Sunteți pe pagina 1din 5

Case Histo °es of Pump

Explosions while Running Isolated


b
Douglas S. Giles' and Peter N, Lodal
,Senior Chemical Engineer
bSenior Technical Associate
Tennessee Operations, Eastman Chemical Company, Kingsport, TN 37662

ally valved in when necessary. Since this pumping


Standard industrial centrifugal pumps that isolate operation can be interrupted for several hours at a
process material (i.e. "deadheaded" with both suction and time with no process penalty (the sludge stream is rel-
discharge valves closed) inside the pump casing can explode atively small, and the column base has a holdup vol-
catastrophically if the pump is inadvertently started and left ume of several hours), no automatic throwover was
running. installed. However, Distributed Control System (DeS)
Case histories and lessons learned at Tennessee Eastman start/stop capability was installed for both pumps.
Division (TED) involVing pump explosions while running On the morning in question, the primary pump
isolated will bepresented in this paper. Case histories involve was running and in service (Figure 1). The spare was
both combustible and non-combustible process streams started remotely without a proper field check to see if
where the pump was inadvertently started and allowed to it had been valved in properly. Some time after the start
run isolated until the process material heated up and built of the operation, the pump casing exploded, with the
enough pressure to rupture the pump housing creating a report audible from several hundred feet away. A small
puff of white smoke, which dissipated within 15 sec-
BLEVE (Boiling Liquid Expanding Vapor Explosion). Inci-
onds, was observed leaving the general vicinity.. The
dent learnings will bepresentedfor each case. pump casing was tom in two (Figure 2), and parts were
found up to 35 feet away. Personnel were not in the
INTRODUCTION immediate vicinity of the pump at the time of the inci-
Significant amounts of time and energy are put into dent, so no injuries were sustained, and all process
hazard analyses to determine the level of risk, and material was contained and disposed of properly.
appropriate safeguards against running a centrifugal Subsequent investigation and analysis indicated
pump completely isolated, or "deadheaded" with both that the pump had run in this condition for some time.
suction and discharge valves closed. Much of the In that time, the temperature of the fluid increased from
debate centers on whether or not the consequences of 60 0 C to approximately 230 0 C, raising the process
such an action are dependent upon the fluid being vapor pressure to over 210 psig. Mechanical analysis of
pumped. The following case histories illustrate the the casing and the failed bolts indicated that the failure
real hazard potential of improper isolation, regardless pressure was in the 200-225 psig range, in good agree-
of what fluid is being pumped. ment with the temperature analysis. A further piece of
supporting data was found in the local pressure gauge,
CASE 1: SLUDGE PUMP
which had a range of 0-150 psig. Although the gauge
A distillation column underflow containing organic
indicator was wrapped around the stop pin, a manual
acids and decomposition solids (sludge) was pumped
reconstruction of the needle indicated a pressure of
from the column to a heated dumpster via parallel
approximately 200 psig.
3,500 rpm centrifugal pumps, capable of a maximum
(low-flow) 140 psi discharge. This level of discharge
pressure is required due to the viscosity of the materi- CASE 2: CAUSTIC (SODIUM HYDROXIDE) PUMP
al and the distance it must be pumped. Normally, one A chemical manufacturing operation which had
pump runs continuously, with the other pump manu- been shut down permanently was "abandoned in

152 June 2001 Process Safety Progress (Vo1.20, No.2)


Figure 1. Sludge pumps. Figure 2. Close-up of damaged head.

Figure 3. Damaged caustic pump. Figure 4. Another view of the pump.

place" to save the cost of demolition and removal of of the incident, so no injuries were sustained, and
the equipment. Among the equipment items were a all material was contained and disposed of proper-
50% caustic (sodium hydroxide) tank and centrifugal ly.
feed pump. The pump had been isolated by closing
both the suction and discharge hand valves, but had
never been drained. On the afternoon in question, a CASE 3: CONDENSATE PUMP
contractor was sent into the area to start a local venti- A large (2,600 gpm, 250 ft head, 75 HP motor) cen-
lation fan in preparation for an unrelated maintenance trifugal condensate pump was discovered to have
activity in an adjacent area. Unbeknownst to the con- exploded following a major steam system upset (Fig-
tractor, the caustic pump wiring and starter had never ures 12-17). Significant damage was done to the instal-
been de-energized. Further, the switch used to start the lation and surrounding piping. A five-pound piece of
pump was identical to the switch used to start the venti- the pump casing was found more than 400 feet from
lation fan. Although the switch was labeled, the tag was the installation (Figure 13). As with the previous two
very small, and could only be read from up close. These examples, both the suction and discharge valves were
switches were remote (> 50 ft) from the caustic pump
found in the closed position. The manual valves were
installation, well outside of the diked area, and labeled
with an engraved, hard-to-read tag. There was no logi- in the closed position due to a plantwide power upset
cal proximity reason to assume that the switch and that had temporarily cut off electrical power, allOWing
pump were associated with one another. condensate to flow backwards through the pump.
Some time after the pump was started, a loud Recognizing that a restart with the impeller turning
boom was reported, rattling windows as far as 200 backwards could cause significant damage to the
feet from the pump. The pump head was dam- pump, operations closed the valves, not recognizing
aged, and the motor and baseplate were complete- that the power had not been permanently shut off.
ly dislodged as a result of the forces generated by Because no one was present in the immediate vicinity
the explosion (Figures 3-11). No one was present of the pumps at the time of the incident, no injuries
in the immediate vicinity of the pump at the time were sustained.

Process Safety Progress (Vo1.20, No.2) June 2001 153


Figure 5. Damaged head. Figure 6. Damaged head.

Figure 7. Damaged motor and baseplate. Figure 8. Another view of the damaged motor and
baseplate.

COMMON FACTORS 1. One was pumping a combustible fluid, one a


Although these three pumps were of different sizes non-combustible water/caustic mix, and the
and were filled with different fluids, they had some other, just water.
features in common: 2. One pump was a 1,750 rmp pump capable of only
1. Isolation-All pumps had been completely isolat- 123 feet head of discharge; the other two were
ed by closing both the suction and discharge hand 3,500 rpm pump capable of 275-300 feet head dis-
valves. charge.
2. Fluid Filled-All pumps were liquid filled when
isolated
3. Remote Start Capability-All pumps had the capa- CONCLUSIONS
bility for remote start, two from a control room, Although pumping dissimilar fluids at different dis-
and the other from a hand switch remotely located charge pressures, all of these pumps appear to have
from the pump. sustained a boiling liqUid expanding vapor explosion
4. Lack of Run Indication-None of the pumps were (BLEVE). The key feature allowing this to happen was
provided with indication that they were running to the combination of liquid-filled total isolation and
an occupied location. Hence, they all ran for some remote start capabilities that allowed the pumps to run
period of time before rupturing. isolated for a significant period of time undetected. In
5. Seal Failure-None of the pumps was protected general, the potential for damage increases as the size
by the failure of the seal providing relief prior and horsepower of the pump increases, and seal failure
to explosion (as is sometimes assumed). For as a relief mechanism was not adequate in any of these
cases 1 and 2, the viscous, dirty nature of the cases. While these examples do not cover all possible
fluid may have contributed to this. For case 3, mechanisms for pump explosions, they do illustrate the
the reasons are unclear. need for careful analysis of centrifugal pump installa-
Also of note are the dissimilarities between the tions with remote start capability to prevent such an
two operations: occurrence, since hazard assessments do not always
address these factors. In fact, remote stop capabilities
are often added as a safety feature, and the remote start

154 June 2001 Process Safety Progress (Vo1.20, No.2)


Figure 9. Damaged impeller. Figure 10. Close-up of impeller.

Figure 11. Damaged baseplate and motor. Figure 12. Damaged condensate pump.

Figure 13. A piece of the condensate pump casing Figure 14. Installation showing both pumps.
found 400 feet from the installation.
capability comes with it at almost no additional cost.
ACKNOWLEDGMENTS
Since it offers a convenience, remote start is some-
The authors wish to thank Tennessee Operations
times incorporated without a full assessment of the
Management, Eastman Chemical Company, for per-
implications of adding such a feature. For addition-
mission to share these cases and their learnings with
al information on risk and cost assessment for cen-
the broader safety community.
trifugal pumps, refer to the paper by Schisla and
Chastain [1].

Process Safety Progress (Vo1.20, No.2) June 2001 155


Figure 15. Damaged impeller. Figure 16. Damaged motor.

LITERATURE CITED
1. Schisla, R.M. andJ.W. Chastain, "Risk and Cost
Assessment of Catastrophic Failures of Pumps
Resulting from Isolated Running," 5th Biannual
Process Plant Safety Symposium, Houston, TX,
April 2001.

Figure 17. Damaged piping.

156 June 2001 Process Safety Progress (Vo1.20, No.2)

S-ar putea să vă placă și