The breaker should be clean and arc chutes intact. Inspect the
main contacts and finger clusters for abnormalities. Check that
lubrication is in accordance with manufacturers specifications
and mechanically charge, close and trip the circuit breaker
multiple times.
3.) Verify that the circuit breaker fits inside of its cell
and is properly aligned.
Look inside the cell for any obvious signs of bent guides or
other components. Check that the circuit breaker racking
mechanism operates smoothly. Do not rack the circuit breaker
onto live bus until all other testing is completed!
Verify that the circuit breaker fits inside of its cell and is
properly aligned. PHOTO: EATON.
Electrical Tests
5.) Inspect bolted connections, fuses, and
contact/pole resistance using a low-resistance ohm
meter
Verify and document the long time pickup, long time delay,
short time pickup, short time delay, instantaneous pickup,
ground fault pickup and ground fault delay using a high current
test set.