The sequence is used for
seq. Close GB GB Reference the closed before excita-
+TB Handbook tion function. The excita-
2262 Breaker Timer 0.0 s 5.0 s tion will be activated at
seq. 999.0 s the selected speed in
menu 2263.
2263 Breaker RpmOK 0 rpm 1450
seq. 4000 rpm rpm
2264 Volt. Timer 1.0 s 5.0 s
discharge 20.0 s

DEIF Page 134 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
2265 Volt. rerun Setpoint 30%-100% 30%
lvl

2266 ExcCtr Setpoint Exc. Follow Exc.


cooldown busbar – Follow
Exc. busbar
Constant
OFF

DEIF Page 135 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.3 Control parameters - regulation


3.3.1 Regulation
No. Setting Min. Factory Notes Ref. Description
Max. setting
2510 Frequency control analogue
2511 f control f Kp 0.00 2.50 Designer’s PID controller for frequency
60.00 Reference control.
2512 f control f Ti 0.00 s 1.50 s Handbook This menu is only applicable
60.00 s if "analogue" or “EIC” is
selected in menu 2781.
2513 f control f Td 0.00 s 0.00 s
The droop setting will be ap-
2.00 s
plied on top of the regulation
2514 f droop Droop 0% 0% output.
setting 10%
2530 Power control analogue
2531 P con- P Kp 0.00 2.50 Designer’s PID controller for power con-
trol 60.00 Reference trol.
2532 P con- P Ti 0.00 s 1.50 s Handbook This menu is only applicable
trol 60.00 s if "analogue" or “EIC” is
selected in menu 2781.
2533 P con- P Td 0.00 s 0.00 s
trol 2.00 s
2540 Power load sharing control analogue
2541 P LS P LS Kp 0.00 2.50 Designer’s PID controller for load shar-
control 60.00 Reference ing control.
2542 P LS P LS Ti 0.00 s 1.50 s Handbook This menu is only applicable
control 60.00 s if "analogue" or “EIC” is
selected in menu 2781.
2543 P LS P LS Td 0.00 s 0.00 s
control 2.00 s
2550 Analogue governor offset
2551 Ana- Offset 0% 50% Designer’s PID controller for freq. con-
logue 100% Reference trol.
GOV Handbook This menu is only applicable
2552 Ana- Offset 0% 50% if "analogue" or “EIC” is
logue 100% selected in menu 2781.
GOV
2553 Ana- Offset 0% 50%
logue 100%
GOV
2554 Ana- Offset 0% 50%
logue 100%
GOV
2570 Frequency control relay output
2571 f control Dead 0.2% 1.0% Designer’s This menu is only applicable
relay band 10.0% Reference if "relay" is selected in menu
2572 f control Kp 0 10 Handbook 2781.
relay 100 The droop setting will be ap-
plied on top of the regulation
2573 f droop Droop 0% 0%
output.
relay setting 10%

DEIF Page 136 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
2580 Power control relay output
2581 P con- Dead 0.2% 2.0% Designer’s This menu is only applicable
trol relay band 10.0% Reference if "relay" is selected in menu
2582 P con- Kp 0 10 Handbook 2781.
trol relay 100
2590 Load sharing control relay output
2591 LS ctrl. f dead 0.2% 1.0% Designer’s This menu is only applicable
relay band 10.0% Reference if "relay" is selected in menu
2592 LS ctrl. LS Kp 0 10 Handbook 2781.
relay 100
2593 LS ctrl. P dead 0.2% 2.0%
relay band 10.0%
2594 LS ctrl. P weight 0.0% 10.0%
relay 100.0%
2600 Relay control
2601 Relay GOV ON 10 ms 500 ms Designer’s This menu is only applicable
control time 6500 ms Reference if "relay" is selected in menu
2602 Relay GOV pe- 50 ms 2500 ms Handbook 2781.
control riod time 32500 ms NOTE: In the PC utility soft-
ware, settings 2603/2604 are
2603 Relay Relay Not used Not
found under menu 2602.
control output A Option- used
Output A is increase and out-
(Increase dep.
put B is decrease.
relay)
2604 Relay Relay Not used Not
control output B Option- used
(De- dep.
crease
relay)
2610 Power ramp up
2611 Power Speed 0.1%/s 2.0%/s Designer’s The delay point determines
ramp up 20.0%/s Reference when the generator will make
2612 Power Delay 1% 10% Handbook a temporary stop ramping up
ramp up point 100% after closing of the generator
breaker to preheat the en-
2613 Power Delay 0s 10 s
gine before commencing
ramp up time 9900 s
load taking.
2614 Island Enable OFF OFF If the delay function is not
needed, set this time to 0.
ramp ON
Power % settings relate to
2615 Power Steps 0 1 nominal generator power.
ramp up 100

2616 Power Speed 0.1%/s 0.1&/s Can be activated by ch. 2624


ramp up 20%/s or M-Logic.
2

DEIF Page 137 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
2620 Power ramp down
2621 Power Speed 0.1%/s 3.3%/s Designer’s The breaker open point de-
ramp 20.0%/s Reference termines when the "open
down Handbook breaker" relay output is acti-
2622 Power Breaker 1% 5% vated to open the generator
ramp open 20% breaker before reaching 0
down point kW. Power % settings relate
to nominal generator power.
2623 Power Speed 0.1%/s 0.1%/s Slope of Ramp 2, when
ramp 20.0%/s ramping down. (Not used for
down deload)
2
2624 Auto Enable OFF ON ON: Ramp 2 is used with
ramp ON Freq. dependent P droop
select OFF: Ramp 2 is enabled via
M-Logic

2640 Voltage control analogue


2641 U con- U Kp 0.00 2.50 Option: PID controller for voltage
trol 60.00 AVR con- control.
2642 U con- U Ti 0.00 s 1.50 s trol This menu is only applicable
trol 60.00 s (D1) if “analogue” or “EIC” is
selected in menu 2783.
2643 U con- U Td 0.00 s 0.00 s
The droop setting will be ap-
trol 2.00 s
plied on top of the regulation
2644 U droop Droop 0% 0% output.
setting 10%
2650 Reactive power control analogue
2651 Q con- Q Kp 0.00 2.50 Option: PID controller for reactive
trol 60.00 AVR con- power control.
2652 Q con- Q Ti 0.00 s 1.50 s trol The reactive power control is
trol 60.00 s (D1) used for power factor as well
as reactive power control.
2653 Q con- Q Td 0.00 s 0.00 s
This menu is only applicable
trol 2.00 s
if analogue output is selected
in menu 2783.
2660 Reactive power load sharing control analogue
2661 Q load Q LS Kp 0.00 2.50 Option: The VAr (Q) load sharing is
sh. ctrl 60.00 AVR con- based on a mix of voltage
2662 Q load Q LS Ti 0.00 s 1.50 s trol and VAr control. The setting
sh. ctrl 60.00 s (D1) 2664 is setting the impact of
the VAr controller over the
2663 Q load Q LS Td 0.00 s 0.00 s
voltage controller.
sh. ctrl 2.00 s
This menu is only applicable
2664 Q load Q weight 0.0% 10.0% if “analogue” or “EIC” is
sh. ctrl 100.0% selected in menu 2783.

DEIF Page 138 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
2670 Analogue AVR output offset
2671 Ana- Offset 0% 50% Option: This setting sets the offset of
logue 100% AVR con- the analogue output when
AVR trol starting the generator.
2672 Ana- Offset 0% 50% (D1) This menu is only applicable
logue 100% if “analogue” or “EIC” is
AVR selected in menu 2783.
2673 Ana- Offset 0% 50%
logue 100%
AVR
2674 Ana- Offset 0% 50%
logue 100%
AVR
2690 Voltage control relay
2691 U con- U dead 0.0% 2.0% Option: PI controller for voltage con-
trol band 10.0% AVR con- trol.
2692 U con- U Kp 0 10 trol This menu is only applicable
trol 100 (D1) if "relay" is selected in menu
2783.
2693 U droop Droop 0% 0%
The droop setting will be ap-
relay setting 10%
plied on top of the regulation
output.
2700 Reactive power control relay
2701 Q con- Q dead 0.0% 2.0% Option: PI controller for reactive pow-
trol band 10.0% AVR con- er control.
2702 Q con- Q Kp 0 10 trol The reactive power control is
trol 100 (D1) used for power factor as well
as reactive power control.
This menu is only applicable
if "relay" is selected in menu
2783.
2710 Reactive power load sharing control relay
2711 Q load U dead 0.0% 1.0% Option: The VAr (Q) load sharing is
sh. ctrl band 10.0% AVR con- based on a mix of voltage
2712 Q load U Kp 0 10 trol and VAr control. The setting
sh. ctrl 100 (D1) 2664 is setting the impact of
the VAr controller over the
2713 Q load Q dead 0.0% 2.0%
voltage controller.
sh. ctrl band 10.0%
This menu is only applicable
2714 Q load Q weight 0.0% 10.0% if "relay" is selected in menu
sh. ctrl 100.0% 2783.
2720 Relay control setup (AVR)
2721 Relay AVR ON 10 ms 100 ms Option: Relay outputs for voltage/
control time tN 3000 ms AVR con- VAr/power factor control.
2722 Relay AVR per 50 ms 500 ms trol This menu is only applicable
control time tP 15000 ms (D1) if "relay" is selected in menu
2723 Relay Relay Not used Not 2783.
control output A Option- used
(U in- dep.
crease)

DEIF Page 139 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
2724 Relay Relay Not used Not
control output B Option- used
(U de- dep.
crease)
2740 Delay regulation
2741 Delay Timer 0s 3s Designer’s Delay of activating regulation
reg. 9900 s Reference after running feedback has
2742 Delay Relay Not used Not Handbook been detected.
reg. output A Option- used
dep.
2743 Delay Relay Not used Not
reg. output B Option- used
dep.
2744 Delay Enable OFF OFF
reg. ON
2760 Overlap
2761 Overlap Setpoint OFF OFF Designer’s If set ON the generator and
ON Reference mains breaker will never both
2762 Overlap Timer 0.10 s 0.30 s Handbook be closed for a longer time
99.90 s period than the selected.

2770 EIC speed control


2771 Scania Droop 0.0% 0.0% Option: Setting of speed control via
control 25.0% J1939 engine communication inter-
2772 Scania rpm User User (H5 or H7) face.
control 1500 The settings are only
RPM applicable if "Scania" is
1800 selected in menu 7561.
RPM
Low idle

2773 Cum- Kp 0.00 5.00


mins 10.00
Gain

2780 Regulator output


2781 Reg. GOV Relay EIC Relay Designer’s Selection of the speed out-
output Analogue Reference put: Relay, analogue or en-
Handbook gine interface communica-
tion. Analogue and EIC are
option-dependent.
2782 Man GOV 0.1 sec 5 sec Designer's This timer is used to define
step 10 sec Reference how long the governor up/
Handbook down pulse should be, by ac-
tivating an AOP button or a
digital input.

DEIF Page 140 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
2783 Reg. AVR Relay Relay Option: Generator voltage control
output Analogue AVR con- based on relay, analogue or
EIC trol EIC output signals.
(D1) Analogue selection is only
Option: available if option E1, E2,
J1939 (H5 EF2, EF4 or F2 is present.
or H7)
2784 Man AVR 0.1 sec 5 sec Designer's This timer is used to define
step 10 sec Reference how long the AVR up/down
handbook pulse should be, by activat-
ing an AOP button or a digital
input.
2790 EIC speed demand switch
2791 EIC Local Ana. CAN Ana. Option: See description in option H5
speed norm sw. Up/Down CAN Engine manual.
dem. ECU communi-
sw. Up/Down cation
CAN (H5)
Ana. ECU
Ana. ECU
rel.
Frequen-
cy
2792 EIC Local Ana. CAN Ana.
speed Emerg Up/Down CAN
dem. sw. ECU
sw. Up/Down
CAN
Ana. ECU
Ana. ECU
rel.
Frequen-
cy
2793 EIC Remote Ana. CAN Ana.
speed norm sw. Up/Down CAN
dem. ECU
sw. Up/Down
CAN
Ana. ECU
Ana. ECU
rel.
Frequen-
cy

DEIF Page 141 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
2794 EIC Remote Ana. CAN Ana.
speed Emerg Up/Down CAN
dem. sw. ECU
sw. Up/Down
CAN
Ana. ECU
Ana. ECU
rel.
Frequen-
cy
2950 Base load
2951 Base Power 10% 90% Designer’s Setting and enabling of base
load set 120% Reference load running. Note: Base
2952 Base Enable OFF OFF Handbook load is only possible in semi
load ON auto mode.
Menu 2953 specifies what
2953 Base Return Semi au- Auto
mode to return to after base
load mode to mode mode
load is completed.
Auto
mode
2960 Warm up ramp
2960 Warm up Setpoint Option- Multi- Designer’s When the function input is
type dep. input Reference activated, it ramps to the SP
102 Handbook from “Power ramp up”
2961 Warm up Setpoint 0 deg. 0 deg. (channel 2612) and disables
thresh. the “Power ramp up”
482 deg.
function. When the input is
2962 Warm up Enable OFF OFF set low again, it ramps
type ON beyond the limitation.

DEIF Page 142 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.4 Control parameters - output setup


3.4.1 Digital output setup
No. Setting Min. Factory Notes Ref. Description
Max. setting
5000 Relay 05
5001 Relay Func- Alarm re- Horn re- Designer’s Function selections:
05 tion lay ND lay Reference - Alarm relay ND
Alarm re- Handbook - Limit relay
lay NE - Horn relay
5002 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
05 lay 999.9 s
5010 Relay 08
5011 Relay Func- Alarm re- Alarm re- Designer’s Function selections:
08 tion lay ND lay ND Reference - Alarm relay ND
Alarm re- Handbook - Limit relay
lay NE - Horn relay
5012 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
08 lay 999.9 s This relay is only available if
no mains breaker is control-
led by the AGC.
5020 Relay 11
5021 Relay Func- Alarm re- Alarm re- Designer’s Function selections:
11 tion lay ND lay ND Reference - Alarm relay ND
Alarm re- Handbook - Limit relay
lay NE - Horn relay
5022 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
11 lay 999.9 s This relay is only available if
no mains breaker is control-
led by the AGC.
5030 Relay 14
5031 Relay Func- Alarm re- Alarm re- Designer’s Function selections:
14 tion lay ND lay ND Reference - Alarm relay ND
Alarm re- Handbook - Limit relay
lay NE - Horn relay
5032 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
14 lay 999.9 s This relay is only available if
no generator breaker is con-
trolled by the AGC.
5040 Relay 17
5041 Relay Func- Alarm re- Alarm re- Option G4 Function selections:
17 tion lay ND lay ND and G5 - Alarm relay ND
Alarm re- - Limit relay
lay NE - Horn relay
5042 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
17 lay 999.9 s This relay is only available if
no generator breaker is con-
trolled by the AGC.

DEIF Page 143 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
5050 Relay 20
5051 Relay Func- Alarm re- Alarm re- Designer’s Function selections:
20 tion lay ND lay ND Reference - Alarm relay ND
Alarm re- Handbook - Limit relay
lay NE - Horn relay
5052 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
20 lay 999.9 s This relay is only available if
"Relay" is selected in menu
5271.
5060 Relay 21
5061 Relay Func- Alarm re- Alarm re- Designer’s Function selections:
21 tion lay ND lay ND Reference - Alarm relay ND
Alarm re- Handbook - Limit relay
lay NE - Horn relay
5062 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
21 lay 999.9 s This relay is only available if
"Relay" is selected in menu
5272.
5070 Relay 29
5071 Relay Func- Alarm re- Alarm re- Option Function selections:
29 tion lay ND lay ND M14.2 - Alarm relay ND
Alarm re- - Limit relay
lay NE - Horn relay
5072 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
29 lay 999.9 s
5080 Relay 31
5081 Relay Func- Alarm re- Alarm re- Option Function selections:
31 tion lay ND lay ND M14.2 - Alarm relay ND
Alarm re- - Limit relay
lay NE - Horn relay
5082 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
31 lay 999.9 s
5090 Relay 33
5091 Relay Func- Alarm re- Alarm re- Option Function selections:
33 tion lay ND lay ND M14.2 - Alarm relay ND
Alarm re- - Limit relay
lay NE - Horn relay
5092 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
33 lay 999.9 s
5100 Relay 35
5101 Relay Func- Alarm re- Alarm re- Option Function selections:
35 tion lay ND lay ND M14.2 - Alarm relay ND
Alarm re- - Limit relay
lay NE - Horn relay
5102 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
35 lay 999.9 s

DEIF Page 144 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
5110 Relay 57
5111 Relay Func- Alarm re- Alarm re- Option M12 Function selections:
57 tion lay ND lay ND - Alarm relay ND
Alarm re- - Limit relay
lay NE - Horn relay
5112 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
57 lay 999.9 s
5120 Relay 59
5121 Relay Func- Alarm re- Alarm re- Option M12 Function selections:
59 tion lay ND lay ND - Alarm relay ND
Alarm re- - Limit relay
lay NE - Horn relay
5122 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
59 lay 999.9 s
5130 Relay 61
5131 Relay Func- Alarm re- Alarm re- Option M12 Function selections:
61 tion lay ND lay ND - Alarm relay ND
Alarm re- - Limit relay
lay NE - Horn relay
5132 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
61 lay 999.9 s
5140 Relay 63
5141 Relay Func- Alarm re- Alarm re- Option M12 Function selections:
63 tion lay ND lay ND - Alarm relay ND
Alarm re- - Limit relay
lay NE - Horn relay
5142 Relay OFF de- 0.0 s 5.0 s - Alarm relay NE
63 lay 999.9 s
5150 Relay 65
5151 Relay Func- Alarm re- Alarm re- Designer’s Used for governor UP com-
65 tion lay ND lay ND Reference mand if "Relay" is selected
Alarm re- Handbook in menu 2781.
lay NE Function selections:
5152 Relay OFF de- 0.0 s 5.0 s - Alarm relay ND
65 lay 999.9 s - Limit relay
- Horn relay
- Alarm relay NE
5160 Relay 67
5161 Relay Func- Alarm re- Alarm re- Designer’s Used for governor DOWN
67 tion lay ND lay ND Reference command if "Relay" is selec-
Alarm re- Handbook ted in menu 2781.
lay NE Function selections:
5162 Relay OFF de- 0.0 s 0.0 s - Alarm relay ND
67 lay 999.9 s - Limit relay
- Horn relay
- Alarm relay NE

DEIF Page 145 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
5170 Relay 69
5171 Relay Func- Alarm re- Alarm re- Designer’s Used for AVR UP command
69 tion lay ND lay ND Reference if "Relay" is selected in
Alarm re- Handbook menu 2783.
lay NE Function selections:
5172 Relay OFF de- 0.0 s 5.0 s - Alarm relay ND
69 lay 999.9 s - Limit relay
- Horn relay
- Alarm relay NE
5180 Relay 71
5181 Relay Func- Alarm re- Alarm re- Designer’s Used for AVR DOWN com-
71 tion lay ND lay ND Reference mand if "Relay" is selected
Alarm re- Handbook in menu 2783.
lay NE Function selections:
5182 Relay OFF de- 0.0 s 5.0 s - Alarm relay ND
71 lay 999.9 s - Limit relay
- Horn relay
- Alarm relay NE
5190 Relay 90
5191 Relay Func- Alarm re- Alarm re- Option Function selections:
90 tion lay ND lay ND M14.6: - Alarm relay ND
Alarm re- 4 x relay - Limit relay
lay NE output, slot - Horn relay
5192 Relay OFF de- 0.0 s 5.0 s 6 - Alarm relay NE
90 lay 999.9 s
5200 Relay 92
5201 Relay Func- Alarm re- Alarm re- Option Function selections:
92 tion lay ND lay ND M14.6: - Alarm relay ND
Alarm re- 4 x relay - Limit relay
lay NE output, slot - Horn relay
5202 Relay OFF de- 0.0 s 5.0 s 6 - Alarm relay NE
92 lay 999.9 s
5210 Relay 94
5211 Relay Func- Alarm re- Alarm re- Option Function selections:
94 tion lay ND lay ND M14.6: - Alarm relay ND
Alarm re- 4 x relay - Limit relay
lay NE output, slot - Horn relay
5212 Relay OFF de- 0.0 s 5.0 s 6 - Alarm relay NE
94 lay 999.9 s
5220 Relay 96
5221 Relay Func- Alarm re- Alarm re- Option Function selections:
96 tion lay ND lay ND M14.6: - Alarm relay ND
Alarm re- 4 x relay - Limit relay
lay NE output, slot - Horn relay
5222 Relay OFF de- 0.0 s 5.0 s 6 - Alarm relay NE
96 lay 999.9 s

DEIF Page 146 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
5230 Relay 126
5231 Relay Func- Alarm re- Alarm re- Option Function selections:
126 tion lay ND lay ND M14.8: - Alarm relay ND
Alarm re- 4 x relay - Limit relay
lay NE output, slot - Horn relay
5232 Relay OFF de- 0.0 s 5.0 s 8 - Alarm relay NE
126 lay 999.9 s
5240 Relay 128
5241 Relay Func- Alarm re- Alarm re- Option Function selections:
128 tion lay ND lay ND M14.8: - Alarm relay ND
Alarm re- 4 x relay - Limit relay
lay NE output, slot - Horn relay
5242 Relay OFF de- 0.0 s 5.0 s 8 - Alarm relay NE
128 lay 999.9 s
5250 Relay 130
5251 Relay Func- Alarm re- Alarm re- Option Function selections:
130 tion lay ND lay ND M14.8: - Alarm relay ND
Alarm re- 4 x relay - Limit relay
lay NE output, slot - Horn relay
5252 Relay OFF de- 0.0 s 5.0 s 8 - Alarm relay NE
130 lay 999.9 s
5260 Relay 132
5261 Relay Func- Alarm re- Alarm re- Option Function selections:
132 tion lay ND lay ND M14.8: - Alarm relay ND
Alarm re- 4 x relay - Limit relay
lay NE output, slot - Horn relay
5262 Relay OFF de- 0.0 s 5.0 s 8 - Alarm relay NE
132 lay 999.9 s
5270 Transistor output setup
5271 Transis- T20 kWh pulse kWh Designer’s The transistor outputs on
tor 20 Relay pulse Reference terminals 21 and 22 can be
5272 Transis- T21 kVArh kVArh Handbook configured as relay outputs
tor 21 pulse pulse or pulse signals. If "Relay" is
Relay selected, the relays 20 and
21 will be available.
If set to "Relay", external re-
lays are needed due to limi-
ted current output. Max. 10
mA.

DEIF Page 147 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.5 Control parameters - analogue output


3.5.1 Analogue output limits
No. Setting Min. Factory Notes Ref. Description
Max. setting
5720 PWM 68 limits
5721 PWM 68 Min. 0% 10% Option: For Caterpillar engines.
limits 50% PWM output
5722 PWM 68 Max. 50% 90% (EF5)
limits 100%
5780 Aout 66 limits
5781 AOut 66 lim- Min. -25/0 mA -20/0 mA Option: Min. range and factory
its 10 mA 2 x analogue out- setting value is option-
5782 AOut 66 lim- Max. 10 mA 20 mA puts (E1/E2) dependent.
its 25 mA
5790 Aout 71 limits
5791 AOut 71 lim- Min. -25/0 mA -20/0 mA Option: Min. range and factory
its 10 mA 2 x analogue out- setting value is option-
5792 AOut 71 lim- Max. 10 mA 20 mA puts (E1/E2) dependent.
its 25 mA
5800 Aout 91 limits
5801 AOut 91 lim- Min. 0 mA 0 mA Option: Min. range and factory
its 10 mA 2 x analogue out- setting value is option-
5802 AOut 91 lim- Max. 10 mA 20 mA puts (F1) dependent.
its 20 mA
5810 Aout 95 limits
5811 AOut 95 lim- Min. 0 mA 0 mA Option: Min. range and factory
its 10 mA 2 x analogue out- setting value is option-
5812 AOut 95 lim- Max. 10 mA 20 mA puts (F1) dependent.
its 20 mA

DEIF Page 148 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.6 Control parameters - transducer outputs


3.6.1 Transducer outputs
No. Setting Min. Factory Notes Ref. Description
Max. setting
5820 P output 1
5821 P output 1 Transducer Disabled Disabled Option: Setpoint selec-
A Option-dep. Analogue outputs tions for all
5822 P output 1 Transducer Disabled Disabled (E2 or F1 or EF2) transducer out-
B Option-dep. puts:
- Disabled
5823 P output 1 Setpoint Disabled Disabled
- 0-20 mA
-10-0-10 V
- 4-20 mA
5824 P output 1 Max. value 0 kW 500 kW - 0-10 V
20000 kW - -10-0-10 V
5825 P output 1 Min. value -9999 kW 0 kW
20000 kW
5830 P output 2
5831 P output 2 Transducer Disabled Disabled Option:
A Option-dep. Analogue outputs
5832 P output 2 Transducer Disabled Disabled (E2 or F1 or EF2)
B Option-dep.
5833 P output 2 Setpoint Disabled Disabled
-10-0-10 V
5834 P output 2 Max. value 0 kW 500 kW
20000 kW
5835 P output 2 Min. value -9999 kW 0 kW
20000 kW
5840 P output 3
5841 P output 3 Transducer Disabled Disabled Option:
A Option-dep. Analogue outputs
5842 P output 3 Transducer Disabled Disabled (E2 or F1 or EF2)
B Option-dep.
5843 P output 3 Setpoint Disabled Disabled
-10-0-10 V
5844 P output 3 Max. value 0 kW 500 kW
20000 kW
5845 P output 3 Min. value -9999 kW 0 kW
20000 kW
5850 S output
5851 S output Transducer Disabled Disabled Option:
A Option-dep. Analogue outputs
5852 S output Transducer Disabled Disabled (E2 or F1 or EF2)
B Option-dep.
5853 S output Setpoint Disabled Disabled
-10-0-10 V

DEIF Page 149 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
5854 S output Max. value 0 kVA 600 kVA
20000 kVA
5855 S output Min. value -9999 kVA 0 kVA
20000 kVA
5860 Q output
5861 Q output Transducer Disabled Disabled Option:
A Option-dep. Analogue outputs
5862 Q output Transducer Disabled Disabled (E2 or F1 or EF2)
B Option-dep.
5863 Q output Setpoint Disabled Disabled
-10-0-10 V
5864 Q output Max. value 0 kVAr 400 kVAr
16000 kVAr
5865 Q output Min. value 8000 kVA 0 kVAr
16000 kVA
5870 PF output
5871 PF output Transducer Disabled Disabled Option: Positive value
A Option-dep. Analogue outputs means induc-
5872 PF output Transducer Disabled Disabled (E2 or F1 or EF2) tive.
B Option-dep. Negative value
means capaci-
5873 PF output Setpoint Disabled Disabled
tive.
-10-0-10 V
5874 PF output Max. value 0.50 0.80
0.99
5875 PF output Min. value -0.99 -0.80
-0.50
5880 f output
5881 F output Transducer Disabled Disabled Option:
A Option-dep. Analogue outputs
5882 F output Transducer Disabled Disabled (E2 or F1 or EF2)
B Option-dep.
5883 F output Setpoint Disabled Disabled
-10-0-10 V
5884 F output Max. value 0.0 Hz 55.0 Hz
70.0 Hz
5885 F output Min. value 0.0 Hz 45.0 Hz
70.0 Hz
5890 U output
5891 U output Transducer Disabled Disabled Option: The voltage out-
A Option-dep. Analogue outputs put represents
5892 U output Transducer Disabled Disabled (E2 or F1 or EF2) L1-L2 voltage.
B Option-dep.
5893 U output Setpoint Disabled Disabled
-10-0-10 V

DEIF Page 150 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
5890 U output
5894 U output Max. value 0V 500 V
28000 V
5895 U output Min. value 0V 0V
28000 V
5900 I output
5901 I output Transducer Disabled Disabled Option: The current out-
A Option-dep. Analogue outputs put represents
5902 I output Transducer Disabled Disabled (E2 or F1 or EF2) L1 current.
B Option-dep.
5903 I output Setpoint Disabled Disabled
-10-0-10 V
5904 I output Max. value 0A 1000 A
9000 A
5905 I output Min. value 0A 0A
9000 A
5910 U BB output
5911 U BB output Transducer Disabled Disabled Option: The voltage out-
A Option-dep. Analogue outputs put represents
5912 U BB output Transducer Disabled Disabled (E2 or F1 or EF2) L1-L2 voltage.
B Option-dep.
5913 U BB output Setpoint Disabled Disabled
-10-0-10 V
5914 U BB output Max. value 0V 500 V
28000 V
5915 U BB output Min. value 0V 0V
28000 V
5920 f BB output
5921 F BB output Transducer Disabled Disabled Option:
A Option-dep. Analogue outputs
5922 F BB output Transducer Disabled Disabled (E2 or F1 or EF2)
B Option-dep.
5923 F BB output Setpoint Disabled Disabled
-10-0-10 V
5924 F BB output Max. value 0.0 Hz 55.0 Hz
70.0 Hz
5925 F BB output Min. value 0.0 Hz 45.0 Hz
70.0 Hz

DEIF Page 151 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
5930 Multi-input 102
5931 Multi-input Transducer Disabled Disabled Option:
102 A Option-dep. Analogue outputs
5932 Multi-input Transducer Disabled Disabled (E2 or F1 or EF2)
102 B Option-dep.
5933 Multi-input Setpoint Disabled Disabled
102 -10-0-10 V
5934 Multi-input Max. value 0 500
102 28000
5935 Multi-input Min. value 0 0
102 28000
5940 Multi-input 105
5941 Multi-input Transducer Disabled Disabled Option:
105 A Option-dep. Analogue outputs
5942 Multi-input Transducer Disabled Disabled (E2 or F1 or EF2)
105 B Option-dep.
5943 Multi-input Setpoint Disabled Disabled
105 -10-0-10 V
5944 Multi-input Max. value 0 500
105 28000
5945 Multi-input Min. value 0 0
105 28000
5950 Multi-input 108
5951 Multi-input Transducer Disabled Disabled Option:
108 A Option-dep. Analogue outputs
5952 Multi-input Transducer Disabled Disabled (E2 or F1 or EF2)
108 B Option-dep.
5953 Multi-input Setpoint Disabled Disabled
108 -10-0-10 V
5954 Multi-input Max. value 0 500
108 28000
5955 Multi-input Min. value 0 0
108 28000
5960 P total consumed
5961 P total con- Transducer Disabled Disabled Option:
sumed A Option-dep. Analogue outputs
(E2 or F1 or EF2)
5962 P total con- Transducer Disabled Disabled
sumed B Option-dep.
5963 P total con- Setpoint Disabled Disabled
sumed -10-0-10 V
5964 P total con- Max. value 0 kW 500 kW
sumed 20000 kW
5965 P total con- Min. value -9999 kW 0 kW
sumed 20000 kW

DEIF Page 152 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
5970 P total available
5971 P total avail- Transducer Disabled Disabled Option:
able A Option-dep. Analogue outputs
5972 P total avail- Transducer Disabled Disabled (E2 or F1 or EF2)
able B Option-dep.
5973 P total avail- Setpoint Disabled Disabled
able -10-0-10 V
5974 P total avail- Max. value 0 kW 500 kW
able 20000 kW
5975 P total avail- Min. value -9999 kW 0 kW
able 20000 kW

DEIF Page 153 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.7 Control parameters - analogue regulator output setup


3.7.1 Regulator output selection

These menus are used to select which analogue output to use for governor/AVR (option D1)
control.

No. Setting Available Factory Notes Ref. Descrip-


settings setting tion
5980 Governor output
5981 Governor Transducer A Disabled Disabled Option:
output Transducer 66 Analogue gover-
Transducer 71 nor output (E1/
EF)
5990 AVR output
5991 AVR output Transducer A Disabled Disabled Option:
Transducer 66 Analogue AVR
Transducer 71 output (E1/EF
and D1)

3.8 System parameters


These menus include parameters for the system setup.

DEIF Page 154 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.9 System parameters - general setup


3.9.1 General setup
No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
6000 Nominal settings 1
6001 Nom. set- Fre- 48.0 Hz 50.0 Designer’s The selection of nominal set-
tings 1 quency 62.0 Hz Hz Reference tings to be used is set in menu
6002 Nom. set- Power 1 kW 480 Handbook 6006. A binary input or selec-
tings 1 900 MW kW tion in M-logic can also be
used.
6003 Nom. set- Current 0A 867 A
Voltage and power range de-
tings 1 9000 A
pends on scaling setting in
6004 Nom. set- Voltage 10 V 400 V menu 9030.
tings 1 160 kV
6005 Nom. set- RPM 100 RPM 1500
tings 1 4000 RPM
RPM
6006 Nom. set- Setting 1-4 1
tings 1
6010 Nominal settings 2
6011 Nom. set- Fre- 48.0 Hz 50.0 Designer’s Voltage and power range de-
tings 2 quency 62.0 Hz Hz Reference pends on scaling setting in
6012 Nom. set- Power 1 kW 230 Handbook menu 9030.
tings 2 900 MW kW
6013 Nom. set- Current 0A 345 A
tings 2 9000 A
6014 Nom. set- Voltage 10 V 480 V
tings 2 160 kV
6015 Nom. set- RPM 100 RPM 1500
tings 2 4000 RPM
RPM
6020 Nominal settings 3
6021 Nom. set- Fre- 48.0 Hz 60.0 Designer’s Voltage and power range de-
tings 3 quency 62.0 Hz Hz Reference pends on scaling setting in
6022 Nom. set- Power 1 kW 230 Handbook menu 9030.
tings 3 900 MW kW
6023 Nom. set- Current 0A 345 A
tings 3 9000 A
6024 Nom. set- Voltage 10 V 480 V
tings 3 160 kV
6025 Nom. set- RPM 100 RPM 1800
tings 3 4000 RPM
RPM

DEIF Page 155 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
6030 Nominal settings 4
6031 Nom. set- Fre- 48.0 Hz 60.0 Designer’s Voltage and power range de-
tings 4 quency 62.0 Hz Hz Reference pends on scaling setting in
6032 Nom. set- Power 1 kW 230 Handbook menu 9030.
tings 4 900 MW kW
6033 Nom. set- Current 0A 345 A
tings 4 9000 A
6034 Nom. set- Voltage 10 V 480 V
tings 4 160 kV
6035 Nom. set- RPM 100 RPM 1800
tings 4 4000 RPM
RPM
6040 Gen/Mains/busbar A transformer
6041 G/M/BA U pri- 10 V 400 V Designer’s If no voltage transformer is
trans- mary 160 kV Reference present, the primary and sec-
former Handbook ondary side values are set to
6042 G/M/BA U sec- 100 V 400 V generator nominal value.
trans- ondary 690 V Gen/mains/busbar primary
former voltage range depends on
scaling setting in menu 9030.
6043 G/M/BA I pri- 5A 1000 A
trans- mary 9000 A
former
6044 G/M/BA I secon- 1A 5A
trans- dary 5A
former
6050 Busbar settings 1
6051 BB set- U pri- 10 V 400 V Designer’s If no voltage transformer is
ting 1 mary 160 kV Reference present, the primary and sec-
6052 BB set- U sec- 100 V 400 V Handbook ondary side values are set to
ting 1 ondary 690 V generator nominal value.
BB primary voltage range de-
6053 BB set- Nominal 10 V 400 V
pends on scaling setting in
ting 1 U1 160 kV
menu 9030.
6054 BB set- Bus Param Param
ting 1 nom. set 1 set 1
set Param
set 2
6060 Busbar settings 2
6061 BB set- U pri- 10 V 400 V Designer's If no voltage transformer is
ting 2 mary 160 kV Reference present, the primary and sec-
6062 BB set- U sec- 100 V 400 V Handbook ondary side values are set to
ting 2 ondary 690 V generator nominal value.
BB primary voltage range de-
6063 BB set- Nominal 10 V 400 V pends on scaling setting in
ting 2 U2 160 kV menu 9030.

DEIF Page 156 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting

6070 Genset mode


6071 Genset Island Designer’s Selections are:
mode Power Reference - Island
manage- Handbook - Auto Mains Failure
ment - Peak Shaving
- Fixed power
- Mains power export
- Load takeover
- Power management (option G5)
- Remote maintenance
- Plant management (option G7)
- Ventilation (option T2)
- Dry alternator (option T2)
6080 Language
6081 Lan- English English Designer’s The master language is Eng-
guage Language Reference lish. Additionally, 11 different
11 Handbook languages can be configured
with the PC utility software.
6082 LED LED colour LED colour Designer’s LED colour scheme 1 is
colours scheme 1 scheme 1 Reference standard, LED colour scheme 2
Handbook corresponds to US medium
LED colour
scheme 2 voltage colour scheme.

DEIF Page 157 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.9.2 Counters and timers


No. Setting Min. Factory Notes Ref. Description
Max. setting
6090 Date and time
6091 Date and Year 2001 2008 Designer’s Used to set up the clock
time 2100 Reference in the unit. Only available
6092 Date and Month 1 1 Handbook from the display.
time 12
6093 Date and Date 1 1
time 31
6094 Date and Week 1 1
time day 7
6095 Date and Hour 0 3
time 23
6096 Date and Minute 0 5
time 59
6100 Counters
6101 Counters Running 0 hrs 0 hrs Designer's Setting 6105 resets the
hour 999 hrs Reference kWh counter to 0. It auto-
6102 Counters Running, 0 th. hrs 0 th. hrs Handbook matically reverts to OFF
th. hours 999 th. after being set ON.
hrs
6103 Counters GB/TB/ 0 0
BTB op- 20000
erations
6104 Counters MB oper- 0 0
ations 20000
6105 Counters kWh OFF OFF
ON
6106 Counters Start at- 0 0
tempts 20000
6110 Service timer 1
6111 Service Enable OFF ON Designer's The timer is reset by ena-
timer 1 ON Reference bling menu 6116. The
6112 Service Running 0 hrs 500 hrs Handbook menu automatically goes
timer 1 hours 9000 hrs OFF.

6113 Service Days 1 days 365 days


timer 1 1000
days
6114 Service Fail class F1...F9 F2
timer 1 (Warn-
ing)
6115 Service Output A Not used Not used
timer 1 Option-
dep.
6116 Service Reset OFF OFF
timer 1 ON

DEIF Page 158 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
6120 Service timer 2
6121 Service Enable OFF ON Designer's The timer is reset by ena-
timer 2 ON Reference bling menu 6126. The
6122 Service Running 0 hrs 500 hrs Handbook menu automatically goes
timer 2 hours 9000 hrs OFF.

6123 Service Days 1 days 365 days


timer 2 1000
days
6124 Service Fail class F1...F9 F2
timer 2 (Warn-
ing)
6125 Service Relay Not used Not used
timer 2 output A Option-
dep.
6126 Service Reset OFF OFF
timer 2 ON

3.9.3 Alarm horn


No. Setting Min. Factory Notes Ref. Description
Max. setting
6130 Alarm horn
6131 Alarm ON 0.0 sec 20.0 sec Designer’s If the setting is adjusted to 0
horn time 990.0 sec Reference s, the horn relay will be acti-
Handbook vated continuously until the
alarm is acknowledged.

3.9.4 Run coil setup


No. Setting Min. Factory Notes Ref. Description
Max. setting
6150 Run coil setup
6151 Run coil ON time 0.0 sec 1.0 sec Designer’s Ref-
setup 600.0 sec erence Hand-
book
6152 Run coil Type Pulse Pulse Designer’s Ref- Pulse: Reset for each
setup Continuous erence Hand- start attempt.
book Continuous: High
throughout all start at-
tempts.

DEIF Page 159 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.9.5 Running, start and stop


No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
6160 Run status
6161 Run sta- Timer 0.0 s 5.0 s Designer’s If a relay output is used, the
tus 300.0 s Reference relay in question must be set
6162 Run sta- Relay Not used Not Handbook to "limit".
tus output A Option- used
dep.
6163 Run sta- Relay Not used Not
tus output B Option- used
dep.
6164 Run sta- Enable OFF OFF
tus ON
6170 Running detection
6171 Running No. of 0 teeth 0 teeth Designer’s If menu 6171 is set to 0, the
detect. teeth 500 teeth Reference magnetic pickup input is not
6172 Running Type Binary in- Fre- Handbook active.
detect. put quency Available running detection
EIC types:
- Binary input
6173 Running Running 0 RPM 1000
- MPU input
detect. RPM 4000 RPM
- Frequency
RPM
- EIC (engine communication)
6174 Running Remove 1 RPM 400 If menu 6175 is set to 0.0, the
detect. starter 2000 RPM oil pressure running detection
RPM is OFF.
6175 Running Pressure 0.0 bar 0.0 bar
detect. level 150.0 bar
6180 Starter
6181 Starter Start 0.0 s 5.0 s Designer’s Menu 6185 and 6186 relate to
prepare 600.0 s Reference using multi-inputs as running
6182 Starter Ext. pre- 0.0 s 0.0 s Handbook feedback.
pare 600.0 s
6183 Starter Start ON 1.0 s 5.0 s
time 180.0 s
6184 Starter Start 1.0 s 5.0 s
OFF 99.0 s
time
6185 Starter Input Multi-in- Multi-
type put 102 input
Multi-in- 102
put 108
6186 Starter Setpoint 0.0 0.0
300.0

DEIF Page 160 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
6190 Start attempts
6191 Start at- Setpoint 1 3 Designer’s Number of start attempts.
tempts 10 Reference
Handbook
6200 Shutdown override
6201 Shut- Attempts 1 7 Designer’s Shutdown override turns all
down 10 Reference shutdowns into warnings. Only
override Handbook exception is overspeed and
6202 Shut- Cooling 0s 240 s emergency stop.
down down 9900 s
override
6203 Shut- Enable OFF OFF
down ON
override
6210 Stop
6211 Stop Cooling 0.0 s 240.0 s Designer’s The extended stop timer starts
down 9900.0 s Reference when the running feedback
6212 Stop Exten- 1.0 s 5.0 s Handbook disappears. During the delay
ded stop 99.0 s time it is not possible to start
the engine.
6213 Stop TYPE Multi-in- Multi-
put 102 input
EIC 102
6214 Stop Setpoint 0 deg. 0 deg.
482 deg.
6220 Hz/V OK
6221 HZ/V OK Timer 1.0 s 5.0 s Designer’s The voltage and frequency
99.0 s Reference have to be continuously within
Handbook the limits during the delay tim-
er before the breaker can be
closed.

3.9.6 Breaker control


No. Setting Min. Factory Notes Ref. Description
Max. setting
6230 Gen/Mains/Tie/Bus tie breaker control
6231 GB/MB/TB/ Close de- 0.0 s 2.0 s Designer’s Menu 6232 is for
BTB control lay 30.0 s Reference compact breakers
6232 GB/MB/TB/ Load time 0.0 s 0.0 s Handbook (need to charge
BTB control 30.0 s spring before closing).

DEIF Page 161 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.9.7 Power derate


No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
6240 Power derate
6241 Power Input Multi-inp. Multi- Design- The derate function lowers the max.
derate 102 inp. er’s Ref- power of the generator set based on
1 EIC 102 erence e.g. water temperature.
6242 Power Start 0 units 16 Handbook Input:
derate derate 20000 units - Multi-input 102
1 units - Multi-input 105
- Multi-input 108
6243 Power Derate 0.1 %/ 5.0 %/
- M-logic
derate slope unit unit
- EIC water temp
1 100.0 %/
- EIC oil temp
unit
- Ambient temp
6244 Power Pro- OFF OFF - Intercool temp
derate portion- ON
1 al
6245 Power Enable OFF OFF
derate ON
1
6246 Power Limit 0.0% 80.0%
derate 100.0%
1
6250 Power derate 2
6251 Power Input Multi-inp. Multi- Design- The derate function lowers the max.
derate 102 inp. er's Ref- power of the generator set based on
2 EIC 102 erence e.g. water temperature.
6252 Power Start 0 units 16 Handbook Input:
derate derate 20000 units - Multi-input 102
2 units - Multi-input 105
- Multi-input 108
6253 Power Derate 0.1 %/ 5.0 %/
- M-logic
derate slope unit unit
- EIC water temp
2 100.0 %/
- EIC oil temp
unit
- Ambient temp
6254 Power Pro- OFF OFF - Intercool temp
derate portion- ON
2 al
6255 Power Enable OFF OFF
derate ON
2
6256 Power Limit 0.0% 80.0%
derate 100.0%
2

DEIF Page 162 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Facto- Notes Ref. Description


Max. ry set-
ting
6260 Power derate 3
6261 Power Input Multi-inp. Multi- Design- The derate function lowers the max.
derate 102 inp. er's Ref- power of the generator set based on
3 EIC 102 erence e.g. water temperature.
6262 Power Start 0 units 16 Handbook Input:
derate derate 20000 units - Multi-input 102
3 units - Multi-input 105
- Multi-input 108
6263 Power Derate 0.1 %/ 5.0 %/
- M-logic
derate slope unit unit
- EIC water temp
3 100.0 %/
- EIC oil temp
unit
- Ambient temp
6264 Power Pro- OFF OFF - Intercool temp
derate portion- ON
3 al
6265 Power Enable OFF OFF
derate ON
3
6266 Power Limit 0.0% 80.0%
derate 100.0%
3

3.9.8 Idle start


No. Setting Min. Factory set- Notes Ref. Descrip-
Max. ting tion
6290 Idle running
6291 Idle start Start timer 0.0 sec. 18000.0 sec. Designer’s Refer-
59940.0 sec. ence Handbook
6292 Idle start Enable start OFF OFF
ON
6293 Idle stop Stop timer 0.0 sec. 18000.0 sec.
59940.0 sec.
6294 Idle stop Enable stop OFF OFF
ON
6295 Idle active Relay out- Not used Not used
put A Option-dep.
6296 Idle active Enable OFF OFF
ON

DEIF Page 163 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.9.9 Engine heater


No. Setting Min. Factory Notes Ref. Description
Max. setting
6320 Engine heater
6321 Engine Setpoint 20 deg. 40 deg. Designer’s Heater function for standstill.
heater 250 deg. Reference Type:
6322 Engine Relay Not used Not Handbook - Multi-input 102
heater output A Option- used - Multi-input 105
dep. - Multi-input 108
- EIC
6323 Engine Type Multi-inp Multi-inp
heater 102 102
EIC
6324 Engine Hystere- 1 deg. 3 deg.
heater sis 70 deg.
6325 Engine Enable OFF OFF
heater ON

3.9.10 Analogue load sharing lines output


No. Setting Min. Factory Notes Ref. Description
Max. setting
6380 Load share out
6381 Load Setpoint 1.0 V 4.0 V Option G3 Adjustment of the ana-
share out 5.0 V Analogue logue load sharing line
load sharing max. value.
6390 Load share type
6391 Load Setpoint Adjustable Option G3 Selection between se-
share type Selco T4800 Analogue lectable load sharing
load sharing line max. value (setting
6381) or adaptation to
Selco T4800 load shar-
ing line.

DEIF Page 164 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.9.11 Master clock


No. Setting Min. Factory Notes Ref. Description
Max. setting
6400 Master clock
6401 Master Start hour 0h 8h Designer’s Compensation for frequency
clock 23 h Reference variation related clock time
6402 Master Stop hour 0h 8h Handbook in the system.
clock 23 h
6403 Master Difference 1s 20 s
clock 999 s
6404 Master Compen- 0.1 Hz 0.1 Hz
clock sation 1.0 Hz
6405 Master Enable OFF OFF
clock ON

3.9.12 Cooling ventilation


No. Setting Min. Factory Notes Ref. Description
Max. setting
6460 Max. ventilation
6461 Max. ventila- Set point 20 deg. 90 deg. Designer's Ref- Ventilation fan
tion 250 deg. erence Hand- control.
6462 Max. ventila- Relay out- Not used Not used book
tion put A Option-dep.
6463 Max. ventila- Hysteresis 1 deg. 5 deg.
tion 70 deg.
6464 Max. ventila- Enable OFF OFF
tion ON

3.9.13 Summer/winter time


No. Setting Min. Factory set- Notes Ref. Description
Max. ting
6490 Summer/winter time
6491 Sum/win Enable OFF OFF Designer’s Ref- The summer/winter time
time ON erence Hand- change follows the
book mainland Europe rules.

DEIF Page 165 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.9.14 Fuel transfer pump logic


No. Setting Min. Factory Notes Ref. Description
Max. setting
6550 Fuel pump logic
6551 Fuel Set- 0% 20% Designer’s Type:
pump point 100% Reference - Multi-input 102
logic start Handbook - Multi-input 105
6552 Fuel Set- 0% 80% - Multi-input 108
pump point 100% - Ext. ana. In 1-8
logic stop - Auto detection

6553 Fuel Fill 0.1 s 60.0 s Note: when using RMI for fuel
pump check 300.0 s pump logic, choose "Auto detec-
logic time tion".
6554 Fuel Relay Not Not
pump output used used
logic A Option-
dep.
6555 Fuel Set- Multi-inp Multi-
pump point 102 inp 102
logic Auto de-
tection
6556 Fuel Fail F1…F9 Warn-
pump class ing
logic (F2)

DEIF Page 166 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.9.15 Fan logic


No. Setting Min. Factory Notes Ref. Description
Max. setting
6560 Fan input settings
6561 Fan input Type -Multi-input Multi-in- Designer's Selection of fan input:
102 put 102 Reference - Multi-input 102, 105,
-Multi-input Handbook 108
105
-Multi-input EIC:
108 - water/oil temp.
- water temp.
6562 Fan prio Priority 0h 0h
- oil temp.
update 200 h
- ambient temp.
6563 1st prio fan Setpoint 20 deg 70 deg - inter cool temp.
start 250 deg - fuel temp.
6564 1st pr. fan Hystere- 0 deg 10 deg
sis 50 deg Ext. analog input:
- 1-8 (option H8)
6565 2nd prio fan Setpoint 20 deg 80 deg
start 250 deg
6566 2nd pr. fan Hystere- 0 deg 10 deg
sis 50 deg

6570 3rd prio fan


6571 3rd prio fan Setpoint 20 deg 90 deg Designer's Selection of fan input:
start 250 deg Reference - Multi-input 102, 105,
6572 Hystere- 0 deg 10 deg Handbook 108
3rd pr. fan
sis 50 deg
EIC:
6573 4th prio fan Setpoint 20 deg 100 deg - water/oil temp.
start 250 deg - water temp.
6574 4th pr. fan Hystere- 0 deg 10 deg - oil temp.
sis 50 deg - ambient temp.
- inter cool temp.
- fuel temp.

Ext. analog input:


- 1-8 option (H8)
6580 Fan outputs
6581 Fan A out- Relay Not used Not used Designer's Selection of relays for
put output A Option-dep. Reference activating fans
6582 Fan B out- Relay Not used Not used Handbook
put output B Option-dep.
6583 Fan C out- Relay Not used Not used
put output C Option-dep.
6584 Fan D out- Relay Not used Not used
put output D Option-dep.
6585 Fan run. Reset OFF OFF
hour reset ON
6586 Fan start Timer 0.0 s 10.0 s
delay 30.0 s

DEIF Page 167 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
6590 Fan A failure
6591 Fan A fail- Timer 0.1 s 10.0 s Designer's
ure 300.0 s Reference
6592 Fan A fail- Output Not used Not used Handbook
ure A Option-dep.
6593 Fan A fail- Output Not used Not used
ure B Option-dep.
6594 Fan A fail- Enable OFF OFF
ure ON
6595 Fan A fail- Fail F1...F9 Warning
ure class (F2)
6600 Fan B failure
6601 Fan B fail- Timer 0.1 s 10.0 s Designer's
ure 300.0 s Reference
6602 Fan B fail- Output Not used Not used Handbook
ure A Option-dep.
6603 Fan B fail- Output Not used Not used
ure B Option-dep.
6604 Fan B fail- Enable OFF OFF
ure ON
6605 Fan B fail- Fail F1...F9 Warning
ure class (F2)
6610 Fan C failure
6611 Fan C fail- Timer 0.1 s 10.0 s Designer's
ure 300.0 s Reference
6612 Fan C fail- Output Not used Not used Handbook
ure A Option-dep.
6613 Fan C fail- Output Not used Not used
ure B Option-dep.
6614 Fan C fail- Enable OFF OFF
ure ON
6615 Fan C fail- Fail F1...F9 Warning
ure class (F2)
6620 Fan D failure
6621 Fan D fail- Timer 0.1 s 10.0 s Designer's
ure 300.0 s Reference
6622 Fan D fail- Output Not used Not used Handbook
ure A Option-dep.
6623 Fan D fail- Output Not used Not used
ure B Option-dep.
6624 Fan D fail- Enable OFF OFF
ure ON
6625 Fan D fail- Fail F1...F9 Warning
ure class (F2)

DEIF Page 168 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.9.16 Diagnostics
No. Setting Min. Factory Notes Ref. Description
Max. setting
6700 Diagnostics
6701 Diagnostics Timer 0s 30 Designer's Ref- Activates diagnostics mode to
30 s erence Hand- read ECU data without start-
6702 Diagnostics Enable OFF OFF book ing engine.
ON

3.9.17 I thermal demand


No. Setting Min. Factory Notes Ref. Description
Max. setting
6840 I thermal demand
6841 I thermal de- Timer 0 min. 8 min. Designer's Refer- Setup of I thermal
mand 20 min. ence Handbook period.
6842 I thermal de- Enable OFF OFF Enabled is used for
mand ON reset.
6843 I max. demand Enable OFF OFF Reset I max. de-
ON mand.

DEIF Page 169 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.9.18 Pulse counter


No. Setting Min. Factory Notes Ref. Description
Max. setting
6850 Pulse counter 1
6851 Pulse coun- Setpoint 0 1 Designer's Ref- Setup of pulse
ter 1 1000 erence Hand- counter.
6852 Pulse coun- Unit Unit/Pulse Unit/Pulse book
ter 1 Pulse/Unit
6853 Pulse coun- Deci- No decimals No deci-
ter 1 mals One decimal mals
Two decimals
Three decimals
6860 Pulse counter 2
6861 Pulse coun- Setpoint 0 1 Designer's Ref- Setup of pulse
ter 2 1000 erence Hand- counter.
6862 Pulse coun- Unit Unit/Pulse Unit/Pulse book
ter 2 Pulse/Unit
6863 Pulse coun- Deci- No decimals No deci-
ter 2 mals One decimal mals
Two decimals
Three decimals

3.9.19 Alarm jump


No. Setting Min. Factory Notes Ref. Description
Max. setting
6900 Alarm jump
6901 Alarm jump Enable OFF ON Designer's Ref- Selection of jump to alarm list
ON erence Hand- view on the display if an alarm
book appears (ON), or stay at
present view (OFF).

3.9.20 Tank capacity


No. Setting Min. Factory Notes Ref. Description
Max. setting
6910 Tank capacity
6911 Tank capacity 0 1250 Designer's Refer- This setting is for entering the
9999 ence Handbook capacity of the day tank.

DEIF Page 170 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.9.21 Command timers


There are four identical command timers in the unit, menu 6960-6996, but only command timer
1 is displayed in this manual.

No. Setting Min. Factory Notes Ref. Description


Max. setting
6960 Command start/stop timer 1
6961 Start timer 1 Set point MO OFF Designer's Ref- Selections are:
days MO-TU- erence Hand- MO
WE-TH- book TU
FR-SA-SU WE
TH
FR
SA
SU
MO-TU-WE-TH
MO-TU-WE-TH-FR
SA-SU
MO-TU-WE-TH-FR-
SA-SU
6962 Start timer 1 Set point 0 10 Designer's Ref-
hour 23 erence Hand-
book
6963 Start timer 1 Set point 0 0 Designer's Ref-
min 59 erence Hand-
book
6964 Stop timer 1 Set point MO MO-TU- Designer's Ref- Selections are:
days MO-TU- WE-TH- erence Hand- MO
WE-TH- FR-SA- book TU
FR-SA-SU SU WE
TH
FR
SA
SU
MO-TU-WE-TH
MO-TU-WE-TH-FR
SA-SU
MO-TU-WE-TH-FR-
SA-SU
6965 Stop timer 1 Set point 0 10 Designer's Ref-
hour 23 erence Hand-
book
6966 Stop timer 1 Set point 0 0 Designer's Ref-
min 59 erence Hand-
book

Start/stop timers can be used in M-Logic.

DEIF Page 171 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.10 System parameters - mains setup


3.10.1 Mains setup
No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
7000 Mains power
7001 Mains Day -20000 750 Designer’s Menu 7000 is for peak shaving/
power kW kW Reference mains power export modes.
20000 Handbook Set values in the AGC mains
kW unit.
7002 Mains Night -20000 1000 Menu 7001/7002 must be a pos-
power kW kW itive value for mains power ex-
20000 port or peak shaving mode.
kW Menu 7001/7002 must be a neg-
ative value for mains power im-
7003 Mains Trans- 0 kW 0 kW
port.
power ducer 20000
max kW
7004 Mains Trans- -20000 0 kW
power ducer kW
min 0 kW
7010 Daytime period
7011 Daytime Start 0h 8h Designer’s Menu 7010 is for peak shaving/
period hour 23 h Reference mains power export modes. The
7012 Daytime Start mi- 0 min 0 min Handbook period outside the daytime period
period nute 59 min is defined as the night pe- riod.

7013 Daytime Stop 0h 16 h


period hour 23 h
7014 Daytime Stop pe- 0 min 0 min
period riod 59 min
7020 Start generator
7021 Start Setpoint 5% 80% Designer’s Menu 7020 is for peak shaving/
genera- 100% Reference mains power export modes.
tor Handbook The setpoint refers to the menu
7022 Start Timer 0.0 s 10.0 s 7000 mains power setting.
genera- 990.0 s
tor
7023 Start Mini- 0% 5%
genera- mum 100%
tor load
7030 Stop generator
7031 Stop Setpoint 0% 60% Designer’s Menu 7030 is for peak shaving/
genera- 80% Reference mains power export modes.
tor Handbook The setpoint refers to the menu
7000 mains power setting.
7032 Stop Timer 0.0 s 30.0 s
genera- 990.0 s
tor

DEIF Page 172 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.10.2 Test
No. Setting Min. Factory Notes Ref. Description
Max. setting
7040 Test running
7041 Test Setpoint 1% 80% Designer’s Available test types:
100% Reference - Simple (engine run only)
7042 Test Test time 0.0 sec. 300.0 Handbook - Load (parallel to mains)
59940.0 sec. sec. - Full (disconnects mains)

7043 Test Return Semi-auto Auto


mode mode mode
Auto mode
7044 Test Test type Simple test Simple
Full test test

3.10.3 Controller settings


No. Setting Min. Factory Notes Ref. Description
Max. setting
7050 Fixed power settings
7051 Fixed power Power 0% 100% Designer’s Ref- Fixed power par-
settings 100% erence Hand- allel with mains
7052 Fixed power Power fac- 0.60 0.90 book settings.
settings tor 1.00
7053 Fixed power Power fac- Inductive Inductive
settings tor Capacitive

DEIF Page 173 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.10.4 Mains failure


No. Setting Min. Factory Notes Ref. Description
Max. setting
7060 U Mains Failure
7061 U Mains Fail. de- 0.5 s 5.0 s Designer’s Menus 7063 and 7064
failure lay 990.0 s Reference relate to nominal set-
7062 U Mains Mains 2s 60 s Handbook tings.
failure OK delay 9900 s Menu 7066 refers to the
mean value of the
7063 U Mains U< 30% 90%
measured voltage.
failure 100%
7064 U Mains U> 100% 110%
failure 120%
7065 U Mains Mains Start eng. Start eng.
failure fail. con- + open MB + open
trol Start en- MB
gine
7066 U Mains U unbal- 2% 100%
failure ance 100%
7070 f Mains Failure
7071 f Mains Fail. de- 0.5 s 5.0 s Designer’s Menus 7073 and 7074
failure lay 990.0 s Reference relate to nominal set-
7072 f Mains Mains 2s 60 s Handbook tings.
failure OK delay 9900 s
7073 f Mains f< 80.0% 95.0%
failure 100.0%
7074 f Mains f> 100.0% 105.0%
failure 120.0%
7080 MB control
7081 MB con- Mode OFF OFF Designer’s Mode shift allows
trol shift ON Reference switching to AMF mode.
7082 MB con- MB close 0.0 s 0.5 s Handbook
trol delay 30.0 s
7083 MB con- Back OFF OFF
trol sync. ON
7084 MB con- Sync to OFF ON
trol Mains ON
7085 MB con- Load 0.0 s 0.0 s
trol time 30.0 s
7090 Mains failure hysteresis
7091 Mains fail. Low volt. 0% 0% Designer’s Hysteresis for when
hyst. hyst. 70% Reference mains is healthy again.
7092 Mains fail. High volt. 0% 0% Handbook
hyst. hyst. 20%
7093 Mains fail. Low freq. 0.0% 0.0%
hyst. hyst. 20.0%
7094 Mains fail. High freq. 0.0% 0.0%
hyst. hyst. 20.0%

DEIF Page 174 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.10.5 Y1(X1) droop curve


No. Setting Min. Factory Notes Ref. Descrip-
Max. setting tion
7120 Y1(x1) Dead band
7121 Y1(x1) Dead Dead band 0.00% 0.40% Designer’s Reference
band low 99.99% Handbook
7122 Y1(x1) Dead Dead band 0.00% 0.50%
band high 99.99%
7123 Y1(x1) Dead Hysterese 0.00% 0.50%
band low 99.99%
7124 Y1(x1) Dead Hysterese 0.00% 0.50%
band high 99.99%
7130 P(x1) Slope
7131 P(x1) Slope MIN 0 kW 200 kW Designer’s Reference
20000 kW Handbook
7132 P(x1) Slope MAX 0 kW 480 kW
20000 kW
7133 P(x1) Slope Slope low -20000 50 kW
kW
20000 kW
7134 P(x1) Slope Slope high -20000 -50 kW
kW
20000 kW
7140 Droop curve 1
7141 Droop curve P(x1) P(x1) P(x1) Designer’s Reference
1 P(x1) Handbook
7142 Droop curve X1 f f
1 f
7143 Droop curve Enable OFF OFF
1 ON

DEIF Page 175 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.10.6 Y2(X2) droop curve


No. Setting Min. Factory set- Notes Ref. Descrip-
Max. ting tion
7150 Y2(x2) Dead band
7151 Y2(x2) Dead Dead band 0.00% 2.00% Option D1
band low 99.99%
7152 Y2(x2) Dead Dead band 0.00% 2.00%
band high 99.99%
7153 Y2(x2) Dead Hysterese low 0.00% 2.10%
band 99.99%
7154 Y2(x2) Dead Hysterese 0.00% 2.10%
band high 99.99%
7160 Q(x2) Slope
7161 Q(x2) Slope MIN -20000 kVAr 200 kVAr Option D1
20000 kVAr
7162 Q(x2) Slope MAX -20000 kVAr 480 kVAr
20000 kVAr
7163 Q(x2) Slope Slope low -20000 kVAr 50 kVAr
20000 kVAr
7164 Q(x2) Slope Slope high -20000 kVAr -50 kVAr
20000 kVAr
7170 Cosphi(x2) Slope
7171 Cosphi(x2) MIN 0.60 0.80 Option D1
Slope 1.00
7172 Cosphi(x2) I/C Inductive Inductive
Slope Capacitive
7173 Cosphi(x2) MAX 0.60 1.00
Slope 1.00
7174 Cosphi(x2) I/C Inductive Inductive
Slope Capacitive
7175 Cosphi(x2) Slope low -1.000 -0.005
Slope 1.000
7176 Cosphi(x2) Slope high -1.000 0.005
Slope 1.000
7180 Droop curve 2
7181 Droop curve 2 Cosphi(x2) Cosphi(x2) Cosphi(x2) Option D1
Q(x2)
7182 Droop curve 2 X2 U U
P
7183 Droop curve 2 Enable OFF OFF
ON

DEIF Page 176 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.10.7 Power offset


No. Setting Min. Factory Notes Ref. Description
Max. setting
7220 Power offset
7221 Power offset 1 Setpoint -20000 kW 0 kW Designer's Refer- Setup of power
20000 kW ence Handbook offset.
7222 Power offset 1 Enable OFF OFF
ON
7223 Power offset 2 Setpoint -20000 kW 0 kW
20000 kW
7224 Power offset 2 Enable OFF OFF
ON
7225 Power offset 3 Setpoint -20000 kW 0 kW
20000 kW
7226 Power offset 3 Enable OFF OFF
ON

3.10.8 Cosphi offset


No. Setting Min. Factory Notes Ref. Description
Max. setting
7240 Cosphi offset
7241 Cosphi offset 1 Setpoint -0.8 0 Designer's Refer- Setup of cosphi off-
0.8 ence Handbook set.
7242 Cosphi offset 1 Enable OFF OFF
ON
7243 Cosphi offset 2 Setpoint -0.8 0
0.8
7244 Cosphi offset 2 Enable OFF OFF
ON
7245 Cosphi offset 3 Setpoint -0.8 0
0.8
7246 Cosphi offset 3 Enable OFF OFF
ON

DEIF Page 177 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.11 System parameters - external communication


3.11.1 External communication
No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
7500 Communication control
7501 Comm. Power OFF OFF Option H2 These settings must be ON if com-
control ON or H3: mands are to be sent via Modbus
7502 Comm. Fre- OFF OFF Modbus or communication. When enabled,
control quency ON Profibus the Modbus values will overrule ex-
ternal and internal settings.
7503 Comm. Voltage OFF OFF
Voltage, power factor and reactive
control ON
power control requires AVR control
7504 Comm. Cosphi OFF OFF (option D1).
control ON
7505 Comm. Reac- OFF OFF
control tive ON
power
7510 External communication
7511 Ext. com- ID 1 1 Option H2 The mode ASCII is used for mo-
munica- 247 or H3: dem communication (ASCII: 7 data
tion Modbus or bit, RTU: 8 data bit).
Profibus
7512 Ext. com- Baud 9600 9600 Option H2:
munica- rate 19200 Modbus
tion
7513 Ext. com- Mode RTU RTU Option H2:
munica- ASCII Modbus
tion

3.11.2 Power management internal communication


No. Setting Min. Factory setting Notes Ref. Description
Max.
7530 Internal communication ID
7531 Int. comm. ID ID 1 1 Designer’s Reference Hand-
16 book

DEIF Page 178 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.12 System parameters - engine interface communication


3.12.1 Engine interface communication
No. Setting Min. Fac- Notes Ref. Description
Max. tory
set-
ting
7560 Engine I/F
7561 En- En- OFF OFF Option: The setting affects the displayed
gine gine Cummins QSX15 Cum- data, but not the Modbus data
I/F type Cummins mins (option H2).
QSK23/45/60/78 Modbus
Cummins QST30 (H6)
7561 En- En- OFF OFF Option: MTU MDEC is only available in
gine gine DDEC J1939/ option H5 or H13.
I/F type EMR MTU Please choose MDEC
JDEC ADEC/ 2000/4000 M.303 when M.201
Iveco MTU or M.304 is required.
Perkins MDEC Menu 7562 is only applicable
Caterpillar (H5) when MTU ADEC is selected as
Volvo Penta engine type.
Volvo Penta EMS J1939 Menu 7563 is for enabling the
2 (H7) EIC commands transmission.
Scania EMS Menu 7564: When set to “ON”,
Scania EMS 2 up to 19 extra views (of 3 lines)
MDEC 2000/4000
are added to the 15 original V1
M.302
views (of 3 lines). These extra
MDEC 2000/4000
views are displaying all the
M.303
present engine com. values
MTU ADEC
broadcasted on this CAN com-
Cummins
munication when this function is
Generic J1939
MTU J1939 set to “ON”.
Smart Connect Menu 7565: "Caterpillar CDVR"
MTU ADEC will not work if MTU protocols
Module 501 are selected in menu 7561.
PSI/Power
Solutions
7562 CAN- Node 0 6
open ID 16
ID
7563 EIC En- OF ON
Con- able F
trols ON
7564 EIC En- OF OFF
Auto able F
view ON
7565 Digital Inter- OFF OFF
AVR face Caterpillar CDVR
proto-
col
7566 TSC1 Source -1 -1
SA addr. 255

DEIF Page 179 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.12.2 Digital AVR parameters (option T2)


Menu Description Min. value Default Comment
Max. value value

2262 Soft-start timer for CBE 0.0 s 5.0 s This setting determines the slope of the soft-
999.0 s start during a CBE start.
6004 Generator nominal 100 V 400 V The nominal voltage for the generator. Nominal
voltage - nominal set 1 160 kV set 1.
6014 Generator nominal 100 V 480 V The nominal voltage for the generator. Nominal
voltage - nominal set 2 160 kV set 2.
6024 Generator nominal 100 V 480 V The nominal voltage for the generator. Nominal
voltage - nominal set 3 160 kV set 3.
6034 Generator nominal 100 V 480 V The nominal voltage for the generator. Nominal
voltage - nominal set 4 160 kV set 4.
6041 Generator voltage 100 V 400 V The nominal voltage for the voltage
transformer primary side 160 kV transformer’s primary side. Placed on generator
side of breaker.
6042 Generator voltage 100 V 400 V The nominal voltage for the voltage
transformer secondary 690 V transformer’s secondary side. Placed on
side generator side of breaker.
6051 Busbar voltage 100 V 400 V The nominal voltage for the voltage
transformer primary side 160 kV transformer’s primary side. Placed on busbar
– busbar nominal set 1 side of breaker. Busbar nominal set 1.
6052 Busbar voltage 100 V 400 V The nominal voltage for the voltage
transformer secondary 160 kV transformer’s secondary side. Placed on busbar
side – busbar nominal side of breaker. Busbar nominal set 1.
set 1
6061 Busbar voltage 100 V 400 V The nominal voltage for the voltage
transformer primary side 160 kV transformer’s primary side. Placed on busbar
– busbar nominal set 2 side of breaker. Busbar nominal set 2.
6062 Busbar voltage 100 V 400 V The nominal voltage for the voltage
transformer secondary 690 V transformer’s secondary side. Placed on busbar
side – busbar nominal side of breaker. Busbar nominal set 2.
set 2
7564 EIC Auto view OFF OFF Enables a Multi-line 2 unit to display readings
ON from the digital AVR. If a reading is not
available, the unit will display N.A.
When this setting has been set to ON, the
setting will be set to OFF afterwards. This is only
a pulse that has been sent, but the Multi-line 2
unit will still display the readings, if any readings
are available.
7565 Digital AVR OFF OFF Selects the CAN bus protocol for interfacing
DEIF DVC between a digital AVR and a Multi-line 2 unit.
310
7741 DAVR primary voltage 400 V 400 V Decides the primary side of a voltage
32000 V transformer for the DVC. (This is the transformer
side that is in contact with the generator
voltage).

DEIF Page 180 of 210


AGC-4 parameter list 4189340688 UK Parameter list

Menu Description Min. value Default Comment


Max. value value

7742 DAVR secondary 50 V 400 V Decides the secondary side of a voltage


voltage 600 V transformer for the DVC. (This is the transformer
side that is in contact with the DVC 310).
7743 DAVR busbar primary 400 V 400 V Decides the primary side of a voltage
voltage 32000 V transformer to the busbar. (This is the
transformer side that is in contact with the
busbar).
7744 DAVR busbar 50 V 400 V Decides the secondary side of a voltage
secondary voltage 600 V transformer to the busbar. (This is the
transformer side that is in contact with the DVC
310).
7745 DAVR enable OFF OFF When set to ON, the DVC 310 expects voltage
ON measurements on the busbar.
7751 PWM threshold 0.00 % 10.00 % Decides the output of the start-on threshold
100.00 % function. A higher number will give a steeper
slope on the start-on threshold function.
7752 Activation threshold 0.00 % 35.00 % Decides the upper limit of the start-on threshold
100.00 % function. When this limit has been reached, the
soft-start function will take action. The
percentage is of nominal voltage.
7753 Soft-start ramp 0.1 s 2.0 s This parameter decides the slope of the soft-
120.0 s start function.
7761 DAVR warning OFF OFF Enables the Multi line 2 to receive warnings from
ON the DVC 310.
7762 DAVR warning fail class Warning Warning Decides the fail class if a warning is sent from
Trip GB the DVC 310.
7763 DAVR trip OFF OFF Enables the Multi line 2 to receive trip alarms
ON from the DVC 310.
7764 DAVR trip fail class Warning Warning Decides the fail class if a trip alarm is sent from
Trip GB the DVC 310.
7771 Knee set point percent 70.0 % 96.0 % Sets the knee set point, from which the DVC 310
of nominal frequency 100.0 % will lower the voltage set point.
7772 U/F slope 1.0 1.0 Decides the slope for the U/F. A higher value will
3.0 make the slope steeper.
7773 Soft voltage recovery 0.1 s/10 Hz 2.0 s/10 Decides how fast the voltage should recover
adjustment 30.0 s/10 Hz Hz from a load impact. It is required to have the
Load Acceptance Module activated to use this.
A lower value will make a steeper slope.
7774 Soft voltage recovery OFF OFF Enables the soft voltage recovery.
ON
7775 Adjustment of Load 70 % 90 % Decides how much the voltage is allowed to
Acceptance Module 100 % drop instantaneously, when a load impact is
applied. A lower value allows a bigger voltage
drop.

DEIF Page 181 of 210


AGC-4 parameter list 4189340688 UK Parameter list

Menu Description Min. value Default Comment


Max. value value

7776 Load Acceptance OFF OFF Enables the Load Acceptance Module.
Module ON
7781 Q droop 0.0 % 2.0 % Decides the slope of the Q droop compensation.
compensation 10.0 % A higher value allows more droop.
7782 U droop compensation 0.0 % 2.0 % Decides the slope of the U droop compensation.
10.0 % A higher value allows more droop.
7783 Droop compensation Q droop Q droop Only one of the droop types can be enabled.
type compen- compen-
sation sation
OFF
7791 I excitation reference 0.0 A 1.5 A Decides the excitation current in Dry Alternator
for Dry Alternator 20.0 A mode.
mode
7792 I excitation reference 0.0 A 0.0 A Decides how much excitation is allowed in a
for Close Before 0.5 A Close Before Excitation sequence. This is during
Excitation the remanence phase.
7793 Transformer excitation 0.0 % 100.0 % Current maximum during transformer excitation
current limit 350.0 % sequence. The value is percentage of nominal
current.
7794 Induction motor 0.0 % 100.0 % Current maximum during an induction motor
starting current limit 350.0 % starting sequence. The value is percentage of
nominal current.
7795 I stator limitation OFF OFF Makes it possible to have the stator current
function enable Magneti- limitation functions disabled, only induction
sation motor starting, or both induction motor starting
and transformer excitation.
7801 PID factor 1 20 Makes it possible to make the AVR regulation
100 faster or slower.
7803 Write all settings to OFF OFF When set to ON, the Multi-line 2 unit will send all
DVC 310 ON the relevant parameters to the DVC 310.
7804 DAVR bias range 1.0 % 10.0 % This setting control defines the outer limits for
30.0 % the regulation. 10 % on a 400 V generator
means that voltage can be regulated from 360 to
440 V.
7805 DAVR controls OFF ON Decides who has the control. When set to ON,
ON the DVC 310 is controlled by the Multi-line 2,
and when set to OFF, the DVC 310 can be
controlled by EasyReg, and the DVC 310 will
not receive any parameters from the Multi-line 2
unit.
7806 DAVR bias analogue 4 to 20 mA 0 to 10 V If the DVC 310 uses analogue bias for
range 0 to 10 V regulation, this defines the type of analogue
interfacing for the DVC 310. The analogue input
on the DVC 310 is hardcoded to be at terminal
AI1.

DEIF Page 182 of 210


AGC-4 parameter list 4189340688 UK Parameter list

Menu Description Min. value Default Comment


Max. value value

7811 PT100_1 threshold 50 °C 160 °C Determines the maximum temperature of the


250 °C winding in phase 1 of the alternator.
7812 PT100_2 threshold 50 °C 160 °C Determines the maximum temperature of the
250 °C winding in phase 2 of the alternator.
7813 PT100_3 threshold 50 °C 160 °C Determines the maximum temperature of the
250 °C winding in phase 3 of the alternator.
7821 Voltage loss detection OFF OFF Enables the voltage loss protection.
enable ON
7822 Excitation current OFF OFF Enables the excitation current protection.
protection ON
7823 Over-voltage protection OFF OFF Enables the over-voltage protection.
ON
7824 Diode fault OFF OFF Enables the diode fault protection.
ON
7825 Shutdown diodes OFF OFF Enables the shutdown diodes function.
ON
7831 DAVR communication 0.0 s 0.0 s A timer for an alarm for communication error to
error timer 100.0 s the DVC 310.
7832 DAVR communication Not used Not used If the DAVR communication fails, it is possible
error output A Relay 63 to activate a relay.
7833 DAVR communication Not used Not used If the DAVR communication fails, it is possible
error output B Relay 63 to activate a relay.
7834 DAVR communication OFF OFF Enables/disables the alarm for communication
error alarm enable ON error between the DVC 310 and the Multi-line 2
unit.
7835 DAVR communication Warning Warning Decides what the Multi-line 2 unit should do, if
error alarm fail class Trip GB the DAVR communication alarm occurs.

3.12.3 CAN port setup


No. Setting Min. Factory Notes Ref. Description
Max. setting
7840 CAN select
7841 CAN A 0, 2, 3, 6 PM CAN Option 0. OFF
PRIMARY G4, G5 1. External I/O
and G8 2. PMS primary
7842 CAN B 0, 2, 3, 6, 9 PM CAN
3. EIC
SECONDARY
6. PMS secondary
7843 CAN C 0, 1, 3, 11 OFF 9. Axiomatic
11. Ext. modules DEIF
7844 CAN D 0, 1, 3, 11 OFF

7845 CAN E 0, 1, 3, 11 OFF

7846 CAN F 0, 1, 3, 11 OFF

DEIF Page 183 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.13 System parameters - external I/O communication setup


3.13.1 External I/O communication setup
No. Setting Min. Fac- Notes Ref. Description
Max. tory
set-
ting
7890 CIO configuration
7891 CIO enable ON OFF Enabling CIO communication.
OFF
7950 KL320x config
7951 KL320x Mod- Pt100 Option: Selection for analogue modules.
config ule 1 (2/3-wire) External I/ The selections for KL 3202/3204 can-
7952 KL320x Mod- 10- O mod- not be changed.
config ule 2 1200 Ω ules (H8) After changing module type, the pa-
(2-wire) rameter list in the PC USW must be
7953 KL320x Mod-
uploaded again.
config ule 3
7954 KL320x Mod-
config ule 4
7970 CAN 1
7971 CAN 1 Type OFF OFF Option: This menu is only activated if option
Beckhoff External I/ H8.2 is activated.
7972 CAN 1 Baud 50k 125k O mod- After changing type, the parameter
125k ules (H8) list in the PC USW must be uploaded
250k again.
Menu 7974 is for reestablishing com-
7973 CAN 1 ID 1 to 64 1
munication after a fault/disconnec-
7974 CAN 1 Reset OFF OFF tion.
ON
7980 CAN 2
7981 CAN 2 Type OFF OFF Option: This menu is only activated if option
Beckhoff External I/ H8.8 is activated.
7982 CAN 2 Baud 50k 125k O mod- After changing type, the parameter
125k ules (H8) list in the PC USW must be uploaded
250k again.
Menu 7984 is for reestablishing com-
7983 CAN 2 ID 1 to 64 1
munication after a fault/disconnec-
7984 CAN 2 Reset OFF OFF tion.
ON

DEIF Page 184 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.14 System parameters - power management setup


3.14.1 Power management setup
No. Setting Min. Factory Notes Ref. Description
Max. setting
8000 Load-dependent start
8001 Load-dep. P set- 1 kW 100 kW Option G4,
start point 20000 kW G5 and G8
8002 Load-dep. S set- 1 kVA 100 kVA
start point 20000 kVA
8003 Load-dep. % set- 1% 90%
start point 100%
8004 Load-dep. Timer 0.0 s 10.0 s
start 990.0 s
8005 Load-dep. Min. 0 kW 20 kW
start load 20000 kW
8010 Load-dependent stop
8011 Load-dep. P set- 1 kW 200 kW Option G4, Menu 8015 set to "ON"
stop point 20000 kW G5 and G8 will block the load-de-
8012 Load-dep. S set- 1 kVA 200 kVA pendent stop if a heavy
stop point 20000 kVA consumer is connected.

8013 Load-dep. % set- 1% 70%


stop point 100%
8014 Load-dep. Timer 5.0 s 30.0 s
stop 990.0 s
8015 Load-dep. Select Blocked Blocked
stop ON ON
Blocked
OFF
8020 PM config
8021 PM config Enable Remote Remote Option G4, Remote and local decide
Local G5 and G8 if the start/stop command
8022 PM config Update Update lo- Update all of the plant is given Re-
cal mote (digital input) or Lo-
Update all cal (from the display).
Update is used to define
if the change of a running
mode will affect all AGCs
connected on the power
management CAN line or
only the local unit where
the running mode is
changed.
8023 Easy Enable ON OFF
Connect OFF

DEIF Page 185 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
8030 Priority selection
8031 Priority se- Priority Manual Manual Option G4, Setup of priorities.
lect. abs. abs. G5 and
Running G8
hours abs.
Fuel opti-
misation
Manual rel.
Running
hours rel.
8080 Priority (1-5)
8081 Priority 1 ID 1 1 Option G4, Menu 8086 is only appli-
32 G5 and cable if “Manual” is selec-
8082 Priority 2 ID 1 2 G8 ted in menu 8031. Menu
32 8086 resets itself to OFF
automatically once the
8083 Priority 3 ID 1 3
new settings have been
32
transmitted.
8084 Priority 4 ID 1 4
32
8085 Priority 5 ID 1 5
32
8086 Transmit Enable ON OFF
new priori- OFF
ty
8090 Priority (6-11)
8091 Priority 6 ID 1 6 Option G4,
32 G5 and
8092 Priority 7 ID 1 7 G8
32
8093 Priority 8 ID 1 8
32
8094 Priority 9 ID 1 9
32
8095 Priority 10 ID 1 10
32
8096 Priority 11 ID 1 11
32
8100 Priority (12-16)
8101 Priority 12 ID 1 12 Option G4,
32 G5 and
8102 Priority 13 ID 1 13 G8
32
8103 Priority 14 ID 1 14
32

DEIF Page 186 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
8104 Priority 15 ID 1 15
32
8105 Priority 16 ID 1 16
32
8106 Priority 17 ID 1 17
32
8110 Running hours
8111 Running Priority 1 hrs 175 hrs Option G4, If menu 8113 is set "ON",
hours Update 20000 hrs G5 and G8 the trip counter in the unit
8112 Running Type Total Trip Absolute will be reset to 0 hours.
hours LoadPro-
filed

8113 Running Trip OFF OFF


hours counter ON
8120 Ground relay
8121 Ground re- Output Not used Not used Option G4, Selection of relay output
lay A Option- G5 and G8 for start point grounding
dep. (8121 and 8122).
8122 Ground re- Output Not used Not used 8123 is used to enable
lay B Option- the ground relay feature.
dep. The timer setting is for
how long a ground relay
8123 Ground re- Enable OFF OFF
feedback failure is accep-
lay ON
ted.
8124 Ground Timer 1s 1s .
failure 5s
8125 Ground Fail F1...F9 Trip GB
failure class (F3)
8130 Ground relay position
8131 Gnd open Timer 1s 1s Option G4, Alarms related to the po-
fail 5s G5 and G8 sition of the ground fail-
8132 Gnd open Fail F1...F9 Trip GB ure breaker.
fail class (F3)
8133 Gnd close Timer 1s 1s
fail 5s
8134 Gnd close Fail F1...F9 Block (F1)
fail class
8135 Gnd pos Timer 1s 1s
fail 5s
8136 Gnd pos Fail F1...F9 Trip GB
fail class (F3)
8140 Stop non-connected DGs
8141 Stop non- Delay 10.0 s 60.0 s Option G4, Stop timer for non-con-
con. DGs 600.0 s G5 and G8 nected gensets.

DEIF Page 187 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
8170 Fuel optimise
8171 Fuel opti- Setpoint 30% 80% Option G4,
mise 100% G5 and G8
8172 Fuel opti- Swap 10 kW 200 kW
mise setpoint 20000 kW
8173 Fuel opti- Timer 0.0 s 10.0 s
mise 999.0 s
8174 Fuel opti- Hours 1 hrs 175 hrs
mise 20000 hrs
8175 Fuel opti- Enable OFF OFF
mise hour ON
8180 Mains config.
8181 Mb failure Enable OFF OFF Option G4, Only available in AGC
start ON G5 and G8 mains unit.
8182 Parallel Enable OFF OFF Auto switch selections:
ON -OFF
-Static section
8183 No break Enable OFF OFF
-Dynamic section
transfer ON
-All sections
8184 Auto Select OFF OFF
switch All sections
8185 Run type Select Run all Run one
mains mains
Run one
mains
8186 Run type ID to run 17 17
32
8190 Tie breaker
8191 Tie break- TB open 0 kW 50 kW Option G4, Only available in AGC
er point 20000 kW G5 and G8 mains unit.
8192 Tie break- Power 1 kW 50 kW
er Capacity 20000 kW
8193 Tie break- P. cap. 5.0 s 30.0 s
er Overrule 999.9 s
8194 Tie break- P cap. OFF OFF
er Overrule ON
8195 Tie break- Load 0.0 s 0.0 s
er time 30.0 s
8200 Heavy consumer 1
8201 Heavy Req. 10 kVA 500 kVA Option G4, Only available in AGC
consumer value 9999 kVA G5 and G8 DG units.
1
8202 Heavy Nom. 10 kW 400 kW
consumer power 9999 kW
1

DEIF Page 188 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
8203 Heavy Load Fixed load Fixed
consumer type Variable load
1 load
8204 Heavy Enable OFF OFF
consumer ON
1
8210 Heavy consumer 2
8211 Heavy Req. 10 kVA 500 kVA Option G4, Only available in AGC
consumer value 9999 kVA G5 and G8 DG units.
2
8212 Heavy Nom. 10 kW 400 kW
consumer power 9999 kW
2
8213 Heavy Load Fixed load Fixed
consumer type Variable load
2 load
8214 Heavy Enable OFF OFF
consumer ON
2
8220 Available power 1
8221 Avail. pow- Setpoint 10 kW 1000 kW Option G4, The setting can be used
er 1 20000 kW G5 and G8 for conditional connection
8222 Avail. pow- Timer 1.0 s 10.0 s of load groups.
er 1 999.9 s The relay(s) used must
be set to “Limit” mode.
8223 Avail. pow- Relay Not used Not used
er 1 output A Option-
dep.
8224 Avail. pow- Relay Not used Not used
er 1 output B Option-
dep.
8225 Avail. pow- Enable OFF OFF
er 1 ON
8230 Available power 2
8231 Avail. pow- Setpoint 10 kW 1000 kW Option G4, The setting can be used
er 2 20000 kW G5 and G8 for conditional connection
8232 Avail. pow- Timer 2.0 s 10.0 s of load groups.
er 2 999.9 s The relay(s) used must
be set to “Limit” mode.
8233 Avail. pow- Relay Not used Not used
er 2 output A Option-
dep.
8234 Avail. pow- Relay Not used Not used
er 2 output B Option-
dep.
8235 Avail. pow- Enable OFF OFF
er 2 ON

DEIF Page 189 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
8240 Available power 3
8241 Avail. pow- Setpoint 10 kW 1000 kW Option G4, The setting can be used
er 3 20000 kW G5 and G8 for conditional connection
8242 Avail. pow- Timer 3.0 s 10.0 s of load groups.
er 3 999.9 s The relay(s) used must
be set to “Limit” mode.
8243 Avail. pow- Relay Not used Not used
er 3 output A Option-
dep.
8244 Avail. pow- Relay Not used Not used
er 3 output B Option-
dep.
8245 Avail. pow- Enable OFF OFF
er 3 ON
8250 Available power 4
8251 Avail. pow- Setpoint 10 kW 1000 kW Option G4, The setting can be used
er 4 20000 kW G5 and G8 for conditional connection
8252 Avail. pow- Timer 4.0 s 10.0 s of load groups.
er 4 999.9 s The relay(s) used must
be set to “Limit” mode.
8253 Avail. pow- Relay Not used Not used
er 4 output A Option-
dep.
8254 Avail. pow- Relay Not used Not used
er 4 output B Option-
dep.
8255 Avail. pow- Enable OFF OFF
er 4 ON
8260 Available power 5
8261 Avail. pow- Setpoint 10 kW 1000 kW Option G4, The setting can be used
er 5 20000 kW G5 and G8 for conditional connection
8262 Avail. pow- Timer 5.0 s 10.0 s of load groups.
er 5 999.9 s The relay(s) used must
be set to “Limit” mode.
8263 Avail. pow- Relay Not used Not used
er 5 output A Option-
dep.
8264 Avail. pow- Relay Not used Not used
er 5 output B Option-
dep.
8265 Avail. pow- Enable OFF OFF
er 5 ON

DEIF Page 190 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
8270 TB power
8271 TB power Trans- 0 kW 0 kW Option G4, AGC mains only: If the
ducer 20000 kW G5 and G8 TB needs to be deloaded
max. before opening, a power
8272 TB power Trans- -20000 kW 0 kW transducer must be con-
ducer 0 kW nected to multi-input 105.
min.
8273 Deload TB Enable OFF OFF
BSync ON
8280 Asymmetric load sharing
8281 Asymmet- Setpoint 1% 80% Option G4, Please refer to the option
ric LS 100% G5 and G8 G4/G5 manual.
8282 Asymmet- Enable OFF OFF
ric LS ON
8290 Detection of BB measurement failure
8291 BB meas Timer 5.0 s 10 s Option G4, If multiple DG controllers
failure 999.9 s G5 and G8 are connected to
8292 BB meas Relay Option-dep. Not used measure on the same
failure output A BB, and the BB
measurement on the next
8293 BB meas Relay Option-dep Not used prioritised DG is not
failure output B
available, this alarm will
8294 BB meas Enable OFF ON exclude the specific DG
failure ON and start the DG with
8295 BB meas Fail F1... F4 Trip + stop next priority.
failure class (F4)
8300 Settings for load-dependent start
8301 Ld. start Setpoint 1 kW 100 kW Option G4,
limit P 2 20000 kW G5 and G8

8302 Ld. start Setpoint 1 kVA 100 kVA


limit S 2 20000 kVA
8303 Ld. start Setpoint 1% 90 %
limit % 2 100 %
8304 Ld. start Timer 0s 10 s
timer 2 990 s
8305 Ld. start Setpoint OFF OFF
timer 2 ON
8310 Settings for load-dependent stop
8311 Ld. stop Setpoint 1 kW 200 kW Option G4,
limit P 2 20000 kW G5 and G8

8312 Ld. stop Setpoint 1 kVA 200 kVA


limit S 2 20000 kVA
8313 Ld. stop Setpoint 1% 70 %
limit % 2 100 %
8314 Ld. stop Timer 0s 30 s
timer 2 990 s

DEIF Page 191 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
8315 Ld. stop Setpoint OFF OFF
timer 2 ON
8320 Priority (18-23)
8321 Priority 18 Setpoint 1 18 Option G4,
32 G5 and G8
8322 Priority 19 Setpoint 1 19
32
8323 Priority 20 Setpoint 1 20
32
8324 Priority 21 Setpoint 1 21
32
8325 Priority 22 Setpoint 1 22
32
8326 Priority 23 Setpoint 1 23
32
8330 Priority (24-29)
8331 Priority 24 Setpoint 1 24 Option G4,
32 G5 and G8
8332 Priority 25 Setpoint 1 25
32
8333 Priority 26 Setpoint 1 26
32
8334 Priority 27 Setpoint 1 27
32
8335 Priority 28 Setpoint 1 28
32
8336 Priority 29 Setpoint 1 29
32
8340 Priority (30-32)
8341 Priority 30 Setpoint 1 30 Option G4,
32 G5 and G8
8342 Priority 31 Setpoint 1 31
32
8343 Priority 32 Setpoint 1 32
32
8880 Load-dependent start/stop calc.
8881 Start/stop S1 kW kW Option G4, These settings are used
calc. kVA G5 and G8 to decide how the load-
8882 Start/stop S2 Value Per- Value dependent start and stop
calc. centage commands in the power
management system
should be calculated.

DEIF Page 192 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
8920 Secured mode
8921 Secured Sec Secured Secured Option G4, Multi-start setpoint 1 and
mode mode OFF mode G5 and G8 2:
Secured OFF - Auto calculation
mode ON - 1 DG
8922 Multi-start Setpoint Auto calcu- Auto cal- - 2 DG
setpoint 1 1 lation culation - 3 DG
Start 16 - 4 DG
DG - 5 DG
- 6 DG
8923 Multi-start Run 1 Minimum 1
- 7 DG
setpoint 1 number
- 8 DG
run. 1-16
- 9 DG
8924 Multi-start Select Multi-start Multi-start - 10 DG
config. set 1 set 1 - 11 DG
Multi-start - 12 DG
set 2 - 13 DG
8925 Multi-start Setpoint Auto calcu- Start 16 - 14 DG
setpoint 2 2 lation DG - 15 DG
Start 16 - 16 DG
DG Minimum number of run-
ning DGs: 1-16 DGs.
8926 Multi-start Run 2 Minimum 1
Multi-start configuration:
setpoint 2 number
Selects between setpoint
run. 1-16
1 and 2.
8930 Heavy consumer 1 variable load
8931 HC 1 VAR Type Multi-in 102 Multi-in Option G4, Type:
load Multi-in 108 102 G5 and G8 - Multi-input 102
8932 HC 1 VAR Setpoint 0 mA 0 mA - Multi-input 105
load min. 10 mA - Multi-input 108
The function is only avail-
8933 HC 1 VAR Setpoint 10 mA 20 mA able in AGC DG units.
load max. 20 mA
8940 Heavy consumer 2 variable load
8941 HC 2 VAR Type Multi-in 102 Multi-in Option G4, Type:
load Multi-in 108 105 G5 and G8 - Multi-input 102
8942 HC 2 VAR Setpoint 0 mA 0 mA - Multi-input 105
load min. 10 mA - Multi-input 108
The function is only avail-
8943 HC 2 VAR Setpoint 10 mA 20 mA able in AGC DG units.
load max. 20 mA
8990 BTB closed ring
8991 Closed Enable ON OFF Option G4, This parameter deter-
ring OFF G5 and G8 mines whether it is al-
lowed to close all BTBs
in a ring bus at the same
time.

DEIF Page 193 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.15 System parameters - jump menus


3.15.1 Jump menus
A number of menus can only be entered using the jump menu.

3.15.2 9000 Software version


Information about the application software version downloaded to the unit. Please check this before contact-
ing DEIF regarding service and support matters. This menu also shows the clock and the date in the unit.

Option N: "W1" displays the IP address and Subnet mask, and "W2" displays the Gateway address and soft-
ware image version.

No. Description Notes


9000 software
version
9000 Shows the software version of the unit. Also shows the date and
clock in the unit.
9001 Shows the revision of the software in the unit.
9002 Shows the IP address and the subnet mask. Requires Option N
9003 Shows the gateway and the image version of the Option N. Requires Option N

3.15.3 9010 Display character test


Shows a test print of the character set in the display.

3.15.4 9020 Service port


The service port can be set up to use the ASCII communication. The ASCII communication is used when the
utility software is connected through a modem.

Selection "0" must be used for cable connection between the AGC and the PC. Selection "1"
must be used for modem connection between the AGC and the PC.

3.15.5 9030 Scaling


No. Setting Min. Factory set- Notes Ref. Description
Max. ting
9030 Scaling of voltage reference
9030 Scaling Setting 10 V-2500 V 100 V-25000 Option G4, This parameter is used
10 kV-160 V G5 and G8 to scale the voltage ref-
kV erence.
Selections:
10 V-2500 V
100 V-25000 V
10 kV-160 kV
1 kV-75 kV

DEIF Page 194 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.15.6 9070 M4 software version


Information about the software version in the engine interface printed circuit board placed in slot 7.

No. Description
9070 M4 software version
9070 Shows the M4 software version
9071 Shows the M4 protocol version
9072 Shows the M4 software revision
9073 Shows the internal protocol version

3.15.7 9100 Device type


No. Setting Min. Factory Notes Ref. Description
Max. setting
9100 Device type
9100 Device Device DG unit DG unit Designer’s This setting is only accessible
type type BTB unit Reference using the JUMP’ button on the
Handbook display.
Available selections:
- DG unit (diesel generator)
- Mains unit (mains connection)
- BTB unit (bus tie breaker)

The unit will return to factory parameter settings if setting in menu 9100 is changed!

3.15.8 911x Password


No. Setting Min. Facto- Notes Ref. Description
Max. ry set-
ting
911x Password
9116 User Set- 0 2000 Designer’s It is recommended to change the
pass- ting 32000 Reference password levels of the user, service
word Handbook and master password if access to
9117 User Set- 0 2001 parameter settings must be restric-
pass- ting 32000 ted.
word
9118 User Set- 0 2002
pass- ting 32000
word

DEIF Page 195 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.15.9 9120 Service menu


This menu is used to show the different timer values, the digital in- and outputs and the status of the different
lines in M-Logic.

No. Description
9120 Service menu
9121 Shows the values of differential timers.
9123 Shows the status of the digital inputs of the unit.
9124 Shows the status of the outputs of the unit.
9125 Shows the status of the different lines in M-Logic.

3.15.10 9130 AC config.


This menu is used to choose the AC configuration.

No. Setting Description


9130 AC config.
9130 AC config. Setting Selections:
- 3 phase L1L2L3
- 2 phase L1L3
- 2 phase L1L2
- 1 phase L1

Phase angles:
L1L2L3: 120 degrees with neutral.
L1L3: 180 degrees (split phase, neutral in the centre).
L1L2: 120 degrees with neutral.
L1: Single phase with phase-neutral.

3.15.11 9140 Angle compensation BB/G


This menu is used to compensate the transformer phase angle when the generator and busbar measure-
ments are made on each side of a transformer.

No. Setting Min. Factory Notes Ref. Description


Max. setting
9140 Angle comp. BB/G
9140 Angle comp. BB/ Angle -179.0 deg. 0.0 Designer’s Refer-
G1 179.0 deg. ence Handbook
9142 Angle comp. BB/ Angle -179.0 deg. 0.0 Designer's Refer-
G2 179.0 deg. ence Handbook

3.15.12 9150 Backlight dimmer


In this menu, it is possible to change the dim of the backlight in the display.

No. Setting Description


9150 Backlight dim
9150 Backlight dimmer Sets the light intensity for the display.

DEIF Page 196 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.15.13 9160 Application drawing


This menu is used to change between different applications. In the bottom right corner, it is shown which ap-
plication is active. When placed on active application, it will say ACT in bottom right corner of the display,
otherwise INACT if not placed on active application.

No. Setting Min. Factory set- Notes Ref. Description


Max. ting
9160 User-defined application
9160 Application A1 A1 Designer's The 4 different applications
A4 Reference available make it possible to shift
Handbook between different plant types.

3.15.14 9170 Internal CAN protocol


Menu 9170 is used to make it possible to interface to AGC units using application SW version 3.20.x or earlier.
Menus 9171 and 9172 are used to speed up power management telegrams between controllers.

No. Setting Min. Factory setting Notes Ref. Description


Max.
9170 Internal CAN protocol
9170 Application Protocol 1 Protocol 2 Option G4, G5
Protocol 2 and G8 power
9171 Int. CAN units <=15 units <=40 units management
<=40 units
9172 Int. CAN Baud 125 kbit 250 kbit
250 kbit

3.15.15 9180 Quick setup (AGC diesel generator)


This menu makes it possible to set up the power management application without using the "Application con-
figuration" tool in the PC utility software.

No. Setting Min. Factory Notes Ref. Description


Max. setting
9180 Quick setup
9180 Quick set- Mode OFF OFF When using this menu, it will
up Setup stand- not be possible to design ap-
alone plications with AGC bus tie
Setup plant units.
9180 Quick set- CAN OFF CAN CAN A
up A CAN B
CAN A+B
9180 Quick set- MB Pulse Pulse
up No breaker
Continuous
Compact
9180 Quick set- GB Pulse Pulse
up Continuous
Compact

DEIF Page 197 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
9180 Quick set- Mains Mains present Mains
up No mains present
present
9180 Quick set- Plant Standard Standard
up type Single DG

3.15.16 9180 Quick setup (AGC mains)


This menu makes it possible to set up the power management application without using the "Application con-
figuration" tool in the PC utility software.

No. Setting Min. Factory Notes Ref. Description


Max. setting
9180 Quick setup
9180 Quick set- Mode OFF OFF When using this menu, it will not
up Setup stand- be possible to design applica-
alone tions with AGC bus tie units.
Setup plant
9180 Quick set- CAN OFF CAN CAN A
up A CAN B
CAN A+B
9180 Quick set- MB Pulse Pulse
up No breaker
EXT/ATS
Continuous
Compact
9180 Quick set- TB Pulse Pulse
up No breaker
Continuous
Compact
9180 Quick set- NX Normally open Normally
up Normally closed open

3.15.17 9190 Application broadcast


This menu makes it possible to broadcast an application between all AGC units connected on the CAN A or
CAN B line.

No. Setting Min. Factory set- Notes Ref. Descrip-


Max. ting tion
9190 Application broadcast
9190 Application Enable OFF OFF
broadcast Broadcast
Broadcast + activate
9190 Application Application Application 1 Application 1
broadcast Application 2
Application 3
Application 4

DEIF Page 198 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.15.18 9230 Memory backup


This menu makes it possible to back-up the memory before changing the internal battery. For additional infor-
mation, please refer to the designer's reference handbook.

No. Setting Description


9230 Memory backup
9231 Backup memory This function stores the memory
9232 Restore memory This function restores the memory

The unit will reboot after loading of an image.

3.16 System parameters - utility software


3.16.1 GSM settings

GSM settings are only accessible in the utility software.

No. Setting Min. Factory setting Notes Ref. Descrip-


Max. tion
10320 GSM Pin code
10320 GSM Pin Function 0 1933 Designer’s
code 9999 Reference
Handbook
10330 Telephone no. 1
10330 Telephone 1 Function 0 12345678903 Designer’s
99999999999 Reference
Handbook

Telephone numbers 2-5 are available in menus 10340-10373.

DEIF Page 199 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.17 System parameters - RMI inputs


3.17.1 RMI 102

RMI 102 settings are only accessible in the utility software.

No. Setting Min. Factory set- Notes Ref. Description


Max. ting
10460 RMI 1 type
10460 RMI 1 type Sensor type 1 Sensor type Designer’s Refer- Selections are:
Configurable 1 ence Handbook -Sensor type 1
RMI -Sensor type 2
-Sensor type 3
-Configurable
RMI
10470 RMI 1 input setpoint 1
10470 RMI 1 inp. 0 Ohm 10 Ohm Designer’s Refer- Configurable RMI
setp. 1 1800 Ohm ence Handbook curve.
10480 RMI 1 output setpoint 1
10480 RMI 1 outp. -49 40 Designer’s Refer- Configurable RMI
setp. 1 482 ence Handbook curve.
10490 RMI 1 input setpoint 2
10490 RMI 1 inp. 0 Ohm 44.9 Ohm Designer’s Refer- Configurable RMI
setp. 2 1800 Ohm ence Handbook curve.
10500 RMI 1 output setpoint 2
10500 RMI 1 outp. -49 50 Designer’s Refer- Configurable RMI
setp. 2 482 ence Handbook curve.
10510 RMI 1 input setpoint 3
10510 RMI 1 inp. 0 Ohm 81 Ohm Designer’s Refer- Configurable RMI
setp. 3 1800 Ohm ence Handbook curve.
10520 RMI 1 output setpoint 3
10520 RMI 1 outp. -49 60 Designer’s Refer- Configurable RMI
setp. 3 482 ence Handbook curve.
10530 RMI 1 input setpoint 4
10530 RMI 1 inp. 0 Ohm 134.7 Ohm Designer’s Refer- Configurable RMI
setp. 4 1800 Ohm ence Handbook curve.
10540 RMI 1 output setpoint 4
10540 RMI 1 outp. -49 80 Designer’s Refer- Configurable RMI
setp. 4 482 ence Handbook curve.
10550 RMI 1 input setpoint 5
10550 RMI 1 inp. 0 Ohm 184 Ohm Designer’s Refer- Configurable RMI
setp. 5 1800 Ohm ence Handbook curve.

DEIF Page 200 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory set- Notes Ref. Description


Max. ting
10560 RMI 1 output setpoint 5
10560 RMI 1 outp. -49 100 Designer’s Refer- Configurable RMI
setp. 5 482 ence Handbook curve.
10570 RMI 1 input setpoint 6
10570 RMI 1 inp. 0 Ohm 200 Ohm Designer’s Refer- Configurable RMI
setp. 6 1800 Ohm ence Handbook curve.
10580 RMI 1 output setpoint 6
10580 RMI 1 outp. -49 110 Designer’s Refer- Configurable RMI
setp. 6 482 ence Handbook curve.
10590 RMI 1 input setpoint 7
10590 RMI 1 inp. 0 Ohm 210 Ohm Designer’s Refer- Configurable RMI
setp. 7 1800 Ohm ence Handbook curve.
10600 RMI 1 output setpoint 7
10600 RMI 1 outp. -49 115 Designer’s Refer- Configurable RMI
setp. 7 482 ence Handbook curve.
10610 RMI 1 input setpoint 8
10610 RMI 1 inp. 0 Ohm 220 Ohm Designer’s Refer- Configurable RMI
setp. 8 1800 Ohm ence Handbook curve.
10620 RMI 1 output setpoint 8
10620 RMI 1 outp. -49 120 Designer’s Refer- Configurable RMI
setp. 8 482 ence Handbook curve.

3.17.2 RMI 105

RMI 105 settings are only accessible in the utility software.

Menus 10630-10790 equal the settings for RMI 102 (10460-10620).

3.17.3 RMI 108

RMI 108 settings are only accessible in the utility software.

Menus 10800-10960 equal the settings for RMI 102 (10460-10620).

DEIF Page 201 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.17.4 Multi-input selections 102, 105, 108


No. Setting Min. Factory setting Notes Ref. Description
Max.
10970 Engineering units
10970 Engineering units Bar/Celsius Bar/Celsius
Psi/Fahrenheit
10980 Multi-input configuration 102
10980 Multi-inp. conf. 102 4-20 mA 0-40V DC Possible selections:
Binary 4-20 mA
0-40V DC
Pt100
Pt1000
RMI oil pressure
RMI water temp
RMI fuel level
Binary
10990 Multi-input configuration 105
10990 Multi-inp. conf. 105 4-20 mA 0-40V DC Possible selections:
Binary 4-20 mA
0-40V DC
Pt100
Pt1000
RMI oil pressure
RMI water temp
RMI fuel level
Binary
11000 Multi-input configurable 108
11000 Multi-inp. conf. 108 4-20 mA 0-40V DC Possible selections:
Binary 4-20 mA
0-40V DC
Pt100
Pt1000
RMI oil pressure
RMI water temp
RMI fuel level
Binary

DEIF Page 202 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.17.5 Multi-input selections option M16.6


No. Setting Min. Factory setting Notes Ref. Description
Max.
11120 Multi-input configuration 91
11120 Multi-inp. conf. 91 4-20 mA 0-5V DC Option M16.6 Possible selections:
Pt100 4-20 mA
0-5V DC
Pt100
11130 Multi-input configuration 93
11130 Multi-inp. conf. 93 4-20 mA 0-5V DC Option M16.6 Possible selections:
Pt100 4-20 mA
0-5V DC
Pt100
11140 Multi-input configuration 95
11140 Multi-inp. conf. 95 4-20 mA 0-5V DC Option M16.6 Possible selections:
Pt100 4-20 mA
0-5V DC
Pt100
11150 Multi-input configurable 97
11150 Multi-inp. conf. 97 4-20 mA 0-5V DC Option M16.6 Possible selections:
Pt100 4-20 mA
0-5V DC
Pt100

DEIF Page 203 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.17.6 Multi-input selections M16.8


No. Setting Min. Factory setting Notes Ref. Description
Max.
11160 Multi-input configuration 127
11160 Multi-inp. conf. 127 4-20 mA 0-5V DC Option M16.8 Possible selections:
Pt100 4-20 mA
0-5V DC
Pt100
11170 Multi-input configuration 129
11170 Multi-inp. conf. 129 4-20 mA 0-5V DC Option M16.8 Possible selections:
Pt100 4-20 mA
0-5V DC
Pt100
11180 Multi-input configuration 131
11180 Multi-inp. conf. 131 4-20 mA 0-5V DC Option M16.8 Possible selections:
Pt100 4-20 mA
0-5V DC
Pt100
11190 Multi-input configurable 133
11190 Multi-inp. conf. 133 4-20 mA 0-5V DC Option M16.8 Possible selections:
Pt100 4-20 mA
0-5V DC
Pt100

3.17.7 4-20 mA input scaling


No. Setting Min. Factory Notes Ref. Description
Max. setting
11010 4-20 mA input scale 102
4-20 mA in- Setpoint No decimal No deci- Selecting "Enable" and writing
put scale Two deci- mal the new setpoint will scale the
102 mal associated min., max. and val-
4-20 mA in- Enable OFF OFF ue automatically.
put scale ON
102

The same settings apply to menus 11020-11110.

DEIF Page 204 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.17.8 Parameter ID
No. Setting Min. Factory Notes Ref. Description
Max. setting
11200 Parameter ID
11201 Parameter Setpoint "Insert text" "Insert text" Designer's Ref- Setup of param-
ID erence Hand- eter ID.
11202 Parameter Password Basic Customer book
ID level Customer
Service

3.18 System parameters - external digital outputs


3.18.1 External digital outputs
No. Setting Min. Factory set- Notes Ref. Descrip-
Max. ting tion
12790 Ext. dig. out 1
Ext. dig. Function Alarm relay ND Alarm relay Option:
out 1 Limit ND External I/O mod-
Alarm relay NE ules (H8)
Ext. dig. OFF delay 0.0 s 5.0 s
out 1 999.9 s

The same settings apply to menus 12800-12940.

3.18.2 External module status


No. Setting Min. Notes Ref. Description
Max.
12950 Ext module 0 -32768 Option: This is a number read in the external module
STATUS 32767 External I/O and displayed in the USW only. Please refer
modules (H8) to option H8 description for details.

The same settings apply to menus 12951-12983 (external modules 1 to 33).

DEIF Page 205 of 210


AGC-4 parameter list 4189340688 UK Parameter list

3.18.3 13000 SuperVision


The following menus define the data used for the "SuperVision" page in the utility software.

No. Setting Min. Factory Notes Ref. Description


Max. setting
13000 Fuel consumption
13000 F. cons. 0% Setpoint 0 l/h 2 l/h Menu 13005 activates display of
load 3000 l/h the expected fuel rate in the utility
13001 F. cons. Setpoint 0 l/h 114.8 l/h software SuperVision page.
50% load 3000 l/h
13002 F. cons. op- Setpoint 0 l/h 168.7 l/h
timum load 3000 l/h
13003 F. cons. Setpoint 0 l/h 228.5 l/h
100% load 3000 l/h
13004 Optimum Setpoint 51% 75%
load 99%
13005 Fuel rate Enable OFF OFF
expected ON

No. Setting Min. Factory setting Notes Ref. Description


Max.
13010 Oil pressure, coolant temp, fuel level input
13010 Oil press. input Setpoint Multi-in 102 Auto detection Selections are:
Auto detection - Multi-input 102
13011 Cool water input Setpoint Multi-in 102 Auto detection - Multi-input 105
Auto detection - Multi-input 108
- Auto detection
13012 Fuel level input Setpoint Multi-in 102 Auto detection
- EIC oil pressure
Auto detection

3.18.4 14000 AC average


The following menus define the data used for the “AC average” page in the utility software. Note that these
menus are only available in the utility software.

No. Setting Min. Factory Notes Ref. Description


Max. setting
14000 Average generator overvoltage L-L 1
14001 Avg G U> Set point 100.0 % 103.0 % Designer’s
L-L 1 120.0 % Reference
Handbook
14002 Avg G U> Timer 0.1 s 10.0 s
L-L 1 100 s
14003 Avg G U> Relay Not used Not used
L-L 1 output A Option-dep.
14004 Avg G U> Relay Not used Not used
L-L 1 output B Option-dep.
14005 Avg G U> Enable OFF OFF
L-L 1 ON
14006 Avg G U> Fail class F1…F9 Warning
L-L 1 (F2)

DEIF Page 206 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
14010 Average generator overvoltage L-L 2
14011 Avg G U> Set point 100.0 % 105.0 % Designer’s
L-L 2 120.0 % Reference
Handbook
14012 Avg G U> Timer 0.1 s 5.0 s
L-L 2 100 s
14013 Avg G U> Relay Not used Not used
L-L 2 output A Option-dep.
14014 Avg G U> Relay Not used Not used
L-L 2 output B Option-dep.
14015 Avg G U> Enable OFF OFF
L-L 2 ON
14016 Avg G U> Fail class F1…F9 Warning
L-L 2 (F2)
14020 Average generator undervoltage L-L 1
14021 Avg G U< Set point 100.0 % 97.0 % Designer’s
L-L 1 120.0 % Reference
Handbook
14022 Avg G U< Timer 0.1 s 10.0 s
L-L 1 100 s
14023 Avg G U< Relay Not used Not used
L-L 1 output A Option-dep.
14024 Avg G U< Relay Not used Not used
L-L 1 output B Option-dep.
14025 Avg G U< Enable OFF OFF
L-L 1 ON
14026 Avg G U< Fail class F1…F9 Warning
L-L 1 (F2)
14030 Average generator undervoltage L-L 2
14031 Avg G U< Set point 100.0 % 95.0 % Designer’s
L-L 2 120.0 % Reference
Handbook
14032 Avg G U< Timer 0.1 s 5.0 s
L-L 2 100 s
14033 Avg G U< Relay Not used Not used
L-L 2 output A Option-dep.
14034 Avg G U< Relay Not used Not used
L-L 2 output B Option-dep.
14035 Avg G U< Enable OFF OFF
L-L 2 ON
14036 Avg G U< Fail class F1…F9 Warning
L-L 2 (F2)
14040 Average generator overvoltage L-N 1
14041 Avg G U> Set point 100.0 % 103.0 % Designer’s
L-N 1 120.0 % Reference
Handbook
14042 Avg G U> Timer 0.1 s 10.0 s
L-N 1 100 s
14043 Avg G U> Relay Not used Not used
L-N 1 output A Option-dep.

DEIF Page 207 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
14044 Avg G U> Relay Not used Not used
L- N 1 output B Option-dep.
14045 Avg G U> Enable OFF OFF
L- N 1 ON
14046 Avg G U> Fail class F1…F9 Warning
L- N 1 (F2)
14050 Average generator overvoltage L-N 2
14051 Avg G U> Set point 100.0 % 105.0 % Designer’s
L-N 2 120.0 % Reference
Handbook
14052 Avg G U> Timer 0.1 s 5.0 s
L-N 2 100 s
14053 Avg G U> Relay Not used Not used
L-N 2 output A Option-dep.
14054 Avg G U> Relay Not used Not used
L-N 2 output B Option-dep.
14055 Avg G U> Enable OFF OFF
L-N 2 ON
14056 Avg G U> Fail class F1…F9 Warning
L-N 2 (F2)
14060 Average generator undervoltage L-N 1
14061 Avg G U< Set point 100.0 % 97.0 % Designer’s
L-N 1 120.0 % Reference
Handbook
14062 Avg G U< Timer 0.1 s 10.0 s
L-N 1 100 s
14063 Avg G U< Relay Not used Not used
L-N 1 output A Option-dep.
14064 Avg G U< Relay Not used Not used
L-N 1 output B Option-dep.
14065 Avg G U< Enable OFF OFF
L-N 1 ON
14066 Avg G U< Fail class F1…F9 Warning
L-N 1 (F2)
14070 Average generator undervoltage L-N 2
14071 Avg G U< Set point 100.0 % 95.0 % Designer’s
L-N 2 120.0 % Reference
Handbook
14072 Avg G U< Timer 0.1 s 5.0 s
L-N 2 100 s
14073 Avg G U< Relay Not used Not used
L-N 2 output A Option-dep.
14074 Avg G U< Relay Not used Not used
L-N 2 output B Option-dep.
14075 Avg G U< Enable OFF OFF
L-N 2 ON
14076 Avg G U< Fail class F1…F9 Warning
L-N 2 (F2)

DEIF Page 208 of 210


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
14080 Average generator overfrequency 1
14081 Avg G f> 1 Set point 100.0 % 103.0 % Designer’s
120.0 % Reference
Handbook
14082 Avg G f> 1 Timer 0.1 s 10.0 s
100 s
14083 Avg G f> 1 Relay Not used Not used
output A Option-dep.
14084 Avg G f> 1 Relay Not used Not used
output B Option-dep.
14085 Avg G f> 1 Enable OFF OFF
ON
14086 Avg G f> 1 Fail class F1…F9 Warning
(F2)
14090 Average generator overfrequency 2
14091 Avg G f> 2 Set point 100.0 % 105.0 % Designer’s
120.0 % Reference
Handbook
14092 Avg G f> 2 Timer 0.1 s 5.0 s
100 s
14093 Avg G f> 2 Relay Not used Not used
output A Option-dep.
14094 Avg G f> 2 Relay Not used Not used
output B Option-dep.
14095 Avg G f> 2 Enable OFF OFF
ON
14096 Avg G f> 2 Fail class F1…F9 Warning
(F2)
14100 Average generator underfrequency 1
14101 Avg G f< 1 Set point 100.0 % 97.0 % Designer’s
120.0 % Reference
Handbook
14102 Avg G f< 1 Timer 0.1 s 10.0 s
100 s
14103 Avg G f< 1 Relay Not used Not used
output A Option-dep.
14104 Avg G f< 1 Relay Not used Not used
output B Option-dep.
14105 Avg G f< 1 Enable OFF OFF
ON
14106 Avg G f< 1 Fail class F1…F9 Warning
(F2)
14110 Average generator underfrequency 2
14111 Avg G f< 2 Set point 100.0 % 95.0 % Designer’s
120.0 % Reference
Handbook
14112 Avg G f< 2 Timer 0.1 s 5.0 s
100 s
14113 Avg G f< 2 Relay Not used Not used
output A Option-dep.

DEIF Page 209 of 211


AGC-4 parameter list 4189340688 UK Parameter list

No. Setting Min. Factory Notes Ref. Description


Max. setting
14114 Avg G f< 2 Relay Not used Not used
output B Option-dep.
14115 Avg G f< 2 Enable OFF OFF
ON
14116 Avg G f< 2 Fail class F1…F9 Warning
(F2)
14120 Average overcurrent 1
14121 Avg I> 1 Set point 50.0 % 115.0 % Designer’s
200.0 % Reference
Handbook
14122 Avg I> 1 Timer 0.1 s 10.0 s
3200 s
14123 Avg I> 1 Relay Not used Not used
output A Option-dep.
14124 Avg I> 1 Relay Not used Not used
output B Option-dep.
14125 Avg I> 1 Enable OFF OFF
ON
14126 Avg I> 1 Fail class F1…F9 Warning
(F2)
14130 Average overcurrent 2
14131 Avg I> 2 Set point 50.0 % 120.0 % Designer’s
200.0 % Reference
Handbook
14132 Avg I> 2 Timer 0.1 s 5.0 s
3200 s
14133 Avg I> 2 Relay Not used Not used
output A Option-dep.
14134 Avg I> 2 Relay Not used Not used
output B Option-dep.
14135 Avg I> 2 Enable OFF OFF
ON
14136 Avg I> 2 Fail class F1…F9 Warning
(F2)

DEIF Page 210 of 210