Sunteți pe pagina 1din 16

Product Bulletin

62.1:DVC6000
D102758X012
February 2010 DVC6000 Digital Valve Controllers

Fisherr FIELDVUEt DVC6000 Digital Valve


Controllers
FIELDVUE DVC6000 digital valve controllers DVC6000 digital valve controllers can be used on
(figures 1 and 2) are communicating, single-- or double--acting actuators. The digital valve
microprocessor--based current--to--pneumatic controller receives feedback of the valve travel
instruments. In addition to the traditional function of position plus supply and actuator pneumatic
converting a current signal to a valve--position pressure. This allows the instrument to diagnose not
pressure signal, DVC6000 digital valve controllers, only itself, but also the valve and actuator to which it
using HARTt communications protocol, give easy is mounted. This provides you with very cost
access to information critical to process operation. effective maintenance information, as the required
This can be done using a Field Communicator at the maintenance can be performed on the instrument
valve or at a field junction box, or by using a and valve when there really is a need.
personal computer or a system console within the
control room. Using HART communication protocol,
information can be integrated into a control system Wiring is economical because DVC6000 digital valve
or received on a single loop basis. controllers use two--wire 4 to 20 mA loop power.
This provides for low cost replacement of existing
analog instrumentation. The two--wire design avoids
the high cost of running separate power and signal
wiring.

W9131--1
W7957 / IL

Figure 1. FIELDVUE DVC6010 Digital Valve Controller Figure 2. FIELDVUE DVC6010 Digital Valve Controller
Mounted on a Sliding--Stem Valve Actuator Mounted on Fisher 585C Piston Actuator

www.Fisher.com
Product Bulletin
62.1:DVC6000
DVC6000 Digital Valve Controllers February 2010

Specifications
Available Configurations Supply Pressure(2)
Valve−Mounted Instrument: Minimum Recommended: 0.3 bar (5 psig)
DVC6010: Sliding−stem applications higher than maximum actuator requirements
DVC6020: Rotary applications and long−stroke Maximum: 10.0 bar (145 psig) or maximum
sliding−stem applications pressure rating of the actuator, whichever is lower
DVC6030: Quarter−turn rotary applications
Remote−Mounted Instrument(1): Medium: Air or Natural Gas(8)
DVC6005: Base unit for 2 inch pipestand or wall
mounting Air Quality: Supply pressure must be clean, dry
DVC6015: Feedback unit for sliding−stem air that meets the requirements of ISA Standard
applications 7.0.01. A maximum 40 micrometer particle size in
DVC6025: Feedback unit for rotary or long−stroke the air system is acceptable. Further filtration
sliding−stem applications down to 5 micrometer particle size is
DVC6035: Feedback unit for quarter−turn rotary recommended. Lubricant content is not to exceed
applications 1 ppm weight (w/w) or volume (v/v) basis.
DVC6000 digital valve controllers can be mounted Condensation in the air supply should be
on Fisher and other manufacturers rotary and minimized
sliding−stem actuators.
Natural Gas: Natural gas must be clean, dry,
Input Signal oil−free, and noncorrosive. H2S content should
not exceed 20 ppm.
Point−to−Point:.
Analog Input Signal: 4−20 mA DC, nominal; split
ranging available
Minimum Voltage Available at Instrument
Terminals must be 10.5 VDC for analog control, Steady−State Air Consumption(3)(4)
11 VDC for HART communication (see instrument Standard Relay:
instruction manual for details) At 1.4 bar (20 psig) supply pressure: Less than
Minimum Control Current: 4.0 mA 0.38 normal m3/hr (14 scfh)
Minimum Current w/o Microprocessor Restart: 3.5 At 5.5 bar (80 psig) supply pressure: Less than
mA 1.3 normal m3/hr (49 scfh)
Maximum Voltage: 30 VDC
Overcurrent Protection: Input circuitry limits Low Bleed Relay(5):
current to prevent internal damage At 1.4 bar (20 psig) supply pressure: Average
Reverse Polarity Protection: No damage occurs value 0.056 normal m3/hr (2.1 scfh)
from reversal of loop current At 5.5 bar (80 psig) supply pressure: Average
Multi−drop:. value 0.184 normal m3/hr (6.9 scfh)
Instrument Power: 11 to 30 VDC at
approximately 8 mA
Reverse Polarity Protection: No damage occurs Maximum Output Capacity(3)(4)
from reversal of loop current
At 1.4 bar (20 psig) supply pressure: 10.0 normal
m3/hr (375 scfh)
Output Signal At 5.5 bar (80 psig) supply pressure: 29.5 normal
Pneumatic signal as required by the actuator, up m3/hr (1100 scfh)
to 95% of supply pressure
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig) Independent Linearity(6)
Action: J Double, J Single Direct, and J Single
Reverse ±0.50% of output span
(continued)

2
Product Bulletin
62.1:DVC6000
February 2010 DVC6000 Digital Valve Controllers

Specifications (continued)
Electromagnetic Compatibility Other Classifications/Certifications
Meets EN 61326−1 (First Edition) TIIS—Japan
Immunity—Industrial locations per Table 2 of KISCO—Korea Industrial Safety Corp.
the EN 61326−1 standard. Performance is
GOST−R—Russian GOST−R
shown in table 2 below.
Emissions—Class A FSETAN—Russian − Federal Service of
ISM equipment rating: Group 1, Class A Technological, Ecological and Nuclear
Inspectorate
Lightning and Surge Protection—The degree of Contact your Emerson Process Management
immunity to lightning is specified as Surge sales office for classification/certification specific
immunity in table 2. For additional surge information
protection commercially available transient
protection devices can be used. Connections
Supply Pressure: 1/4 NPT internal and integral
IEC 61010 Compliance Requirements pad for mounting 67CFR regulator
(Valve−Mounted Instruments Only) Output Pressure: 1/4 NPT internal
Tubing: 3/8−inch recommended
Power Source: The loop current must be derived Vent (pipe−away): 3/8 NPT internal
from a separated extra−low voltage (SELV) power Electrical: 1/2 NPT internal conduit connection.
source optional— M20 internal conduit connection,
Environmental Conditions: Installation Category I spring clamp terminal connection(7)

Vibration Testing Method


Electrical Classification
Tested per ANSI/ISA−S75.13.01 Section 5.3.5. A
Hazardous Area: resonant frequency search is performed on all
three axes. The instrument is subjected to the ISA
CSA—Intrinsically Safe, Explosion proof, specified 1/2 hour endurance test at each major
Division 2, Dust−Ignition proof resonance, plus an additional two million cycles.
FM—Intrinsically Safe, Explosion proof,
Non−incendive, Dust−Ignition proof Humidity Limits
ATEX—Intrinsically Safe, Flameproof, Type n Tested per IEC 61514−2

IECEx—Intrinsically Safe, Flameproof, Type n


Input Impedance
NEPSI—Intrinsically Safe, Flameproof The input impedance of the DVC6000 active
electronic circuit is not purely resistive. For
INMETRO—Intrinsically Safe, Flameproof
comparison to resistive load specifications, an
Refer to tables 3, 4, 5, 6, 7, and 8. equivalent impedance of 550 ohms may be used.
This value corresponds to 11V @ 20 mA.
Electrical Housing:
CSA—Type 4X, IP66 Operating Ambient Temperature Limits(2)
FM—NEMA 4X −40 to 80_C (−40 to 176_F) for most approved
valve−mounted instruments
ATEX—IP66 −60 to 125_C (−76 to 257_F) for remote−mounted
feedback units
IECEx—NEMA 4X, IP66 −52 to 80_C (−62 to 176_F) for valve−mounted
instruments utilizing the Extreme Temperature
NEPSI—IP66 option (fluorosilicone elastomers)
(continued)

3
Product Bulletin
62.1:DVC6000
DVC6000 Digital Valve Controllers February 2010

Specifications (continued)
Construction Materials of moisture that may be introduced via the
Housing, module base and terminal box: instrument air supply.
ASTM B85 A03600 low copper aluminum alloy
(standard) Weight
CF8M (cast 316 stainless steel) (optional for Valve−Mounted Instruments.
valve−mounted instruments only) Aluminum: 3.5 kg (7.7 lbs)
Cover: Thermoplastic polyester Stainless steel: 7.7 kg (17 lbs)
Elastomers.
Standard: Nitrile Remote−Mounted Instruments.
Optional: Fluorosilicone DVC6005 Base Unit: 4.1 kg (9 lbs)
DVC6015 Feedback Unit: 1.3 kg (2.9 lbs)
Stem/Shaft Travel DVC6025 Feedback Unit: 1.4 kg (3.1 lbs)
Linear Actuators with rated travel between 6.35 DVC6035 Feedback Unit: 0.9 kg (2.0 lbs)
mm (0.25 inch) and 606 mm (23.375 inches)
Options
Rotary Actuators with rated travel between 50
degrees and 180 degrees J Supply and output pressure gauges or J Tire
valves J Integral mounted filter regulator
J Stainless steel housing, module base and
Mounting terminal box (valve−mounted instruments only)
Designed for direct actuator mounting or remote J Low−Bleed Relay, J Extreme Temperature
pipestand or wall mounting. Mounting the J Remote Mount J Inline 10 micrometer air filter
instrument vertically, with the vent at the bottom J Safety Instrumented System (SIS) Solutions
of the assembly, or horizontally, with the vent J Safety Related Nuclear Applications J Natural
pointing down, is recommended to allow drainage Gas Certified

NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 − Process Instrument Terminology.
1. 3−conductor shielded cable, 22 AWG minimum wire size, is required for connection between base unit and feedback unit. Pneumatic tubing between base unit output connection and actuator
has been tested to 15 meters (50 feet) maximum without performance degradation.
2. The pressure/temperature limits in this document and any other applicable code or standard should not be exceeded.
3. Normal m3/hour − Normal cubic meters per hour at 0_C and 1.01325 bar, absolute. Scfh − Standard cubic feet per hour at 60_F and 14.7 psia.
4. Values at 1.4 bar (20 psig) based on a single−acting direct relay; values at 5.5 bar (80 psig) based on double−acting relay.
5. The Low Bleed Relay is offered as standard relay for DVC6000 SIS, used for On/Off applications.
6. Typical value. Not applicable for DVC6020 digital valve controllers in long−stroke applications or remote−mounted DVC6005 digital valve controllers with long pneumatic tubing lengths.
7. ATEX/IEC approvals only.
8. Gas Certified DVC6000 digital valve controllers are FM and CSA Single Seal approved for use with natural gas as the supply medium.

Features or within the safety of the control room using either a


Field Communicator, a notebook PC, or a system
D Improved Control—Two−way digital workstation. Your exposure to hazardous
communications give you current valve conditions. environments is minimized and you can avoid having
You can rely on this real−time information to make to access hard−to−reach valve locations.
sound process management decisions. By analyzing
valve dynamics through ValveLinkt software you
D Hardware Savings—DVC6000 digital valve
can identify control areas needing improvement and
controllers, when used in an integrated system,
maintain a high level of system performance.
allow you to realize significant hardware and
installation cost savings by replacing other devices
D Environmental Protection—You can avoid in the process loop, such as positioners and limit
additional field wiring by connecting a leak detector switches, with a FIELDVUE digital valve controller.
or limit switch to the auxiliary terminals in the
DVC6000 digital valve controller. In this way, the
D Built to Survive—Field−tough DVC6000 digital
instrument will issue an alert if limits are exceeded.
valve controllers have fully encapsulated printed
wiring boards that resist the effects of vibration,
D Enhanced Safety—You can check instrument temperature, and corrosive atmospheres. A separate
and valve operation and keep the process running weather−tight field wiring terminal box isolates
smoothly and safely from a remote location. Access field−wiring connections from other areas of the
is possible at a field junction box, marshalling panel, instrument.

4
Product Bulletin
62.1:DVC6000
February 2010 DVC6000 Digital Valve Controllers

Table 1. FIELDVUE DVC6000 Diagnostic Level Capabilities


DIAGNOSTIC LEVEL
CAPABILITY
AC HC AD PD SIS(1) ODV
Auto Calibration n n n n n n
Custom Characterization n n n n n n
Burst Communication n n n n n
Alerts n n n n n
Step Response, Drive Signal Test &
n n n n
Dynamic Error Band, Valve Signature
Performance Tuner n n n n
Travel Control − Pressure Fallback n n n
Performance Diagnostics n n
Partial Stroke Testing n n
Lead/Lag Input Filter(2) n
1. Refer to Bulletin 62.1:DVC6000 SIS for information on DVC6000 digital valve controllers for Safety Instrumented System (SIS) Solutions.
2. Refer to brochure part # D351146X012 / D351146X412 for information on Fisher optimized digital valves for compressor antisurge applications.

D Increased Uptime—With the self−diagnostic instrument will automatically disable the travel
capability of the DVC6000, you can answer sensor, send an alert, and control its output pressure
questions about a valve’s performance, without much like an I/P transducer. This allows the valve
pulling the valve from the line. You can run assembly to continue to operate with reduced
diagnostics (I/P and relay integrity, travel deviation, accuracy until maintenance can be scheduled.
and on−line friction and deadband analysis and
trending) while the valve is in service and operating.
You can also compare the present valve/actuator
signature (bench set, seat load, friction, etc.) against
previously stored signatures to discover
performance changes, before they cause process Diagnostics
control problems.
DVC6000 digital valve controllers are packed with
user−configurable alerts and alarms. When
integrated with a HART communicating system,
D Faster Commissioning—The two−way
these flags provide real−time notification of current
communication capability allows you to quickly
and potential valve and instrument problems. With
commission loops by remotely identifying each
ValveLink software, tests can be performed to
instrument, verifying its calibration, reviewing stored
identify problems with the entire control valve
maintenance notes, and more.
assembly. Diagnostic capabilities available are
Performance Diagnostics (PD) and Advanced
D Easy Maintenance—The DVC6000 is modular Diagnostics (AD). Refer to table 1 for details on the
in design. The module base can be removed from capabilities of each diagnostic level.
the instrument housing without disconnecting the
field wiring, pneumatic connections or stem linkages.
This module contains the critical sub−modules so Performance Diagnostics
component removal is quick and simple. Performance Diagnostics enables the use of
diagnostics while the valve is in service and
operating.
D Travel Control — Pressure Fallback—Valve
position feedback is critical to the operation of a D Red/Yellow/Green Condition Indicator
digital valve controller. Without this feedback, the (see figure 3)
control valve assembly traditionally goes to its fail
safe position. DVC6000 digital valve controllers can D I/P and Relay Integrity Diagnostic
detect position feedback problems caused by a
travel sensor failure or linkage failure and continue D Travel Deviation Diagnostic
to operate in “pressure control” mode. If a problem
with the valve position feedback is detected, the D One−Button Diagnostic

5
Product Bulletin
62.1:DVC6000
DVC6000 Digital Valve Controllers February 2010

ERROR
(RED)

WARNING
(YELLOW)

NO CONDITIONS HAVE
BEEN DETECTED
(GREEN)

Figure 3. Red/Yellow/Green Condition Indicators, Shown in ValveLink Software

The One−Button Diagnostic, (shown in figure 4), is a These diagnostic scans vary the positioner set point
20 second sweep which runs the I/P and Relay at a controlled rate and plot valve operation to
Integrity, Relay Adjustment, Travel Deviation, Supply determine valve dynamic performance. The valve
Pressure, and Air Mass Flow Performance signature test allows you to determine the
Diagnostic tests. When the sweep is complete, valve/actuator friction, bench set, spring rate, and
ValveLink software will show any errors, possible seat load. The Dynamic Error Band test is a
causes, and recommended actions to resolve the combination of hysteresis and deadband plus
error(s). “slewing.” Hysteresis and deadband are static
measurements. However, because the valve is
D On−Line/In−Service Friction and Deadband moving, a dynamic error, or “slewing” error is
Analysis (see figure 5) introduced.

D Friction and Deadband Trending


Dynamic scan tests give a better indication of how
the valve will operate under process conditions
While all diagnostics can be run while the valve is which are dynamic, not static.
inline, only the Performance Diagnostics can be
performed while the valve is in service and
operating. The Step Response Test checks the valve
assemblies response to a changing input signal. and
plots travel versus time. The end results of this test
Advanced Diagnostics allow you to evaluate the dynamic performance of
Advanced Diagnostics include the following dynamic the valve. The Performance Step Test (25
scan tests: pre−configured points) provides a standardized step
test with which to evaluate your valve performance.
D Valve Signature (see figure 6) It utilizes small, medium and large changes.

D Dynamic Error Band Advanced Diagnostics are performed with ValveLink


software. The valve must be out of service for
D Instrument Drive Signal Advanced Diagnostics to be performed.

6
Product Bulletin
62.1:DVC6000
February 2010 DVC6000 Digital Valve Controllers

ERROR TYPE

RECOMMENDED
ACTION

E1035

ERROR POSSIBLE CAUSE


DETECTED (RED)

E1036

Figure 4. One−Button Sweep—Air Mass Flow Diagnostic

W7468/IL

Figure 5. Valve Friction and Deadband Analysis Figure 6. The Valve Signature Display

7
Product Bulletin
62.1:DVC6000
DVC6000 Digital Valve Controllers February 2010

DISTRIBUTED CONTROL SYSTEM (DCS)

MODBUS VALVELINK SOFTWARE

FIELD TERMINATION
ASSEMBLY (FTA)

RS232−TO−RS485
CONVERTER
4−20 mA

HART

CONTROL SYSTEM I/O HART MULTIPLEXER


4−20 mA
+
HART

W8082 −1 / IL

Figure 7. Integrate Information from the Digital Valve Controller into a Non−HART Compatible Control
System With ValveLink Software’s Modbus Interface

Integration D Integrated Control System—A control system


with HART communication capabilities has the ability
to directly gather information from DVC6000 digital
D Non−HART Systems—Because DVC6000 valve controllers. Information such as valve travel,
digital valve controllers operate with a traditional 4 to alerts and alarms can be seamlessly accessed to
20 mA control signal, they directly replace older provide a view into the field device from the safety of
analog instruments. Microprocessor−based the control room.
electronics provide improved performance along with
repeatable and reliable configuration and calibration.
Communication

D Modbus with ValveLink software and HART HART Protocol Overview


multiplexers—HART communication allows you to
extract more value from DVC6000 digital valve The HART (Highway Addressable Remote
controllers beyond their inherent improved Transducer) protocol gives field devices the
performance. When integrated into a multiplexer capability of communicating instrument and process
network and using ValveLink software, the device data digitally. This digital communication occurs over
and valve information is real−time. From the safety the same two−wire loop that provides the 4 to 20 mA
of a control room, multiple instruments can be process control signal, without disrupting the
monitored for alerts and alarms. Additionally, tasks process signal (figure 8). In this way, the analog
such as configuration, calibration and diagnostic process signal, with its faster response, can be used
testing do not require special trips to the field. for control. At the same time, the HART digital
ValveLink software can communicate via Modbus to communication gives access to calibration,
the distributed control system (DCS) to provide configuration, diagnostic, maintenance, and
critical information such as valve travel alerts and additional process data. The protocol provides total
alarms (figure 7). system integration via a host device.

8
Product Bulletin
62.1:DVC6000
February 2010 DVC6000 Digital Valve Controllers

+0.5 V

0
ANALOG
SIGNAL

−0.5 V

1200 Hz 2200 Hz
,1, ,0,

AVERAGE CURRENT CHANGE DURING COMMUNICATION = 0


A6174/IL

Figure 8. HART Frequency Shift Keying Technique

The HART protocol gives you the capability of W9128


multidropping, where you can network several
devices to a single communications line. This
Figure 9. Perform Configuration and Calibration at the Valve
process is well suited for remote applications such
or Anywhere on the 4 to 20 mA Loop with the 375 Field
as pipelines, custody transfer sites, and tank farms. Communicator

Field Communicator
You can perform configuration and calibration at the the valve is in service and operating. Valve
valve or anywhere on the two−wire loop via a Field Signature, Dynamic Error Band, and Step Response
Communicator (see figure 9). Powerful tools such as are displayed in an intuitive user−friendly
Setup Wizard and Auto Travel Calibration automate environment that allows easy interpretation of data.
the tasks of commissioning DVC6000 digital valve
controllers. These automation tools not only save
time, but also provide accurate and repeatable Diagnostic graphs can be superimposed over those
results. previously stored to view areas of valve degradation.
This allows plant personnel to concentrate efforts on
equipment that needs repair, avoiding unnecessary
ValveLink Software maintenance. This diagnostic capability is readily
ValveLink software is a WindowsR−based software accessible and available to you either in the control
package that allows easy access to the information room or on the plant floor. In addition to the
available from DVC6000 digital valve controllers. diagnostic features, ValveLink software contains an
Audit Trail, Batch Runner for automating repetitive
Using ValveLink software, you can monitor the tasks, and Trending to view valve performance.
performance characteristics of the valve and obtain
vital information without having to pull the valve from
the line. I/P and Relay Integrity and Travel Deviation ValveLink software provides integration into AMSt
Diagnostics, as well as On−Line Friction and and DeltaVt systems with HART and fieldbus
Deadband Analysis and Trending can be run while communications.

9
Product Bulletin
62.1:DVC6000
DVC6000 Digital Valve Controllers February 2010

TERMINAL BOX
TERMINAL BOX COVER

HOUSING

PNEUMATIC RELAY

GAUGES

COVER

TRAVEL SENSOR

PRINTED WIRING BOARD ASSEMBLY

W9329
MODULE BASE ASSEMBLY I/P CONVERTER

Figure 10. FIELDVUE DVC6000 Digital Valve Controller Assembly (Valve−Mounted Instrument)

Principle of Operation pressure and amplifies the small pneumatic signal


from the I/P converter into a single larger pneumatic
DVC6000 instruments (figures 10 and 11) receive a output signal used by a single−acting actuator. For
set point and position the valve where it needs to be. double−acting actuators, the relay accepts the
pneumatic signal from the I/P converter and provides
D The input signal provides electrical power and two pneumatic output signals.
the set point simultaneously. It is routed into the
terminal box through a twisted pair of wires.
D The change in relay output pressure to the
D The input signal is then directed to the printed actuator causes the valve to move.
wiring board assembly where the microprocessor
runs a digital control algorithm resulting in a drive
signal to the I/P converter. D Valve position is sensed through the feedback
linkage by the instrument’s travel sensor. The travel
sensor is electrically connected to the printed wiring
D The I/P converter assembly is connected to board to provide a travel feedback signal used in the
supply pressure and converts the drive signal into a control algorithm.
pressure output signal.

D The I/P output is sent to the pneumatic relay The valve continues to move until the correct
assembly. The relay is also connected to supply position is attained.

10
Product Bulletin
62.1:DVC6000
February 2010 DVC6000 Digital Valve Controllers

4−20 mA
INPUT SIGNAL
+
HART

AUXILIARY
TERMINALS

TERMINAL BOX

VALVE TRAVEL
PRINTED FEEDBACK
WIRING BOARD
DRIVE
SIGNAL

OUTPUT A

I/P
CONVERTER
SUPPLY
PNEUMATIC PRESSURE
RELAY

OUTPUT B

VALVE AND ACTUATOR


E0408 / IL

Figure 11. FIELDVUE DVC6000 Digital Valve Controller Block Diagram

Installation All pressure connections on the digital valve


controllers are 1/4 NPT internal connections. The
The DVC6010 digital valve controller is designed for digital valve controller outputs are typically
yoke mounting to sliding stem actuators. DVC6020 connected to the actuator inputs using 3/8−inch
digital valve controllers are designed for mounting to diameter tubing. Remote venting is available.
rotary actuators or long−stroke sliding−stem
actuators (over 4 inches travel). DVC6030 digital
valve controllers are designed for mounting on Ordering Information
virtually any quarter−turn actuator.
When ordering, specify:
The DVC6005 digital valve controller base unit may 1. Actuator type and size
be remote mounted on 2 inch pipestand or wall. The
remote−mounted DVC6005 base unit connects to 2. Maximum actuator travel or rotation
the DVC6015, DVC6025, or DVC6035 feedback unit
mounted on the actuator. Feedback wiring and 3. Options
pneumatic tubing to the control valve assembly must
be connected in the field. a. Supply pressure regulator

Refer to Fisher bulletin 62.1:DVC6000(S1) b. Supply and output gauges


(D103308X012) for DVC6000 digital valve controller
dimensional information. c. HART filter

d. Stainless steel housing (valve−mounted


The digital valve controllers are 4 to 20 mA loop instruments only)
powered and do not require additional power.
Electrical connections are made in the terminal box. e. Remote mounting

11
Product Bulletin
62.1:DVC6000
DVC6000 Digital Valve Controllers February 2010

Table 2. EMC Summary Results—Immunity


Performance Criteria(1)
Port Phenomenon Basic Standard Test Level Point−to− Multi−drop
Point Mode Mode
Electrostatic discharge 4 kV contact
IEC 61000−4−2 A(2) A
(ESD) 8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
Enclosure Radiated EM field IEC 61000−4−3 1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80% A A
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
Rated power frequency
IEC 61000−4−8 60 A/m at 50 Hz A A
magnetic field
Burst IEC 61000−4−4 1 kV A(2) A
I/O signal/control Surge IEC 61000−4−5 1 kV (line to ground only, each) A(2) A
Conducted RF IEC 61000−4−6 150 kHz to 80 MHz at 3 Vrms A A
1. A = No degradation during testing. B = Temporary degradation during testing, but is self−recovering.
2. Excluding auxiliary switch function, which meets Performance Criteria B.

Table 3. Hazardous Area Classifications—CSA (Canada)


Certification Enclosure
Type Certification Obtained Entity Rating Temperature Code
Body Rating
Ex ia Intrinsically Safe Vmax = 30 VDC
Class I,II,III Division 1 GP A,B,C,D,E, Imax = 226 mA Type 4X, IP66
F,G per drawing GE42818 T5 Ci = 5 nF T5(Tamb v 80_C) Single Seal Device
Natural Gas Approved Li = 0.55 mH
Explosion Proof
DVC60x0 Type 4X, IP66
Class I Division 1 GP B,C,D T6 −−− T6(Tamb v 80_C)
DVC60x0S Single Seal Device
Natural Gas Approved
(x = 1,2,3)
Class I Division 2 GP A,B,C,D T6
Class II Division 1 GP E,F,G T6
Type 4X, IP66
Class II Division 2 GP F,G T6 −−− T6(Tamb v 80_C) Single Seal Device
Class III
Natural Gas Approved
Ex ia Intrinsically Safe Vmax = 30 VDC Voc = 9.6 VDC
Class I,II,III Division 1 GP A,B,C,D, Imax = 226 mA Isc = 3.5 mA Type 4X, IP66
E,F,G per drawing GE42818 T5 Ci = 5 nF Ca = 3.6 uF T5(Tamb v 80_C) Single Seal Device
Natural Gas Approved Li = 0.55 mH La = 100 mH
Explosion Proof
Type 4X, IP66
Class I Division 1 GP B,C,D T6 −−− T6(Tamb v 80_C)
CSA DVC6005 Single Seal Device
Natural Gas Approved
Class I Division 2 GP A,B,C,D T6
Class II Division 1 GP E,F,G T6
Type 4X, IP66
Class II Division 2 GP FG T6 −−− T6(Tamb v 80_C) Single Seal Device
Class III
Natural Gas Approved
Vmax = 30 VDC T4(Tamb v 125_C)
Ex ia Intrinsically Safe
Imax = 17.5 mA
Class I,II,III Division 1 GP A,B,C,D, T5(Tamb v 95_C) Type 4X, IP66
Ci = 0 uF
E,F,G per drawing GE42818
Li = 0 mH T6(Tamb v 80_C)

T4(Tamb v 125_C)
DVC60x5 Explosion Proof
−−− T5(Tamb v 95_C) Type 4X, IP66
(x = 1,2,3) Class I Division 1 GP B,C,D T6
T6(Tamb v 80_C)

Class I Division 2 GP A,B,C,D T6 T4(Tamb v 125_C)


Class II Division 1,2 GP E,F,G T6 −−− T5(Tamb v 95_C) Type 4X, IP66
Class III
T6(Tamb v 80_C)

12
Product Bulletin
62.1:DVC6000
February 2010 DVC6000 Digital Valve Controllers

Table 4. Hazardous Area Classifications—FM (United States)


Certification Enclosure
Type Certification Obtained Entity Rating Temperature Code
Body Rating
Intrinsically Safe Vmax = 30 VDC
Class I,II,III Division 1 GP A,B,C,D, Imax = 226 mA
E,F,G per drawing GE42819 T5 Ci = 5 nF T5(Tamb v 80_C) NEMA 4X
Natural Gas Approved Li = 0.55 mH
Pi = 1.4 W
DVC60x0 Explosion Proof
DVC60x0S Class I Division 1 GP B,C,D T6 −−− T6(Tamb v 80_C) NEMA 4X
(x = 1,2,3) Natural Gas Approved
Class I Division 2 GP A,B,C,D T6
Class II Division 1 GP E,F,G T6
Class II Division 2 GP F,G T6 −−− T6(Tamb v 80_C) NEMA 4X
Class III
Natural Gas Approved
Intrinsically Safe Vmax = 30 VDC Voc = 9.6 VDC
Class I,II,III Division 1 GP A,B,C,D,E, Imax = 226 mA Isc = 3.5 mA T4(Tamb v 125_C)
F,G per drawing GE42819 T5 Ci = 5 nF Ca = 3.6 uF T5(Tamb v 95_C) NEMA 4X
Natural Gas Approved Li = 0.55 mH La = 100 mH
Pi = 1.4 W Po = 8.4 mW T6(Tamb v 80_C)

Explosion Proof
FM DVC6005 Class I Division 1 GP B,C,D T6 −−− T6(Tamb v 60_C) NEMA 4X
Natural Gas Approved
Class I Division 2 GP A,B,C,D T6
Class II Division 1 GP E,F,G T6
Class II Division 2 GP F,G T6 −−− T6(Tamb v 60_C) NEMA 4X
Class III
Natural Gas Approved
Vmax = 30 VDC
Intrinsically Safe Imax = 17.5 mA T4(Tamb v 125_C)
IS Class I,II,III Division 1 GP A,B,C,D, Ci = 0 nF T5(Tamb v 95_C) NEMA 4X
E,F,G per drawing GE42819 Li = 0 mH
Pi = 105 mW T6(Tamb v 80_C)

DVC60x5 T4(Tamb v 125_C)


Explosion Proof
(x = 1,2,3) −−− T5(Tamb v 95_C) NEMA 4X
XP Class I Division 1 GP A,B,C,D
T6(Tamb v 80_C)

NI Class I Division 2 GP A,B,C,D T4(Tamb v 125_C)


DI Class II Division 1 GP E,F,G −−− T5(Tamb v 95_C) NEMA 4X
S Class II Division 2 GP F,G
T6(Tamb v 80_C)

13
Product Bulletin
62.1:DVC6000
DVC6000 Digital Valve Controllers February 2010

Table 5. Hazardous Area Classifications—ATEX


Enclosure
Certificate Type Certification Obtained Entity Rating Temperature Code
Rating
II 1 G & D
Gas Ui = 30 VDC
Ex ia IIC T5/T6—Intrinsically Safe Ii = 226 mA
T5(Tamb v 80_C)
Dust Ci = 5 nF IP66
Li = 0.55 mH T6(Tamb v75_C)
Ex iaD 20 T100_C (Tamb v 80_C)
Pi = 1.4 W
Ex iaD 20 T85_C (Tamb v 75_C)
II 2 G & D
Gas
DVC60x0 Ex d IIB+H2 T5/T6—Flameproof T5(Tamb v 85_C)
DVC60x0S Dust −−− IP66
(x = 1,2,3) T6(Tamb v75_C)
Ex tD A21 IP66 T90_C (Tamb v 85_C)
Ex tD A21 IP66 T80_C (Tamb v 75_C)
II 3 G & D
Gas
Ex nCL IIC T5/T6—Type n
T5(Tamb v 80_C)
Dust −−− IP66
T6(Tamb v75_C)
Ex tD A22 IP66 T85_C (Tamb v 80_C)
Ex tD A22 IP66 T80_C (Tamb v 75_C)
II 1 G & D
Gas Ui = 30 VDC Uo = 9.6 VDC
Ex ia IIC T5/T6—Intrinsically Safe Ii = 226 mA Io = 3.5 mA
T5(Tamb v 80_C)
Dust Ci = 5 nF Co = 3.6 uF IP66
Li = 0.55 mH Lo = 100 mH T6(Tamb v75_C)
Ex iaD 20 T100_C (Tamb v 80_C)
Pi = 1.4 mW Po = 8.4 mW
Ex iaD 20 T85_C (Tamb v 75_C)
II 2 G & D
Gas
Ex d IIB T5/T6—Flameproof T5(Tamb v 80_C)
DVC6005 Dust −−− IP66
T6(Tamb v75_C)
Ex tD A21 IP66 T85_C (Tamb v 80_C)
ATEX Ex tD A21 IP66 T75_C (Tamb v 70_C)
II 3 G & D
Gas
Ex nL IIC T5/T6—Type n
T5(Tamb v 80_C)
Dust −−− IP66
T6(Tamb v75_C)
Ex tD A22 IP66 T85_C (Tamb v 80_C)
Ex tD A22 IP66 T80_C (Tamb v 75_C)
II 1 G & D
Gas
Ui = 30 VDC
Ex ia IIC T4/T5/T6—Intrinsically Safe T4(Tamb v 125_C)
Dust Ii = 17.5 mA
Ci = 0 uF T5(Tamb v 95_C) IP66
Ex iaD 20 T135_C (Tamb v 125_C) Li = 0 mH
Pi = 105 mW T6(Tamb v 80_C)
Ex iaD 20 T100_C (Tamb v 95_C)
Ex iaD 20 T85_C (Tamb v 80_C)
II 2 G & D
Gas
Ex d IIC T4/T5/T6—Flameproof T4(Tamb v 125_C)
DVC60x5 Dust
−−− T5(Tamb v 95_C) IP66
(x = 1,2,3) Ex tD A21 IP66 T130_C (Tamb v 125_C)
T6(Tamb v 80_C)
Ex tD A21 IP66 T100_C (Tamb v 95_C)
Ex tD A22 IP66 T85_C (Tamb v 80_C)
II 3 G & D
Gas
Ex nA IIC T4/T5/T6—Type n T4(Tamb v 125_C)
Dust
−−− T5(Tamb v 95_C) IP66
Ex tD A22 IP66 T130_C (Tamb v 125_C)
T6(Tamb v 80_C)
Ex tD A22 IP66 T100_C (Tamb v 95_C)
Ex tD A22 IP66 T85_C (Tamb v 80_C)

14
Product Bulletin
62.1:DVC6000
February 2010 DVC6000 Digital Valve Controllers
Table 6. Hazardous Area Classifications—IECEx
Enclosure
Certificate Type Certification Obtained Entity Rating Temperature Code
Rating
Intrinsically Safe Ui = 30 VDC
Gas Ii = 226 mA
T5(Tamb v 80_C) NEMA 4X,
Ex ia IIC T5/T6 per drawing GE42990 Ci = 5 nF
IP66
Li = 0.55 mH T6(Tamb v 75_C)
DVC60x0 Pi = 1.4 W
DVC60x0S Flameproof T5(Tamb v 80_C) NEMA 4X,
(x = 1,2,3) Gas −−−
IP66
Ex d IIB+H2 T5/T6 T6(Tamb v 75_C)
Type n
T5(Tamb v 80_C) NEMA 4X,
Gas −−−
T6(Tamb v 75_C) IP66
Ex nC IIC T5/T6
Intrinsically Safe Ui = 30 VDC Uo = 9.6 VDC
Gas Ii = 226 mA Io = 3.5 mA
T5(Tamb v 80_C) NEMA 4X,
Ex ia IIC T5/T6 per drawing GE42990 Ci = 5 nF Co = 3.6 uF
IP66
Li = 0.55 mH Lo = 100 mH T6(Tamb v 75_C)
Pi = 1.4 W Po = 8.4 mW
DVC6005 Flameproof T5(Tamb v 80_C) NEMA 4X,
Gas −−−
IECEx IP66
Ex d IIB T5/T6 T6(Tamb v 75_C)
Type n
T5(Tamb v 80_C) NEMA 4X,
Gas −−−
T6(Tamb v 75_C) IP66
Ex nC IIC T5/T6
Intrinsically Safe Ui = 30 VDC
Gas Ii = 17.5 mA T4(Tamb v 125_C)
NEMA 4X,
Ex ia IIC T4/T5/T6 Ci = 0 uF T5(Tamb v 95_C) IP66
Li = 0 mH
Pi = 105 mW T6(Tamb v 80_C)

DVC60x5 Flameproof T4(Tamb v 125_C)


NEMA 4X,
(x = 1,2,3) Gas −−− T5(Tamb v 95_C) IP66
Ex d IIC T4/T5/T6
T6(Tamb v 80_C)

Type n T4(Tamb v 125_C)


NEMA 4X,
Gas −−− T5(Tamb v 95_C) IP66
Ex nA IIC T4/T5/T6
T6(Tamb v 80_C)

Table 7. Hazardous Area Classifications—NEPSI


Enclosure
Certificate Type Certification Obtained Entity Rating Temperature Code
Rating
Intrinsically Safe Ui = 30 V
Gas Ii = 226 mA
T5(Tamb v 80_C) NEMA 4X,
Ex ia IIC T5/T6 Ci = 5 nF
IP66
Dust Li = 0.55 mH T6(Tamb v 75_C)
DVC60x0 DIP A21 T5 Pi = 1.4 W
NEPSI
(x = 1,2,3) Flameproof
Gas
T5(Tamb v 80_C) NEMA 4X,
Ex d IIC T5/T6(1) −−−
IP66
Dust T6(Tamb v 75_C)
DIP A21 T5
1. Except acetylene.

Table 8. Hazardous Area Classifications—INMETRO


Enclosure
Certificate Type Certification Obtained Entity Rating Temperature Code
Rating
Intrinsically Safe Ui = 30 V
BR−Ex ia IIC T5 Ii = 180 mA
Ci = 5 nF T5(Tamb v 80_C) Type 4X, IP66
DVC60x0 Li = 0.55 mH
INMETRO
(x = 1,2,3) Pi = 1.4 W
Flameproof
−−− T6(Tamb v 60_C) Type 4X, IP66
BR−Ex d IIB+H2 T6

15
Product Bulletin
62.1:DVC6000
DVC6000 Digital Valve Controllers February 2010

Note
Neither Emerson, Emerson Process
Management, nor any of their affiliated
entities assumes responsibility for the
selection, use, or maintenance of any
product. Responsibility for the
selection, use, and maintenance of any
product remains with the purchaser
and end user.

Fisher, FIELDVUE, ValveLink, AMS, and DeltaV are marks owned by one of the companies in the Emerson Process Management business
division of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson
Electric Co. All other marks are the property of their respective owners. HART is a mark owned by the HART Communication Foundation. This
product may be covered under one or more of the following patents (5,451,923; 5,434,774; 5,439,021; 5,265,637) or under pending patent
applications.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they
are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or
applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the
designs or specifications of such products at any time without notice. Neither Emerson, Emerson Process Management, nor any of their affiliated
entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of
any product remains solely with the purchaser and end user.

Emerson Process Management


Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Chatham, Kent ME4 4QZ UK
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com

16
EFisher Controls International LLC 2000, 2010; All Rights Reserved

S-ar putea să vă placă și