Sunteți pe pagina 1din 1

MODEL VM-5S DUAL TACHOMETER

VM-5 SERIES MONITOR

SPECIFICATIONS

No entry if additional
Model Code / Additional Spec. Code( spec. code is not specified. )
VM-5S- -
Monitor range Input signal Recorder output Relay output
1 to 1,000rpm 1 VK,RD,FK Series*1 0 4 to 20mADC 1 CH1 : 4 points (SR1,SR2,SR3,SR4) 6 CH1 : 2 points (SR1,SR2) CH2 : 2 points (SR3,SR4)
2 to 2,000rpm 2 VE Series*2 1 1 to 5VDC SR1,SR2,SR3,SR4 Individual output SR1,SR3 OR output SR2,SR4 OR output
3 to 5,000rpm 3 MS Series*3 Output card CH1 : 2 points (SR1,SR2) CH2 : 2 points (SR3,SR4) CH1 : 2 points (SR1,SR2) CH2 : 2 points (SR3,SR4)
2 7
4 to 10,000rpm 4 VC Series*2 2 /IS… or /RE… SR1,SR3 Individual output SR2,SR4 Individual output SR1,SR3 OR output SR2,SR4 AND output
5 to 15,000rpm Note) option CH1 : 2 points (SR1,SR2) CH2 : 2 points (SR3,SR4) CH1 : 2 points (SR1,SR2) CH2 : 2 points (SR3,SR4)
3 8
6 to 20,000rpm *1 VK transducer can not detect the wire break SR1,SR3 Individual output SR2,SR4 OR output SR1,SR3 AND output SR2,SR4 Individual output
7 to 30,000rpm in the sensor system, so RD or FK driver 4 CH1 : 2 points (SR1,SR2) CH2 : 2 points (SR3,SR4) A CH1 : 2 points (SR1,SR2) CH2 : 2 points (SR3,SR4)
8 to 50,000rpm which can detect the wire break shall be SR1,SR3 Individual output SR2,SR4 AND output SR1,SR3 AND output SR2,SR4 OR output
A to 99,999rpm recommended. Especially in case of the CH1 : 2 points (SR1,SR2) CH2 : 2 points (SR3,SR4) CH1 : 2 points (SR1,SR2) CH2 : 2 points (SR3,SR4)
application for zero speed monitor, RD or 5 B
SR1,SR3 OR output SR2,SR4 Individual output SR1,SR3 AND output SR2,SR4 AND output
FK driver shall be strongly recommended
for safety.
- -

Speed relay Speed relay Speed relay Speed relay Hysterisis set value Hysterisis set value Alarm reset Alarm reset Alarm reset Alarm reset Alarm reset
type type type type (shaped waveform circuit) (shaped waveform circuit) (SR1) (SR2) (SR3) (SR4) (OK)
(SR1) (SR2) (SR3) (SR4) (CH1) (CH2)
Over Over Over Over 0 1.0V 0 1.0V 0 AUTO-RESET 0 AUTO-RESET 0 AUTO-RESET 0 AUTO-RESET 0 AUTO-RESET
0 speed 0 speed 0 speed 0 speed
1 0.1V 1 0.1V 1 SELF-HOLD 1 SELF-HOLD 1 SELF-HOLD 1 SELF-HOLD 1 SELF-HOLD
Under 1 Under 1 Under 1 Under 2 0.2V 2 0.2V Note) *2 Input abnormal alarm is not applicable in case of VC and VE input signal.
1 speed speed speed speed 3 0.5V 3 0.5V *3 Short circuit is not detectable in case of MS input signal.

- - /(IS or RE )/5G /TRP/CEM

Relay mode Relay mode Relay mode Relay mode Relay mode First Trigger Monitor/pulse Recorder option
Input power supply Tropical CE
Isolate output
(SR1) (SR2) (SR3) (SR4) (OK) output*4 mode*5 output output requirements spec. marking
NORMALLY NORMALLY NORMALLY NORMALLY NORMALLY 0 OFF 0 AUTO Pulse 0 4 to 20mADC 2 0 to -10VDC
0 85 to 264VAC
0 0 0 0 0 0
DE-ENERGIZED DE-ENERGIZED DE-ENERGIZED DE-ENERGIZED DE-ENERGIZED 1 ON 1 MANUAL output 1 1 to 5VDC 3 0 to 10VDC1 24VDC
NORMALLY NORMALLY NORMALLY NORMALLY NORMALLY Monitor 2 0 to -10VDC 4 0 to -5VDC2 110VDC
1 1 1 1 1 1
ENERGIZED ENERGIZED ENERGIZED ENERGIZED ENERGIZED output 3 0 to 10VDC 5 0 to 5VDCNote) *4 It is necessary to set all
4 0 to -5VDC monitor units in the same
! WARNING rack in first out function
This monitor is designed for monitoring but not for controlling the rotor speed. 5 0 to 5VDC
ON when it is used first out
• Use the speed relay contact only for alarms. When recorder output code 2 function.
• Use the recorder output only for data recording. is selected, specify this
• When a zero speed system is designed using this monitor, other enable contact should be provided by the option code. *5 Auto trigger mode is not
customer for the reliable and safe engagement of the turning gear. selectable, in case of zero
speed use.

Ordering Information Standard Specifications


INPUT If the indicated rotation speed is different from the input rotation SPEED RELAY SET POINT 4 points (SR1,SR2,SR3,SR4)
SPEED/INDICATED speed, enter into the space below. SPEED RELAY SET More than 1rpm : Speed relay can be set in 1 rpm increments until
SPEED CHANGED RATIO Input ratio speed rpm rpm RANGE 110% of monitor range
(NON-STANDARD In case of a magnification more than 1, the resolution Less than 1rpm : Speed relay can be set in 0.1 rpm increment
SPECIFICATION) deteriorates in proportion to the magnification factor. SPEED RELAY SET ACCURACY ±1 digit or less(on digital indicator)
SPEED RELAY SET SR1 : SPEED RELAY OUTPUT 4 points (SR1,SR2,SR3,SR4)
VALUE SR2 : ALARM OUTPUT 1 points (OK) or 2 points (OK1,OK2)
SR3 : ROTOR SPEED LCD digital meter with 5 digits (7 segments, with back light)
SR4 : LCD bar graph meter (40 segments, with back light)
SR2 ≥ SR1 SR4 ≥ SR3 SPEED RELAY SR1,SR3 : (yellow LED)
(SR2 ≤ SR1 SR4 ≤ SR3 in case of both under speed) INDICATOR SR2,SR4 : (red LED)
Preset to 50% of monitor range unless specified otherwise. ABNOR. ALARM INDICATOR OK : (green LED)
SPEED RELAY BYPASS INDICATOR BYPASS :(red LED)
HYSTERESIS TRANSDUCER INPUT VK, RD,FK Series, VE Series, MS Series, VC Series
Speed relay hysteresis can be specified from 0 to 100rpm. (1rpm step) Number of input points : 2 points
SR1 : INPUT IMPEDANCE Approx.5kΩ
SR2 : INPUT VOLTAGE Min.:2Vpk-pk, Max.:100Vpk-pk
SR3 : MIN. PULSE WIDTH Approx.50µsec
SR4 : MIN. INDICATED FREQUENCY Lower of 1Hz or under speed setting.
Preset to 10rpm unless specified otherwise. MAX. INPUT FREQUENCY 10kHz
NO. OF INPUT PULSE 1 to 120 pulse
TRIGGER MODE AUTO, MANUAL (selectable)
NO. OF INPUT P/R Can be specified from 1 to 120 pulse. In case of auto trigger mode, input pulse duty ratio should be
Pulses/rev. : between 10 and 90% and input pulse frequency should be 1Hz and
DIMENSION OF TARGET over. it depends on the target.
(Model VK, RD,FK) D BA D A
C D B
C EXTERNAL CONTACT INPUT Contact type : Dry contact
C (FROM REAR PANEL) Contact for external reset
DIGITAL METER ±(0.003% of rdg. +1 digit) at 25°C(77°F)
±(0.03% of rdg.+1 digit) at 0 to 65°C(32 to 149°F)
BAR GRAPH METER ±2.5% of F.S.
RECORDER OUTPUT ±0.5% of F.S. at 25°C(77°F)
CONVERSION ACCURACY ±2.0% of F.S. at 0 to 65°C (32 to 149°F)
CAUTION) To detect a projection(gear), provide surface A of the projection with a concentric RECORDER OUTPUT Voltage or current output proportional to monitor range
curve. (FROM REAR PANEL) 1 to 5VDC (output impedance : 250Ω)
Do not make it flat. VK-202A 4 to 20mADC (max. load resistance : 500Ω)
VK-452A
Input RD-05A VK-302P 0 to -10VDC*,0 to 10VDC*,0 to -5VDC*,0 to 5VDC*
A= mm FK-452F
FK-202F (output impedance : 100() (*option)
B= mm A ≥6 ≥ 16 ≥8 Number of output points : 2 points
C= mm Dimension of target B ≥7 ≥ 20 ≥8 MONITOR/PULSE Monitor output/Pulse output, selectable
D= mm [recommended]
(mm) C ≥ 2.5 ≥ 4.5 ≥ 2.5 OUTPUT Monitor output : Input signal is output via a buffer amplifier.
D ≥ 16 ≥ 36 ≥ 20 (FROM FRONT, REAR Signal level : -0.8 to -22VDC(VK, RD)
Set gap PANEL) ±15V(MS),0 to 15VDC(VE), 0 to 5VDC(VC)
1.0 to 1.5 2.5 to 3.5 1.0 to 1.5 Pulse output : Shaped pulse signal is output via a buffer amplifier.
[recommended](mm)
Signal level : -1 to +1V(PL),4 to 6V(PH)
Output impedance : Approx.100( (load resistance 50k( or more)
OTHERS TEMPERATURE RANGE Operating temperature : 0 to 65°C(32 to 149°F)
Storage temperature : -30 to +85°C(-22 to +185°F)
Relative humidity : 20 to 95%RH(noncondensing)
MATERIAL AND FINISH Face plate : Aluminum Munsell N-4.0 (equiv.)
MASS Monitor : max.0.7kg
(including single unit instrument rack max.2.5kg)

39511E4.5
Issued : Feb.1995