ReadMe
This document contains important information about the SoMove Lite software.
Please read the complete document before you start the installation and operation
of the product.
Schneider Electric assumes no responsibility for any errors that may appear in this document. If you have any
suggestions for improvements or amendments or have found errors in this publication, please notify us. No part of this
document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without
express written permission of Schneider Electric. All pertinent state, regional, and local safety regulations must be
observed when installing and using this product. For reasons of safety and to help ensure compliance with documented
system data, only the manufacturer should perform repairs to components. When devices are used for applications with
technical safety requirements, the relevant instructions must be followed. Failure to use Schneider Electric software or
approved software with our hardware products may result in injury, harm, or improper operating results. Failure to observe
this information can result in injury or equipment damage.
© 2012 Schneider Electric. All rights reserved.
5. SoMove Lite V1.6.1.1
══════════════════════════════════════
SoMove is user-friendly setup software for PCs, for setting up of Schneider Electric motor control
devices. SoMove software incorporates various functions for the device setup phases, such as
Configuration preparation, Start-up and Maintenance.
1.1 Registration
The Product must be registered with in 4 days of first use, if not the application will stop working
after this period. You must register to continue to use the product.
2 System Requirements
══════════════════════════════════════
2.1 Supported Operating Systems
This software can be installed on the following operating systems:
> Microsoft Windows XP Professional SP3 32 Bit
> Microsoft Windows Vista Business Edition 32Bit SP1
> Microsoft Windows 7 32 bit
> Microsoft Windows 7/Vista 64 bit
2.4 Pre-requisites
.NET Framework 3.5 SP1 must be installed, before installing SoMove. This is downloadable from
the Microsoft website at below link
http://download.microsoft.com/download/2/0/e/20e90413-712f-438c-988e-
fdaa79a8ac3d/dotnetfx35.exe
Adobe version 8.0 and above recommended for the proper functioning of Online help
3 Installation
══════════════════════════════════════
3.1 Administrator Privileges
In order to install SoMove Lite software, you must have administrative privileges to install and
uninstall programs.
Note: Admin privileges are not required to run SoMove Lite once installed.
You can re-run the installer from the Add/Remove Programs Control Panel.
If you have already installed SoMove Lite, the installer gives you options to Modify, Repair or
Remove SoMove Lite.
Note: To Modify or Repair SoMove installer should be available.
4 Restrictions
══════════════════════════════════════
1. Limited print features (only parameters list is printable)
2. In Communication -> Edit connection -> Advanced, the scan modes “Range” and “All” for MB
TCP communication will always connect the first device in the scan range.
3. SoMove will not run properly if Chinese fonts are not available in the system.
You need to relaunch the application and the language will be English by default.
You may change the language after this relaunch.
4. Com port setting are disabled sometimes (Random behavior)
5. SoMove crashes with COM port configured to COM3 in some laptops.
5 AltivarDtmLibrary
══════════════════════════════════════
5.1 Overview
The AltivarDtmLibrary is a software component which represents a package of several DTMs.
The AltivarDtmLibrary Installer is the child installer of SoMove Lite which will launch the different
DTM installers that it referenced.
The following schema represents the Tree of installers of the AltivarDtmLibrary.
5.4 Information
5.1.1 Function: Connection, Load from device, Store to device actions are prohibited
when ARE<>No in the connected device. This parameter is reserved to transfer ATV31
configurations with a loader or keypad.
└─> DTMs: ATV31-312
5.5 Restrictions
5.1.3 Device conversion (firmware compatibility) is not available with this version
└─> DTMs: ATV71
5.1.5 FDR function does not SAVE with SoMove (with a PLC configured)
└─> DTMs: ATV61
5.1.6 Several Help button exists in dialog boxes but have no action
└─> DTMs: ATV12, ATV31-312, ATV71, ATV32,ATV61
5.1.7 Store to device is not permitted when the PLC program is running in the
connected device, a popup error indicates «Store to device is not possible.
└─> DTMs: ATV32
5.1.8 Command panel sometimes cannot be made inactive when the ADC parameter
in automatic DC injection is changed to continuous and executed a Run and stop.
└─> DTMs: ATV32
5.1.9 Command Panel: Drive status is not updated even after resetting the EPF1
(External fault on Li3). Updates only on restarting the application
└─> DTMs: ATV32
5.1.10 Random exception thrown when assigning multi configuration through drive.
└─> DTMs: ATV32
5.1.11 MyMenu sometimes does not get updated in the drive after setting it through the
application.
└─> DTMs: ATV32
5.1.12 After the connection lost, drive still shows online for long time and command
panel also is in active state
└─> DTMs: ATV32
5.1.13 Export to PDF file: Some parameters are missing in the pdf file. e.g.:-EN 19 to
EN 35, OIR and TAFI.
└─> DTMs: ATV32
5.1.15 Store to device is not updating LLS & LTS value in drive.
└─> DTMs: ATVLift
5.1.16 Parameter set switching does not work for frequency threshold if changed via
command panel.
└─> DTMs: ATV71
5.7 Troubleshoot
1. Load from Device - If a load from device action is interrupted by a device power OFF, then the
subsequent load from device actions will fail.
Resolution:
* Power ON the device and try Load from device again, or if problem persists still then
* Restart SoMove and try Load from device again
2. Functional Block - In ATVLogic configuration dialog box, an error message warns “Date is
integer”.
Resolution:
* The date must be entered in the required format: 8 digits: MMDDYYYY
3. Functional Block - If you want copy / paste a whole program from the PRE to the AUX for
example, we have the following behavior:
> Only blocks are pasted (no Inputs/outputs and no links will be pasted).
> The past operation will not paste all blocks copied from the PRE section. It depends on the
position of the last click in the window.
> Create link on 'paste blocks' is not always possible. In this case, it is necessary to delete blocks
and create new one.
6.3 Restrictions
6.4.1 Several Help button exists in dialog boxes but have no action
└─> DTMs: ATS22, ATS48
6.4.2 In the Fault Tab , LFT parameter when it is having INF fault , save the project and open back
, the long label remains as INF instead of “Internal Detected Fault” and when FCS is
performed when LFT is INF on a opened project , Long Label and Value becomes Empty .
└─> DTMs: ATS22
6.4.3 If the fault is INF, the value column is updated as “Internal”- in the fields other than LFT also.
└─> DTMs: ATS22, ATS48
6.5 Troubleshoot
1. Load from Device - If a load from device action is interrupted by a device power OFF, then the
subsequent load from device actions will fail.
Resolution:
* Power ON the device and try Load from device again, or if problem persists still then
* Restart SoMove and try Load from device again
7 ModbusDtmLibrary
══════════════════════════════════════
This document gives recommendations and provides additional information for installing and
running the
Communication DTM for Modbus Serial
Communication DTM for Modbus TCP
Software Component Name Version
MdobusDtmLibrary V 2.0.8
MB Serial Communication DTM V 2.0.24
MB TCP Communication DTM V 2.0.19
Note: During the installation of the Modbus Communication Library also the Schneider PC Driver
for Modbus Serial Line will be installed on the system.
7.2 Directories
By default, Modbus Communication DTM Library Configuration Software will be installed in the
directory.
-<CommonProgramFiles>
-Schneider Electric Shared
- Modbus Communication DTM Library
- Modbus Serial Line CommDTM
- Modbus TCP CommDTM
8.4. Information
8.4.1 Scaling Sketch not available for following drive versions as the rescaling function is not
supported by the drive
└─> DTMs: LXM32A <V1.6, LXM32C <V1.6, LXM32M <V1.4
8.5. Restrictions
4.1 Supported Languages DE, EN, FR, IT, ES
└─> DTMs: LXM32M
5.1 Several Help button exists in dialog boxes but have no action
└─> DTMs: LXM32A, LXM32C, LXM32M
5.2 Oscilloscope: no auto scale after acquisition with “Keep Trace” function
└─> DTMs: LXM32A, LXM32C, LXM32M
5.3 Oscilloscope: LXM32M: Selecting an empty Slot in the Channel select dialog
may lead to a crash└─> DTMs: LXM32M
5.4 Sporadic connection Lost may occur due to bad timing behavior of USB to
RS485 dongles └─> DTMs: LXM32A, LXM32C, LXM32M
5.5 eSM config: Sometimes the button to change to “Grid view” disappears. Save
and reopen the project to solve this issue. └─> DTMs: LXM32M
9 TesysDtmLibrary
══════════════════════════════════════
9.1 Overview
The TeSysDTMLibrary is a software component which represents a package of several DTMs
dedicated to SoMove Lite software tool.
PC must be connected point to point with Modbus protocol:
TeSys T with HMI port
TeSys U with LUCM** port.
The following schema represents the Tree of installers of the TeSysDtmLibrary.
9.3. Restrictions
9.3.1 This library release is available in English, French, Italian, Spain and German
language only.
└─> DTMs: Tesys U, Tesys T
9.3.2 This library release is dedicated to SoMove Lite software running in Microsoft
Windows XP Professional SP3 32 bits and Windows7 32 bits operating system
└─> DTMs: Tesys U, Tesys T
9.3.3 Depending on amount of data to display value refresh time can take few
seconds.
└─> DTMs: Tesys U, Tesys T
9.3.4 Depending on the PC load, Start and Stop commands should be separated by
significant time
└─> DTMs: Tesys U, Tesys T
9.4.1 Some menu items are not greyed even if related command is not contextually
available.
└─> DTMs: Tesys U, Tesys T
9.4.2 Some tree items and parameter groups remain displayed even if they are empty.
└─> DTMs: Tesys U, Tesys T
9.4.3 Depending on the amount of online data exchanges, it may take few seconds to
refresh some values.
└─> DTMs: Tesys U, Tesys T
9.5. Troubleshoot
1. Load from Device
- If a load from device action is interrupted by a device power OFF, then the subsequent load
from device actions may fail.
Resolution:
Power ON the device and try to Load from device again,.
If problem persists, then restart SoMove and try to Load from device again.
10 SoMove Troubleshoot
══════════════════════════════════════
1. Connection lost in Serial Communication
In Case of “Connection Lost” when using Serial Communication, configure the Inter-Char
Timeout from the Modbus Driver as follows:
1. Select the Modbus driver from the taskbar. The default settings for Inter-Char Timeout will be
automatic.
Fig: 1
2. Select the COM Port to be used and change the Inter-Char Timeout value to higher value.
E.g. 50 ms.
Fig: 2
3. Online help: Adobe version 10 and above, the user has to disable the Protected Mode at
startup in the Adobe Reader preference:
In Adobe Reader X, go to Edit>Preferences>General and uncheck "Enable Protected Mode at
startup"