Documente Academic
Documente Profesional
Documente Cultură
T0 dq
behavior at low speed, a feed-forward compensation of the low-pass
delay
filter response was implemented in order to reduce the estimation sin(θˆ)
sin
error with respect to the pure integrator.
T0
The block scheme depicted in Fig. 2 represents the implemen-
delay
tation of the flux observer. As the voltages applied to PMSG are not
available (i.e., no sensors are employed to perform this operation),
the voltages Vαβ could be estimated from the duty cycles, DCuvw , Fig. 3. Block scheme of the single-phase PLL.
of the PWM modules and from the measure of the DC Link voltage,
VDC . The outputs of the block LPF Compensator in Fig. 2 are the √
two terms |C(ω)| and 6 C(ω), which compensate the response of factor 3. In order to correctly preload the flux observer these facts
the low-pass filter, regaining the correct phase lag and magnitude of must be taken into account.
the ideal integrator. The term 6 C(ω) drives the block αβ/dq, that The knowledge of the rotor angle before the PWM turn-on al-
represents the Park Transform, here employed as a rotation trans- lows to obtain a better converter startup, that, in any case, is critical
formation to correct the phase of the initial flux estimate, as stated due to DC Link voltage.
before. In fact, before the PWM turn-on, the DC Link is charged with
In the end, a standard three phase d-q PLL [5] is employed to a DC voltage level equal to the peak of the phase-to-phase voltage,
extract from λmαβ the information regarding the rotor speed ω and in fact the freewheeling diodes in parallel with the full-bridge tran-
the rotor angle. sistors act as a three-phase uncontrolled rectifier. As it is known, the
three-phase full bridge driven by a sinusoidal PWM (SPWM) works
VDC RIα RI β
LIα LI β
in linear
√
modulation [8] with an amplitude of the first harmonic up to
duty-cycles VDC 3
Rotation Matrix
2
,therefore this level may not be sufficient to prevent an over-
DCu Vα
uvw
αβ Low-pass filter αβ current because the front-end full-bridge has not sufficient DC Link
DCv
DCw
dq
αβ
Vβ
Low-pass filter dq voltage to impose the desired phase current.
This overcurrent can be very significant in case of high effi-
C (ω )
∠C (ω )
λmβ
ciency PM generators since they are often characterized by a low
LPF
ω
d-q PLL
winding impedance.
Compensator
λmα In order to reduce the initial overcurrent, an over-modulation
sen(θ ) cos(θ ) technique has to be implemented. In this paper the adopted solution
was the injection of a third voltage harmonic in the duty-cycles of
Fig. 2. Block scheme of the implemented flux observer. the standard SPWM. Other approaches, such as the Space Vector
Modulation (SVM [8]) would lead to similar results.
As explained in subsection 2.1, the FOC relies on the esteem of the With the information regarding the rotor flux, the field oriented con-
rotor angle to correctly control the electrical torque. However, as the trol can be implemented. Figure 4 illustrates the block scheme of the
phase voltage is not measured, the duty cycles are employed instead. field oriented torque control. The blocks uvw/αβ and αβ/dq repre-
This mechanism, however, does not work if the PWM switching is sent, respectively, the Clarke and Park transforms, while the power
disabled, i.e. at the startup of the converter. stage is represented by a Voltage Source Inverter (VSI). Two Pro-
For this reason, an instrument transformer was added between portional Integral (PI) regulators control the direct and quadrature
the phases u and v of the generator. With the information regarding components of the generator currents. Since a surface permanent
the phase-to-phase voltage before the PWM startup, it is possible to magnet generator has been chosen, the direct current component is
preload the flux observer with the correct value of flux amplitude and forced to zero in order to improve the generator efficiency.
phase. The term Vqemf represents the feed-forward compensation of the
In order to perform this task, a dedicated PLL structure was generator emf, and can be computed if the machine constant and the
employed to correctly track the rotor angle with arbitrary genera- speed are known. As explained before, during the startup the flux
tor speed. This structure, named transport delay PLL [6], is pre- observer is precharged by the single-phase PLL, as the duty cycles
sented in Fig. 3 and represents a standard quadrature PLL where are not available if the PWM is not activated.
the quadrature version of the input signal is generated by a transport
delay block. A constant delay T0 , that corresponds to a π/2 phase 2.4. Maximum Power Point Tracking
delay, can be used only with a constant input pulsation, ω0 = 2Tπ0 .
When the frequency is not constant, as for this application, it is suf- The wind turbine allows to convert the kinetic energy of the wind
ficient to substitute the cosine function of the Park transform of the into mechanical power and then into electrical power. The power
PLL with the same transport delay applied to the sine of the esti- generated by the turbine, depending on the blades and wind speeds,
mated angle [7]. can be derived as (3), assuming a perpendicular incidence of the
Obviously, the angle of the phase-to-phase voltage will be lead- wind to the blades’ rotational plane. In (3) Pt is the turbine power,
ing the phase voltage by π/6, and its amplitude will be greater by a ρ is the air density, R the blade radius, vw the wind speed and
196
by the flux observer (Fig. 2), is used to generate the current set-point
Vq emf Iq∗ (Fig. 4).
Other MPPT algorithms based on the Perturb and Observe
I q* Vq* (P&O) principle usually applied for photovoltaic systems, were not
Vα* Vu*
PI dq αβ 0
I$ q Vv* taken into account due to their poor performances when applied to
VSI PMSG
I d* = 0 Vd * Vβ* Vw* wind turbines.
PI
αβ uvw
Fig. 6 shows an example of an actual implementation of the
I$ d V0* = sin(3θ ) 6
Vuv
MPPT algorithm based on the knowledge of the MPP locus of the
Iu
θ αβ wind turbine. The numerical values used are the same of the experi-
Iv
mental test bed of section 5.
Iw
Iα uvw Below a specific value of speed (the cut-in speed, i.e., 100 rpm)
dq
Iβ
the converter is not operational. After that, the converter tracks the
VDC
αβ DCuvw MPP characteristic, and the torque request is parabolic. When the
0 Iαβ rated power of the converter is reached (i.e., 900W), the converter
Flux
Observer
1 Single-Phase enters the derating zone, where the maximum power is limited and
PLL
startup ? the torque request decreases with the speed.
If the power limit of the converter is not sufficient to keep the
Fig. 4. Block scheme of the implemented torque control. wind turbine in a safe operating area (i.e., below the maximum
speed), the converter stop the operation (cut-out), and other safety
mechanisms, usually mechanical brakes, intervene to stop the tur-
bine.
Cp (λ, β) is the power conversion coefficient that depends on the
tip-speed ratio λ and the pitch angle β.
1000
1
Pt = πρCp (λ, β)R2 vw 3
(3)
Converter output
800
2 MPPT
Derating
power [W]
600
For fixed-pitch turbines, the power curves for different wind Disconnection
400
speeds are similar to those depicted in Fig. 5. For every wind speed,
there is a particular turbine speed that corresponds to the maximum 200
power conversion (optimal tip speed ratio). Obviously, a wind con- 0
0 200 400 600 800 1000
verter must control the turbine rotational speed in order to follow the
optimal tip speed ratio when the wind speed changes, therefore the
20
MPPT algorithm must be implemented. cut−out
Converter torque
reference [Nm]
15
cut−in
10
v8
Maximum power locus 5
v 0
7 0 200 400 600 800 1000
Turbine output power
v3
v2
0 v1 3. GRID-CONNECTED CONVERTER
197
chosen for the inverter is the full-bridge driven by the unipolar (three regulates the braking torque of the generator in order to fix the DC
∗
output voltage levels) modulation. A LC filter at the full-bridge out- Link voltage to the value VDC−gen while the grid-connected stage
put is employed to reduce the switching harmonics due to the PWM. is still verifying if the grid voltage satisfies the requirements. When
The converter is separated by the grid by a couple of relays. the grid-connected stage starts injecting power into the grid, it also
∗ ∗
The main tasks of the inverter is the grid connection and current regulates the DC Link voltage to a value VDC < VDC−gen (mode
control, that can be performed only if the conditions regarding the 2).
grid voltage are satisfied. Moreover, in order to control the grid cur- The active front-end is implemented to limit the maximum brak-
rent igrid , the DC Link voltage must be above the peak of the grid ing torque (extracted power) to a suitably small value when it is
voltage. in DC Link control operation (mode 1). In fact, when the grid-
In order to correctly track the grid voltage frequency, a PLL was connected is not operational, a low power is needed to fix the DC
implemented, the structure is the transport delay PLL employed also Link voltage. When the grid-connected becomes operational, it will
∗
in the active front-end converter (Fig. 3). be able to fix the DC Link voltage to VDC , while the DC Link
Many topologies of current control are available in literature [9], controller of the active front-end will be saturated to the maximum
for this application the d-q current control [10] was chosen for the value.
very good performances that it can obtain regarding harmonic power Upon the detection of this operation, the active front-end com-
distortion and zero steady-state error. mutates to MPPT operation (mode 3), seeking the maximum point
The block scheme of the current control is reported in Fig. 7. of power transfer. This is the normal operation of the back-to-back
From the grid current igrid a virtual quadrature system Iαβ is gen- converter.
erated. With the grid voltage angle obtained by the PLL a Park In this condition, if a grid voltage fault occurs, the grid-
transform is executed, and two PI regulators generate the voltage connected converter stops working, while the active front-end is
set points for the converter. In order to enhance the dynamic behav- still absorbing the maximum available power (mode 4). This will
v
ior of the system, a feed-forward voltage vF F = Vgrid is added to inevitably lead to an overvoltage of the DC Link, that is detected
DC
the modulation index. by the active front-end, which returns in DC Link voltage control
operation (from mode 4 to mode 1).
vFF S
I d* Vd * Vβ * vgrid 1 2 3
PI dq LF
Active front-end Active front-end Active front-end
I$ d I q* I q*
* *
VDC VDC
CF − gen Torque − gen Torque ω I q*
Vq * PI PI Torque
LF Control Control MPPT
PI αβ VˆDC VˆDC Control
I q*
I$ q θGRID
Grid-connected Grid-connected Grid-connected
PLL • Grid voltage check
*
VDC I d* Grid *
VDC I d* Grid
• Grid frequency check PI Current PI Current
Iα • DC Link voltage check
VˆDC Control VˆDC Control
• Relay disconnected
dq
Iβ
Delay Active front-end
αβ 90° Grid-connected
• Requirements satisfied • Regulator
• Relay connection saturation detected
• MPPT Operation
Fig. 7. Block scheme of the implemented grid current control.
4
Active front-end
ω I q*
Torque
MPPT
Control
4. DC LINK VOLTAGE CONTROL Active front-end Grid-connected
• DC Link overvoltage Grid-connected • Grid voltage fault
• DC Link control
In sections 2.3 and 3 the control scheme of the main tasks of each Operation
•
•
Grid voltage check
Grid frequency check
• Relay disconnection
converter were detailed, however further control is needed in order •
•
DC Link voltage check
Relay disconnected
to make the back-to-back converter fully functional. As a matter of
fact, each converter can regulate the DC Link voltage with a simple
PI Controller. If the controller is executed by the active front-end Fig. 8. Transitions between the modes of operation of the back-to-
converter, the output of the PI controller will be a torque demand back converter.
in order to charge the DC Link capacitor. On the other hand, if the
DC Link control is performed by the grid-connected converter, the
regulator output will be a grid current demand to discharge/charge 5. EXPERIMENTAL RESULTS
the DC Link capacitor.
The issue of the DC Link control is that the grid-connected oper- A back-to-back converter based on two DSP Freescale MC56F8323
ation is asynchronous to the active front-end, as the grid connection (for every full-bridge) was built and its performance was evaluated
must occur only when specific conditions are satisfied. Neverthe- with a suitable test bed. The converter was connected to a PMSG
less, the main task of the active front-end is to maximize the energy (1.2 kW rated power, 6 pole pairs, nominal speed 500 rpm and nomi-
harvesting from the wind generator. nal voltage 240 Vrms) connected to a speed regulated induction mo-
In order to render the implementation more robust, the two con- tor drive, a schematic of the test bed is reported in Fig. 9. The
verters do not perform any kind of communication, but the synchro- induction motor drive was controlled by a PC with a dSpace board.
nization is performed with the DC Link voltage and current moni- Fig. 10 and Fig. 11 show, respectively, the realized converter
toring and a specific switching strategy is implemented. and the test bed used for the experiments.
Fig. 8 presents the 4 modes of operation of the back-to-back In the following some oscilloscope captures are reported in or-
converter. At the converter startup (Mode 1), the active front-end der to highlight the correct operations of the converter in every con-
198
Induction Back-to-back
Motor PMSG Converter
Grid
Voltage
Speed-controlled
Induction Motor
Drive
Fig. 11. Picture of the test bed comprising the brushless generator
Fig. 9. Schematic of the test bed realized for the experimental results and the prime mover.
Fig. 12. Singe-phase PLL employed compute the correct rotor angle
before the PWM turn-on. Phase voltage Vu (100 V/div), rotor an-
gle (0.5π/div), reconstructed quadrature system Vα , Vβ , (200 V/div).
Fig. 10. Picture of the realized back-to-back converter. Time base 10 ms/div.
dition.
Fig. 12 shows the correct flux observer precharge at the con-
verter startup. The phase voltage was obtained by recreating the
neutral voltage with a resistive divider in wye connection. As it can
be seen, the angle could be correctly estimated even if the only mea-
sure available was the phase-to-phase voltage Vuv .
The correct operation of the grid-connected converter and the
d-q grid current control are highlighted in Fig. 13, where a low dis-
tortion sinusoidal current is injected into the grid.
The following captures show the modes of operation switching
implemented for the DC Link control. In Fig. 14 the active front-end
converter is regulating the DC Link voltage until the grid-connected
converter starts the power transfer to the grid. After this point the Fig. 13. Grid current igrid (10 A/div) and voltage vgrid (200 V/div).
grid-connected converters fixes the DC link voltage to 400V and the Time base 20 ms/div.
active front-end commutates to MPPT mode. Instead, Fig. 15 shows
the transition of the active front-end when the grid-connected con-
verter is disconnected to the grid (i.e., due to anomalies in the grid the velocity profile of the prime mover.
voltage or frequency). When the voltage limit (430V) is reached, the
converter commutates from the MPPT mode to the DC Link control. 6. CONCLUSION
Finally, Fig. 16 shows switching from the MPPT to the derating
operating mode. Due to the long time base operated by the oscillo- This paper presents the overall control of a back-to-back converter
scope during the capture time, only the envelope of the currents is for wind energy conversion systems. Two full-bridges converters
visible. For the sake of simplicity, a linear torque-speed character- compose respectively the AC/DC active front-end for the wind gen-
istic was chosen for the open loop MPPT instead of the MPP locus erator and the DC/AC grid-connected converter. A suitable sensor-
of Fig. 5. The prime mover drive was instructed to perform a speed less field-oriented control has been implemented for the active front-
ramp from 100 rpm to 500 rpm (the rated speed). As can be seen, end and experimental results show the effectiveness of the solutions
the algorithm correctly chooses the braking torque in accordion to to control the generator torque. The grid-connected converter is able
199
7. REFERENCES
[1] R.C. Portillo, M.M. Prats, J.I. Leon, J.A. Sanchez, J.M. Car-
rasco, E. Galvan, and L.G. Franquelo, “Modeling strategy
for back-to-back three-level converters applied to high-power
wind turbines,” IEEE Transactions on Industrial Electronics,
vol. 53, no. 5, pp. 1483 –1491, oct. 2006.
[2] M. Pucci and M. Cirrincione, “Neural mppt control of wind
generators with induction machines without speed sensors,”
IEEE Transactions on Industrial Electronics, vol. 58, no. 1,
pp. 37 –47, jan. 2011.
Fig. 14. Grid connected converter turn-on and active rectifier com- [3] Shuhui Li, T.A. Haskew, R.P. Swatloski, and W. Gathings,
mutation to DC Link control to MPPT. DC Link voltage VDC , input “Optimal and direct-current vector control of direct-driven
power (800 W/div), igrid (10 A/div) and operating mode indicator. pmsg wind turbines,” IEEE Transactions on Power Electron-
Time base 50 ms/div. ics, vol. 27, no. 5, pp. 2325 –2337, may 2012.
[4] P.P. Acarnley and J.F. Watson, “Review of position-sensorless
operation of brushless permanent-magnet machines,” Indus-
trial Electronics, IEEE Transactions on, vol. 53, no. 2, pp. 352
– 362, april 2006.
[5] F. Blaabjerg, R. Teodorescu, M. Liserre, and A.V. Timbus,
“Overview of control and grid synchronization for distributed
power generation systems,” Industrial Electronics, IEEE
Transactions on, vol. 53, no. 5, pp. 1398 –1409, oct. 2006.
[6] S.A. Oliveira da Silva, R. Novochadlo, and R.A. Modesto,
“Single-phase pll structure using modified p-q theory for util-
ity connected systems,” in IEEE Power Electronics Specialists
Conference, 2008. PESC 2008, june 2008, pp. 4706 –4711.
Fig. 15. Grid disconnection operation. VDC , igrid (10 A/div), iu (5 [7] M. Ciobotaru, R. Teodorescu, and F. Blaabjerg, “Control of
A/div) and operating mode indicator. Time base 50 ms/div. single-stage single-phase pv inverter,” in European Conference
on Power Electronics and Applications, 2005, 2005.
[8] A.M. Hava, R.J. Kerkman, and T.A. Lipo, “Carrier-based
pwm-vsi overmodulation strategies: analysis, comparison, and
design,” IEEE Transactions on Power Electronics, vol. 13, no.
4, pp. 674 –689, jul 1998.
[9] F. Blaabjerg, R. Teodorescu, M. Liserre, and A.V. Timbus,
“Overview of control and grid synchronization for distributed
power generation systems,” IEEE Transactions on Industrial
Electronics, vol. 53, no. 5, pp. 1398 –1409, oct. 2006.
[10] G. Franceschini, E. Lorenzani, and G. Buticchi, “Saturation
compensation strategy for grid connected converters based on
line frequency transformers,” IEEE Transactions on Energy
Fig. 16. Derating operation. Operating mode indicator, generator Conversion, 2012.
speed and generator phase current iu (green trace, 3 A/div). Time
base 1 s/div.
to regulate the active power transferred to the grid and the experi-
mental results show the good performance of the d-q control of the
grid current. The control of the DC Link voltage represents a manda-
tory requirement, as no communication was implemented between
the two converters. Suitable mechanisms have been implemented to
ensure the correct operation of the two converters in any condition.
200